Danfoss QDV 15 Data sheet

Data Sheet
Shut-off valve Type QDV 15
Quick Closing Drain Valve designed particularly for draining oil from systems
QDV is a shut-o valve, designed particularly for draining oil from systems containing refrigerant (ammonia) under pressure.
The valve will close immediately on release of the handle, thus protecting user and environment against unnecessary refrigerant leaks. The valve should as a rule be installed as illustrated in g. 1.
QDV is designed to meet the safety demands specied by national and international authorities within industrial refrigeration.
Features:
• Applicable to R717 (ammonia)
• Meets the safety demands within industrial refrigeration
• Handle can be positioned 360°
• Built-in integral relief device opening when 16 bar (232 psig) is exceeded. (preventing hydraulic pressure building up between shut- o valve and QDV)
• Can be supplied together with a stop valve for quick on site mounting (g. 1)
• Max. operating pressure: 40 bar (580 psig)
• Temperature range: -50 °C – +150 °C (-58 °F – +302 °F)
Classication: DNV, CRN, BV, EAC etc. To get an updated list of certication on the products please contact your local Danfoss Sales Company.
AI183386419531en-001001
Shut-o valve, Type QDV 15
Media
Refrigerants
Liquid refrigerant can be trapped between the stop valve and drain valve causing an unsafe, high-pressure situation, or potentially damaging either valve.
The internal relief device in the Danfoss QDV allows refrigerant to slowly bleed if internal valve pressure exceeds 16 bar (232 psig). Further, the valve is easily actuated by hand (without tools), and has an internal spring mechanism to instantly close the valve if the actuator is let go. All QDV valves are in angle orientation with FPT outlet, suitable for safe draining.
New refrigerants
Danfoss products are continually evaluated for use with new refrigerants depending on market requirements.
When a refrigerant is approved for use by Danfoss, it is added to the relevant portfolio, and the R number of the refrigerant (e.g. R513A) will be added to the technical data of the code number. Therefore, products for specic refrigerants are best checked at store.danfoss.com/en/, or by contacting your local Danfoss representative.
© Danfoss | Climate Solutions | 2021.02 AI183386419531en-001001 | 2
Oil
Q
DV
Temperature range
-50 °C – 150 °C (-58 °F – 302 °F)
Maximum operating pressure
40 bar (580 psig)
No.
Part
Material
DIN/EN
ASTM
1
Housing
Steel
G20Mn5QT EN10213-3
LCC A352
2
Bonnet
Steel St37-2
S235JR EN 10025
AISI 1015
3
Spindle/Cone
Stainless steel X10CrNiS18-9
S189 EN 10088-3
AISI 303
4
Spring
Steel5O-ring
Cloroprene
6
O-ring
Cloroprene
Shut-o valve, Type QDV 15
Product specication
Pressure and temperature data
QDV is a backpressure dependent valve. If any tube or hose is mounted on the outlet of the QDV it has to be calculated to prevent back pressure building up when relieving.
For further information please see installation guide for QDV. Flammable hydrocarbons are not recommended, for further information please contact your local Danfoss Sales Company.
Figure 1: QDV
Table 1: Pressure and temperature
Material specication
Figure 2: QDV 15
Table 2: QDV 15
© Danfoss | Climate Solutions | 2021.02 AI183386419531en-001001 | 3