Danfoss PVE 7 Series Service Manual

Page 1
Service Manual
Electrohydraulic Actuators
PVE Series 7
powersolutions.danfoss.com
Page 2
Revision history Table of revisions
Date Changed Rev
Service Manual
PVE Series 7
2 | © Danfoss | August 2017 AX00000348en-US | 0101
Page 3
Abbreviations Chart
List of abbreviations for PVG/PVE...............................................................................................................................................4
Danfoss Literature Reference.......................................................................................................................................................5
Warnings
PVE warnings......................................................................................................................................................................................6
General Information
Introduction........................................................................................................................................................................................7
General instructions........................................................................................................................................................................ 8
Safety precautions............................................................................................................................................................................8
PVG with the PVE overview...........................................................................................................................................................9
Troubleshooting............................................................................................................................................................................... 9
Connector Overview.....................................................................................................................................................................10
Hydraulic Principle Variants....................................................................................................................................................... 12
Exchanging PVE
Before replacing or dismounting a PVE.................................................................................................................................14
Dismounting of PVE...................................................................................................................................................................... 14
Mounting of Replacement..........................................................................................................................................................15
Test and use of PVG and Actuator........................................................................................................................................... 15
Returning Replaced Actuator for Customer Claims.......................................................................................................... 15
Service Manual
PVE Series 7
Contents
©
Danfoss | August 2017 AX00000348en-US | 0101 | 3
Page 4
List of abbreviations for PVG/PVE
Abbreviation Description
ASIC Application Specific Integrated Circuit - the part of the PVE where spool position is controled to
follow setpoint ATEX Certificated for use in explosive environment AVC Auxillery Valve Comand - ISOBUS/J1939 standard signal for valve control AVCTO Auxillery Valve Comand Time Out - Fault monitoring setting AVEF Auxillery Valve Estimated Flow - ISOBUS/J1939 standard signal for valve feedback CAN Controller Area Network - Communication method used by PVED CLC Closed Loop Circuit CRC Cyclic Redundancy Check - Method for ensuring validity of data.
-DI PVE with Direction Indication DM1 Diagnostic Message 1 - J1939 message informing about present fault DM2 Diagnostic Message 2 - J1939 message informing about fault history DM3 Diagnostic Message 3 - J1939 message clearing fault history DSM Device State Machine. Deterministic description of system process ECU Electronic Control Unit EH Electrohydraulic
-F PVE for Float spool. Two variants: 4 pin with float at 75%. 6 pin with separate float. FMEA Failure Mode Effect Analysis ISOBUS Communication standard for CAN J1939 Communication standard for CAN LED Light Emitting Diode LS Load Sensing LVDT Linear Variable Differential Transducer - Position sensor NC Normally Closed solenoid valve in PVE NC-H Normally Closed standard solenoid valve in PVEH NC-S Normally Closed solenoid valve Super in PVES NO Normally Open solenoid valve in PVE PLC Programmable Logical Circuit PLUS+1
®
Trademark for Danfoss controllers and programming tool POST Power On Self Test. Boot up evaluation for PVED Pp Pilot Pressure. The oil gallery for PVE actuation PVB Proportional Valve Basic module - valve slice PVBS Proportional Valve Basic module Spool PVBZ Proportional Valve Basic module Zero leakage PVE Proportional Valve Electric actuator PVEA PVE variant with 2-6 % hysteresis PVED PVE variant Digital controlled via CAN communication PVEH PVE variant with 4-9% Hysteresis PVEM PVE variant with 25-35% hysteresis PVEO PVE variant with ON/OFF actuation PVEP PVE variant PWM controled PVES PVE variant with 0-2% hysteresis PVEU PVE variant with US 0-10V PVG Proportional multi-section Valve Group PVHC PV variant with High Current controlled valve actuator
Service Manual
PVE Series 7
Abbreviations Chart
4 | © Danfoss | August 2017 AX00000348en-US | 0101
Page 5
Abbreviation Description
PVM Proportional Valve Manual control with handle PVP Proportional Valve Pump side module.Inlet PVS Proportional Valve end plate PVSK Proportional Valve end plate crane. Inlet module with Spool Control PWM Pulse Width Modulation S4 DJ Series 4 Digital J1939 service tool software for PVED-CC SAE Society Automotive Engineering
-R PVE with Ramp function
-NP PVE with solenoid disable in Neutral Position
-SP PVE with Spool Position feedback uC Microcontroller uCSM Microcontroller State Machine U
DC
Power supply Direct Current; also called V
bat
for battery voltage
U
S
Steering voltage for the PVE control; also called V
S
Danfoss Literature Reference
Danfoss literature reference for PVG and PVE products
Title Type Order number
PVG 32 Proportional Valve Groups Service Manual 11039167 PVG 100 Proportional Valve Groups Service Manual 11048807 PVG 32 Proportional Valve Groups Technical Information 520L0344 PVG 100 Proportional Valve Groups Technical Information 520L0720 PVG 120 Proportional Valve Groups Technical Information 520L0356 PVE Series 7 Technical information BC00000XXXen-US0101 PVG 32 Metric ports Technical Information 11051935
Service Manual
PVE Series 7
Abbreviations Chart
©
Danfoss | August 2017 AX00000348en-US | 0101 | 5
Page 6
PVE warnings
W
Warning
Not applying to the Operational Conditions can compromise safety. All brands and all types of directional control valves – including proportional valves – can fail and cause
serious damage. It is therefore important to analyze all aspects of the application. Because the proportional valves are used in many different operation conditions and applications, the machine builder/ system integrator alone is responsible for making the final selection of the products – and assuring that all performance, safety and Warning requirements of the application are met.
A PVG with PVE can only perform according to description if conditions in this Technical Information are met.
In particularly exposed applications, protection in the form of a shield is recommended. When the PVE is in fault mode the quality of performance and validity of feedback is limited depending
on the fault type. Error pins from more PVEs may not be connected. Inactive error pins are connected to ground and will
disable any active signal. Error pins are signal pins and can only supply very limited power consumption. Deviation from recommended torque when mounting parts can harm performance and module. Adjustment of the position transducer (LVDT) will influence calibration, and thereby also safety and
performance. When replacing the PVE, the electrical and the hydraulic systems must be turned off and the oil pressure
released. PVEA is not for use on PVG 100. Hydraulic oil can cause both environmental damage and personal injury. Module replacement can introduce contamination and errors to the system. It is important to keep the
work area clean and components should be handled with care. After replacement of modules or cables wiring quality must be verified by a performance test. By actuation at voltage below nominal PVG will have reduced performance. The PVE is not designed for use with voltage outside nominal. Obstacles for the Pilot oil can have direct influence on spool control. Reduced pilot oil pressure will limit spool control. Too high pilot oil pressure can harm the PVE.
Service Manual
PVE Series 7
Warnings
6 | © Danfoss | August 2017 AX00000348en-US | 0101
Page 7
Introduction
This manual includes information for trouble shooting and servicing the PVE actuators. The actuators are used on PVG 32, PVG 100, PVG120 and some EH steerings. This manual does not cover the PVG in general nor any steering.
PVE actuators
The PVE for PVG 32 and PVG 100 are the same, for PVG 120 includes a special interface plate, has another LVDT-pin and allows larger spool travel. Service on the actuators is identical independent of valve size.
In general service on PVE is limited to exchange of O-rings and connectors or whole actuator. Performing service, trouble shooting and repair may require removal of valve and valve parts from the
application. This can easily introduce misplaced parts and contamination and thereby thread performance and safety. Following cleanliness requirements is a prerequisite for service.
For general description, specifications and operating parameters on PVG valves and actuators please see the relevant Technical Information listed in reference list. Danfoss technical literature is available on
www.danfoss.com.
A worldwide network of Danfoss Global Service Partners is available for major repairs. Danfoss trains and certifies Global Service Partners on a regular basis. You can locate your nearest Global Service Partner using the distributor locator at www.danfoss.com.
W
Warning
Do not attempt to service PVG valves without build sheet specifications for reference.
Service Manual
PVE Series 7
General Information
©
Danfoss | August 2017 AX00000348en-US | 0101 | 7
Page 8
General instructions
Follow these general procedures when servicing PVG 32 valves:
Avoid injuries or material damage
Plan the process thoroughly. Block wheels and other moving parts to prevent undesired movement. Secure against leakage of hydraulic fluid. Hydraulic fluid can cause contamination, cause burns due to temperature and other injuries due to high pressure. Follow all instructions from machine builder.
Keep it clean
Cleanliness is the primary mean of assuring long lifetime for the application. Clean the outside of the valve thoroughly before any disassembly. Cap ports and hoses when opening. Avoid contamination by both dirt and chemical agents. Clean parts using a clean solvent wash and air dry.
Replace all O-rings and gaskets
Danfoss recommends inspection of O-rings and gaskets and replacement if wear or contamination could be relevant. Dried out O-rings and gaskets must be replaced.
Safety precautions
Always consider safety precautions before beginning a service procedure. Protect yourself and others from injury. Follow instructions from machine manufacture carefully. Read and include the warnings from the relevant PVG literature in your work planing.
W
Warning
Ensure stable conditions
Manipulation on a mechanical, hydraulic and electrical system can potentially create dangerous situations. Please ensure that all necessary precautions are taken to prevent dangerous situations.
W
Warning
Release hydraulic pressure in system
Shut down pump and release pressure in all work functions, in tank and pilot pressure if not released by previous operations
W
Warning
Disengage electrical system
Disengage power supply and system control. If relevant for application, disengage system output e.g. error pin, direction indicator.
Service Manual
PVE Series 7
General Information
8 | © Danfoss | August 2017 AX00000348en-US | 0101
Page 9
PVG with the PVE overview
The PVG is a sectional spool valve stack with up to 12 individually controlled proportional valves. The PVG with the PVE can be operated as single valves or several valves in cooperation. The oil flow out of the work section (A- or B-port) can be controlled by a combination of the following:
PVE controlling the spool position using pilot oil pressure.
A handle (PVM) in mechanical interface with the spool.
The analog PVE Series 7 is an electro-hydraulic actuator used to control a single work section of a PVG proportional valve group. The PVE Series 7 actuator program includes variants with different performance levels and features for PVG 32/100/120/128/256.
The actuator positions the main spool in a PVG work section in order to control either the flow or the pressure of the oil distributed to/from the work function. The control signal to the actuator is an analog voltage signal, enabling the user to operate the work function remotely by means of a joystick, a controller or the like.
The electro-hydraulic solenoid valve bridge of the actuator is available in different designs, utilizing different regulation principles, depending on performance variant. The actuator positions the main spool by distributing pilot oil pressure to either side of it, pressurizing one side by pilot pressure while relieving the opposite side to tank and vice versa. All proportional actuators feature a closed-loop spool control and continuous fault monitoring.
The analog PVE Series 7 actuator program features five different main hydraulic principle variants (PVEO/M/A/H/S). The different hydraulic principles combined with the different solenoid valve regulation principles determine whether the actuator controls the spool proportionally according to a demand signal or ON/OFF according to a voltage signal.
Valve section - standard mounted - seen from PVP with naming
Troubleshooting
The Service Manuals for PVG 32 and PVG 100 have a thorough description of system troubleshooting and parts troubleshooting. Please look for descriptions there before starting with the actuator. The actuator is an electrohydraulic subsystem used for moving the spool and thereby opens the valve for work flow.
Service Manual
PVE Series 7
General Information
©
Danfoss | August 2017 AX00000348en-US | 0101 | 9
Page 10
Connector Overview
PVEO/PVEO-R/PVEO-HP
Connector Pin 1 Pin 2 Pin 3 Pin 4
1x4 AMP Udc_A Udc_B GND GND 1x4 DEU Udc_A GND GND Udc_B 1x4 DIN Udc_A Udc_B GND
PVEO-DI
Connector Pin 1 Pin 2 Pin 3 Pin 4
2x4 AMP (A) Udc_A Udc_B GND GND 2x4 AMP (B) DI-B DI-A GND Udc
2
PVEM
Connector Pin 1 Pin 2 Pin 3 Pin 4
1x4 DIN Udc Us Error GND
PVEA/PVEH/PVES
Connector Pin 1 Pin 2 Pin 3 Pin 4
1x4 AMP Us Udc GND Error 1x4 DEU Us Error GND Udc 1x4 DIN Udc Us Error GND
PVEA-DI/PVEH-DI
Connector Pin 1 Pin 2 Pin 3 Pin 4
2x4 AMP (A) Us Udc GND Error 2x4 AMP (B) DI-A DI-B GND Udc
2
2x4 DEU (A) Us Error GND Udc 2x4 DEU (B) Udc
2
GND DI-A DI-B
PVEH-FLA
Connector Pin 1 Pin 2 Pin 3 Pin 4 Pin 5 Pin 6
1x6 AMP Us Udc GND Error Float 1x6 DEU Us Error Float GND Udc
PVEH-SP/PVES-SP
Connector Pin 1 Pin 2 Pin 3 Pin 4 Pin 5 Pin 6
1x6 DEU Us Error SP GND Udc
Service Manual
PVE Series 7
General Information
10 | © Danfoss | August 2017 AX00000348en-US | 0101
Page 11
Connector diagrams
1x4 DEUTSCH
2
3
4
1
1x6 DEUTSCH
1
2
3 4
5 6
2x4 DEUTSCH
3 4
1
2
1
2
3 4
A
B
1x4 DIN
1 2
3
4
1x4 AMP
2418
1 2 3 4
1x6 AMP
1
2
34
5 6
2x4 AMP
1 2 3 4
Service Manual
PVE Series 7
General Information
©
Danfoss | August 2017 AX00000348en-US | 0101 | 11
Page 12
Hydraulic Principle Variants
Principle of PVEO/PVEO-R/PVEO-DI
21
0
Pp
LVDT
LED Circuit /
Microcontroller
Power Supply
PVEO-DI
A B
DI_B DI_A
LED
Udc
Ramp Ramp
SV1 SV2
P109126
Principle of PVEM
21
0
Pp
LVDT
SV2SV1
Micro-
controller
Power Supply
U
DC
U
S
Error
LED
P109132
Principle PVEA
21
0
Pp
Micro-
controller
Power
Supply
NP
DI_B DI_A
Udc
LED Error
Us
Udc
2
Special Features
NC1 NC3
LVDT
P109147
Service Manual
PVE Series 7
General Information
12 | © Danfoss | August 2017 AX00000348en-US | 0101
Page 13
Principle of PVEH
21
0
Pp
Micro-
controller
Power Supply
U
S
Special Features
SP
NP
Uf DI_B DI_A
Udc
2
LED
Error
Udc
NC1 NC3
NO4
NO2
LVDT
P109148
Principle of PVES
21
0
Pp
Micro-
controller
Power Supply
Special Features
SP
LED Error
Us
Udc
NC1 NC3
NO2 NO4
LVDT
P109149
Troubleshooting actuator
For warranty claims please verify and describe below points before replacing actuator.
Function of external parts
Spool can move as expected when activated by PVM
Pilot pressure is available
Control signal can activate other PVE/PVHC
Cabling is undamaged
Connectors are with sealing and dry
Function of PVE
Failure is temporary/continues
Failure is in one direction (A or B) or both
Visible damage
Service Manual
PVE Series 7
General Information
©
Danfoss | August 2017 AX00000348en-US | 0101 | 13
Page 14
These guidelines are only meant to point out issues that could be related to the application, the PVG and its actuator. Danfoss can and will not give directives how work has to be planed and supervised.
Before replacing or dismounting a PVE
1. Ensure that the actuator has to be dismounted. Follow the trouble shooting procedure to make sure
that the failure is not elsewhere in the application. See Service Manual for PVG32 and PVG100.
2. Clean surroundings on PVG for dirt and rust/oxidations; and do not use cleaning agents or methods
that require higher IP than the actuator supports.
3. Have a clean area to put new PVE/PVHC before mounting.
4. Have a clean area to put old PVE/PVHC before eventually returning for investigation.
5. Have the right tools at hand.
6. Ensure that spare part is the correct actuator .
7. Unpack replacing actuator:
a) If actuator has LVDT avoid mishandling and bending of it
b) Ensure all O-rings are in place
c) Ensure new bolts are present
d) Ensure presence of eventually electrical connector sealing
e) Eventually clean off excessive oil with a soft tissue. PVE must still be coated with a thin oil film
f) Keep actuator protected from a pollution during the whole process. Keep in a bag.
Mounting of PVE variants
5 [0.2]
8 ± 0.5 N·m [70 ± 4.4 lbf·in]
PVEO/M/A Series 7
5 [0.2]
8 ± 0.5 N·m [70 ± 4.4 lbf·in]
PVEH/S Series 7
P109120
Dismounting of PVE
1. Remove connector(s) from PVE:
a) Pull connector, not cable.
b) Verify if cable and connectors can be reused or must be replaced e.g. isolation, lock.
2. Loosen and unscrew bolts counter clockwise. Be aware of leaking oil.
3. Remove PVE/PVHC carefully:
a) Don’t introduce pollution to PVB nor actuator. Marked areas are especial sensible to pollution
“cover”.
b) Ensure O-rings are removed with actuator.
c) Place removed actuator safe best in a bag.
4. Eventually clean PVB carefully with a soft tissue to have clean interface for replacing actuator.
Service Manual
PVE Series 7
Exchanging PVE
14 | © Danfoss | August 2017 AX00000348en-US | 0101
Page 15
Mounting of Replacement
1. Avoid contamination - also oil in connectors.
2. Avoid harming LVDT pin.
3. Depending on PVB – actuator orientation place one or all bolts in actuator bolt holes.
4. Reassure that O-rings are in place on actuator.
5. Place actuator on PVB and screw bolts lose and clockwise.
6. Tighten bolts to torque indicated in instruction.
7. Connect wiring.
Test and use of PVG and Actuator
After replacement of actuator the system must be tested after manufactures guidelines. After service the PVG must be tested according to manufactures guidelines. Ensure that safety functions
and performance apply to demands. Before restart bleed system. PVG can be bleed through PVM. Let application run for In worst cases air
must be washed out by oil in up to 5 minutes activation.
Returning Replaced Actuator for Customer Claims
If replaced actuator is returned to Danfoss for analysis description of malfunction and application must be submitted too. See form in section “returning claims”.
Service Manual
PVE Series 7
Exchanging PVE
©
Danfoss | August 2017 AX00000348en-US | 0101 | 15
Page 16
Danfoss Power Solutions is a global manufacturer and supplier of high-quality hydraulic and electronic components. We specialize in providing state-of-the-art technology and solutions that excel in the harsh operating conditions of the mobile off-highway market. Building on our extensive applications expertise, we work closely with our customers to ensure exceptional performance for a broad range of off-highway vehicles.
We help OEMs around the world speed up system development, reduce costs and bring vehicles to market faster.
Danfoss – Your Strongest Partner in Mobile Hydraulics.
Go to www.powersolutions.danfoss.com for further product information.
Wherever off-highway vehicles are at work, so is Danfoss. We offer expert worldwide support for our customers, ensuring the best possible solutions for outstanding performance. And with an extensive network of Global Service Partners, we also provide comprehensive global service for all of our components.
Please contact the Danfoss Power Solution representative nearest you.
Local address:
Danfoss Power Solutions GmbH & Co. OHG
Krokamp 35 D-24539 Neumünster, Germany Phone: +49 4321 871 0
Danfoss Power Solutions ApS
Nordborgvej 81 DK-6430 Nordborg, Denmark Phone: +45 7488 2222
Danfoss Power Solutions (US) Company
2800 East 13th Street Ames, IA 50010, USA Phone: +1 515 239 6000
Danfoss Power Solutions Trading (Shanghai) Co., Ltd.
Building #22, No. 1000 Jin Hai Rd Jin Qiao, Pudong New District Shanghai, China 201206 Phone: +86 21 3418 5200
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
©
Danfoss | August 2017 AX00000348en-US | 0101
Products we offer:
Bent Axis Motors
Closed Circuit Axial Piston Pumps and Motors
Displays
Electrohydraulic Power Steering
Electrohydraulics
Hydraulic Power Steering
Integrated Systems
Joysticks and Control Handles
Microcontrollers and Software
Open Circuit Axial Piston Pumps
Orbital Motors
PLUS+1® GUIDE
Proportional Valves
Sensors
Steering
Transit Mixer Drives
Comatrol
www.comatrol.com
Turolla
www.turollaocg.com
Hydro-Gear
www.hydro-gear.com
Daikin-Sauer-Danfoss www.daikin-sauer-danfoss.com
Loading...