Danfoss EVR 2, EVR 8, EVRH 10, EVRH 40, R 410A Data sheet

...
Data sheet
Solenoid valves for R 410A and R744 (CO2) EVR 2 to EVR 8 and EVRH 10 to EVRH 40
EVR 2 and EVR 3 (direct operated) and EVR 4 to EVR 8 / EVRH 10 to EVRH 40 (servo-operated) are high pressure solenoid valves specially designed to meet the requirements of high pressure refrigerants such as R410A and R744 (CO2). The EVRH valve can be used for liquid, suction and hot gas lines.
Features • Normally Closed and Normally Open
Coils for AC and DC voltages
Suitable for R410A and R744 (CO2)
• Media temperatures up to 221°F
• Design pressure 655 psig
© Danfoss | DCS (rja) | 2017.03
• MOPD up to 350 psi
• Solder connections up to 7/8 inch
• Extended soldering ends
• Solders without dismantling the valve
DKRCC.PD.B00.C3.22 | 1
Data sheet | Solenoid valves for R410A and R744 (CO2), EVR 2 to EVR 8, EVRH 10 to EVRH 40
Approvals
Technical data
The Low Voltage Directive (LVD) 2014/35/EU with amendments EN 60730-2-8.
Listed
Temperature of medium
-40 – 105 °C for 10 or 12 W coil Max. 130 °C during defrost
-40 – 80 °C for 20 W coil
Opening dierential pressure Δp [psig]
Type
Min. ODP
EVR 2 0 350 260 0.19 EVR 3 0 300 260 0.32 EVR 4 0.7 300 260 0.7 EVR 6 0.7 300 260 0.92 EVR 6 NO 0.7 300 300 0.92 EVR 8 0.7 300 260 1.3 EVRH 10 0.7 300 260 2.2 EVRH 15 0.7 300 260 3.0 EVRH 20 0.7 300 190 5.8 EVRH 22 0.7 300 190 6.9 EVRH 25 1.0 300 260 12 EVRH 32 1.0 300 260 18 EVRH 40 1.0 300 260 29
(with standard coil)
14 – 17 W AC 20 W DC
Refrigerants
R744, R22/R407C, R404A/R507, R410A, R134a, R407A, R23, R744. For other refrigerants, please contact Danfoss.
Note: EVR 2 – EVR 3 and EVRH 25 – EVRH 40 are not suitable for R744 (CO2)applications with media temperatures constantly below 0 °C. For other media temperatures, please contact Danfoss.
MOPD
Cv value
[gal/min]
© Danfoss | DCS (rja) | 2017.03
DKRCC.PD.B00.C3.22 | 2
Data sheet | Solenoid valves for R410A and R744 (CO2), EVR 2 to EVR 8, EVRH 10 to EVRH 40
Ordering Solenoid valve – Normally Closed (NC) – Soldering ODF without coil
EVR / EVRH Valves
1)
Type Coil type Connection size [in.] Code no.
EVR 2 AC/DC 1/4
EVR 3
EVR 4
AC/DC 1/4 AC/DC 3/8 AC/DC 3/8 AC/DC 1/2 AC/DC 3/8
EVR 6
AC/DC 1/2 AC/DC 5/8
EVR 8
AC/DC 1/2
AC/DC 5/8 EVRH 10 AC/DC 1/2 EVRH 15 AC/DC 5/8 EVRH 20 AC 7/8 EVRH 25 AC/DC 1 1/8
1)
EVRH 32
AC/DC – EVRH 40 AC/DC 1 5/8
Only available with mm connections
Solenoid valve – Normally Open (NO)
Type Coil type Connection size [in.] Code no.
EVR 6 AC/DC 3/8
EVRH 10 AC/DC 1/2
032F7100 032F7105 032F1157 032F7110 032F7111 032F7115 032F1162 032F7117 032F7121
032F7122 032G1077 032G1078 032G1079 032G1059 032G1081 032G1062
032F1164
032F1329
BJ and BX Coils
Wire length
Coil type
Voltage
[V AC]
Frequency
[Hz]
Junction box NEMA 2
BJ024CS 7 18 24 50 / 60 14
BJ120CS 7 18
BJ240CS 7 18
110 – 120
110
208 – 240
230
60 50
60 50
BJ120BS 7 18 120 60 16
BJ208BS 7 18 208 60 16
BJ240BS 7 18 240 60 16
Conduit boss NEMA 4
BX024CS 18 46 24 50 / 60 14
BX024CS 71 180 24 50 / 60 14
BX024CS 98 250 24 50 / 60 14
BX120CS 18 46
BX120CS 36 91
BX120CS 71 180
110 – 120
110
60 50
BX120CS 98 250
BX240CS 18 46
BX240CS 98 250
208 – 240
230
60 50
BX120BS 98 250 120 60 16
BX208BS 98 250 208 60 16
BX240BS 98 250 240 60 16
Power
consumption
[W] Code no.[in] [cm]
15 16
14 17
15 16
14 17
018F4100
018F4110
018F4120
018F4130
018F4132
018F4134
018F4102
018F4103
018F4104
018F4112
018F4113
018F4114
018F4115
018F4122
018F4123
018F4131
018F4133
018F4135
Technical data
© Danfoss | DCS (rja) | 2017.03
Design
In accordance with UL 429
Power supply
Alternating current (AC)
Permissible voltage variation
Alternating current (AC): 50 Hz and 60 Hz: -10% – 15% 50/60 Hz: ± 10%
Power consumption
Alternating current (AC): Inrush: 49 VA; Holding: 28 VA, 14 – 17 W
Insulation of coil wire
Class H according to IEC 85
Connection
Junction box or Conduit boss
Enclosure, IEC 60529
Junction box NEMA 2 ~ IP 12–32 Conduit boss NEMA 4 ~ IP 54
Ambient temperature
-40 °F – 122 °F (-40 °C – 50 °C)
DKRCC.PD.B00.C3.22 | 3
Data sheet | Solenoid valves for R410A and R744 (CO2), EVR 2 to EVR 8, EVRH 10 to EVRH 40
Capacity, R410A Liquid capacity
Type
EVR 2 0.56 0.78 0.96 1.1 1.23 1.35 1.46 EVR 3 0.98 1.37 1.68 1.93 2.15 2.36 2.55 EVR 4 2.12 2.98 3.65 4.2 4.69 5.14 5.55 EVR 6 2.79 3.92 4.8 5.52 6.16 6.75 7.3
EVR 8 3.94 5.54 6.78 7.8 8.7 9.54 10.3 EVRH 10 6.63 9.31 11.4 13.1 14.6 16 17.3 EVRH 15 9.07 12.7 15.6 17.9 20 21.9 23.7 EVRH 20 17.5 24.5 30 34.5 38.5 42.2 46.6 EVRH 22 20.82 29.4 36 41.4 46.2 50.6 54.8 EVRH 25 33.65 47.59 58.29 67.31 75.25 82.44 89.04 EVRH 32 53.85 76.15 93.27 107.69 120.41 131.90 142.47 EVRH 40 84.14 118.99 145.73 168.27 188.13 206.09 222.60
1 2 3 4 5 6 7
Liquid capacity Q0 tons at pressure drop across valve p psi
Capacities are based on: liquid temperature tl = 100 °F
Evaporating temperature te = 40 °F Superheat 10 °F
Capacity, R410A Suction vapour capacity
Type
EVR 2
EVR 3
EVR 4
EVR 6
EVR 8
EVRH 10
EVRH 15
EVRH 20
EVRH 22
EVRH 25
EVRH 32
EVRH 40
Note: Bold gures refer to rated capacity
Pressure
drop Δp [psi]
1 0.04 0.05 0.07 0.07 0.08 0.09 0.10 0.11 2 0.06 0.07 0.09 0.11 0.12 0.13 0.14 0.16 3 0.07 0.09 0.12 0.13 0.14 0.16 0.18 0.19 1 0.07 0.09 0.12 0.13 0.14 0.16 0.18 0.20 2 0.10 0.13 0.16 0.18 0.21 0.23 0.25 0.28 3 0.12 0.16 0.20 0.23 0.25 0.28 0.31 0.34 1 0.15 0.20 0.25 0.28 0.31 0.35 0.39 0.43 2 0.22 0.28 0.36 0.40 0.45 0.49 0.55 0.60 3 0.27 0.35 0.44 0.49 0.55 0.61 0.67 0.74 1 0.20 0.26 0.33 0.37 0.41 0.46 0.51 0.56 2 0.29 0.37 0.47 0.53 0.59 0.65 0.72 0.79 3 0.35 0.46 0.58 0.65 0.72 0.80 0.88 0.97 1 0.28 0.36 0.46 0.52 0.57 0.64 0.71 0.78 2 0.41 0.52 0.66 0.74 0.82 0.91 1.01 1.10 3 0.49 0.64 0.81 0.91 1.01 1.12 1.23 1.36 1 0.48 0.62 0.79 0.89 0.98 1.09 1.20 1.33 2 0.68 0.88 1.12 1.25 1.39 1.54 1.70 1.87 3 0.84 1.08 1.37 1.54 1.71 1.89 2.09 2.30 1 0.66 0.85 1.09 1.21 1.35 1.50 1.65 1.81 2 0.93 1.21 1.53 1.72 1.91 2.11 2.33 2.56 3 1.14 1.48 1.88 2.10 2.33 2.59 2.85 3.14 1 1.27 1.64 2.09 2.33 2.59 2.88 3.17 3.49 2 1.79 2.32 2.95 3.30 3.67 4.06 4.48 4.93 3 2.20 2.85 3.61 4.04 4.49 4.98 5.49 6.04 1 1.51 1.95 2.49 2.77 3.08 3.43 3.77 4.15 2 2.13 2.76 3.51 3.93 4.37 4.83 5.33 5.87 3 2.62 3.39 4.29 4.81 5.34 5.92 6.53 7.19 1 2.46 3.23 4.13 4.63 5.16 5.72 6.33 6.96 2 3.39 4.50 5.78 6.49 7.25 8.05 8.91 9.82 3 4.04 5.42 7.01 7.89 8.82 9.81 10.87 11.98 1 3.93 5.17 6.61 7.40 8.25 9.16 10.12 11.14 2 5.42 7.20 9.25 10.39 11.60 12.89 14.26 15.70 3 6.46 8.68 11.22 12.62 14.11 15.70 17.38 19.17 1 6.15 8.08 10.32 11.57 12.90 14.31 15.82 17.41 2 8.47 11.25 14.45 16.23 18.12 20.14 22.27 24.54 3 10.09 13.56 17.53 19.72 22.05 24.53 27.16 29.95
Suction vapour capacity Q0 tons at evaporating temperature te °F
-40 -20 0 10 20 30 40 50
© Danfoss | DCS (rja) | 2017.03
The table values refer to evaporator capacity and are given as a function of evaporating temperature te and pressure drop p across the valve. Capacities are based on liquid temperature tl = 100 °F ahead of the expansion valve and superheat ts = 7 °F. For each additional 10 °F of superheat, the table capacities must be reduced by 2%.
Correction factors for liquid temperature t
l
When liquid temperature tl ahead of the expansion valve is other than 100°F, adjust the table capacities by multiplying them by the appropriate correction factor found in the following table:
tl˚F 80 90 100 110 120 Factor 1.10 1.05 1.00 0.95 0.90
DKRCC.PD.B00.C3.22 | 4