Danfoss PVED-CC User guide

Technical Information
Proportional Valves
PVED-CC, Series 5 ISObus
www.danfoss.com
Technical Information
PVED-CC Series 5 ISObus
Revision history Table of revisions
Date Changed Rev
October 2021 Minor data corrections 0107
June 2020 Updated code numbers 0106
November 2019 Added 4m EMC proof cables to ISOBus code numbers 0105
October 2017 Correction - AMP connector 0104
July 2017 Correction to image 'AMP 2x 4pin AMT Junior Power Timer.' 0103
February 2016 Literature order number changed. 0102
Changed document number from 'BC00000361' to 'BC187186484889' XX
Range and default updated
October 2015 ISObus added to the title 0001
June 2015 First version 0000
0101
2 | © Danfoss | October 2021 BC187186484889en-000107
Technical Information
PVED-CC Series 5 ISObus

Contents

Introduction
Technical data
Communication
Parameters
Diagnostics
PVED-CC ISObus code numbers..................................................................................................................................................4
Operating data overview...............................................................................................................................................................5
Connectors..........................................................................................................................................................................................6
LED coloring for PVED-CC Series 5............................................................................................................................................. 7
Physical dimensions........................................................................................................................................................................ 7
PVED-CC Hysteresis and Ripple...................................................................................................................................................8
PVED-CC Reaction Times............................................................................................................................................................... 8
PVED-CC ISObus message overview..........................................................................................................................................9
PVED-CC Address claim..................................................................................................................................................................9
Commanded address................................................................................................................................................................... 10
PGN: Auxiliary Valve Command................................................................................................................................................10
PGN: Auxiliary Valve Estimated Flow...................................................................................................................................... 11
PGN: Vehicle Fluid Temperature...............................................................................................................................................12
PGN: Diagnostic Message 1........................................................................................................................................................13
PGN: Diagnostic Message 2........................................................................................................................................................15
PGN: Diagnostic Message 3........................................................................................................................................................18
PGN: Diagnostic Message 4........................................................................................................................................................18
PGN: Diagnostic Message 11..................................................................................................................................................... 22
PGN: Diagnostic Message 13..................................................................................................................................................... 23
Parameter overview......................................................................................................................................................................24
PVED-CC ISObus Process data...................................................................................................................................................26
Process data messages...........................................................................................................................................................26
Process data overview............................................................................................................................................................ 26
Setpoint transfer feature: Write process data.................................................................................................................27
Frame format..............................................................................................................................................................................27
Write data.................................................................................................................................................................................... 27
Linked fault flags.......................................................................................................................................................................27
Read data.....................................................................................................................................................................................28
PVED-CC (ISObus) Diagnostics log ......................................................................................................................................... 29
Diagnostic history..........................................................................................................................................................................31
Temperature histogram...............................................................................................................................................................31
©
Danfoss | October 2021 BC187186484889en-000107 | 3
Technical Information
PVED-CC Series 5 ISObus
PVED-CC ISObus Introduction
The PVED-CC Series 5 ISOBUS is a high performance digital actuator for the valve families PVG 32 and PVG
100. The PVED-CC Series 5 ISOBUS offers CAN bus control through loop cables simplifying the wire harness
and build-in intelligence where actuator specific features tailor the actuator behavior to the exact function need.

PVED-CC ISObus code numbers

Connector type Code number Description
DEUTSCH 11107869 PVED-CC
AMP 11107870 PVED-CC
11189931 PVED-CC for PVG 128/256 11007498 4 m cable 11095741 4 m EMC proof cable (twisted pair) 11007531 0.1 m loop cable 11111916 0.3 m loop cable 11095622 0.175 loop cable 11007561 CAN bus terminator
157B4994 4 m cable with gray connector 157B4995 4 m cable with black connector 11095740 4 m EMC proof cable (twisted pair) 157B4987 0.1 m loop cable 11095581 0.175 m loop cable 11163647 CAN bus terminator with gray connector 157B4988 CAN bus terminator with black connector
4 | © Danfoss | October 2021 BC187186484889en-000107
Technical Information
PVED-CC Series 5 ISObus

Technical data

Operating data overview

Electrical data
Voltage 12 V Current consumption Operating
Neutral - Power state
Energy consumption Operating
Neutral - Power state
Supply voltage (V
) Nominal
bat
Range Maximum ripple
CAN bus
*
PVED communicating on CAN bus, but not fully operable.
Alive 5.5 – 36 V
520 mA 260 mA
80 mA 45 mA
6.24 W 6.24 W
1 W 1.1 W
11 – 32 V
9 – 35.9 V
5%
Temperature range
Min. Max.
Temperature Ambient
Oil Storage 110°C
–40°C
DC
DC
DC
*
DC
24 V
DC
90°C
Hydraulic data
Pilot pressure Tank pressure Continues
Intermittent
Oil consumption Electrical de-energized
Spool locked position Continuous changing spool position
Contamination
(ISO 4406) 23/19/16
Viscosity range Nominal
Minimum Maximum
*
PVED have reduced operating performance
Government regulations
Description Standard Low Voltage EMC Directive Safety
2006/95/EC
2004/108/EC
ISO4413:2010
13.5 ± 1.5 bar
25 bar
40 bar
0 l/min
0.7 l/min
12 – 75 mm2/s
4.2 – 12 mm2/s
75 – 1000 mm2/s
*
©
Danfoss | October 2021 BC187186484889en-000107 | 5
CAN-H GND Vbat+ CAN-L
1 CAN-L 2
Vbat+
3
GND
4 CAN-H
4 3
2 1
V310451.A
2 CAN-L 3 Vbat+
4 GND
1 CAN-H
3 Vbat+
4 GND
2 CAN-L
1 CAN-H
Technical Information
PVED-CC Series 5 ISObus
Technical data

Connectors

Available 2x4 pin connectors: AMP Junior Power Timer andDEUTSCH DT06-4S-E003. Pins are internally connected in pairs between connectors. Mating connectors are not supplied by Danfoss.
AMP connector
AMP Junior Power Timer (2x4 pin)
Terminal Seal Housing IP rating
929930-1 (4 pcs)
*
There is no black/gray coding of the connector
828901-1 (4 pcs)
Pinout:
1. CAN Low
2. Vbat+
3. GND
4. CAN High
2-967059-1 (gray) or 1-967059-1 (black)
*
IP66
DEUTSCH connector
DT06-4S-E003 (2x4 pin)
Pinout:
1. CAN High
2. CAN Low
3. Vbat+
4. GND
IP rating: IP67; IP69K without connector
6 | © Danfoss | October 2021 BC187186484889en-000107
Width
Depth
Height
V310 454.A
Technical Information
PVED-CC Series 5 ISObus
Technical data

LED coloring for PVED-CC Series 5

LED Characteristic
Color LED Characteristic Description
Green constant No error – Actuating
Green flashing @ 1.5 Hz Neutral – Power save
Red constant Internal error
Red flashing @ 1.5 Hz External or Float error
Yellow Disable mode

Physical dimensions

Depth Width Height
85 mm [3.35 in] 45 mm [1.77 in] 116 mm [4.57 in]
*
Excluding connector height
©
Danfoss | October 2021 BC187186484889en-000107 | 7
*
PFC [%]
100
0
Spool Position [%]
100
BP
h
0
v
Fixed position
Spool Position
P301822
100
0
Spool Position [%]
Time
T0 T1
T2
Spool Position
PFC (%)
Supply Voltage (UDC)
Max. spool pos. to neutral
T2
Neutral to max. spool pos.
T1
Boot-up
T0
P301823
Technical Information
PVED-CC Series 5 ISObus
Technical data

PVED-CC Hysteresis and Ripple

Definition of hysteresis
Hysteresis (h) Rated [%] 1.45% Steady state ripple at constant command signal Rated [%] 0.29%

PVED-CC Reaction Times

Reaction times
Definition of Step Response
Reaction Time (nominal)
T0 – Boot-up 440 ms T1 – Constant PFC command 177 ms T2 – Constant PFC command 114 ms
*
Including Power-On-Self-Test (POST) and safety sub-system initialization.
*
8 | © Danfoss | October 2021 BC187186484889en-000107
Technical Information
PVED-CC Series 5 ISObus

Communication

PVED-CC ISObus message overview

Message ID Message type DLC Translation Direction
0x18EEFFyy*PVED-CC Address claim on
0x0CFE3xyy*PGN: Auxiliary Valve
0x0CFE1xyy*PGN: Auxiliary Valve
0x18FE68yy*PGN: Vehicle Fluid
0x18FECAyy*PGN: Diagnostic Message 1
0x18EAxxyy*PGN: Diagnostic Message 2
0x18FECByy*DM2 data on page 16 8 Rx On request 0x18EAxxyy*PGN: Diagnostic Message 3
0x18EAFFyy*DM 3 data on page 18 3 Rx On request 0x18EAxxyy*PGN: Diagnostic Message 4
0x1CEBxxyy*DM4 on page 19 8 Rx On request 0x18EAxxyy*PGN: Diagnostic Message 11
0x18E8FFyy*DM 11 data on page 23 8 Rx On request 0x18DFFFyy*PGN: Diagnostic Message 13
*
x = destination address (0x0-0xF), yy = source address
page 9
Command on page 10
Estimated Flow on page
11
Temperature on page 12
on page 13
on page 15
on page 18
on page 18
on page 22
on page 23
8 Claim address on CAN
bus
3 or 8 Auxiliary valve command Tx Controller
= AVC DLC Auxiliary Valve Estimated
Flow
8 Vehicle fluid temperature Tx Controller
8 Active Diagnostic
Trouble Code
3 Previously Active
Diagnostic Trouble Codes
3 Reset of Previously Active
Diagnostic Trouble Codes
6 Freeze Frame Parameters Tx On request
3 Reset of Active
Diagnostic Trouble Codes
8 Stop/Start broadcast Tx On request
(from controller)
Rx On power-up
Rx Configurable
Rx 1000 ms/event
Tx On request
Tx On request
Tx On request
Timing
dependent Recommended: 100 ms
Recommended: 100 ms
dependent
triggered

PVED-CC Address claim

Upon power-up the PVED will log onto the CAN bus network by claiming the address is has been given upon parameterization.
Frame format
Msg ID DLC Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
0x18EEFFyy*8 Name
*
yy = source address
Address claim data
Byte 1 0x01 Identity number Byte 2 0x00
Byte 3 0x20
Byte 4 Danfoss = 0x39 Byte 5 0x08 Bit 8 to 4: Function Instance (0x00)
©
Danfoss | October 2021 BC187186484889en-000107 | 9
0x07
Name assigned by Danfoss 0x001
Bits 16 to 13: Identity number Bits 12 to 1: Manufacturer Code
Bits 3 to 1: ECU Instance (0x0x1)
Technical Information
PVED-CC Series 5 ISObus
Communication

Commanded address

Byte 6 0xFF Function (0xFF) Byte 7 0x02 Bits 8 to 2: Vehicle System (0x01)
Bit 1: Reserved (0x01)
Byte 8 0x20 Bit 8: Arbitrary address (0x00)
Bits 7 to 5: Industry Group – Agriculture and Forestry
Bits 4 to 1: Vehicle system instance (0x00)
(0x02)
Commanded address enables the master to rename the PVED.
Only one PVED with same address can be present at the network at a time.
Frame format
Message ID DLC Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
BAM 0x1CECFFyy*8 BAM No of bytes No of
DT 1 0x1CEBFFyy*8 Sequence Name DT 2 0x1CEBFFyy*8 Sequence Name
*
yy = source address
cont.
New node ID
packets
Reserved
Reserved PGN
Upon receiving new node ID the PVED will perform a reset of itself. After reset it will claim the new address.

PGN: Auxiliary Valve Command

The Auxiliary Valve Command (abbreviated AVC) is the command value sent from a master controller to control the PVED. The PVE will only accept messages with correct node ID and ignore any AVC commands if invalid.
Frame format
*
**
AVC data
Msg ID DLC Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
0x0CFE3xyy*3 or 8
x = destination address (0x0-0xF), yy = source address
Both DLC of 3 or 8 is valid for AVC message. Any other DLC will cause the PVED to raise an error flag.
**
PFC Reserved Valve
state
Reserved
Transmission rate: 100ms (recommended)
Transmission rate range: Recommended minimum Tx = 10ms
Recommended maximum Tx = AVC Timeout/2
*
Byte 1
Port Flow Command
Request port flow as a percentage of full flow Resolution:
Valid range: 0-100%
0.4%/bit
0 - 250 0x00 – 0xFA
10 | © Danfoss | October 2021 BC187186484889en-000107
Technical Information
PVED-CC Series 5 ISObus
Communication
Byte 2 Reserved (FF)
**
Byte 3
Byte 4 Reserved (FF) Byte 5 Byte 6 Byte 7 Byte 8
*
PFC = 0 is interpreted as a neutral command
**
In blocked state the value in PFC is ignored
Valve state Bits 8 and 7: Fail safe mode – block (0x00) supported
Bits 6 and 5: Reserved Bits 4 to 1: Valve state:
Blocked (neutral) = 0b0000 Extend = 0b0001 Retract = 0b0010 Float = 0b0011 Hand operation = 0b1010 Emergency stop = 0b1110
Linked fault flags
Fault SPN FMI
AVC not recieved within timeout period 298985 19 Invalid data in AVC 520676 19

PGN: Auxiliary Valve Estimated Flow

The Auxiliary Valve Estimated Flow (abbreviated AVEF) is the feedback sent from the PVED to the master controller telling the assumed flow/spool position.
Frame format
Msg ID DLC Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
0x0 CFE1xyy*3 or 8
*
x = destination address (0x0-0xF), yy = source address
**
The DLC will follow that of the AVC PGN.
Default transmission rate: 100ms (recommended)
Transmission rate range: Minimum Tx = 10ms
**
Extend port flow
Retract port flow
Valve state
Reserved
Maximum Tx = 10 000ms
©
Danfoss | October 2021 BC187186484889en-000107 | 11
Technical Information
PVED-CC Series 5 ISObus
Communication
AVEF data
Byte 1 Extend port flow
Estimated flow out of extend port as a percentage of full flow
Resolution: 1%/bit Offset: 125
0x7D
Date range: 0-100%
125 - 225 0x7D – 0xE1
Byte 2 Retract port flow
Estimated flow out of retract port as a percentage of full flow
Resolution: 1%/bit Offset: 125
0x7D
Date range: 0-100%
125 - 225 0x7D – 0xE1
Byte 3 Valve state Bits 8 and 7: Fail safe mode – 0b00 and 0b01 is supported but safe state is always
blocked Bits 6 and 5: Reserved Bits 4 to 1: Valve state: Block (neutral) = 0b0000
Extend = 0b0001 Retract = 0b0010 Float = 0b0011 Hand operation = 0b1010
Error = 0b1110 Byte 4 Reserved (FF) Byte 5 Byte 6 Byte 7 Byte 8

PGN: Vehicle Fluid Temperature

The Vehicle Fluid Temperature can be used as input for the temperature dependent spool timeout. If the PGN VFT is not received by the actuator within 10000ms the onboard temperature sensor will be used as trigger.
Frame format
Msg ID DLC Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
0x18FE68yy*8 Temperature Data not of importance
*
yy = source address
12 | © Danfoss | October 2021 BC187186484889en-000107
Technical Information
PVED-CC Series 5 ISObus
Communication

PGN: Diagnostic Message 1

VFT data
Byte 1 Temperature in °Celsius Resolution: 1 °C/bit
Offset: 40
0x28
Date range: -40-120 °C
0 - 160
0x00 – 0xA0 Byte 2 Reserved (FF) Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
The Active trouble code message (abbreviated DM1) is used by the PVED to transmit an active fault onto the CAN bus and give as a periodic status message.
Frame format
Msg ID DLC Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
0x18CEFAyy*8 Lamp
*
yy = source address
status
Flash status
Fault information Occurrence
counter
Reserved
Default transmission rate: 1000ms (Can be disabled) / event triggered
DM1 data
Byte 1 Lamp status
Used by controller – not related to the actuator LED No fault (default state): 0x00 Warning and Info type
faults: Critical or Severe type
faults:
Byte 2 Flash status
Used by controller – not
related to the actuator LED Byte 3 Fault information Bits 24 to 6: SPN of active fault Byte 4 Bits 5 to 1: FMI of active fault Byte 5 Byte 6 Occurrence counter (OC) Bit 8: Conversion method
Byte 7 Reserved (FF) Byte 8
Amber lamp: 0x04
Red lamp: 0x10
Flashing: 0xFF
Bits 7-1: Occurrence counter
Number of times the active fault has appeared previously
©
Danfoss | October 2021 BC187186484889en-000107 | 13
Technical Information
PVED-CC Series 5 ISObus
Communication
In the event of multiple faults happening simultaneously the PVED will use the Broadcast Announce Message (BAM) transport protocol.
The BAM message size depends on the number of previous faults.
Frame format
Msg ID DLC Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
0x1CECFFyy*8 BAM No of bytes No of
0x1CEBFFyy*8 Sequence Lamp
0x1CEBFFyy*8 Sequence Fault 2 cont. Fault 3 0x1CEBFFyy*8 Sequence Fault 4 BAM cont.
*
yy = source address
status
Reserved Fault 1 Fault 2
packets
Reserved DM 1 PGN
Transport protocol from J1939-21
BAM Byte 1 BAM
Byte 2 Number of bytes Byte 3 Byte 4 Number of packets
How many messages are sent in the complete BAM Byte 5 Reserved (FF) Byte 6 DM 1 PGN (0x00FECA) Byte 7 Byte 8
Data Transfer DT1 Byte 1 Sequence
Identification number of the BAM message in the BAM sequence Byte 2 Lamp status
Used by controller – not related to the actuator LED
Info or warning type
faults:
Critical or severe type
faults: Byte 3 Reserved (FF) Byte 4 Fault information of Byte 5 Bits 5 to 1: FMI of fault Byte 6 Byte 7 Occurrence counter
Byte 8 Fault information of fault 2
fault 1
Number of times the active fault has appeared previously
SPN of fault
Amber lamp: 0x04
Red lamp: 0x10
Bits 24 to 6: SPN of fault
14 | © Danfoss | October 2021 BC187186484889en-000107
Technical Information
PVED-CC Series 5 ISObus
Communication
Data Transfer DT2 Byte 1 Sequence
Identification number of the BAM message in the BAM sequence Byte 2 Fault information of Byte 3 Bits 5 to 1: FMI of fault Byte 4 Occurrence counter
Byte 5 Fault information of Byte 6 Bits 5 to 1: FMI of fault Byte 7 Byte 8 Occurrence counter
Data Transfer DT3 Byte 1 Sequence
Byte 2 Fault information of Byte 3 Bits 5 to 1: FMI of fault Byte 4 Byte 5 Occurrence counter
Byte 6 BAM continued Byte 7 Byte 8
fault 2 cont.
Number of times the active fault has appeared previously
fault 3
Number of times the active fault has appeared previously
Identification number of the BAM message in the BAM sequence
fault 3
Number of times the active fault has appeared previously
Bits 24 to 6: SPN of fault
Bits 24 to 6: SPN of fault
Bits 24 to 6: SPN of fault

PGN: Diagnostic Message 2

The Previously Active Diagnostic Trouble Codes (abbreviated DM2) is used to trigger the PVED to transmit all previously active fault onto the CAN bus.
Frame format
Request frame format
Msg ID DLC Byte 1 Byte 2 Byte 3
0x18EAxxyy
*
xx = destination address (0x80-0x8F), yy = source address
*
3 Request PGN LSB Request PGN MSB 0x00
0xCB 0xFE
Response frame format
Msg ID DLC Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
0x18FECByy*8 Lamp
*
yy = source address
status
Flash status
Fault information Occurrence
counter
Reserved
Transmission rate: on request
©
Danfoss | October 2021 BC187186484889en-000107 | 15
Technical Information
PVED-CC Series 5 ISObus
Communication
DM2 data
Byte 1 Lamp status
Used by controller – not related to the actuator LED No fault (default state): 0x00 Warning and Info type
faults: Critical or Severe type
faults:
Byte 2 Flash status
Used by controller – not
related to the actuator LED Byte 3 Fault information Bits 24 to 6: SPN of active fault Byte 4 Bits 5 to 1: FMI of active fault Byte 5 Byte 6 Occurrence counter (OC)
Number of times the active fault has appeared previously Byte 7 Reserved (FF) Byte 8
Amber lamp: 0x04
Red lamp: 0x10
Flashing: 0xFF
In the event of Multiple previously active faults the PVED will use the Broadcast Announce Message (BAM) transport protocol.
The BAM message size depends on the number of previous faults.
Frame format
Msg ID DLC Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
0x1CECFFyy*8 BAM No of bytes No of
0x1CEBFFyy*8 Sequence Lamp
0x1CEBFFyy*8 Sequence Fault 2 cont. Fault 3 0x1CEBFFyy*8 Sequence Fault 4 BAM cont.
*
yy = source address
status
Reserved Fault 1 Fault 2
packets
Reserved DM 2 PGN
Transport protocol from J1939-21
BAM Byte 1 BAM
Byte 2 Number of bytes Byte 3 Byte 4 Number of packets
How many messages are sent in the complete BAM Byte 5 Reserved (FF) Byte 6 DM 2 PGN (0x00FECB) Byte 7 Byte 8
16 | © Danfoss | October 2021 BC187186484889en-000107
Technical Information
PVED-CC Series 5 ISObus
Communication
Data Transfer DT1 Byte 1 Sequence
Identification number of the BAM message in the BAM sequence
Byte 2 Lamp status
Used by controller – not related to the actuator LED Info or warning type
faults: Critical or severe type
faults: Byte 3 Reserved (FF) Byte 4 Fault information of Byte 5 Bits 5 to 1: FMI of fault Byte 6 Byte 7 Occurrence counter
Byte 8 Fault information of fault 2
Data Transfer DT2 Byte 1 Sequence
Byte 2 Fault information of Byte 3 Bits 5 to 1: FMI of fault Byte 4 Occurrence counter
Byte 5 Fault information of Byte 6 Bits 5 to 1: FMI of fault Byte 7 Byte 8 Occurrence counter
Data Transfer DT3 Byte 1 Sequence
Byte 2 Fault information of Byte 3 Bits 5 to 1: FMI of fault Byte 4 Byte 5 Occurrence counter
Byte 6 BAM continued Byte 7 Byte 8
fault 1
Number of times the active fault has appeared previously
SPN of fault
Identification number of the BAM message in the BAM sequence
fault 2 cont.
Number of times the active fault has appeared previously
fault 3
Number of times the active fault has appeared previously
Identification number of the BAM message in the BAM sequence
fault 3
Number of times the active fault has appeared previously
Amber lamp: 0x04
Red lamp: 0x10
Bits 24 to 6: SPN of fault
Bits 24 to 6: SPN of fault
Bits 24 to 6: SPN of fault
Bits 24 to 6: SPN of fault
Busy response
If the BAM session is unavailable due to ongoing transmission of DM1 or DM2 messages a busy response will be transmitted.
Msg ID DLC Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
0x18E8FFyy*8 Control
*
yy = source address
©
Danfoss | October 2021 BC187186484889en-000107 | 17
byte 0x02 0xFF 0xFF 0x05 0xCB 0xFE 0x00
0x00 Reserved Address busy
acknowledge
Requested PGN
Technical Information
PVED-CC Series 5 ISObus
Communication

PGN: Diagnostic Message 3

The Clear/Reset of Previously Active Diagnostic Trouble Codes (abbreviated DM3) is used by the controller to clear the diagnostics log within the PVED
Frame format
Request frame format
Msg ID DLC Byte 1 Byte 2 Byte 3
0x18EAxxyy
*
xx = destination address (0x80-0x8F), yy = source address
*
3 Request PGN LSB Request PGN MSB 0x00
0xCC 0xFE
Response frame format
Msg ID DLC Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
0x18E8FFyy*8 Control
*
yy = source address
byte
0x00 Reserved Address
acknowledge
Request PGN

PGN: Diagnostic Message 4

Transmission rate: on request
DM 3 data
Byte 1 Control byte Positive acknowledge: 0x00
Busy: 0x02 Byte 2 0x00 Byte 3 Reserved (FF) Byte 4 Byte 5 Address acknowledge
Source address of requestor Byte 6 DM 3PGN (0x00FECC) Byte 7 Byte 8
The Freeze Frame Parameters (abbreviated DM4) is used to trigger the PVED to transmit all current and previously active faults of a specific fault code stored in the diagnostic history onto the CAN bus.
Request frame format
Msg ID DLC Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6
0x18EAxxyy
*
xx = destination address (0x80-0x8F), yy = source address
*
6 DM4 PGN LSB DM4 PGN 2
0xCD 0xFE 0x00
byte
nd
DM4 PGN MSB SPN/FMI
18 | © Danfoss | October 2021 BC187186484889en-000107
Technical Information
PVED-CC Series 5 ISObus
Communication
Timeouts
No message received by actuator after last packet was transmitted: 1250ms
No message received by actuator after a hold the connection open message was received: 1050ms
Transmission rate: on request
DM4
Response frame format
No entries of the requested fault code The actuator diagnostic history does not contain any record of the requested fault code.
Msg ID DLC Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
0x18FECDyy*8 0x00 0x00 0x00 0x00 0xFE 0xFF (Reserved)
*
yy = source address
Entries of requested fault code found
Actuator request to establish connection
Msg ID DLC Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
0x1CECxxyy*8 Control
*
xx = destination address (0x80-0x8F), yy = source address
**
maximum number of packets that can be sent to one DM4 request = 8
byte
0x10 0xCD 0xFE 0x00
Total no of bytes with data available
Total no if packet
Number of packets that can be sent to one request
Request PGN (DM4)
**
Master ECU to establish connection
Msg ID DLC Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
0x1CECxxyy*8 Control
*
xx = destination address (0x80-0x8F), yy = source address
**
Must be equal to byte 5 in the actuator request to establish connection – if master ECU is busy set to 0x00 meaning the connection is maintained open until timeout, but no data will be transmitted until new message arrives.
byte
0x11 0xFF 0xFF 0xCD 0xFE 0x00
Total no of packets can be
**
sent
Next packet no
Reserved Request PGN (DM4)
After the connection is established the PVED will transmit the content of the diagnostic history. The following frames will be sent for all occurrences of the enquired fault.
©
Danfoss | October 2021 BC187186484889en-000107 | 19
Technical Information
PVED-CC Series 5 ISObus
Communication
Diagnostic history frame format
Msg ID DLC Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
0x1CEBxxyy*8 Sequence no Length SPN/FMI Occurren
ce / fault status
0x1CEBxxyy*8 Sequence no Operating time 1st occurrence
Operating time last occurrence
Fault ID Operating
time 1st occurrence
cont. 0x1CEBxxyy*8 Sequence no Environmental data for 1st fault record 0x1CEBxxyy*8 Sequence no 0x1CEBxxyy*8 Sequence no 0x1CEBxxyy*8 Sequence no 0x1CEBxxyy*8 Sequence no 0x1CEBxxyy*8 Sequence no 0x1CEBxxyy*8 Sequence no
*
xx = destination address (0x80-0x8F), yy = source address
Diagnostic history data
Message 1 Byte 1 Sequence number
Byte 2 Freeze Frame Length Byte 3 Fault information Bits 24 to 6: SPN of fault Byte 4 Bits 5 to 1: FMI of fault Byte 5
*
Byte 6
Byte 7 Byte 8
Message 2 Byte 1 Sequence number
Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
Message 3 Byte 1 Sequence number
Byte 2 Valve state upon fault occurrence Byte 3 Set point at fault occurrence Byte 4 Byte 5 Demand value at fault occurrence Byte 6 Byte 7 Spool position at fault occurence Byte 8
Occurrence count and current state Bits 8 to 2: Number of times the active fault has appeared previously Bit 1: Current state of the fault
code
*
Fault ID
*
Operating time of 1st occurrence of the fault (LSB)
*
Operating time of 1st occurrence of the fault
*
*
*
Operating time of last occurrence of the fault
*
*
*
0 = previous fault 1 = currently active fault
20 | © Danfoss | October 2021 BC187186484889en-000107
Technical Information
PVED-CC Series 5 ISObus
Communication
Diagnostic history data (continued)
Message 4 Byte 1 Sequence number
Byte 2 Battery voltage Byte 3 Byte 4 Operating time Byte 5 Byte 6 Byte 7 Byte 8 Last spool position before fault occurrence
Message 5 Byte 1 Sequence number
Byte 2 Last demand value before fault occurrence Byte 3 2nd to last spool position before fault occurrence Byte 4 2nd to last demand value before fault occurrence Byte 5 3rd to last spool position before fault occurrence Byte 6 3rd to last demand value before fault occurrence Byte 7 4th to last spool position before fault occurrence Byte 8 4th to last demand value before fault occurrence
Message 6 Byte 1 Sequence number
Byte 2 5th to last spool position before fault occurrence Byte 3 5th to last demand value before fault occurrence Byte 4 6th to last spool position before fault occurrence Byte 5 6th to last demand value before fault occurrence Byte 6 7th to last spool position before fault occurrence Byte 7 7th to last demand value before fault occurrence Byte 8 8th to last spool position before fault occurrence
Message 7 Byte 1 Sequence number
Byte 2 8th to last demand value before fault occurrence Byte 3 9th to last spool position before fault occurrence Byte 4 9th to last demand value before fault occurrence Byte 5 File number Byte 6 Byte 7 Line number Byte 8
Message 8 Byte 1 Sequence number
Byte 2 PCB temperature Byte 3 Reserved (0xFF) Byte 4 Byte 5 Byte 6 Byte 7 Checksum Byte 8
*
Fields are different from the J1939 standard
©
Danfoss | October 2021 BC187186484889en-000107 | 21
Technical Information
PVED-CC Series 5 ISObus
Communication
Master ECU to terminate connection upon receiving last packet with end of message acknowledge
Msg ID DLC Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
0x1CECxxyy*8 Control
*
xx = destination address (0x80-0x8F), yy = source address
byte
0x13 0xFF 0xCD 0xFE 0x00
Total number of data bytes received
Total number of packets received
Reserved Request PGN (DM4)
Abort connection
Both master ECU and PVED can abort the connection at any time
Abort message frame format
Msg ID DLC Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
0x1CECxxyy*8 Control byte Abort
0xFF 0xFF 0xFF 0xFF 0xCD 0xFE 0x00
*
xx = destination address (0x80-0x8F), yy = source address
reason
Reserved Request PGN (DM4)

PGN: Diagnostic Message 11

Abort message data
Byte 1 Control byte 0xFF Byte 2 Abort reason 1: Already in one or more connections and cannot
support another 2: System resources needed to perform other tasks –
session terminated
3: Timeout occurred - session terminated Byte 3 Reserved 0xFF Byte 4 Byte 5 Byte 6 Request PGN (DM4) 0xCD Byte 7 00xFE Byte 8 0x00
The Clear/Reset of Active Diagnostic Trouble Codes (abbreviated DM 11) is used as command along with two consecutive blocked states to recover to active state when the fault state has been entered due to a non-severe fault.
DM 11 support can be enabled/disabled by the PLUS+1® Service Tool.
Frame format
Request frame format
Msg ID DLC Byte 1 Byte 2 Byte 3
0x18EAxxyy
*
x = destination address (0x80-0x8F), yy = source address
*
3 Request PGN LSB Request PGN MSB 0x00
0xD3 0xFE
22 | © Danfoss | October 2021 BC187186484889en-000107
Technical Information
PVED-CC Series 5 ISObus
Communication
Answer frame format
Msg ID DLC Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
0x18E8FFyy*8 Control
*
yy = source address
byte
0x00 Reserved Address
acknowledge
Request PGN
Transmission rate: on request
DM 11 data
Byte 1 Control byte Positive acknowledge: 0x00
Negative acknowledge: 0x01 Byte 2 0x00 Byte 3 Reserved (FF) Byte 4 Byte 5 Address acknowledge
Source address of requestor Byte 6 DM 11 PGN (0x00FED3) Byte 7 Byte 8

PGN: Diagnostic Message 13

The Start Diagnostics message (abbreviated DM 13) is used to bring the PVED from Inactive Control State to full operational mode.
DM 13 support can be enabled/disabled by the PLUS+1® Service Tool.
Frame format
Request frame format
Msg ID DLC Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
0x18DFFFyy*8 Network
*
yy = source address
type 0xFD
Reserved
Transmission rate: on request
©
Danfoss | October 2021 BC187186484889en-000107 | 23
Technical Information
PVED-CC Series 5 ISObus

Parameters

Parameter overview

The following parameters can be configured within a PVED-CC Series 5 ISOBUS to tailor the behavior to the exact need of the function which it controls. All parameters can be changed using the PLUS+1
®
Service Tool.
Parameter overview
Parameter Description Range Default
NodeID (source address)
Vehicle serial number
Scaling of port flow command* – Extend
Scaling of port flow command* – Retract
Dead band offset* – Extend
Source address of the PVED 128 - 143 128
0x80-0x8F 0x80
Free fields to enter vehicle serial number or other machine specific data
Scaling of the spool stroke. 100% scaling = 7mm spool stroke
Scaling of the spool stroke. 100% scaling = 7mm spool stroke
Spool stroke when given a PFC of 1.
Dead band offset is superimposed on top of the spool curve dead band jump.
free (23 positions) blank
Resolution: 0.4% 0-100% 100% 0-250 250 0x00-0xFA 0xFA Resolution: 0.4% 0-100% 100% 0-250 250 0x00-0xFA 0xFA 0-100% 0 0x00-0x64 0x00
Dead band offset* – Retract
Progressivity curve
- Extend Progressivity curve -
*
Retract Ramp up* - Extend Time to stroke spool from neutral to full stroke.
Ramp down* ­Extend
Ramp up* - Retract Time to stroke spool from neutral to full stroke.
Ramp down* ­Retract
Invert ports
*
Spool stroke when given a PFC of 1.
Dead band offset is superimposed on top of the spool curve dead band jump.
*
Pre-defined curves to change flow from linear to progressive
Pre-defined curves to change flow from linear to progressive
Full stroke is defined by the scaling parameter.
Time to stroke spool from full stroke to neutral.
Full stroke is defined by the scaling parameter
Full stroke is defined by the scaling parameter
Time to stroke spool from full stroke to neutral.
Full stroke is defined by the scaling parameter
Inverts PFC Inverted/not
0-100% 0 0x00-0x64 0x00
1-16 1
1-16 1
Resolution: 16 ms 0-4000 ms 0 ms 0-250 0 0x00-0xFA 0x00 Resolution: 16 ms 0-4000 ms 0 ms 0-250 0 0x00-0xFA 0x00 Resolution: 16 ms 0-4000 ms 0 ms 0-250 0 0x00-0xFA 0x00 Resolution: 16 ms 0-4000 ms 0 ms 0-250 0 0x00-0xFA 0x00
Not inverted
inverted
24 | © Danfoss | October 2021 BC187186484889en-000107
Technical Information
PVED-CC Series 5 ISObus
Parameters
Parameter overview (continued)
Parameter Description Range Default
Power Save Reduce power consumption by making the PVED enter a
sleep mode when in neutral.
Time delay configurable
ON/OFF ON
Power save entry delay
Low voltage reaction delay
AVEF transmit time How often is the AVEF transmitted onto the bus Resolution: 1 ms
AVC timeout Timeout period for receiving the AVC message from the
Support DM13 Choose whether or not Start Diagnostics (DM13
Float ramp time Time to stroke the spool from full flow to float position Resolution: 1 ms
Float threshold
Support DM11 Choose whether or not Reset of Active DTCs (DM11) is
Temperature dependent spool timeout
Temperature dependent spool timeout float add­on
DM1 status transmission
Enable KWP2000 Enable actuator to respond to KWP2000 protocol
KWP2000 ID Respond to global or specific KWP2000 messages Global/specific Global
Time the spool has to stay in neutral position before power save mode is entered
Time from voltage drops below acceptable limit (9VDC) to the DM1 is transmitted
master
message) is required to have the PVED operate
*
Minimum PFC needed to be received by the PVED before allowed to enter float
required to leave fault state Allowed time to stroke the spool from full stroke to
neutral for in a 10 °C temperature interval from -40 to +130 °C
Time added to temperature dependent timeout to reach float position
Transmission of DM1 message will occur either as status each 1000 ms or by fault event
messages
Resolution: 100 ms 0-8000 ms 500 ms 0-80 50 0x00-0x50 0x32 Resolution: 100 ms 0-2000 ms 1000 ms 0-20 10 0x00-0x14 0x0A
0-10000 ms 100 ms 0-10000 100 0x00-0x2710 0x64 Resolution: 1 ms 0-10000 ms 300 ms 0-10000 300 0x00-0x2710 0x12C Enable/disable Disable
0-500 ms 0 ms 0-500 0 0x00-0x1F4 0x00 Resolution: 0.4% 0-100% 0% 0-250 0 0x00-0xFA 0x00 Enable/disable Enable
Resolution: 100 ms 0-25500 ms See graph 0-255 0x00-0xFF Resolution: 1% 0-100% 100% 0-255 255 0x00-0xFF 0xFF Status message /
event triggered Enable/disable Enable
below
Status message
©
Danfoss | October 2021 BC187186484889en-000107 | 25
P301 824A
-40 to -30 °C-40 to -30 °C-40 to -30 °C
-30 to -20 °C-30 to -20 °C-30 to -20 °C
-20 to -10 °C-20 to -10 °C-20 to -10 °C
-10 to 0 °C-10 to 0 °C-10 to 0 °C
0 to 10 °C0 to 10 °C0 to 10 °C
10 to 20 °C10 to 20 °C10 to 20 °C
20 to 30 °C20 to 30 °C20 to 30 °C
30 to 40 °C30 to 40 °C30 to 40 °C
40 to 50 °C40 to 50 °C40 to 50 °C
50 to 60 °C50 to 60 °C50 to 60 °C
60 to 70 °C60 to 70 °C60 to 70 °C
70 to 80 °C70 to 80 °C70 to 80 °C
80 to 90 °C80 to 90 °C80 to 90 °C
90 to 100 °C90 to 100 °C90 to 100 °C
100 to 110 °C100 to 110 °C100 to 110 °C
110 to 120 °C110 to 120 °C110 to 120 °C
120 to 130 °C120 to 130 °C120 to 130 °C
000
100010001000
200020002000
300030003000
400040004000
500050005000
600060006000
700070007000
800080008000
Technical Information
PVED-CC Series 5 ISObus
Parameters
Parameter overview (continued)
Parameter Description Range Default
KWP2000 message timeout
Timeout period for receiving KWP2000 message from the master
Resolution: 1 sec 0-255 sec 5 sec 0-255 5 0x00-0xFF 0x05
Reserved bits in
Chooses wether the reserved bits in byte 3 of AVEF is 0 or10/1 1
AVEF byte 3
*
Part of Process Data and can be modified at runtime.
Timeout as a function of temperature

PVED-CC ISObus Process data

Process Data is part of the parameters in the PVED-CC Series 5 ISOBUS. These data can be changed at runtime using the CAN bus messages shown.

Process data messages

Message ID Message type DLC Control Byte (Byte 1)
*
*
Write Command 8 0x00 Read Command 8 0x10
0x0CCBxxyy 0x0CCBxxyy
*
xx = destination address (0x80-0x8F), yy = source address

Process data overview

Data Dictionary column Process Data Parameter
0 Scaling of PFC – Extend 1 Scaling of PFC – Retract 3 Progressivity Curve – Extend 4 Dead band Offset – Extend 5 Dead band Offset – Retract 6 Progressivity Curve – Retract 8 Ramp up – Extend
26 | © Danfoss | October 2021 BC187186484889en-000107
Technical Information
PVED-CC Series 5 ISObus
Parameters
Data Dictionary column Process Data Parameter
9 Ramp down – Extend 10 Ramp up – Retract 11 Ramp down – Retract 12 Invert ports 13 Float Threshold 14 Commit to EEPROM 15 Restore Factory Settings

Setpoint transfer feature: Write process data

The write process data will change the behavior of the PVED, and thereby the valve, at runtime by changing the value of a given parameter.

Frame format

Write frame format
Msg ID DLC Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
0x0CCBxxyy*8 Control
*
xx = destination address (0x80-0x8F), yy = source address
Byte
Count number
Impleme nt type and position
Data dictionary row / column
Process data variable parameters
Not used

Write data

Byte 1 Control Byte (0x00) Byte 2 Count number (0x00) Byte 3 Implement type and position (0x00) Byte 4 Data dictionary Bits 8-5: Data dictionary row (0x06)
Bits 4-1: Data dictionary column Byte 5 Process data variable (0x00) Byte 6 Byte 7 Not used by PVED (0x00) Byte 8

Linked fault flags

Fault SPN FMI
Process data out of range 298983 2 Process data out of range at boot-up 520579 2
Read frame format
Msg ID DLC Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
0x0CCCBxxyy*8 Control
*
xx = source address
Byte
Count number
Impleme nt type and position
Data dictionary row / column
Process data variable parameters
Not used in PVED
Transmission rate: on request
©
Danfoss | October 2021 BC187186484889en-000107 | 27
Technical Information
PVED-CC Series 5 ISObus
Parameters

Read data

Byte 1 Control Byte (0x10) Byte 2 Count number (0x00) Byte 3 Implement type and position (0x00) Byte 4 Data dictionary Bits 8-5: Data dictionary row (0x06)
Bits 4-1: Data dictionary column Byte 5 Process data variable Byte 6 Byte 7 Not used by PVED (0x00) Byte 8
28 | © Danfoss | October 2021 BC187186484889en-000107
Technical Information
PVED-CC Series 5 ISObus

Diagnostics

PVED-CC (ISObus) Diagnostics log

The PVED-CC Series 5 contains a diagnostic log saving the occurrence of all faults listed below (sorted in asending order by SPN). The faults are transmitted onto the CAN bus through the DM1 message upon occurrence and previously active faults can be enquired through the DM2 message. The complete list of active and previously active faults can be seen in the PLUS+1® Service Tool.
Diagnostics log
FaultIDFault Description SPN FMI Severity SPN + FMI byte values as
4 Supply voltage above upper limit Actuator supply voltage above
5 Supply voltage below lower limit Actuator supply voltage below
34 Memory (flash) corrupted Actuator component fault. 628 12 SEVERE 0x74 0x02 0x0C 32 Memory (RAM) corrupted Actuator component fault. 1557 12 SEVERE 0x15 0x06 0x0C 42 PSM buffer overload Actuator component fault. 298965 11 SEVERE 0xD5 0x8F 0x8B 39 PSM operation fault Actuator component fault. 298966 11 SEVERE 0xD6 0x8F 0x8B 57 Loss and recovery of CAN bus
connection
3 Interpolation fault Actuator component fault. 298968 11 SEVERE 0xD8 0x8F 0x8B 53 Commit-to-EEPROM invalid cmd. Command Commit-to-EEPROM
58 AVC not recieved within timeout
period
61 Float threshold set point not given Setpoint less than float threshold
49 Actual main spool position exceeds
set point recieved.
48 Main spool not in neutral at boot up. Main spool not at neutral position in
47 Float not reached. Main spool cannot reach float
29 POST fault Power On Self-Test failed. Actuator
27 Handshake bootup fault. Actuator component fault. 298993 11 SEVERE 0xF1 0x8F 0x8B 63 Stack usage >90% Actuator component fault. 298996 2 CRITICAL 0xF4 0x8F 0x82 62 Solenoid driver validation fault Actuator component fault. 298997 2 CRITICAL 0xF5 0x8F 0x82 35 Memory (EEPROM) communication
fault
2 Parameter truncation change Value of parameter changed due to
1 Internal calculation fault Actuator component fault. 299004 11 SEVERE 0xFC 0x8F 0x8B 0 Software Initialisation fault Software could not initialize. Check
12 Handshake not received by safeUC Actuator component fault. 299007 11 SEVERE 0xFF 0x8F 0x8B 13 Transducer signal frequency out of
range.
specified upper limit. Please ensure sufficient power supply.
specified lower limit. Please ensure sufficient power supply.
CAN bus connection to the actuator failed but recovered. Please verify connection.
out of valid range. Auxillary Valve Command not
recived by actuator before timeout specified
given when commanded into float position.
Main spool stroke further away from neutral than demanded by setpoint. (Dependent on timeout value).
the module at time of bootup.
position.
cannot start up.
Actuator component fault. 299001 12 CRITICAL 0xF9 0x8F 0x8C
truncation.
that no active errors are present on CAN bus.
Actuator component fault. 299008 8 SEVERE 0x00 0x90 0x88
627 3 WARNING 0x73 0x02 0x03
627 4 WARNING 0x73 0x02 0x04
298967 19 WARNING 0xD7 0x8F 0x93
298983 2 INFO 0xE7 0x8F 0x82
298985 19 WARNING 0xE9 0x8F 0x93
298986 19 WARNING 0xEA 0x8F 0x93
298988 7 CRITICAL 0xEC 0x8F 0x87
298989 7 CRITICAL 0xED 0x8F 0x87
298990 7 CRITICAL 0xEE 0x8F 0x87
298992 12 SEVERE 0xF0 0x8F 0x8C
299002 11 SEVERE 0xFA 0x8F 0x8B
299005 11 SEVERE 0xFD 0x8F 0x8B
seen in DM1/DM2 frames Byte 3 Byte 4 Byte 5
©
Danfoss | October 2021 BC187186484889en-000107 | 29
Technical Information
PVED-CC Series 5 ISObus
Diagnostics
Diagnostics log (continued)
FaultIDFault Description SPN FMI Severity SPN + FMI byte values as
14 Safety demodulator A: signal out of
range 16 Safety-controller PSU out of range Actuator component fault. 299010 2 SEVERE 0x02 0x90 0x82 18 Safety-controller fuse bit fault Actuator component fault. 299011 2 SEVERE 0x03 0x90 0x82 15 Safety demodulator B: signal out of
range 17 Safety-controller: Voltage reference
out of range 19 Safety-controller spool position
cross validation fault 20 Safety switch state fault Actuator component fault. Not able
51 SPI buffer overload Actuator component fault. 299020 2 INFO 0x0C 0x90 0x82 52 SPI communication fault Actuator component fault. 299021 2 SEVERE 0x0D 0x90 0x82 25 Handshake bootup fault. Actuator component fault. 299022 12 SEVERE 0x0E 0x90 0x8C 26 Safety switch state fault. Actuator component fault. 299023 12 SEVERE 0x0F 0x90 0x8C 31 Spool position cross validation fault Actuator component fault. 299025 2 SEVERE 0x11 0x90 0x82 28 Safety-controler initialization fault. Actuator component fault. 299026 12 WARNING 0x12 0x90 0x8C 30 Safety-controller task scheduling
fault 38 Memory (EEPROM) corrupted Actuator component fault. 299029 12 SEVERE 0x15 0x90 0x8C 64 CRC fault The Operator has not approved the
65 Invalid hardware version. Actuator component fault. 520448 2 SEVERE 0x00 0xF1 0xE2 56 AVEF from Work Function actuators
not recieved within timeout period
55 Corrupted data received by Inlet
actuator 54 COMM : Running number validation
for AVC and AVEF
41 Memory (EEPROM) CRC fault Actuator component fault. 520576 2 INFO 0x80 0xF1 0xE2 37 PWM calibration Actuator component fault. 520577 2 SEVERE 0x81 0xF1 0xE2 40 Config sector CRC fault Actuator component fault. 520578 2 SEVERE 0x82 0xF1 0xE2 33 Memory (EEPROM) invalid
parameter 43 Average operating temp above
limit.
44 Current temp above upper limit. The current temperature the
6 5V PSU out of range Actuator component fault. 520582 2 SEVERE 0x86 0xF1 0xE2 7 Spool position calculation fault Actuator component fault. 520583 2 SEVERE 0x87 0xF1 0xE2 50 LVDT supply frequency out-of-range Actuator component fault. 520584 2 SEVERE 0x88 0xF1 0xE2 8 V reference signal out of range. Actuator component fault. 520585 2 SEVERE 0x89 0xF1 0xE2
Actuator component fault. 299009 2 SEVERE 0x01 0x90 0x82
Actuator component fault. 299012 2 SEVERE 0x04 0x90 0x82
Actuator component fault. 299013 2 SEVERE 0x05 0x90 0x82
Actuator component fault. 299014 2 SEVERE 0x06 0x90 0x82
to perform safe operation!
Actuator component fault. 299028 12 SEVERE 0x14 0x90 0x8C
data change
Auxillary Valve Estimated Flow not recived from Work Function actuators by Inlet actuator before timeout specified
CRC or DLC data received from Inlet actuator is corrupted
The running number for Auxillary Valve Command nd Auxillary Valve Estimated Flow could not be validated.
One or more configured EEPROM parameters out of specified range.
The average detected operating temperature is above the upper limit specified.
actuator operates in is above specified operation limit.
299015 12 SEVERE 0x07 0x90 0x8C
299030 2 SEVERE 0x16 0x90 0x82
520449 19 WARNING 0x01 0xF1 0xF3
520450 19 CRITICAL 0x02 0xF1 0xF3
520451 19 CRITICAL 0x03 0xF1 0xF3
520579 2 SEVERE 0x83 0xF1 0xE2
520580 16 WARNING 0x84 0xF1 0xF0
520581 0 CRITICAL 0x85 0xF1 0xE0
seen in DM1/DM2 frames Byte 3 Byte 4 Byte 5
30 | © Danfoss | October 2021 BC187186484889en-000107
Technical Information
PVED-CC Series 5 ISObus
Diagnostics
Diagnostics log (continued)
FaultIDFault Description SPN FMI Severity SPN + FMI byte values as
9 GND signal unstable. Actuator component fault. 520586 3 SEVERE 0x8A 0xF1 0xE3 60 Safety switch state fault Actuator component fault. Not able
to perform safe operation! 10 Demodulator A: signal out of range Actuator component fault. 520588 2 SEVERE 0x8C 0xF1 0xE2 11 Demodulator B: signal out of range Actuator component fault. 520589 2 SEVERE 0x8D 0xF1 0xE2 45 Current temp below lower limit. The current temperature the
actuator operates in is below
specified operation limit. 46 Main spool cannot return to neutral Main spool cannot return back to
neutral by neutral command
setpoint. 36 Fault overload More than three faults were raised
simultaneously. 59 AVC data recieved invalid Auxillary Valve Command input
recieved by actuator. Invalid state
and/or flow request sent from
controller.
520587 12 SEVERE 0x8B 0xF1 0xEC
520590 1 CRITICAL 0x8E 0xF1 0xE1
520591 7 CRITICAL 0x8F 0xF1 0xE7
520592 0 SEVERE 0x90 0xF1 0xE0
520676 19 WARNING 0xE4 0xF1 0xF3
seen in DM1/DM2 frames Byte 3 Byte 4 Byte 5

Diagnostic history

With occurrence of severe faults the actuator must always be repowered. With multiple occurrences of severe faults replace actuator.
In addition to the diagnostic log, the PVED-CC Series 5 holds a record of the last 16 faults occurred. The faults are stored in a FIFO buffer.
Besides the fault code the history also contains more information on the behavior and state of the valve upon fault occurrence. The diagnostic history can be seen in the PLUS+1® Service Tool.
Parameter Description
Fault ID ID number of the fault raised Valve State State of device upon fault occurrence Current set point Set point upon fault occurrence Current spool position Spool position upon fault occurrence Battery voltage Battery voltage upon fault occurrence Operating time Operating time upon fault occurrence Setpoint and spool position history Last 9 setpoint and spool positions prior to fault
Temperature Temperature upon fault occurrence
*
Operating time is logged every 6 minutes when the power to the PVED is ON
Temperature is either received through PGN: VFT or onboard PCB temperature sensor
occurrence
*

Temperature histogram

The PVED-CC Series 5 logs the temperature and time each 6 minutes. This temperature record is used to make a temperature histogram.
The temperature used is the one received in the PGN: Vehicle Fluid Temperature. If no PGN:VFT is received the PVED uses the onboard PCB temperature sensor.
The Temperature Histogram can be seen in the PLUS+1® Service Tool.
©
Danfoss | October 2021 BC187186484889en-000107 | 31
Danfoss Power Solutions GmbH & Co. OHG
Krokamp 35 D-24539 Neumünster, Germany Phone: +49 4321 871 0
Danfoss Power Solutions ApS
Nordborgvej 81 DK-6430 Nordborg, Denmark Phone: +45 7488 2222
Danfoss Power Solutions (US) Company
2800 East 13th Street Ames, IA 50010, USA Phone: +1 515 239 6000
Danfoss Power Solutions Trading (Shanghai) Co., Ltd.
Building #22, No. 1000 Jin Hai Rd Jin Qiao, Pudong New District Shanghai, China 201206 Phone: +86 21 2080 6201
Products we offer:
Hydro-Gear
www.hydro-gear.com
Daikin-Sauer-Danfoss
www.daikin-sauer-danfoss.com
Cartridge valves
DCV directional control
valves Electric converters
Electric machines
Electric motors
Gear motors
Gear pumps
Hydraulic integrated
circuits (HICs) Hydrostatic motors
Hydrostatic pumps
Orbital motors
PLUS+1® controllers
PLUS+1® displays
PLUS+1® joysticks and
pedals PLUS+1® operator
interfaces PLUS+1® sensors
PLUS+1® software
PLUS+1® software services,
support and training Position controls and
sensors PVG proportional valves
Steering components and
systems Telematics
Danfoss Power Solutions is a global manufacturer and supplier of high-quality hydraulic and electric components. We specialize in providing state-of-the-art technology and solutions that excel in the harsh operating conditions of the mobile off-highway market as well as the marine sector. Building on our extensive applications expertise, we work closely with you to ensure exceptional performance for a broad range of applications. We help you and other customers around the world speed up system development, reduce costs and bring vehicles and vessels to market faster.
Danfoss Power Solutions – your strongest partner in mobile hydraulics and mobile electrification.
Go to www.danfoss.com for further product information.
We offer you expert worldwide support for ensuring the best possible solutions for outstanding performance. And with an extensive network of Global Service Partners, we also provide you with comprehensive global service for all of our components.
Local address:
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequent changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
©
Danfoss | October 2021 BC187186484889en-000107
Loading...