In a Danfoss SM / SY / SZ scroll compressor, the
compression is performed by two scroll elements
located in the upper part of the compressor.
Suction gas enters the compressor at the suction
connection. As all of the gas ows around and
through the electrical motor, thus ensuring
complete motor cooling in all applications, oil
droplets separate and fall into the oil sump.
After exiting the electrical motor, the gas enters
the scroll elements where compression takes
place. Ultimately, the discharge gas leaves the
compressor at the discharge connection.
The gure below illustrates the entire
compression process. The centre of the orbiting
scroll (in grey) traces a circular path around
the centre of the xed scroll (in black). This
movement creates symmetrical compression
pockets between the two scroll elements.
Low-pressure suction gas is trapped within
each crescent-shaped pocket as it gets formed;
continuous motion of the orbiting scroll serves
to seal the pocket, which decreases in volume
as the pocket moves towards the centre of the
scroll set increasing the gas pressure. Maximum
compression is achieved once a pocket reaches
the centre where the discharge port is located;
this stage occurs after three complete orbits.
Compression is a continuous process: the
scroll movement is suction, compression and
discharge all at the same time.
First orbit:
SUCTION
Second orbit:
COMPRESSION
Third orbit:
DISCHARGE
4
SM SY SZ 084-09 0-100-110-120 -148-161-175-185-240-300-380
FRCC.PC.003.A5.22
Application guidelines
Features
In addition to the existing SM range compressors
previously available, Danfoss is completing its
range with 3 compressors.
The new SM112-124-147 and SZ147 compressors
benet from a further improved design to
achieve the highest eciency.
Gas circulation, motor cooling and oil behaviour
are improved by a new patented motor cap
design.
Heat shield that lowers the heat transfer between
discharge and suction gas and the acoustic level
New PTFE spring seal for even lower leaks
R22 optimized scroll prole
Part protection and assembly reduces internal
leaks and increases life durability.
Improved part isolation reduces greatly acoustic
levels.
Gas intake design induces higher resistance to
liquid slugging.
SM112-124 -147 an d SZ147
FRCC.PC.003.A5.22
Patented motor cap
Patented motor centering spacer
Improved lower bearing centering
5
Application guidelines
Compressor model designation
Danfoss scroll compressors are available
both as single compressors and as tandem
units. The example below presents the single
compressor nomenclature which equals the
technical reference as shown on the compressor
nameplate.
Nomenclature
Family, lubricant
& refrigerant
SZ
SY
Family, lubricant
& refrigerant
SM: Scroll, Mineral oil, R22/R417A*
SY: Scroll, POE lubricant, R22/R417A
(and R407C for SY185-240-300)
SZ: Scroll, POE lubricant, R407C - R134a
(and R404A, R507A for SZ084 to SZ185)
Nominal capacity
in thousand Btu/h at 60 Hz, R22,
ARI conditions
TR = Ton of Refrigeration COP = Coecient Of Performance EER = Energy Eciency Ratio
Displacement at nominal speed: 2900 rpm at 50 Hz, 3500 rpm at 60Hz Net weight with oil charge
Data given for code 4 compressor, for full data details and capacity tables refer to Online Datasheet Generator: ww w.danfoss.com/ODSG
Net
weight
Rating conditions
SM/SY compressorsSZ compressors
RefrigerantR22R407C
Frequency50 Hz50 Hz
Standard rating conditionsARI standard conditionsEvaporating temperature45°F45°F (dew point)
Condensing temperature130° F130°F (dew point)
Sub-cooling15° F15° F
Superheat20°F20°F
Subject to modication without prior notication
For full data details and capacity tables refer to Online Datasheet Generator : www.danfoss.com/odsg
TR = Ton of Refrigeration COP = Coecient Of Performance EER = Energy Eciency Ratio
Displacement at nominal speed: 2900 rpm at 50 Hz, 3500 rpm at 60Hz Net weight with oil charge
Data given for code 4 compressor, for full data details and capacity tables refer to Online Datasheet Generator: ww w.danfoss.com/ODSG
Swept
volume
Displace-
ment
Oil
charge
Net
weight
Rating conditions
SM/SY compressorsSZ compressors
RefrigerantR22R407C
Frequency60 Hz60 Hz
Standard rating conditionsARI standard conditionsEvaporating temperature45°F45°F (dew point)
Condensing temperature130° F130°F (dew point)
Sub-cooling15° F15° F
Superheat20°F20°F
Subject to modication without prior notication
For full data details and capacity tables refer to Online Datasheet Generator : www.danfoss.com/odsg
8
FRCC.PC.003.A5.22
Application guidelines
SM/SZ 084-090-100-110-120
Dimensions
Ø 9.45
A: 18.29
B: 20.26
A: 20
B: 21.97
4 holes Ø 0.76
11.18
8.66
A: 9.92
B: 11.35
A: 5.59
B: 7.02
A: 6.42
B: 7.05
3.91
11.18
8.66
Ø 9.06
Ø 10
4.54
3.95
7.29
A: 15.02
B: 16.99
A: 11.60
B: 13.02
A: 6.17
B: 6.38
A: SM/SZ 084-090-100
B: SM/SZ 110-120
FRCC.PC.003.A5.22
30°
6.41
45°
Grommet
Steel mounting sleeve
Rubber grommet
3.89
HM 8 bolt
Lock washer
Flat washer
Nut
All dimensions in inch
Compressor
base plate
1.10 inch
9
B: SM124-147
Application guidelines
Dimensions
SM 112-124 -SM/SZ147*
* except code 3
A: 21.06
B: 21.26
4.61
10.94
7.44
4 holes
Ø 0.75
30 °
Ø 8.80
Ø 8.69
Ø 9.57
9.06
7.5
A: 10.84
B: 20.04
3.98
6.18
6.06
4 holes
Ø 0.75
SM/SZ147 code 3
Ø 8.82
Ø 9.57
21.26
20.04
10.94
3.98
9.06
7.5
30°
9.06
60 °
7.5
A: SM112
30 °
6.06
6.81
7.09
9.06
60°
7.5
30°
Grommet
HM 8 bolt
Lock washer
Flat washer
Steel mounting sleeve
Rubber grommet
Nut
7.87
6.06
6.81
All dimensions in inch
Compressor
base plate
1.10 inch
10
FRCC.PC.003.A5.22
Application guidelines
Dimensions
SM /SZ 148-161
7.79
7.87
3.92
SM 148-161 code 3SM 148-161 code 4
Ø 10.47
Ø10.47
14.79
23.27
17.33
17.33
7.09
4.54
10.65
3.92
30°
7.32
6.8
8.66
11.18
6.24
8.23
4 holes
Ø 0.76
8.66
11.18
14.08
3.89
Grommet
Lock washer
Flat washer
Steel mounting sleeve
Rubber grommet
HM 8 bolt
13.03
7.36
All dimensions in inch
Compressor
base plate
1.10 inch
FRCC.PC.003.A5.22
Nut
11
Application guidelines
Dimensions
SM/SZ 175-185 & SY185
20.81
Brazed versionRotolock version
Ø 10.47
Ø 10.08
26.69
7.80
Ø 12.45
9.34
7.09
4.33
25.25
9.39
7.76
7.09
7.67
30°
6.74
7.32
13.60
11
7.36
4 holes
Ø 0.76
12
14.60
16.91
Grommet
HM 8 bolt
Lock washer
Flat washer
6.57
7.96
All dimensions in inch
Compressor
base plate
Steel mounting sleeve
Rubber grommet
Nut
12
FRCC.PC.003.A5.22
1.10 inch
Application guidelines
Dimensions
SY/SZ 240-300-380
Brazed versionRotolock version
Ø13.54
Discharge 1”1/8
Discharge
A&B: 1”1/8
C: 1”3/8
Ø13.54
A: 27.2±2
B: 67.63±2
C: 28.58
A: 24.33
B: 24.76
C: 25.71
15.43
Suction
A&B: 1”5/8
C: 2”1/8
7.7
12
7.95
90°
15.43
11.58
7.62
8.11
A&B: 15.83 - C: 16.54
8.23
30°
35°
5.5
7.32
3.43
Ø13.11
6.29
3.86
4 holes Ø0.98
17.87
7.36
A: 18.88±1.2
B: 19.31±1.2
C: 20.26±1.2
8.50
A: SY/SZ240
B: SY/SZ300
C: SY/SZ380
A: 27.2±2
B: 67.63±2
A: 24.33
B: 24.76
15.43
A: SY/SZ240
B: SY/SZ300
15.91
12
187
8.50
Suction
A: 1”1/2
B: 1”5/8
7.7
Ø13.11
A: 18.88±1.2
B: 19.31±1.2
6.29
3.86
3.43
15.43
11.58
30°
7.62
7.95
8.19
90°
15.90
7.32
35°
5.5
8.23
4 holes Ø0.98
17.87
FRCC.PC.003.A5.22
Grommet
Lock washer *
Large flat *
1.06 inch washer
Steel mounting sleeve
Rubber grommet
* not supplied with compressor
All dimensions in inch
HM 10 Bolt *
Compressor base plate
1.41 inch
Nut *
13
Application guidelines
Dimensions
Connection details
Model
VersionVK-R-S -W-YC-J-P-U-XALMA - MBAA - ABAA - AB
Suction and discharge connectionbrazedrotolockbrazedbrazedrotolockbrazedbrazed
All Danfoss SM / SY / SZ scroll compressors come
equipped with a sight glass (1"1/8-18 UNF) which
may be used to determine the amount and
condition of the oil contained within the sump.
SM/SZ 112-124-147: 1"3/4 rotolock connector
allowing use of 1"3/4-7/8" or 1"3/4-1"1/8
SY/SZ240-300-380: 1/2" are
Other models: 3/8" are
This connection must be used to mount an oil
equalisation line when two or more compressors
are mounted in parallel (please refer to
Danfoss Parallel Application Guide lines
reference FRCC.PC.005 for details).
1
1
2
2
Oil drain connection
Schrader
14
The oil drain connection allows oil to be removed
from the sump for changing, testing, etc. The
tting contains an extension tube into the oil
sump to more eectively remove the oil. The
connection is a female 1/4" are tting.
Note: on SY/SZ 240 to 380, it is not possible to
drain oil from the suction connection.
The oil ll connection and gauge port is a 1/4"
male are connector incorporating a schrader
valve.
FRCC.PC.003.A5.22
Application guidelines
Electrical data, connections and wiring
Motor voltage
Wiring connections
SM / SZ 084 - 090 - 100 - 110 - 112
- 120 - 124 - 147* -148* - 161*
*Except for motor voltage
code 3
Danfoss SM / SY / SZ scroll compressors are available in ve dierent motor voltages.
Nominal voltage
Voltage range
Nominal voltage
Voltage range
50 Hz
60 Hz
50 Hz
60 Hz
Motor voltage
code 3
-380-400 V - 3 ph500 V - 3 ph-
-340-440 V450 - 550 V-
200-230 V - 3 ph460 V - 3 ph575 V - 3 ph380 V - 3 ph
180 - 253 V414 - 506 V517 - 632 V342 - 418 V
Motor voltage
code 4
Motor voltage
code 7
Motor voltage
code 9
Electrical power is connected to the compressor terminals by Ø 3/16” (4.8 mm) screws. The maximum
tightening torque is 2.2ft.lb. Use a 1/4’’ ring terminal on the power leads.
The terminal box is provided with a Ø 1" and a
Ø 1.14" knockouts.
Ø 1.14 inch knockout
Power supply
Terminal box
Ø 1 inch knockout
SM/SZ 147 code 3
SM / SZ 148 & 161 code 3-175185 & SY185 - R & C version
The terminal box is provided with a Ø 1.59" hole
for power supply and a Ø 0.65" knockout.
The terminal box is provided with 2 double
knockouts for the power supply and 3 knockouts
for the safety control circuit.
The 2 power supply, double knockouts
accommodate the following diameters:
Ø 1”3/4 hole (for a 1”1/4 conduit) and Ø 1”3/8
hole (for a 1” conduit),
Ø 1.26” hole & Ø 1” hole
The 3 other knockouts are as follows:
Ø 0.81”
Ø 7/8” (for a 1/2” conduit)
Ø 0.65”
Ø 0.65”
knockout
Cover holding screw (x2) - Torque: 1.6 ft.lb
Faston 1/4" tabs
Power supply
Ø 1.59” hole
Power supply
Terminal box
Sump heater
FRCC.PC.003.A5.22
15
Internal control contact
connection
Application guidelines
Electrical data, connections and wiring
SM/SZ 175-185 - J, K, P, S, U, W,
X, Y versions
The terminal box is provided with 2 double
knockouts for the power supply and 3 knockouts
for the safety control circuit.
The 2 power supply, double knockouts
accommodate the following diameters:
Ø 1”3/4 hole (for a 1”1/4 conduit) and Ø1”3/8
hole (for a 1” conduit)
Ø1.26” hole & Ø1” hole
The 3 other knockouts are as follows:
Ø 0.81”, Ø 7/8” (for a 1/2” conduit) and Ø 0.65”
The motor protection module comes
preinstalled within the terminal box and has
pre-wired thermistor connections. The module
must be connected to a power supply of the
appropriate voltage. The module terminals are
0.25" size Faston type except for 24V DC module
(screw connection).
SY/SZ 240 – 300 – 380The terminal box is provided with 2 triple
knockouts and 1 single knockout for power
supply and 4 double knockouts for the safety
control circuit.
The 3 power supply knockouts accommodate the
following diameters:
• Ø 2 inch (UL 1"1/2 conduit) & Ø 1.72 inch (UL
1"1/4 conduit) & Ø 1.36 inch (UL 1" conduit)
• Ø 1.59 inch (ISO40) & Ø 1.27 inch (ISO32) & Ø 1
inch (ISO25)
• Ø 1 inch (ISO25)
The 4 others knockouts are as follows:
• Ø 0.89 inch (PG16) (UL 1/2") & Ø 0.65 inch
(ISO16) (x2)
• 0.81 inch (ISO20 or PG13.5) (x2)
Cover holding screw (x2) - Torque: 1.6 ft.lb
L1
Terminal box
Motor Protection
N
Module
1
2
12
14
11
Faston 1/4" tabs
Power supply
Safety circuit
Protection module
power supply
Sump heater
LN12141211
Module power
Black
Faston 1/4” tabs
Power supply
Blue
Brown
Thermistor
M1 - M2
Control circuit
}
}
Safety
circuit
Module
power supply
Sump heater
IP rating
16
The motor protection module comes
preinstalled within the terminal box. Phase
sequence protection connections and thermistor
connections are pre-wired. The module must be
connected to a power supply of the appropriate
voltage. The module terminals are 0.25" size
Faston type.
Phase sequence input
L1 L2 L3
Black Blue Brown
Internal control contact
LNS1 S2 M1 M2
Thermistor
Module power
connection
Safety
circuit
The compressor terminal box according to IEC529 is IP54 for all models when correctly sized IP54
rated cable glands are used.
• First numeral, level of protection against contact and foreign objects
5 - Dust protected
• Second numeral, level of protection against water
4 - Protection against water splashing.
FRCC.PC.003.A5.22
Application guidelines
Electrical data, connections and wiring
Terminal box temperature
The temperature inside the terminal box may not
exceed 158°F. Consequently, if the compressor
is installed in an enclosure, precautions must be
taken to avoid that the temperature around the
compressor and in the terminal box would rise
too much. The installation of ventilation on the
enclosure panels may be necessary. If not, the
SM /S Z11016027230.72
SM /S Z11217732240.72
SM/SZ12016 030280.72
SM /SZ12 417732270.72
SM/SZ14 718135310.62
SM/SZ14 815538360.75
SM/SZ16115538380 .75
SM /SZ175 *23543420.48
SM/SZ185 *23543430.48
SY/ SZ24 026062620.42
SY/ SZ30 030574740.36
Locked Rotor Amp value is the higher current as
LRAMCCMMTMax . op. currentWinding resistance
AAAAΩ
measured on mechanically blocked compressor
tested under nominal voltage. The LRA value
can be used as rough estimation for the starting
electronic protection module may not operate
properly. Any compressor damage related to this
will not be covered by Danfoss warranty. In the
same manner, cables must be selected in a way
to insure that terminal box temperature does not
exceed 158°F.
current. However in most cases, the real starting
current will be lower. A soft starter can be
applied to reduce starting current.
FRCC.PC.003.A5.22
17
Application guidelines
Electrical data, connections and wiring
MMT (Max Must Trip current)
MCC (Maximum Continuous
Current)
Max. operating Current
Winding resistance
The MMT is dened for compressors without
their own motor protection. This MMT value
is the maximum at which the compressor can
be operated in transient conditions and out of
the application envelope. The tripping current
The MCC is the current at which the motor
protection trips under maximum load and
low voltage conditions. This MCC value is the
maximum at which the compressor can be
operated in transient conditions and out of the
The max. operating current is the current
when the compressors operates at maximum
load conditions and 10% below the highest
value of its nominal voltage (59°F evaporating
temperature and 154.4°F condensing
temperature).
Winding resistance is the resistance between
indicated terminal pins at 77°F (resistance value
+/- 7%).
Winding resistance is generally low and it
requires adapted tools for precise measurement.
Use a digital ohm-meter, a "4 wires" method and
measure under stabilised ambient temperature.
Winding resistance varies strongly with winding
temperature ; if the compressor is stabilised
at a dierent value than 77°F, the measured
resistance must be corrected with following
formula:
of external overcurrent protection (thermal
overload relay or circuit breaker not provided
with compressor) must never exceed the MMT
value.
application envelope. Above this value, the
internal motor protection or external electronic
module will cut-out the compressor to protect
the motor.
Max Oper. A can be used to select cables and
contactors.
In normal operation, the compressor current
consumption is always less than the Max Oper. A
value.
a + t
R
= R
amb
77°F
a + t
t
: reference temperature = 77°F
77°F
t
: temperature during measurement (°F)
amb
R
: winding resistance at 77°F
77°F
R
: winding resistance at t
amb
amb
77°F
amb
Coecient a = 234.5
Danfoss MCI soft-start
controller
18
The inrush current for the Danfoss scroll
compressors with motor code 4 (400V / 3 / 50Hz
or 460V / 3 / 60Hz) can be reduced using the
Danfoss digitally-controlled MCI compressor soft
starter. MCI soft starters are designed to reduce
the starting current of 3-phase AC motors; MCI
soft starters can reduce the in-rush current by
up to 40%, thereby eliminating the detrimental
Compressor model
SM / SZ 084
SM / SZ 090
SM / SZ 100
SM / SZ 110
SM / SZ 120
SM 112-124 - SM/SZ147
SM / SZ 161 - 148
SM / SZ 175 - 185
SY / SZ 240 - 300 - 380MCI 50CM *
* By-pass contactor (K1) required.
FRCC.PC.003.A5.22
Soft start reference
ambient max. 104°F
eects of high starting torque surges and costly
demand charges from the resultant current
spike. Upon starting, the controller gradually
increases the voltage supplied to the motor until
full-line voltage has been reached. All settings,
such as ramp-up time (less than 0.5 sec) and
initial torque, are preset and do not require
modication.
MCI 15 C
MCI 25CMCI 25C*
Soft start reference
ambient max. 131°F
MCI 15 C
MCI 25C
CONTROL CIRCUIT
Application guidelines
Electrical data, connections and wiring
Input controlled soft start
MCI with bypass contactor
General wiring information
When the control voltage is applied to A1 A2, the MCI soft starter will start the motor,
according to the settings of the ramp-up time
and initial torque adjustments. When the control
voltage is switched OFF, the motor will switch o
instantaneously.
By means of the built-in auxiliary contact (23-24)
the bypass function is easily achieved, see wiring
diagram below.
No heat is generated from the MCI. As the
contactor always switches in no-load condition
it can be selected on the basis of the thermal
current (AC-1).
The wiring diagrams below are examples for a
safe and reliable compressor wiring. In case an
alternative wiring logic is chosen, it's imperative
to respect the following rules.
When a safety switch trips, the compressor must
stop immediately and must not re-start until
the tripping condition is back to normal and
the safety switch is closed again. This applies to
the LP safety switch, the HP safety switch, the
discharge gas thermostat and the motor safety
thermostat.
In specic situations, such as winter start
operation, an eventual LP control for pumpdown cycles may be temporarily bypassed to
13-14 contact not applicable with MCI 25C
allow the system to build pressure. But it remains
mandatory for compressor protection to apply
an LP safety switch. The LP safety switch must
never be bypassed.
Pressure settings for the LP and HP safety
switch and pump-down are indicated section
“Operating conditions”.
When ever possible (ie. PLC control), it is
recommended to limit the possibilities of
compressor auto restart to less than 3 to 5 times
during a period of 12 hours when caused by
motor protection or LP safety switch tripping.
This control must be managed as a manual reset
device.
Compressor models SM / SZ 175 – 185 R and C version
CONTROL CIRCUIT
F1
F1
KAKAKA
KM
A1
A3
180s
KS
A2
TH
LP
KS
KM
KA
LLSV
L1 L3 L2
Q1
KS
LPS
HP
DGT
KS
KM
F2
T1
T2
T3
ThM
M
2
1
CONTROL CIRCUIT
F1
F1
KS
KM
KAKAKA
KS
A1
LPS
A3
180s
HP
A2
DGT
TH
KA
KS
1
2
L1 L3 L2
T1
Q1
KM
F2
T2
T3
ThM
M
Wiring diagram with pump-down cycle
Compressor models SM/SZ175-185 (J, K, P, S, U, W, X, Y versions)
A1
A2
LP
Wiring diagram with pump-down cycle
LPS
A3
L1
MPM
1
N
Compressor models SY / SZ 240 - 300 - 380
A1
A2
LP
LPS
A3
MPM
Wiring diagram without pump-down cycle
A1
2
11
12
14
LPS
A3
A2
L1
MPM
1
N
2
11
12
14
S
Wiring diagram without pump-down cycle
A1
LPS
A3
A2
S
KS
MPM
S
Legends
20
Wiring diagram with pump-down cycle
Fuses F1
Compressor contactor KM
Control relay KA
Safety lo ck out relay KS
Optional sho rt cycle timer (3 min) 180 s
Extern al overload protection F2
Pump-d own pressure switch LP
High pressure sa fety switch HP
Control device TH
FRCC.PC.003.A5.22
Wiring diagram without pump-down cycle
Liquid Line Solenoid valve LLSV
Discharge gas th ermostat DGT
Fused disconnect Q1
Motor safety thermostat thM
Compressor motor M
Motor Protecti on Module MPM
Thermistor chain S
Safety p ressure switch LPS
Application guidelines
Motor protectionThe table below shows the protection method for the various compressors models.
SM/SZ 115-125-16 0-175-18 5
R & C version
SM 112- 124-147Internal motor protectionPhase sequence detector
SM/SZ 084 -09 0-10 0-110-120-14 8-
161 - SZ147
SM /SZ175-185
J-K-P-S-U-W-X-Y version
SY/SZ 240-300 -380Electronic module located in terminal box
Electrical data, connections and wiring
Overheating protectionOver current protectionLocked rotor protectionPhase reversal protection
Electronic module located in terminal boxReverse vent.
REC
Recommended Required No test or additional safeties required
REQREC
Compressor models SM/SZ084 - 090 - 100 110 - 112 - 120 - 124 - 147 - 148 - 161 have been
provided with an internal overload motor
protection to prevent against excessive current
and temperature caused by overloading,
low refrigerant ow phase loss or incorrect
motor rotation. The cutout current is the MCC
value listed in section "Three phase electrical
characteristics".
The protector is located in the star point of the
motor and, should it be activated, will cut out all
three phases. It will be reset automatically.
Compressor models SM/SZ175 - 185 R & C
versions have been provided with a bimetallic
single-pole, single-throw thermostat located
in the motor windings. In the event of motor
overheating caused by low refrigerant ow or
improper motor rotation, the thermostat will
open. Because the thermostat is an automatic
reset device, it must be wired within a lockout
safety circuit with a manual reset to restart the
unit. For over-current and phase loss protection,
an external overload protector must be used.
The external overload protector can be either a
thermal overload relay or a circuit breaker:
A thermal overload relay should be set to trip
at not more than 140% of the compressor-rated
load current.
While not compulsory, an additional external
overload protection is still advisable for either
alarm or manual reset.
Then it must be set below MCC value (at max
operating current):
• when the motor temperature is too high, then
the internal protector will trip
• when the current is too high the external
overload protection will trip before the internal
protection therefore oering possibility of
manual reset.
A circuit breaker, on the other hand, should be
set at not more than 125% of the compressor
rated load current.
The rated load current is the maximum current
expected during operations of the considered
application.
Further requirements for the external overload
protector are:
• Over-current protection: the protector must
trip within 2 minutes at 110% of the Maximum
Must-Trip current (MMT).
• Locked rotor protection: the protector must
trip within 10 seconds upon starting at a locked
rotor current (LRA).
• Single-phasing protection: the protector
must trip when one of the three phases fails.
Compressor models SY/SZ 240 - 300 - 380
and SM/SZ115-125-160-175-185 J, K, P, S,
U, W, X, Y versions are delivered with a pre-
installed motor protection module inside the
terminal box. This device provides for ecient
and reliable protection against overheating and
overloading (as well as phase loss/reversal for SY/
SZ 240-300-380).
FRCC.PC.003.A5.22
The motor protector comprises a control module
and PTC sensors embedded in the motor
winding. The close contact between thermistors
and windings ensures a very low level of thermal
inertia.
The motor temperature is being constantly
measured by a PTC thermistor loop
connected on S1-S2 (called 1-2 on SM/
SZ115-125 -160-175-185).
21
Application guidelines
Electrical data, connections and wiring
Phase sequence and reverse
rotation protection
If any thermistor exceeds its response
temperature, its resistance increases above
the trip level (4,500 Ω) and the output relay
then trips -ie. contacts M1-M2 (or 11-14 for SM/
SZ175-185) are open. After cooling to below
the response temperature (resistance < 2,750
Ω), a 5 minute time delay is activated. After this
delay has elapsed, the relay is once again pulled
in ie. contacts M1-M2 (11-14 for SM/SZ175-185)
are closed. The time delay may be cancelled by
means of resetting the mains (L-N disconnect) for
approximately 5 sec.
Use a phase meter to establish the phase
orders and connect line phases L1, L2 and L3
to terminals T1, T2 and T3, respectively. The
compressor will only operate properly in a single
Compressor model SM112-124-147 have no
internal reverse rotation protection. If reverse
rotation occurs it will be obvious as soon as
power is turned on. The compressor will not
build-up any pressure, the sound level will be
abnormally high and power consumption will be
minimal. In such case, shut down the compressor
A red/green twin LED is visible on the module.
A solid green LED denotes a fault free condition.
A blinking red LED indicates an identiable fault
condition:
PTC overheat
Appr. 1 second
Delay timer active (after PTC overheat)
Appr. 1 second
direction, and the motor is wound so that if the
connections are correct, the rotation will also be
correct.
immediately and connect the phases to their
proper terminals. Prolonged reverse rotation will
damage the compressor.
A phase sequence detector is strongly
recommended.
Compressor models SM / SZ 084 to 185 (except
SM112-124 & 147) incorporate an internal reverse
vent valve which will react in the presence of
reverse rotation and will allow refrigerant to
circulate through a by-pass from the suction to
the discharge. Although reverse rotation is not
destructive, even over long periods of time up
to several days it should be corrected as soon
as possible. Reverse rotation will be obvious
Compressor models SY / SZ 240 to 380 are
delivered with an electronic module which
provides protection against phase reversal and
loss at start-up. Apply the recommended wiring
diagrams. The circuit should be thoroughly
checked in order to determine the cause of the
phase problem before re-energizing the control
circuit.
The phase sequencing and phase loss
monitoring functions are active during a 5 sec.
window 1 sec. after compressor start-up (power
on L1-L2-L3).
to the user as soon as power is turned on; the
compressor will not build up any pressure, the
sound level will be abnormally high and power
consumption will be minimal. If reverse rotation
symptoms occur, shut the compressor down and
connect the phases to their proper terminals. If
reverse rotation is not halted, the compressor
will cycle o on the internal motor protection.
Should one of these parameters be incorrect, the
relay would lock out (contact M1-M2 open). The
red led on the module will show the following
blink code:
In case of phase
reverse error:
Appro. 1 second
In case of phase
loss error:
Appro. 1 second
22
FRCC.PC.003.A5.22
Application guidelines
Electrical data, connections and wiring
Voltage unbalance
Compressor
Phase monitoring
Phase sequence module logic
start
0 1 s 6 s
The operating voltage limits are shown in the
table section "Motor voltage". The voltage
applied to the motor terminals must lie within
these table limits during both start-up and
normal operations. The maximum allowable
% voltage
unbalance
Vavg = Mean voltage of phases 1, 2, 3.
V1-2 = Voltage between phases 1 & 2.
The lockout may be cancelled by resetting the
power mains (disconnect L-N) for approximately
5 sec.
voltage unbalance is 2%. Voltage unbalance
causes high amperage over one or several
phases, which in turn leads to overheating and
possible motor damage. Voltage unbalance is
given by the formula:
x 100
2 x Vavg
V1-3 = Voltage between phases 1 & 3.
V2-3 = Voltage between phases 2 & 3.
FRCC.PC.003.A5.22
23
Application guidelines
Approval and certications
Approvals and certicates
Pressure Equipment
Directive 97/23/EC
Low voltage directive
2006/95/EC
SM / SY / SZ scroll compressors comply with the
following approvals and certicates.
CE 0062 or CE 0038 or CE0871
(European Directive)
UL
(Underwriters Laboratories)
Other approvals / certicatesContact Danfoss
ProductsSM084 to 185SZ084 to 185 & SY185SY/SZ 240 to 380
Refrigerating uidsGroup 2Group 2Group 2
Category PEDIIIIII
Evaluation module D1D1D1
Service temperature - Ts-31°F < Ts < 145°F-31°F < Ts < 127°F-31°F < Ts < 127°F
Service pressure - Ps368 psig363 psig290 psig
Declaration of conformity
ref Pressure Equipment Directive 97/23/EC
ProductsSM/SZ084 to SY/SZ380
Declaration of conformity
ref. Low voltage Directive 2006/95/EC
Certicates are listed on the product datasheets:
http://www.danfoss.com/odsg
SM / SY / SZ models
All
All 60 Hz
SM / SY / SZ models
Contact Danfoss
Contact Danfoss
Machines directives
2006/42/EC
Internal free volume
ProductsSM/SZ084 to SY/SZ380
Manufacturer's declaration of incorporation
ref. Machines Directive 2006/42/EC
The scroll compressor application range is
inuenced by several parameters which need to
be monitored for a safe and reliable operation.
These parameters and the main
recommendations for good practice and safety
devices are explained hereunder.
When choosing a refrigerant, dierent aspects
must be taken into consideration:
• Legislation (now and in the future)
• Safety
• Application envelope in relation to expected
running conditions
R22 is an HCFC refrigerant and is still a wide
use today. It has a low ODP (Ozone Depletion
Potential). Starting from 1st January 2010, the
use of virgin R22 refrigerant is no longer allowed
in the European Union. Refer to FRCC.EN.049 for
R22 retrot recommendations.
• Refrigerant and lubricants
• Motor supply
• Compressor ambient temperature
Application envelope (evaporating temperature,
condensing temperature, return gas
temperature)
Additional points could inuence the nal
choice:
• Environmental considerations
• Standardisation of refrigerants and lubricants
• Refrigerant cost
• Refrigerant availability
When R22 is applied in refrigeration applications
it can lead to high discharge temperature.
Carefully check all other parameters that can
inuence the discharge temperature.
R407C
R134 a
R404A
R507
Mineral oil
R407C is an HFC refrigerant and has a zero ozone
depletion potential (ODP=0) R407C is a zeotropic
mixture and has a temperature glide of 45.3°F
R134a is an HFC refrigerant and has zero ozone
depletion potential (ODP = 0). R134a is a pure
refrigerant and has zero temperature glide. For
R404A is an HFC refrigerant and has zero
ozone depletion potential (ODP = 0). R404A
is especially suitable for low evaporating
temperature applications but it can also be
applied to medium evaporating temperature
applications. R404A is a mixture and has a very
R507 is an HFC refrigerant with properties
comparable to R404A. R507 has no ozone
depletion potential (ODP = 0). As with R404A,
R507 is particularly suitable for low evaporating
Mineral oil can be applied in system using HCFC's
refrigerant because it has a good miscibility
with HCFC and oil that leave the compressor
with refrigerant may not be trapped in lines or
but has a superior thermodynamic properties
compared to R22.
applications with high evaporating and high
condensing temperatures, R134a is the ideal
choice.
small temperature glide, and therefore must
be charged in its liquid phase, but for most
other aspects this small glide can be neglected.
Because of the small glide, R404A is often called
a near-azeotropic mixture.
temperature applications but it can also be
used for medium evaporating temperature
applications. R507 is an azeotropic mixture with
no temperature glide.
exchangers. The chlorine contained in HCFC's
improves lubricity in bearings used with mineral
oil. Mineral oil has a very low hygroscopicity but
may chemically react with water and form acids.
POE oil
Polyol Ester Oil (POE) is miscible with HFC's
(while mineral oil is not), but has to be evaluated
regarding lubricate ability in compressors.
POE oil has better thermal stability than
FRCC.PC.003.A5.22
refrigerant mineral oil. POE is more hygroscopic
and also holds moisture more tightly than
mineral oil. It also chemically react with water
leading to acid and alcohol formation.
25
Application guidelines
Operating conditions
Motor supplySM / SY / SZ scroll compressors can be operated
at nominal voltages as indicated on page 18.
Under-voltage and over-voltage operation is
Compressor ambient
temperature
SM / SY / SZ compressors can be applied from
-31°F to 145.4°F (for SM/SZ084 to 185) and 127.4°F
(for SY/SZ 240 to 380) ambient temperature. The
compressors are designed as 100 % suction gas
High ambient temperature
In case of enclosed tting and high ambient
temperature it’s recommend to check the
temperature of power wires and conformity to
their insulation specication.
Low ambient temperature
Although the compressor itself can withstand
low ambient temperature, the system may
require specic design features to ensure safe
Application envelope at dew
temperatures
The operating envelopes for SM / SY / SZ
scroll compressors are given in the gures
below, where the condensing and evaporating
temperatures represent the range for steadystate operation. Under transient conditions, such
as start-up and defrost, the compressor may
operate outside this envelope for short periods.
The gures below show the operating envelopes
for SM / SY compressors with refrigerants R22
and for SZ compressors with R407C, R134a,
R404A and R507C.
allowed within the indicated voltage ranges. In
case of risk of under-voltage operation, special
attention must be paid to current draw.
cooled without need for additional fan cooling.
Ambient temperature has very little eect on the
compressor performance.
In case of safe tripping by the compressor
overload protection the compressor must cool
down to about 140°F before the overload will
reset. A high ambient temperature can strongly
delay this cool-down process.
and reliable operation. See section ‘Specic
application recommendations’.
The operating limits serve to dene the
envelope within which reliable operations of the
compressor are guaranteed:
• Maximum discharge gas temperature: 275°F
• A suction superheat below 9°F (18°F for R407C)
is not recommended due to the risk of liquid
ood back
• Maximum superheat of 54°F
• Minimum and maximum evaporating and
condensing temperatures as per the operating
envelopes.
SM084 to 185
SY185 to 380
R22
26
Condensing temperature (°F)
FRCC.PC.003.A5.22
160
150
140
130
120
110
100
90
80
-1001 02030405060
S.H. = 9°F
S.H. = 20°F
S.H. = 54°F SUPERHEAT
Evaporating temperature (°F)
160
150
Application guidelines
Operating conditions
SZ084 to 185
R134a
SZ240 - 380
R134a
150
140
130
120
110
100
Condensing temperature (°F)
90
80
010203040506070
S.H. = 20°F
S.H. = 54°F SUPERHEAT
Evaporating temperature (°F)
160
150
140
130
S.H. = 20 °F
S.H. = 54°F SUPERHEAT
120
Condensing temperature (°F)
110
100
90
80
0102030405060
Evaporating temperature (°F)
SZ084 to 185
R404A / R507A
140
130
120
110
Condensing temperature (°F)
100
90
80
-100102030405060
S.H. = 20°F
S.H. = 54°F SUPERHEAT
Evaporating temperature (°F)
FRCC.PC.003.A5.22
27
Application guidelines
Operating conditions
SZ084 to 185 & SY185
R407C
at DEW temperature
SZ240 to 380 & SY240-300
R407C
at DEW temperature
160
150
140
130
120
110
Condensing temperature (°F)
100
90
80
-10010203040506070
160
150
140
130
120
110
Condensing temperature (°F)
100
S.H. = 20°F
S.H. = 20°F
Dew temperature conditions
S.H. = 54 °F SUPERHEAT
Evaporating temperature (°F)
Dew temperature conditions
S.H. = 54°F SUPERHEAT
Application envelopes at
mean temperatures
28
90
80
-100102030405060
Refrigerant R407C is a zeotropic mixture,
which causes a temperature glide in both the
evaporator and condenser. When discussing
evaporating and condensing temperatures
therefore, it is important to indicate whether
these are DEW point values or MEAN point
values. In the gure below, the dashed lines
reect constant temperature and do not
correspond with the constant pressure lines.
FRCC.PC.003.A5.22
Evaporating temperature (°F)
For a given cycle, the MEAN point temperatures
are typically about 35.6° to 37.4°F lower than
DEW point temperatures. In these Selection and
Application Guidelines, Danfoss Commercial
Compressors displays temperatures as DEW
point values.
The performance tables for R407C are also based
on DEW point values.
Condensing temperature (°F)
pressure (log)
enthalpy
Dew
Dew
Mean
Mean
Application guidelines
Dew temperature and mean
temperature for R407C
Operating conditions
The following operating diagrams show the dierence between mean and dew temperature
application envelopes.
Dew temperature
Example for SZ 084 to 185
Mean temperature
Example for SZ 084 to 185
160
150
140
130
120
110
Condensing temperature (°F)
100
90
80
-10010203040506070
160
150
140
130
S.H. = 20°F
Dew temperature conditions
S.H. = 54 °F SUPERHEAT
Evaporating temperature (°F)
Mean temperature conditions
FRCC.PC.003.A5.22
120
110
100
90
80
-100102030405060
S.H. = 20 °F
S.H. = 54 °F SUPERHEAT
Evaporating temperature (°F)
29
160
Condensing temperature (°F)
Evaporating temperature (°F)
Application guidelines
Operating conditions
Discharge temperature
protection
The discharge gas temperature must not exceed
275°F. The discharge gas thermostat accessory kit
(code 7750009) includes all components required
for installation, as shown below. The thermostat
must be attached to the discharge line within
150 mm from the compressor discharge port and
must be thermally insulated and highly xed on
the pipe.
DGT protection is required if the high and low
pressure switch settings do not protect the
compressor against operations beyond its
specic application envelope. Please refer to the
examples on following page, which illustrates
where DGT protection is required (ex.1) and
where it is not (ex.2).
A discharge temperature protection device must
be installed on all heat pumps. In reversible
air-to-air and air-to-water heat pumps the
150
140
discharge temperature must be monitored
during development test by the equipment
manufacturer.
The DGT should be set to open at a discharge gas
temperature of 275°F.
The compressor must not be allowed to cycle
on the discharge gas thermostat. Continuous
operations beyond the compressor’s operating
range will cause serious damage to the
compressor.
Thermostat
Discharge line
Bracket
Example 1
Insulation
HP1
130
120
110
100
90
80
-100102030405060
DGT - limit
LP2LP1
Example 1 (R22, SH = 20°F)
LP switch setting:
LP1 = 26 psig (1.4°F)
HP switch setting:
HP1 = 363 psig (143.6°F)
Risk of operation beyond the application envelope.
DGT protection required.
High and low pressure
protection
High pressure
A high-pressure (HP) safety switch is required to
shut down the compressor should the discharge
pressure exceed the values shown in the table
next page. The high-pressure switch can be set
to lower values depending on the application
and ambient conditions. The HP switch must
Example 2
R22
Example 2 (R22, SH = 20°F)
LP switch setting:
LP2 = 42 psig (19.4°F)
HP switch setting:
HP2 = 305 psig (131°F)
No risk of operation beyond the application envelope.
No DGT protection required.
either be placed in a lockout circuit or consist of
a manual reset device to prevent cycling around
the high-pressure limit. If a discharge valve is
used, the HP switch must be connected to the
service valve gauge port, which must not be
isolated.
HP2
30
FRCC.PC.003.A5.22
T
Application guidelines
Operating conditions
Internal pressure relief valve
Low pressure
The SY/SZ240 to SY/SZ380 incorporate an
internal relief valve set to open between the
HP
internal high and low pressure sides of the
compressor when the pressure dierential
between the discharge and suction pressures
surpasses 450 to 551 psi.
This safety feature prevents the compressor from
LP
Relief valve
developing dangerously high pressures should
the high pressure cutout, for whatever reason,
fail to shut down the compressor.
A low pressure (LP) safety switch must be
used. Deep vacuum operations of a scroll
compressor can cause internal electrical arcing
and scroll instability. Danfoss scroll compressors
exhibit high volumetric eciency and may draw
very low vacuum levels, which could induce such
a problem. The minimum low-pressure safety
switch (loss of charge safety switch) setting is
Working pressure range high side158 - 401152 - 42297 - 292184 - 451
Working pressure range low side20 - 10015 - 928 - 5629 - 106
Maximum high pressure safety switch setting406427297457
*LP safet y switch shall never be bypassed and shall have no time delay.
** Recommended pump-down switch settings: 1.5 bar (R22, R407C, R4 04A) or 1 bar (R134a) below nominal evaporating pressure.
given in the following table. For systems without
pump-down, the LP safety switch must either
be a manual lockout device or an automatic
switch wired into an electrical lockout circuit.
The LP switch tolerance must not allow for
vacuum operations of the compressor. LP switch settings for pump-down cycles with automatic
reset are also listed in the table below.
R22
psig
R407C
psig
R134a
psig
R4 04A/ R507A
psig
Note that these two dierent low pressure
switches also require dierent settings. The low
pressure pump down switch setting must always
be within the operating envelope, for example
13 psi for R22. The compressor can be operated
Cycle rate limitDanfoss recommends a restart delay timer to
limit compressor cycling. The timer prevents
reverse compressor rotation, which may occur
during brief power interruptions.
full time under such condition. The minimum low
pressure safety switch setting may be outside
the normal operating envelope and should
only be reached in exceptional (emergency)
situations, for example 7 psi for R22.
necessary, place an anti-short-cycle timer in the
control circuit, connected as shown in the wiring
diagram section "Suggested wiring diagrams
logic". A three-minute (180-sec) time out is
recommended.
The system must be designed in a way that
guarantees a minimum compressor running
time of 2 minutes so as to provide for sucient
Please contact Danfoss Technical Support for any
deviation from this guidelines.
motor cooling after start-up along with proper
oil return. Note that the oil return may vary since
it depends upon system design.
There must be no more than 12 starts per
hour (6 when a resistor soft-start accessory is
A1
H
TT
A2
introduced); a number higher than 12 reduces
the service life of the motor-compressor unit. If
FRCC.PC.003.A5.22
~
KA
TH
KA
~
A2A3A1
180 s
31
U trap, as short as possible
3D flexibility
Application guidelines
System design recommendations
General
Essential piping design
considerations
Suction lines
Successful application of scroll compressors
is dependent on careful selection of the
compressor for the application. If the compressor
is not correct for the system, it will operate
Proper piping practices should be employed to
ensure adequate oil return, even under minimum
load conditions with special consideration given
to the size and slope of the tubing coming
from the evaporator. Tubing returns from the
evaporator should be designed so as not to trap
oil and to prevent oil and refrigerant migration
back to the compressor during o-cycles.
Piping should be designed with adequate
three-dimensional exibility. It should not be in
contact with the surrounding structure, unless
If the evaporator lies above the compressor, as
is often the case in split or remote condenser
systems, the addition of a pump-down cycle
is strongly recommended. If a pump-down
cycle were to be omitted, the suction line must
have a loop at the evaporator outlet to prevent
refrigerant from draining into the compressor
during o-cycles.
If the evaporator were situated below the
compressor, the suction riser must be trapped so
as to prevent liquid refrigerant from collecting at
the outlet of the evaporator while the system is
beyond the limits given in this manual. Poor
performance, reduced reliability, or both may
result.
a proper tubing mount has been installed.
This protection proves necessary to avoid
excess vibration, which can ultimately result
in connection or tube failure due to fatigue
or wear from abrasion. Aside from tubing and
connection damage, excess vibration may be
transmitted to the surrounding structure and
generate an unacceptable noise level within that
structure as well (for more information on noise
and vibration, see the section on: "Sound and
vibration management").
idle, which would mislead the expansion valve's
sensor (thermal bulb) at start-up.
To condenser
HP
U-trap
0.5% slope
max. 13 ft
max. 13 ft
13 ft/s or more
U-trap, as short as possible
26 to 40 ft/s
0.5% slope
13 ft/s or more
LP
Evaporator
Discharge lines
Heat exchangers
32
When the condenser is mounted at a higher
position than the compressor, a suitably sized
«U»-shaped trap close to the compressor is
necessary to prevent oil leaving the compressor
from draining back to the discharge side of the
compressor during o cycle. The upper loop also
helps avoid condensed liquid refrigerant from
draining back to the compressor when stopped.
An evaporator with optimized distributor and
circuit will give correct superheat at outlet and
optimal use of the exchange surface. This is
critical for plate evaporators that have generally
a shorter circuit and a lower volume than shell &
tubes and air cooled coils.
For all evaporator types a special care is required
for superheat control leaving the evaporator and
oil return.
FRCC.PC.003.A5.22
Upper loop
HP
U Trap
LP
Condenser
A sub-cooler circuit in the condenser that creates
high sub cooling will increase eciency at high
condensing pressure.
Furthermore, for good operation of the
expansion device and to maintain good
eciency in the evaporator it is important
to have an appropriate sub cooling. Without
adequate sub cooling, ash gas will be formed at
the expansion device resulting in a high degree
of vapor at the expansion device inlet leading to
low eciency.
Application guidelines
System design recommendations
Refrigerant charge limitDanfoss SM / SY / SZ compressors can tolerate
liquid refrigerant up to a certain extend
without major problems. However, excessive
liquid refrigerant in the compressor is always
unfavorable for service life. Besides, the
installation cooling capacity may be reduced
because of the evaporation taking place in the
compressor and/or the suction line instead of the
evaporator. System design must be such that the
amount of liquid refrigerant in the compressor
is limited. In this respect, follow the guidelines
given in the section: “essential piping design
recommendations” in priority.
BELOW charge limitABOVE charge limit
Cooling only systems,
Packaged units
Cooling only systems
with remote condensor
and split system units
Reversible heat pump system
No test or additional safeties required
Refrigerant migration & oodback test
REC
Crankcase heater, because full system
REC
charge is not denable (risk of overcharging)
Specic tests for repetitive oodback
REQ
Sump heater
REQ
Defrost test For more details refer to section "Reversible heat pump system.
REQ
Recommended Required No test or additional safeties required
Note: for special conditions such as low ambient temperature, low refrigerant load or brazed plate heat exchangers please refer
to corresponding section "Specic application recommendations".
REQREC
Use the tables below to quickly evaluate the
required compressor protection in relation with
the system charge and the application.
Compressor models
S 084-090-10019
S 110 -12022
S 112-124 -14717
S 148-16128
S 175-18530
S 24035
S 300-38044
Refrigerant migration & oodback test
REQ
Sump heater
REQ
Refrigerant migration & oodback test
REQ
Sump heater
REQ
Liquid receiver (in association with LLSV & pump down)
REC
Refrigerant charge limit
(lbs)
More detailed information can be found in the paragraphs hereafter. Please contact Danfoss
Technical Support for any deviation from these guidelines.
O-cycle migrationO-cycle refrigerant migration is likely to occur
when the compressor is located at the coldest
part of the installation, when the system uses
a bleed-type expansion device, or if liquid is
allowed to migrate from the evaporator into
the compressor sump by gravity. If too much
liquid refrigerant accumulates in the sump it
will saturate the oil and lead to a ooded start:
when the compressor starts running again,
the refrigerant evaporates abruptly under the
sudden decrease of the bottom shell pressure,
causing the oil to foam. In extreme situations,
this might result in liquid slugging (liquid
entering the scroll elements), which must be
avoided as it causes irreversible damage to the
compressor.
Danfoss SM/SZ/SY scroll compressors can
tolerate occasional ooded starts as long as
the total system charge does not exceed the
maximum compressor refrigerant charge.
A suitable test to evaluate the risk of o-cycle
migration is the following:
• Stabilize the non running system at 41°F
ambient temperature,
• Raise the ambient temperature to 68°F and
keep it for 10 minutes,
• Start the compressor and monitor sump
temperature, sight glass indication and sound
level.
The presence of liquid in the crankcase can be
easily detected by checking the sump level
through the oil sight glass. Foam in the oil sump
indicates a ooded start.
A noisy start, oil loss from the sump and sump
cool down are indications for migration.
Depending on the amount of migration graduate
measures shall be taken:
• Sump heater
• Liquid line solenoid valve
• Pump down cycle
FRCC.PC.003.A5.22
33
Application guidelines
System design recommendations
Sump heaterThe surface sump heaters are designed to
protect the compressor against o cycle
migration of refrigerant. When the compressor
is idle, the oil temperature in the sump of the
compressor must be maintained at no lower
than 18°F above the saturation temperature of
the refrigerant on the low-pressure side. This
requirement ensures that the liquid refrigerant
is not accumulating in the sump. A sump heater
is only eective if capable of sustaining this
level of temperature dierence. Tests must be
conducted to ensure that the appropriate oil
temperature is maintained under all ambient
conditions (temperature and wind). However,
below 23°F ambient temperature and a wind
speed of above 16 ft/sec, we recommend that
the heaters be thermally insulated in order to
limit the surrounding energy losses.
Since the total system charge may be undened,
a sump heater is recommended on all standalone compressors and split systems. In addition,
any system containing a refrigerant charge in
excess of the maximum recommended system
charge for compressors requires a crankcase
heater. A crankcase heater is also required on all
reversible cycle applications.
The heater must be energized for a minimum
of 6 hours before initial start-up (compressor
service valves opened) and must remain
energized whenever the compressor is o.
Provide separate electrical supply for the
heaters so that they remain energized even
when the machine is out of service (eg. seasonal
shutdown).
Sump heater accessories are available from
Danfoss (see section "Accessories").
Liquid line solenoid valve
(LLSV)
Pump-down cycle
An LLSV may be used to isolate the liquid charge
on the condenser side, thereby preventing
against charge transfer or excessive migration to
the compressor during o-cycles.
A pump-down cycle represents one of the most
eective ways to protect against the o-cycle
migration of liquid refrigerant. Once the controls
has been satised, a solenoid valve closes on
the condenser outlet. The compressor then
pumps the majority of the system charge into
the condenser and receiver before the system
stops on the low pressure pump-down switch.
This step reduces the amount of charge on the
low side in order to prevent o-cycle migration.
Recommended settings of the low-pressure
pump-down switch can be found in the table
section "High and low pressure protection". For
suggested wiring diagrams, please see section
"Suggested wiring diagram logic".
In certain conditions, the discharge valve may
not completely seal and result in compressor
restarts during pump down applications. An
external, non-bleeding check valve may need to
be installed.
The quantity of refrigerant on the low pressure
side of the system can be further reduced by
using a pump-down cycle in association with the
LLSV.
Tests for pump down cycle approval:
• As the pump-down switch setting is inside the
application envelope, tests should be carried
out to check unexpected cut-out during
transient conditions (ie. defrost – cold starting).
When unwanted cut-outs occur, the low
pressure pump-down switch can be delayed. In
this case a low pressure safety switch without
any delay timer is mandatory.
• While the thermostat is o, the number of
pressure switch resets should be limited to
avoid short cycling of the compressor. Use
dedicated wiring and an additional relay which
allows for one shot pump-down.
The pump-down allows to store all the
refrigerant in the high pressure side circuit. On
unitary or close-coupled systems, where the
system refrigerant charge is expected to be both
correct and denable the entire system charge
34
FRCC.PC.003.A5.22
Application guidelines
System design recommendations
Liquid ood back
may be stored in the condenser during pumpdown if all components have been properly
sized.
Other application needs a liquid receiver to store
the refrigerant.
During normal operation, refrigerant enters
the compressor as a superheated vapor. Liquid
ood back occurs when a part of the refrigerant
entering the compressor is still in liquid state.
Liquid ood back test - Repetitive liquid
ood back testing must be carried out under
expansion valve threshold operating conditions:
a high pressure ratio and minimum evaporator
load, along with the measurement of suction
superheat, oil sump temperature and discharge
gas temperature.
During operations, liquid ood back may be
detected by measuring either the oil sump
temperature or the discharge gas temperature.
If at any time during operations, the oil sump
temperature drops to within 10K or less above
Receiver dimensioning requires special attention.
The receiver shall be large enough to contain
part of the system refrigerant charge but it shall
not be dimensioned too large. A large receiver
easily leads to refrigerant overcharging during
maintenance operation.
system design must be such that repeated and
excessive ood back is not possible.
A continuous liquid ood back will cause oil
dilution and, in extreme situations lead to lack
of lubrication and high rate of oil leaving the
compressor.
the saturated suction temperature, or should
the discharge gas temperature be less than 54°F
above the saturated discharge temperature, this
indicates liquid ood back.
Continuous liquid ood back can occur with
a wrong dimensioning, a wrong setting or
malfunction of the expansion device or in case of
evaporator fan failure or blocked air lters.
A suction accumulator providing additional
protection as explained hereunder can be used
to solve light continuous liquid ood back.
Suction accumulator
Suction accumulator: a suction accumulator
oers protection against refrigerant ood back
at start-up, during operations or defrosting by
trapping the liquid refrigerant upstream from
the compressor. The suction accumulator also
protects against o-cycle migration by providing
additional internal free volume to the low side of
the system.
A suction accumulator must be carefully
dimensioned, taking into account the refrigerant
charge as well as the gas velocity in the suction
line.
FRCC.PC.003.A5.22
The accumulator should not be sized for less
than 50% of the total system charge. Tests must
be conducted to determine the actual refrigerant
holding capacity needed for the application.
Depending on the operating conditions it may
happen that the recommended connections of
the accumulator are one size smaller than the
suction line.
35
Application guidelines
Specic application recommendations
Low ambient application
Low ambient start-upUnder cold ambient conditions (<32°F), upon
start-up the pressure in the condenser and,
if present, the receiver may be so low that
a sucient pressure dierential across the
expansion device cannot be developed to
properly feed the evaporator. As a result, the
compressor may go into a deep vacuum, which
can lead to compressor failure due to internal
arcing and instability in the scroll members.
Under no circumstances should the compressor
be allowed to operate under vacuum. The
low-pressure control must be set in accordance
with the table section "High and low pressure
protection" in order to prevent this from
happening.
Early feeding of the evaporator and
management of the discharge pressure could
help to attenuate these eects.
Low pressure dierentials can also cause
the expansion device to «hunt» erratically,
which might cause surging conditions within
the evaporator, with liquid spillover into the
compressor. This eect is most pronounced
during low load conditions, which frequently
occur during low ambient conditions.
Low ambient operations
The Danfoss SM/SY/SZ scroll compressor requires
a minimum pressure dierential of 87 to 102 psi
between the suction and discharge pressures
to force the orbiting scroll down against the
oil lm on the thrust bearing. Anything less
than this dierential and the orbiting scroll
can lift up, causing a metal-to-metal contact.
It is therefore necessary to maintain sucient
discharge pressure in order to ensure this
pressure dierential. Care should be taken during
low ambient operations when heat removal
from air-cooled condensers is greatest and
head pressure control may be required for low
ambient temperature applications. Operation
under low pressure dierential may be observed
by a signicant increase in the sound power level
generated by the compressor.
It is recommended that the unit be tested and
monitored at minimum load and low ambient
conditions as well. The following considerations
should be taken into account to ensure proper
system operating characteristics.
Expansion device: The expansion device
should be sized to ensure proper control of
the refrigerant ow into the evaporator. An
oversized valve may result in erratic control.
This consideration is especially important in
manifolded units where low load conditions may
require the frequent cycling of compressors.
This can lead to liquid refrigerant entering the
compressor if the expansion valve does not
provide stable refrigerant super-heat control
under varying loads.
levels during low loading periods. A minimum of
9 °F stable superheat is required.
Head pressure control under low ambient
conditions: Several possible solutions are
available to prevent the risk of compressor to
vacuum and low pressure dierential between
the suction and discharge pressures.
In air-cooled machines, cycling the fans with
a head pressure controller will ensure that the
fans remain o until the condensing pressure
has reached a satisfactory level. Variable speed
fans can also be used to control the condensing
pressure. In water-cooled units, the same can
be performed using a water regulator valve
that is also operated by head pressure, thereby
ensuring that the water valve does not open until
the condensing pressure reaches a satisfactory
level.
The minimum condensing pressure must be
set at the minimum saturated condensing
temperature shown in the application envelopes.
Under very low ambient conditions, in which
testing has revealed that the above procedures
might not ensure satisfactory condensing and
suction pressures, the use of a head pressure
control valve is recommended. Note: This
solution requires extra refrigerant charge, which
can introduce other problems. A non-return
valve in the discharge line is recommended and
special care should be taken when designing the
discharge line.
36
The superheat setting of the expansion device
should be sucient to ensure proper superheat
FRCC.PC.003.A5.22
For further information, please contact Danfoss.
Application guidelines
Specic application recommendations
Sump heaters
Low load operations
Brazed plate heat
exchangers
Sump heaters are strongly recommended on
all systems where the compressor is exposed to
low ambient temperatures, especially split and
remote condenser installations. The sump heater
The compressors should be run for a
minimum period in order to ensure that the
oil has sucient time to properly return to the
A brazed plate heat exchanger needs very little
internal volume to satisfy the set of heat transfer
requirements. Consequently, the heat exchanger
oers very little internal volume for the
compressor to draw vapor from on the suction
side. The compressor can then quickly enter into
a vacuum condition; it is therefore important
that the expansion device be sized correctly
and that a sucient pressure dierential across
the expansion device be available to ensure
adequate refrigerant feed into the evaporator.
This aspect is of special concern when operating
the unit under low ambient and load conditions.
For further information on these conditions,
please refer to the previous sections.
will minimize refrigerant migration caused by
the large temperature gradient between the
compressor and the remainder of the system,
please refer to section "O-cycle migration".
compressor sumps and that the motor has
sucient time to cool under conditions of lowest
refrigerant mass ows.
Due to the small volume of the brazed plate heat
exchanger, no pump-down cycle is normally
required. The suction line running from the heat
exchanger to the compressor must be trapped to
avoid refrigerant migration to the compressor.
When using a brazed plate heat exchanger as
the condensing coil, a sucient free volume for
the discharge gas to accumulate is required in
order to avoid excess pressure buildup. At least 1
meter of discharge line is necessary to generate
this volume. To help reduce the gas volume
immediately after start-up even further, the
supply of cooling water to the heat exchanger
may be opened before the compressor starts
up so as to remove superheat and condense the
incoming discharge gas more quickly.
Electronic expansion valveThe use of an electronic expansion valve requires
a specic compressor start / stop control.
A specific compressor start sequence control has
to be set when an electronic expansion valve
(EXV) is used. The sequence must be adjusted
according to the EXV step motor speed to allow
time for the EXV to open before the compressor
starts to avoid running under vacuum conditions.
The EXV should be closed at compressor stop
not to let refrigerant in liquid phase entering the
Reversible heat pump
systems
Transients are likely to occur in reversible heat
pump systems, i.e. a changeover cycle from
cooling to heating, defrost or low-load short
cycles. These transient modes of operation
may lead to liquid refrigerant carryover (or
oodback) or excessively wet refrigerant return
conditions. As such, reversible cycle applications
require specic precautions for ensuring a long
compressor life and satisfactory operating
characteristics. Regardless of the refrigerant
charge in the system, specic tests for repetitive
compressor. Ensure that the EXV closes when the
supply voltage to the controller is interrupted (ie
power cut o) by the use of a battery back up.
EXV Opened
Closed
Compressor On
O
oodback are required to conrm whether
or not a suction accumulator needs to be
installed. A crankcase heater and discharge gas
thermostat are required for reversible heat pump
applications.
The following considerations cover the most
important issues when dealing with common
applications. Each application design however
should be thoroughly tested to ensure
acceptable operating characteristics.
FRCC.PC.003.A5.22
37
Application guidelines
Specic application recommendations
Sump heatersSump heaters are mandatory on reversible
cycle applications given the high probability of
liquid migration back to the compressor sump
Discharge temperature
thermostat
Heat pumps frequently utilize high condensing
temperatures in order to achieve a sucient
temperature rise in the medium being heated. At
the same time, they often require low evaporator
pressures to obtain sucient temperature
dierentials between the evaporator and the
outside temperature. This situation may result
in high discharge temperature; as such, it is
mandatory that a discharge gas thermostat
be installed on the discharge line to protect
Discharge line
and reversing valve, solenoid
valves
The Danfoss SM/SY/SZ scroll compressor is a high
volumetric machine and, as such, can rapidly
build up pressure in the discharge line if gas
in the line becomes obstructed even for a very
short period of time which situation may occur
with slow-acting reversing valves in heat pumps.
Discharge pressures exceeding the operating
envelope may result in nuisance high-pressure
switch cutouts and place excess strain on both
the bearings and motor.
To prevent such occurrences, it is important that
a 1-meter minimum discharge line length be
allowed between the compressor discharge port
and the reversing valve or any other restriction.
This gives sucient free volume for the discharge
gas to collect and to reduce the pressure peak
during the time it takes for the valve to change
during o-cycles due to the outdoor location of
most units and operations during low ambient
conditions.
the compressor from excessive temperatures.
Operating the compressor at too high discharge
temperatures can result in mechanical damage
to the compressor as well as thermal degradation
of the compressor lubricating oil and a lack of
sucient lubrication.
The discharge gas thermostat should be set
to shut down the compressor in the event
discharge gas rises above 275°F.
position. At the same time, it is important that
the selection and sizing of the reversing or 4-way
valve ensure that the valve switches quickly
enough to prevent against too high discharge
pressure and nuisance high-pressure cutouts.
Check with the valve manufacturer for optimal
sizing and recommended mounting positions.
In applications with heat recovery or condenser
partialisation, servo piloted solenoid valve has
to be properly sized or associated with a second
small valve in parallel, in order to avoid quick
discharge pressure drops when opening. This
phenomenon could lead to hammering eects
and create constraints on the non return valve
integrated in discharge tting (SM/SY/SZ180 to
380).
Defrost and reverse cycle
38
The Danfoss SM/SY/SZ scroll compressor has the
ability to withstand a certain amount of liquid
refrigerant dynamic slug.
When compressors are installed in parallel,
in order to limit liquid amount handled per
compressor when beginning and ending defrost,
it is recommended to avoid running part load
(keep all compressors running or keep them
stopped when moving 4-way valves).
FRCC.PC.003.A5.22
For further details, please refer to Parallel
application guidelines FRCC.PC.005.
EXV can also be opened when compressors are
stopped and before 4 way valve is moving in
order to decrease pressure dierence. Opening
degree and time have to be set in order to keep
a minimum pressure dierence for 4 way valve
moving.
Application guidelines
Specic application recommendations
Suction line accumulator
Water utilizing systems
The use of a suction line accumulator is strongly
recommended in reversible cycle applications as
a result of the possibility of a substantial quantity
of liquid refrigerant remaining in the evaporator,
which acts as a condenser during the heating
cycle.
This liquid refrigerant can then return to the
compressor, either ooding the sump with
refrigerant or as a dynamic liquid slug when
Apart from residual moisture in the system
after commissioning, water could also enter the
refrigeration circuit during operation. Water in
the system shall always be avoided. Not only
because it can shortly lead to electrical failure,
sludge in sump and corrosion but in particular
because it can cause serious safety risks.
Common causes for water leaks are corrosion
and freezing.
Corrosion: Materials in the system shall be
compliant with water and protected against
corrosion.
the cycle switches back to a defrost cycle or to
normal cooling operations.
Sustained and repeated liquid slugging and
oodback can seriously impair the oil’s ability
to lubricate the compressor bearings. This
situation can be observed in wet climates where
it is necessary to frequently defrost the outdoor
coil in an air source heat pump. In such cases a
suction accumulator becomes mandatory.
Freezing: When water freezes into ice its volume
expands which can damage heat exchanger
walls and cause leaks. During o periods water
inside heat exchangers could start freezing when
ambient temperature is lower than 32°F. During
on periods ice banking could occur when the
circuit is running continuously at too low load.
Both situations should be avoided by connecting
a pressure and thermostat switch in the safety
line.
FRCC.PC.003.A5.22
39
Application guidelines
Sound and vibration management
Starting sound level
During start-up transients it is natural for the
compressor sound level to be slightly higher
than during normal running. SM / SY / SZ scroll
compressors exhibit very little increased start-up
transient sound. If a compressor is miswired,
compressor rotation is characterized by an
objectionable sound. To correct reverse rotation,
disconnect power and switch any two of the
three power leads at the unit contactor. Never
switch leads at the compressor terminals.
the compressor will run in reverse. Reverse
Running sound level
50 Hz60 Hz
Model
S 084708718748748775 5011120Z0356
S 0907087287587787755011120Z0356
S 100708738758778775 5011120Z0356
S 1107587787888187755010120Z0356
S 112756--786--120Z0035S 1207587787888187755010120Z0356
S 124736--776--120Z0035S 147
S 148
S 161
S 17580881882.588487755007120Z0353
S 18580881882.588487755007120Z0353
S 24082783.578578777755016120Z0355
S 30082784786787.577755016120Z0355
S 3808778 7.579279177755022120Z0355
For SM/SZ147-3 - 50 Hz, use acoustic hood reference 120Z135 For SM148 - 161 code 3, no acoustic hood available
Sound power and attenuation are given at rated ARI conditions, measured in free space. * Bottom insulations are provided in surface sump heater accessories.
Materials are UL approved and RoHS compliant.
Data given for code 4 compressor, for full data details and capacity tables refer to Online Datasheet Generator: ww w.danfoss.com/ODSG
Sound power
R22R407CR22R407C
dB(A)
746778786818120Z0035-
7987988388387755017120Z0356
79.587988488387755017120Z0356
Attenuation
dB(A)
Sound power
dB(A)
Attenuation
dB(A)
Sound power
dB(A)
Attenuation
dB(A)
Sound power
dB(A)
Attenuation
dB(A)
Acoustic
hood code
number
Bottom
insulation
code n°
*
Stopping sound level
Sound generation in
a refrigeration or air
conditioning system
40
SM / SY / SZ compressors are equipped with a
discharge valve which closes at compressor shut
down and thus prevents the compressor from
running backwards. This reduces the stopping
sound to a metallic click caused by the closing
valve.
Typical sound and vibration in Refrigeration and
Air-Conditioning systems encountered by design
and service engineers may be broken down into
the following three source categories.
Sound radiation: This generally takes an
airborne path.
FRCC.PC.003.A5.22
When the pressure dierence or gas ow at shut
down should be very low, this can delay the
discharge valve from closing and lead to a longer
noise duration.
Mechanical vibrations: These generally extend
along the parts of the unit and structure.
Gas pulsation: This tends to travel through the
cooling medium, i.e. the refrigerant.
The following sections will focus on the causes
and methods of mitigation for each of the above
sources.
Application guidelines
Sound and vibration management
Compressor sound radiation
For sound radiating from the compressor, the
emission path is airborne and the sound waves
are travelling directly from the machine in all
directions.
The Danfoss SM / SY / SZ scroll compressor is
designed to be quiet and the frequency of the
sound generated is pushed into the higher
ranges, which not only are easier to reduce but
also do not generate the penetrating power of
lower-frequency sound.
Use of sound-insulation materials on the inside of
unit panels is an eective means of substantially
reducing the sound being transmitted to the
outside. Ensure that no components capable of
transmitting sound / vibration within the unit
Mechanical vibrationsVibration isolation constitutes the primary
method for controlling structural vibration.
Danfoss SM / SY / SZ scroll compressors are
designed to produce minimal vibration during
operations. The use of rubber isolators on
the compressor base plate or on the frame
of a manifolded unit is very eective in
reducing vibration being transmitted from the
compressor(s) to the unit. Rubber grommets
are supplied with all Danfoss compressors.
Once the supplied rubber grommets have been
properly mounted, vibration transmitted from
the compressor base plate to the unit are held
to a strict minimum. In addition, it is extremely
important that the frame supporting the
come into direct contact with any non-insulated
parts on the walls of the unit.
Because of the Danfoss’s unique design of a
full-suction gas-cooled motor, compressor body
insulation across its entire operating range is
possible. Acoustic hoods are available from
Danfoss Commercial Compressors as accessories.
They have been developed to meet specic extra
low noise requirement. They incorporate sound
proong materials and oer excellent high and
low frequency attenuation. These hoods are
quick and easy to install and do not increase the
overall size of the compressors to a great extend.
Refer to section "Running sound level" for sound
attenuation and code numbers.
mounted compressor be of sucient mass and
stiness to help dampen any residual vibration
potentially transmitted to the frame. For further
information on mounting requirements, please
refer to the section on mounting assembly.
The tubing should be designed so as to both
reduce the transmission of vibrations to other
structures and withstand vibration without
incurring any damage. Tubing should also be
designed for three-dimensional exibility. For
more information on piping design, please see
the section entitled "Essential piping design
considerations".
Gas pulsationThe Danfoss SM / SY / SZ scroll compressor
has been designed and tested to ensure that
gas pulsation has been optimized for the
most commonly encountered air conditioning
pressure ratio. On heat pump installations and
other installations where the pressure ratio
lies beyond the typical range, testing should
be conducted under all expected conditions
FRCC.PC.003.A5.22
and operating congurations to ensure
that minimum gas pulsation is present. If an
unacceptable level is identied, a discharge
muer with the appropriate resonant volume
and mass should be installed. This information
can be obtained from the component
manufacturer.
41
Application guidelines
Installation
Compressor handling and
storage
Each SM / SY / SZ compressor is shipped with
printed Instructions for installation. These
instructions can also be downloaded from our
Each Danfoss SM / SY / SZ scroll compressor is
equipped with two lift rings on the top shell.
Always use both these rings when lifting the
compressor. Use lifting equipment rated and
certied for the weight of the compressor.
A spreader bar rated for the weight of the
compressor is highly recommended to ensure a
better load distribution. The use of lifting hooks
closed with a clasp and certied to lift the weight
of the compressor is also highly recommended.
Always respect the appropriate rules concerning
lifting objects of the type and weight of these
compressors. Maintain the compressor in an
upright position during all handling manoeuvres
(maximum of 15° from vertical).
Never use only one lifting lug to lift the
compressor. The compressor is too heavy for the
single lug to handle, and the risk is run that the
lug could separate from the compressor with
extensive damage and possible personal injury
as a result.
web site:
www.danfoss.com or directly from:
http://instructions.cc.danfoss.com
and between -31°F and 158°F when charged with
nitrogen.
When the compressor is mounted as part
of an installation, never use the lift rings on the
compressor to lift the installation. The risk is run
that the lugs could separate from the compressor
or that the compressor could separate from the
base frame with extensive damage and possible
personal injury as a result.
Never apply force to the terminal box with the
intention of moving the compressor, as the
force placed upon the terminal box can cause
extensive damage to both the box and the
components contained inside.
HEAVY
Compressor mounting
Store the compressor not exposed to rain,
corrosive or ammable atmosphere between
-31°F and 122°F when charged with refrigerant
Maximum inclination from the vertical plane
while operating must not exceed 3 degrees.
All compressors come delivered with four rubber
mounting grommets and metal sleeve liners that
serve to isolate the compressor from the base
frame. These grommets must always be used to
Mounting of SM/SZ 084-090-100-110-120-148161-175-185: the required bolt size is HM8. This
bolt must be tightened to a torque of 15 ft.lbs.
The bolts and washers are supplied with the
assembly kit.
Mounting of SM/SZ 112-124-147: the required
bolt size is HM8. This bolt must be tightened to
a torque of 11 ft/lbs. The bolt and washers are
supplied with the assembly kit. When a surface
sump heater is used, it must be applied after
grommets are mounted on compressor in order
to avoid surface sump heater damage.
do not lift
manually
mount the compressor in single application.
These grommets attenuate to a great extent the
transmission of compressor vibrations to the
base frame. The grommets must be compressed
until contact between the at washer and the
steel-mounting sleeve is established.
HM 8 bolt
Lock washer
Flat washer
Steel mounting sle eve
Rubber grommet
Nut
HM 8 bolt
Lock washer
Flat washer
Steel mounting
sleeve
Rubber grommet
Nut
Compressor
base plate
1.10 inch
0.59 inch
42
FRCC.PC.003.A5.22
Application guidelines
Installation
Mounting of SY/SZ 240-300-380: the required
bolt size is HM10. The minimum required at
washer outside diameter is 20 ft.lbs. Mounting
bolts must be tightened to a torque of 30 ft.lbs.
These bolts and washers are not supplied with
the compressor.
Note: The large at washer must be positioned
in place before shipping the unit with the
compressor installed.
Note: for parallel assemblies see specic recommendations in Danfoss parallel application
guidelines", FRCC.PC.005.
Compressor holding chargeEach compressor is shipped with a nominal dry
nitrogen holding charge between 4 and 10 psi
and is sealed with elastomer plugs.
Before the suction and discharge plugs are
removed, the nitrogen holding charge must
be released via the suction schrader valve to
avoid an oil mist blowout. Remove the suction
System cleanlinessThe refrigerant compression system, regardless
of the type of compressor used, will only provide
high eciency and good reliability, along with a
long operating life, if the system contains solely
the refrigerant and oil it was designed for. Any
other substances within the system will not
improve performance and, in most cases, will be
highly detrimental to system operations.
The presence of non-condensable substances
and system contaminants, such as metal
shavings, solder and ux, have a negative
impact on compressor service life. Many of these
contaminants are small enough to pass through
a mesh screen and can cause considerable
damage within a bearing assembly. The use
of highly-hygroscopic polyester oil in SZ
compressors requires that the oil be exposed to
the atmosphere just as little as possible.
Lock washer *
Large flat *
1.06 inch washer
Steel mounting sleeve
Rubber grommet
* not supplied with compressor
HM 10 Bolt *
Compressor base plate
1.41 inch
Nut *
plug rst and the discharge plug afterwards.
The plugs shall be removed only just before
connecting the compressor to the installation
in order to avoid moisture from entering the
compressor. When the plugs are removed, it is
essential to keep the compressor in an upright
position so as to avoid oil spillage.
System contamination is one of main factors
aecting equipment reliability and compressor
service life. It is important therefore to
take system cleanliness into account when
assembling a refrigeration system.
During the manufacturing process, circuit
contamination may be caused by:
• Brazing and welding oxides,
• Filings and particles from the removal of burrs
in pipe-work,
• Brazing ux,
• Moisture and air.
Consequently, when building equipment
and assemblies, the precautions listed in the
following paragraphs must be taken.
TubingOnly use clean and dehydrated refrigeration
grade copper tubing. Tube cutting must be
carried out so as not to deform the tubing
roundness and to ensure that no foreign debris
remains within the tubing. Only refrigerantgrade ttings should be used and these must be
Brazing and soldering
Do not blend the compressor discharge or
suction lines or force system piping into the
compressor connections, because this will
increase stresses that are a potential cause of
FRCC.PC.003.A5.22
of both a design and size to allow for a minimum
pressure drop through the completed assembly.
Follow the brazing instructions next pages.
Never drill holes into parts of the pipe-works
where llings and particles can not be removed.
failure. Recommended brazing procedures and
material, are described on following page. Never
drill holes into parts of the pipe-works. Where
llings and particles can not be removed.
43
heat shield
Application guidelines
Installation
Copper to copper connections
Dissimilar metals connection
Compressor connection
When brazing copper-to-copper connections,
the use of a copper / phosphorus brazing alloy
containing 5% silver or more with a melting
When manipulating dissimilar metals such as
copper and brass or steel, the use of silver solder
and anti-oxidant ux is necessary.
When brazing the compressor ttings, do not
overheat the compressor shell, which could
severely damage certain internal components
due to excessive heating. Use of a heat shield
and/or a heat-absorbent compound is highly
recommended. Due to the relatively sizable
tubing and tting diameters used for the large
scroll, a double tipped torch using acetylene is
recommended for the S240-300-380 brazing
operation.
A
C
B
For rotolock version compressors, solder sleeves
are available. For brazing the suction and
discharge connections, the following procedure
is advised:
•
Make sure that no electrical wiring is connected
to the compressor.
•
Protect the terminal box and compressor
painted surfaces from torch heat damage (see
diagram).
•
Remove the teon gaskets when brazing
rotolock connectors with solder sleeves.
•
Use only clean refrigeration-grade copper
tubing and clean all connections.
•
Use brazing material with a minimum of 5%
silver content.
•
Purge nitrogen or CO2 through the compressor
in order to prevent against oxidation and
ammable conditions. The compressor should
not be exposed to the open air for extended
periods.
•
Use of a double-tipped torch is recommended.
•
Apply heat evenly to Area A until the brazing
temperature is reached. Move the torch to
Area B and apply heat evenly until the brazing
temperature has been reached there as well, and
then begin adding the brazing material. Move
the torch evenly around the joint, in applying
temperature of below 1472°F is recommended.
No ux is required during brazing.
only enough brazing material to ow the full
circumference of the joint.
•
Move the torch to Area C only long enough to
draw the brazing material into the joint, but not
into the compressor.
•
Remove all remaining ux once the joint has
been soldered with a wire brush or a wet cloth.
Remaining ux would cause corrosion of the
tubing.
In addition, for discharge connections equipped
with a non return valve integrated in discharge
tting (SY/SZ240-300) the direction of the
torch has to be as described on the picture, and
maximum brazing time should be less than 2
minutes to avoid NRVI damages.
Ensure that no ux is allowed to enter into the
tubing or compressor. Flux is acidic and can
cause substantial d amage to the internal parts of
the system and compressor.
The polyolester oil used in SY / SZ compressors
is highly hygroscopic and will rapidly absorb
moisture from the air. The compressor must
therefore not be left open to the atmosphere
for a long period of time. The compressor tting
plugs shall be removed just before brazing the
compressor.
Before eventual unbrazing the compressor or
any system component, the refrigerant charge
must be removed from both the high and low
pressure sides. Failure to do so may result in
serious personal injury. Pressure gauges must be
used to ensure all pressures are at atmospheric
level.
For more detailed information on the
appropriate materials required for brazing
or soldering, please contact the product
manufacturer or distributor. For specic
applications not covered herein, please contact
Danfoss Commercial Compressors for further
information.
44
FRCC.PC.003.A5.22
Application guidelines
Installation
System pressure test
Leak detection
Always use an inert gas such as nitrogen for
pressure testing. Never use other gasses such as
an inammable mixture. Do not exceed the
following pressures:
oxygen, dry air or acetylene as these may form
Maximum compressor test pressure (low side)SM/SZ 084 - 185: 363 psigSZ/SY240 - 380: 290 psig
Maximum compressor test pressure (high side)464 psig
Maximum pressure dierence between high and
low side of the compressor:
Pressurize the system on HP side rst then LP
side to prevent rotation of the scroll. Never let
the pressure on LP side exceed the pressure on
HP side with more than 72 psi.
On SY/SZ240-300 models which have an
or if an external non return valve is present on
the discharge line, we advise to pressurize the
system not quicker than 70 psi/s to allow enough
pressure equalisation between LP and HP side
over the scroll elements.
348 psig
internal non return-valve in discharge tting
Leak detection must be carried out using a
mixture of nitrogen and refrigerant or nitrogen
and helium, as indicated in the table below.
Never use other gasses such as oxygen, dry air
Compressor modelLeak detection with refrigerantLeak detection with a mass spectrometer
SM-SY compressorsNitrogen & R22Nitrogen & Helium
or acetylene as these may form an inammable
mixture.
Pressurize the system on HP side rst then Low
side.
Vacuum evacuation and
moisture removal
SZ compressorsNitrogen & R134a or R407CNitrogen & Helium
Note 1: Leak detection with refrigerant may be forbidden in some countries. Check local regulations.
Note 2: The use of leak detecting additives is not recommended as they may aect the lubricant properties.
Moisture obstructs the proper functioning of the
compressor and the refrigeration system.
SM / SY / SZ compressors are delivered with
<100ppm moisture level. The required moisture
level in the circuit after vacuum dehydration
Air and moisture reduce service life and increase
condensing pressure, and cause excessively high
discharge temperatures, which can destroy the
lubricating properties of the oil. Air and moisture
also increase the risk of acid formation, giving
rise to copper platting. All these phenomena
can cause mechanical and electrical compressor
failure.
For these reasons it’s important to perform a
vacuum dehydration on the system to remove
all residual moisture from the pipe-work after
must be < 100 ppm for systems with an SM / SY
/ SZ.
• Never use the compressor to evacuate the
system.
• Connect a vacuum pump to both the LP & HP
sides.
• Evacuate the system to a pressure of 0.02 inHg
(300 μm Hg) absolute.
Do not use a megohm meter nor apply power to
the compressor while it’s under vacuum as this
may cause internal damage.
assembly;
FRCC.PC.003.A5.22
45
Application guidelines
Installation
Filter driersA properly sized & type of drier is required.
Important selection criteria include the driers
water content capacity, the system refrigeration
capacity and the system refrigerant charge.
The drier must be able to reach and maintain
a moisture level of 50 ppm end point dryness
(EPD).
For new installations with SM/SY/SZ compressors
with polyolester oil, Danfoss recommends using
the Danfoss DML (100% molecular sieve) solid
core lter drier. Molecular sieve lter driers with
loose beads from third party suppliers shall be
avoided. For servicing of existing installations
where acid formation is present the Danfoss
DCL (solid core) lter driers containing activated
alumina are recommended.
Refrigerant charging
For the initial charge the compressor must not
run and eventual service valves must be closed.
Charge refrigerant as close as possible to the
nominal system charge before starting the
compressor. This initial charging operation must
be done in liquid phase. The best location is on
the liquid line between the condenser outlet
and the lter drier. Then during commissioning,
when needed, a complement of charge can be
done in liquid phase: slowly throttling liquid in
on the low pressure side as far away as possible
from the compressor suction connection while
compressor is running. The refrigerant charge
quantity must be suitable for both summer and
winter operations.
The drier is to be oversized rather than under
sized. When selecting a drier, always take into
account its capacity (water content capacity),
the system refrigeration capacity and the system
refrigerant charge.
After burn out, remove & replace the liquid line
lter drier and install a Danfoss type DAS burnout drier of the appropriate capacity. Refer to the
DAS drier instructions and technical information
for correct use of the burnout drier on the
liquid line. Also for new installations with SM
compressors with mineral oil the Danfoss DCL
drier is recommended.
Vacuum or charge from one side can seal the
scrolls and result in a non-starting compressor.
When servicing, always ensure that LP/HP
pressures are balanced before starting the
compressor.
Be sure to follow all government regulations
regarding refrigerant reclamation and
storage. For more detailed information, see
"Recommended refrigerant system charging
practice" news bulletin FRCC.EN.050.
Insulation resistance and
dielectric strength
46
Insulation resistance must be higher than 1
megohm when measured with a 500 volt direct
current megohm tester.
Each compressor motor is tested at the factory
with a high potential voltage (hi-pot) that
exceeds the UL requirement both in potential
and in duration. Leakage current is less than 0.5
mA.
SM/SY/SZ scroll compressors are congured
with the pump assembly at the top of the shell,
and the motor below. As a result, the motor
can be partially immersed in refrigerant and
oil. The presence of refrigerant around the
motor windings will result in lower resistance
FRCC.PC.003.A5.22
values to ground and higher leakage current
readings. Such readings do not indicate a faulty
compressor.
In testing insulation resistance, Danfoss
recommends that the system be rst operated
briey to distribute refrigerant throughout the
system. Following this brief operation, retest the
compressor for insulation resistance or current
leakage.
Never reset a breaker or replace a fuse without
rst checking for a ground fault (a short circuit to
ground). Be alert for sounds of arcing inside the
compressor.
Application guidelines
Installation
Commissioning
Oil level checking and
top-up
The system must be monitored after initial
start-up for a minimum of 60 minutes to ensure
proper operating characteristics such as:
• Proper metering device operation and desired
super heat readings,
• Suction and discharge pressure are within
acceptable levels,
In installations with good oil return and line
runs up to 66 ft, no additional oil is required.
If installation lines exceed 66 ft, additional oil
may be needed. 1 or 2% of the total system
refrigerant charge (in weight) can be used to
roughly dene the required oil top-up quantity
but in any case the oil charge has to be adjusted
based on the oil level in the compressor sight
glass.
When the compressor is running under stabilized
conditions the oil level must be visible in the
sight glass.
The presence of foam lling in the sight glass
indicates large concentration of refrigerant in the
oil and / or presence of liquid returning to the
compressor.
• Low foaming in sight glass and compressor
sump temperature 18°F above saturation
temperature to show that there is no refrigerant
migration taking place,
• Acceptable cycling rate of compressors,
including duration of run times,
• Current draw of individual compressors within
acceptable values (max. operating current),
• No abnormal vibrations and noise.
after the compressor stops.
When the compressor is o, the level in the
sight glass can be inuenced by the presence of
refrigerant in the oil.
Always use original Danfoss oil from new cans.
Compressor seriesOil
SMMineral oil 160P
SYP.O.E. 320 SZ
SZP.O.E. 160 SZ
Top-up the oil while the compressor is idle. Use
the schrader connector or any other accessible
connector on the compressor suction line and
a suitable pump. See News bulletin «Lubricants
lling in instructions for Danfoss Commercial
Compressors».
SM161BrazedInternalSM161-3VAISM161-4VAISM161-7VAISM161- 9VA I
SM175
SM185
SY185 **
SY240
SY300
SY380
** No module version available
SM/SY compressors in industrial pack: use numbers from above table and replace the last digit by "M". Example: SY240A3CAM, except for voltage codes
6 and 7 available in single pack only
BrazedThermostatSM185-3CAISM185-4CAISM185-7CAISM185-9C AI
BrazedModule 24 V ACSM185-3PCISM185-4PCISM185 -7PCI-
BrazedModule 230 V AC-SM185- 4XCI-SM185-9XCI
RotolockThermostatSM185-3RISM185-4RISM185-7RISM185-9RI
RotolockModule 24 V ACSM185-3SCISM185- 4SCISM185-7SCIRotolockModule 230 V AC-SM185- 4YCI-SM185-9YCI
SZ compressors in industrial pack: use numbers from above table and replace the last digit by "M". Example: SZ240A4CAM, except for voltage codes 6
and 7 available in single pack only
3479
200-230/3/60
460/3/60
380-400/3/50
575/3/60
500/3/50
380/3/60
50
FRCC.PC.003.A5.22
Application guidelines
Solder sleeve adaptator set
Accessories
Typ e Code n°DescriptionApplicationPackaging
7765005 Solder sleeve adapter set (1"3/4~1"1/8), (1"1/4~3/4")SM/SZ084-090-100Multipack6
120Z0 405 Solder sleeve adapter set (1"3/4~1"3/8), (1"1/4~7/8")
7765006* Solder sleeve adapter set (1"3/4~1"3/8), (1"1/4~7/8")
7765028 Solder sleeve adapter set (2"1/4~1"5/8), (1"3/4~1"1/8)SM/SZ160-175-185, SY/SZ 240-300Multipack6
120Z0317
* Diameter restrictor
Rotolock adaptor
Typ e Co de n°DescriptionApplicationPackaging
120Z0366 Adaptor (1"1/4 Rotolock -3/4" ODS)Models with 3/4" ODFMultipack10
120Z0367 Adaptor (1"1/4 Rotolock - 7/8" ODS)Models with 7/8" ODFMultipack10
120Z0364 Adaptor (1"3/4 Rotolock -1"1/8 ODS)Models with 1"1/8 ODFMultipack10
120Z0 431 Adaptor (1"3/4 Rotolock -1"3/8" ODS)Models with 1"3/8 ODFMultipack10
320SZ775 4121POE lubricant, 320SZ, 1.05 quart canSY with R22Multipack12
320SZ120Z0572 POE lubricant, 320SZ, 2.64 quart canSY with R22Multipack4
160P7754001Mineral oil, 160P, 2.64 quart canSM with R22Multipack8
160P7754002Mineral oil, 160P, 5.28 quart canSM with R22Multipack4
Miscellaneous
Typ eCode NoDescriptionApplicationPackaging
8156 019Sight glass with gaskets (black & white)All modelsMultipack4
8156129Gasket for sight glasse, 1"1/8 (white teon)All modelsMultipack10
7956005Gasket for sight glass, 1"1/8 (white teon)All modelsMultipack50
81540 01Danfoss Commercial Compressors blue spray paintAll modelsSingle pack1
Pack
Size
Pack
Size
54
FRCC.PC.003.A5.22
Danfoss Commercial Compressors is a worldwide manufacturer of compressors and condensing
units for refrigeration and HVAC applications. With a wide range of high quality and innovative
products we help your company to nd the best possible energy ecient solution that respects
the environment and reduces total life cycle costs.
We have 40 years of experience within the development of hermetic compressors which has
brought us amongst the global leaders in our business, and positioned us as distinct variable
speed technology specialists. Today we operate from engineering and manufacturing facilities
spread across three continents.
Our products can be found in a variety of applications such as rooftops, chillers, residential air
conditioners, heatpumps, coldrooms, supermarkets, milk tank cooling and industrial cooling
processes.
member of:
www.asercom.org
http://danfoss.us.com
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice.
This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specications already agreed.
All trademarks in this material are property of the respec tive companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
FRCC.PC.003.A5.22 - April 2014 - Replace FRCC.PC.003.A4.22 - February 2013Copyright Danfoss Commercial Compressors - 04/2014
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.