Danfoss PX-F Data sheet

Data Sheet PX-F Series Self-Regulating Cable
Pipe Freeze Protection
General Information
Technical Data
The Danfoss PX-F self-regulating heating cables provide the solution to basic freeze protection applications. The self -regulating Danfoss PX-F series ensure maximum energy eciency by pro­ducing heat only when and where it is needed as it adjusts the power output to the varying conditions along the length of the pipe.
• Cable can be overlapped without creating hot spots or causing a burn out
• Can be cut and spliced in the eld, simplifying the installation process and reducing waste
• Rugged 16 AWG bus cable with longer runs
• Wide variety of wattages
• Limited ten year warranty
Available power outputs:
Cable Diameter: 0.45 x 0.216” (11.5 x 5.5 mm) Rated voltage: 120V-277V Minimum bending radius: 1” (25 mm) (radius to the inside of the tape) Max. rated temperature: 150°F (65°C) Powered
Bus wire type: 16 AWG, (1.25 mm2), Tinned Copper
3, 5, 8, 10 W/ft. at 240 VAC and 120 VAC at 50°F (+10°C) (10, 15, 25, 33) W/m at 240 VAC and 120 VAC at 50°F (+10°C)
185°F (85°C) Un-powered
Product Illustration ­Cable Cross-Section
Typical Application
© Copyright 2016 Danfoss NA.EFH.PXD.06/16 TEL: 866-676-8062, FAX: 416-352-5981 1
PX-F Cable
Danfoss PX Output Curves
Output Curves
W/ft
12.0 40
11.0
10.0
9.0
8.0
7.0
6.0
5.0
4.0
3.0
2.0
1.0
0.0
W/m
35
30
25
20
15
10
DANFOSS PX-F
Power Output Rating
PX-F10
Voltage Conversion Table W/ft. (W/m) @50°F (10°C)
PX-F8
Cable 208V 240V 277V
PX-F3 2.5 (8.5) 3.0 (10.0) 3.5 (12.5)
PX-F5
PX-F3
5
85.0
0.0
50.0 (10)
70.0 (20)
Pipe Temperature °F (°C)
(30)
105.0 (40)
120.0 (50)
140.0 (60)
PX-F5 4.0 (13.5) 5 (15.0) 5.5 (17.5)
PX-F8 7.0 (23.0) 8 (25.5) 8.5 (27.5)
PX-F10 9.5 (31.5) 10.0 (33.0) 10.5 (35.0)
F C
Maximum Total Cable Length (ft./m)
Ordering Information PX Cables ­Cut to Order (by the ft.)
Start-up Temp. 120V 240V
Breaker Size 15A 20A 30A 40A 15A 20A 30A 40A
50°F (10°C) 315 (95) - - - 672 (205) - - -
PX-F3
(3W/ft.)
5°F (-15°C) 266 (69) 295 (90) 312 (95) - 460 (140) 610 (186) 640 (195) -
-15°F (-25°C) 197 (60) 266 (81) 312 (95) - 400 (123) 541 (165) 640 (195) -
50°F (10°C) 197 (67) 262 (80) - - 475 (145) 532 (162) - -
PX-F5*
(5W/ft.)
5°F (-15°C) 148 (45) 200 (61) 262 (80) - 300 (93) 410 (125) 525 (160) -
-15°F (-25°C) 131 (40) 177 (54) 262 (80) - 265 (82) 365 (111) 525 (160) -
50°F (10°C) 141 (43) 190 (58) 206 (63) - 285 (88) 384 (117) 413 (126) -
PX-F8*
(8W/ft.)
5°F (-15°C) 96 (30) 128 (39) 190 (58) 203 (62) 197 (60) 246 (75) 384 (117) 410 (125)
-15°F (-25°C) 88 (27) 108 (33) 167 (51) 203 (62) 164 (50) 230 (70) 345 (105) 410 (125)
50°F (10°C) 108 (33) 148 (45) 177 (54) - 230 (70) 295 (90) 354 (108) -
PX-F10*
(10W/ft.)
5°F (-15°C) 82 (25) 108 (33) 150 (46) 174 (53) 165 (50) 213 (65) 312 (95) 345 (105)
-15°F (-25°C) 72 (22) 98 (30) 141 (43) 174 (53) 148 (45) 190 (58) 279 (85) 345 (105)
*RX-C Cable
Part No. Output @ 50° F (10° C) Voltage
088L1460* 3W/ft 120V
088L1461* 3W/ft 240V
088L1462* 5W/ft 120V
088L1463* 5W/ft 240V
088L1469* 8W/ft 120V
088L1468* 8W/ft 240V
088L1479* 10W/ft 120V
088L1478* 10W/ft 240V
*Minimum Order is 25 ft. (Non-Returnable)
© Copyright 2016 Danfoss NA.EFH.PXD.06/16 TEL: 866-676-8062, FAX: 416-352-5981 2
Ordering Information PX Cables ­By the Spool
Part No. Voltage
Output @ 50°F (10°
C)
Length (ft.)
088L1402 120V 3W/ft 250
088L1470 120V 3W/ft 1,000
088L1412 240V 3W/ft 250
088L1471 240V 3W/ft 1,000
088L1422 120V 5W/ft 250
088L1472 120V 5W/ft 1,000
088L1432 240V 5W/ft 250
088L1473 240V 5W/ft 1,000
088L1516 120V 8W/ft 250
088L1517 120V 8W/ft 1,000
088L1518 240V 8W/ft 250
088L1519 240V 8W/ft 1,000
088L1520 120V 10W/ft 250
088L1521 120V 10W/ft 1,000
088L1522 240V 10W/ft 250
088L1523 240V 10W/ft 1,000
PX Cable Selection Chart (120V/240V)
Insulation Thickness
1/2” Min. 1” Min. 2” Min.
Pipe Diameter
(inches)
Pipe Material
Metal PVC Metal PVC Metal PVC
1/2 3W/ft. 5W/ft. 3W/ft. 3W/ft. 3W/ft. 3W/ft.
3/4 3W/ft. 5W/ft. 3W/ft. 3W/ft. 3W/ft. 3W/ft.
1 5W/ft. 5W/ft. 3W/ft. 3W/ft. 3W/ft. 3W/ft.
1-1/4 5W/ft. 8W/ft. 3W/ft. 5W/ft. 3W/ft. 3W/ft.
1-1/2 5W/ft. 8W/ft. 3W/ft. 5W/ft. 3W/ft. 3W/ft.
2 5W/ft. 8W/ft. 5W/ft. 5W/ft. 3W/ft. 3W/ft.
2-1/2 8W/ft.
3 8W/ft.
4 10W/ft.
6 10W/ft.*
8 -
Consult Factory
Consult Factory
Consult Factory
Consult Factory
Consult Factory
5W/ft. 5W/ft. 3W/ft. 3W/ft.
5W/ft. 5W/ft. 3W/ft. 5W/ft.
5W/ft. 8W/ft. 3W/ft. 5W/ft.
8W/ft.
10W/ft.
Consult Factory
Consult Factory
5W/ft. 5W/ft.
5W/ft. 8W/ft.
Chart based on minimum ambient temperature -22°F / -30°C *Requires 2 runs
© Copyright 2016 Danfoss NA.EFH.PXD.06/16 TEL: 866-676-8062, FAX: 416-352-5981 3
Controls
Part No. Description
088L3422 Weatherproof Thermostat with Water-tight Enclosure, 120V-277V
Accessories
Warranty
Technical Services
Part No. Description
088L0006 Power Connection Kit - Cable to Power Lead, Includes One End Seal
088L0008 Splice/Tee Kit, Includes One End Seal
088L0023 Power Connection Kit - Cable to Box, Includes One End Seal
088L0409 Aluminum Application Tape (165 feet)
088L0412 Warning Labels, 10 pcs.
088L1457 End Seal Kit, includes 5 end seals
Limited ten year warranty.
For technical questions, please contact Danfoss Heating Division North America at 1-866-676-8062. More information on Danfoss Electric Heating products is available at www.LX.Danfoss.com.
Danfoss can accept no responsibility for possible errors in catalogs, brochures, other printed materials, and website information. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alteration can be made without subsequent changes being necessary in
specications already agreed upon. All trademarks in this material are property of the respective companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Danfoss
Toll Free: 1-866-676-8062 Fax: 416-352-5981 www.LX.Danfoss.com www.Heating.Danfoss.us
© Copyright 2016 Danfoss NA.EFH.PXD.06/16 TEL: 866-676-8062, FAX: 416-352-5981 4
Danfoss PX
BRINGING WARMTH TO LIFE