Status Logic........................................................................................................................................................................................ 9
Configure Communication for the Function Block..............................................................................................................9
Configure Primary Communication for Function Block................................................................................................9
Configure Redundant Communication for Function Block...................................................................................... 10
Pre-Made Service Screen.............................................................................................................................................................11
IEC 61508-3 Annex D Supplemental Information.............................................................................................................. 12
PLUS+1® Compliant PVED_CLS_STAT_MSG_OP Function Block
Before You Begin
Before reading this manual, read and understand the safety manual of the entire library (Safety Manual
and Programmer Guide - General, document number AQ00000254).
Warning
Do not change parameters while the machine is driving. Before changing parameters bring the machine
into a safe state to prevent harm for the operator and bystanders.
Warning
Fault detection and diagnostics must be tested with the final application which is assembled from the
function blocks.
PLUS+1® Compliant PVED_CLS_STAT_MSG_OP Function Block
PVED_CLS_STAT_MSG_OP Function Block
This function block configures the PVED_CLS_STAT_MSG_OP for use with the PVED-CLS.
The inputs of the block are formatted to generate the message identifier that the PVED-CLS transmits.
This block receives the message and reformats the data for use in PLUS+1® GUIDE. For more information,
refer to PVED-CLS communication protocol.
Inputs
Enter the PVED_CLS_STAT_MSG_OP function block for an overview of its signals.
To avoid compiler errors, use only the data types specified in this table.
ParameterTypeRangeUnitDescription
ParaBus————This bus contains configuration values. You can replace these values with signals
routed from the application if desired.
CAN.PortPort————Determines which CAN port to transmit data from. This variable can be found in
the CAN sub-bus if using the Main Template.
ChkptBOOLT/F——Enables advanced checkpoints with namespace for each Diag signal.
T: Include checkpoints when compiled.
F: Do not include checkpoints when compiled.
Parameters
Learn how the function block uses parameters to customize the function.
To avoid compiler errors, use only the data types specified in this table.
TimeoutU1610 to 10000msMaximum time in ms between messages before a timeout fault is triggered.
————
CRC 16 used by the PVED-CLS messages.
Polynomial: 0xC86C
Primary default: 19
Redundant default: 90
Outputs
Learn how the outputs of the function block work.
ParameterTypeRangeUnitDescription
Diag
Status
STAT_MSG
Bus————This bus provides diagnostic values for troubleshooting. In
U160, 0x8008——
Bus————This bus provides the output values for the block.
addition, all inputs, parameters, and output signals are
contained inside of the bus.
This signal indicates if a parameter fault is declared. It is a
bitwise code, so multiple items can be reported at a time. The
following status codes are provided:
0x0000: No fault
0x8008: At least one parameter is out of range.
PLUS+1® Compliant PVED_CLS_STAT_MSG_OP Function Block
PVED_CLS_STAT_MSG_OP Function Block
ParameterTypeRangeUnitDescription
ServiceModeState
CAN_RawData ARRAY[8]U8————Data passed directly from the CAN receiver.
Updated BOOLT/F——
MsgTimedOut BOOLT/F——
NoMsgReceived BOOLT/F——
CRC_Fail BOOLT/F——
InvalidSeqNum BOOLT/F——
AUX_Allowed_NA BOOLT/F——
U80 to 255——
Service Mode State. When not in service-mode, this value is
set to 0xFF.
0x00: Direct output control reset
0x01: Direct output control/Direct output control active
0x02…0x0F: Reserved
0x10: WAS calibration reset.
0x11: WAS calibration in progress.
0x12…0x1C: Reserved
0x1D: WAS calibration counter update.
0x1E: WAS calibration failure
0x1F: WAS calibration complete
0x20: Spool calibration reset
0x21: Spool calibration inactive
0x22: Spool calibration arming
0x23: Spool calibration armed
0x24: Spool calibration in progress
0x25: Spool parameters plausibility check
0x26: Spool parameters ready to update
0x27: Spool parameters update
0x28…0x2C: Reserved
0x2D: Spool calibration counter update
0x2E: Spool calibration failure
0x2F: Spool calibration complete
0x30: Joystick calibration reset
0x31: Joystick calibration in progress
0x32…0x3C: Reserved.
0x3D: Joystick calibration counter update.
0x3E: Joystick calibration failure.
0x3F: Joystick calibration complete.
0x40…0xFC: Reserved.
0xFD: No analog joystick configured.
0xFE: No wheel angle sensor configured.
0xFF: Information not available.
Pulses TRUE for one loop when new data is available.
T: Received new data.
F: Did not receive new data.
True if the time since the last status message has exceeded
the value determined by Timeout.
T: The status message has timed out, block outputs set to
zero/false. NA signals set true.
F: No error.
No message has been received yet from the device.
T: No message received since power on.
F: A message has been received since power on.
Detects if the CRC in a message does not match the
calculated CRC that is performed over the data.
T: CRC mismatch.
F: No error.
On a failure, data is switched to safe values.
Detects an invalid sequence number.
T: The CAN counter value does not match the running value.
A message may have been missed.
F: No error.
On a failure, data is switched to safe values.
Indicates if the related signal is available.
T: Signal is not available.
F: Signal available.
PLUS+1® Compliant PVED_CLS_STAT_MSG_OP Function Block
PVED_CLS_STAT_MSG_OP Function Block
ParameterTypeRangeUnitDescription
AUX_Allowed_Flt U80 to 3——
EH_Allowed_NA U80 to 255——
EH_Allowed_Flt BOOLT/F——
STW_ProgChgAllowed_NA BOOLT/F——
STW_ProgChgAllowed_Flt BOOLT/F——
DevChgAllowed_NA BOOLT/F——
DevChgAllowed_Flt BOOLT/F——
Indicates if the related signal is faulted.
T: Signal is faulted.
F: Signal ok.
Indicates if the related signal is available.
T: Signal is not available.
F: Signal available.
Indicates if the related signal is faulted.
T: Signal is faulted.
F: Signal ok.
Indicates if the related signal is available.
T: Signal is not available.
F: Signal available.
Indicates if the related signal is faulted.
T: Signal is faulted.
F: Signal ok.
Indicates if the related signal is available.
T: Signal is not available.
F: Signal available.
Indicates if the related signal is faulted.
T: Signal is faulted.
F: Signal ok.
Diagnostic Signals
Enter the Checkpoints page on the second level of the PVED_CLS_STAT_MSG_OP function block to
access the function block’s signals.
The page contains checkpoints on input, parameter, and output signals. Other topics in this book
describe input, parameter, and output signals.
Status Logic
This topic describes how status logic is indicated for the function block.
The status code indicates whether the parameters used in the function are within their valid range.
ConditionHexBinaryCauseResponseCorrection
Invalid setup
*
Position of set bit in a 16 bit fault or status code. Bit 1 is the least significant bit. Bit 16 set to 1 indicates a standard Danfoss status code or fault code.
0x8008
*
1000At least one parameter is out
of range.
Status code reported.Correct the out of range
parameters.
Configure Communication for the Function Block
The following sequence demonstrates how to setup the function block for primary or redundant
communication.
Note, you need to route the Addr parameter out from the Parameters page.
Configure Primary Communication for Function Block
For primary communication, set the parameter Addr to 19.
PLUS+1® Compliant PVED_CLS_STAT_MSG_OP Function Block
PVED_CLS_STAT_MSG_OP Function Block
Configure Redundant Communication for Function Block
For redundant communication, set the parameter Addr to 90.
Enabling Checkpoints
Chkpt enables the checkpoints for each Diag Bus Signal.
It is pre-connected to a constant True.
Set Chkpt to False if you do not want to use the checkpoints or if you need to free up some memory. Be
aware that Fault and Status signals disappear from the service screen by setting to False.
Warning
The programmer must implement sufficient fault management and is responsible to reach the safe state
according to the safety concept for the application.
Identical Function Blocks Need Different Namespace Values to Successfully Compile
If you use the same function block more than once in an application, you must change each function
block’s namespace value to avoid compiler errors.
All function blocks contain Advanced Checkpoint with Namespace components that enable the PLUS+1
Service Tool to read block input and output values.
Some function blocks contain non-volatile memory components that store function block operating
parameters.
Both these components use memory names (“aliases”) to allocate memory. Identical memory names
cause compiler errors.
The namespace value adds a unique prefix to each component name to avoid errors. Keep each
namespace value short to save controller memory.
PLUS+1® Compliant PVED_CLS_STAT_MSG_OP Function Block
PVED_CLS_STAT_MSG_OP Function Block
OutputTypeDescription
Address
TimeoutmsMaximum time in ms between messages before a timeout fault is triggered.
Status——
Aux Allowed
EH Allowed
Str Chg
Allowed
Inval Seq Num
Current State
Allow Prog Chg
GPS1 allowed
GPS2 allowed
Svc Mode State
Msg Timed Out T/F
No Msg RcvT/F
CRC Fail
——Source address of the PVED-CLS.
This signal indicates if a parameter fault is declared. It’s a bitwise code, so multiple items can be reported at a time.
The following status codes are provided:
0x0000: No fault.
0x8008: At least one parameter is out of range.
——AUX steering device lockout status.
T: AUX device steering allowed.
F: AUX device steering prohibited
2800 East 13th Street
Ames, IA 50010, USA
Phone: +1 515 239 6000
Danfoss
Power Solutions Trading
(Shanghai) Co., Ltd.
Building #22, No. 1000 Jin Hai Rd
Jin Qiao, Pudong New District
Shanghai, China 201206
Phone: +86 21 3418 5200
Products we offer:
Hydro-Gear
www.hydro-gear.com
Daikin-Sauer-Danfoss
www.daikin-sauer-danfoss.com
DCV directional control
•
valves
Electric converters
•
Electric machines
•
Electric motors
•
Hydrostatic motors
•
Hydrostatic pumps
•
Orbital motors
•
PLUS+1® controllers
•
PLUS+1® displays
•
PLUS+1® joysticks and
•
pedals
PLUS+1® operator
•
interfaces
PLUS+1® sensors
•
PLUS+1® software
•
PLUS+1® software services,
•
support and training
Position controls and
•
sensors
PVG proportional valves
•
Steering components and
•
systems
Telematics
•
Danfoss Power Solutions is a global manufacturer and supplier of high-quality hydraulic and
electric components. We specialize in providing state-of-the-art technology and solutions
that excel in the harsh operating conditions of the mobile off-highway market as well as the
marine sector. Building on our extensive applications expertise, we work closely with you to
ensure exceptional performance for a broad range of applications. We help you and other
customers around the world speed up system development, reduce costs and bring vehicles
and vessels to market faster.
Danfoss Power Solutions – your strongest partner in mobile hydraulics and mobile
electrification.
Go to www.danfoss.com for further product information.
We offer you expert worldwide support for ensuring the best possible solutions for
outstanding performance. And with an extensive network of Global Service Partners, we also
provide you with comprehensive global service for all of our components.
Local address:
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alterations can be made without subsequent changes being necessary in specifications already agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.