Danfoss Pressure controls Service guide

Fitter notes Pressure controls
Contents Page
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Placing of surplus capillary tube. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Low-pressure control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
High-pressure control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Example with four compressors in parallel (R404A). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Setting LP for outdoor location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Indicative evaporating pressures (pe) for dierent types of systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Test of contact function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
The correct pressure control for your system. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Pressure controls
© Danfoss A/S (AC-DSL/MWA), 10 - 2006 DKRCC.PF.000.G1.02 / 520H1459 19
Notes
20 DKRCC.PF.000.G1.02 / 520H1459 © Danfoss A/S (AC-DSL/MWA), 10 - 2006
Fitter notes Pressure controls
Installation
Mount the KP pressure control on a bracket or on a completely at surface.
The pressure control can also be mounted on the compressor itself.
In unfavourable conditions, an angle bracket could amplify vibration in the mounting plane. Therefore, always use a wall bracket where strong vibration occurs.
If the risk of water droplets or water spray is present, the accompanying top plate should be used. The plate increases the grade of enclosure to IP 44 and is suitable for all KP pressure controls. To obtain IP 44, the holes in the backplate of the control must be covered by mounting on either an angle bracket (060-105666) or a wall plate (060-105566).
The top plate is supplied with all units incor­porating automatic reset. It can also be used on units with manual reset, but in that case must be purchased separately (code no.: for single unit, 060-109766; for dual unit, 060-109866).
If the unit is to be used in dirty conditions or where it might be exposed to heavy spray - from above or from the side - it should be tted with a protective cap. The cap can be used together with either an angle bracket or a wall bracket.
Al0_0001
Al0_0007
Pressure controls
Al0_0008
If the unit risk being exposed to heavy water inuence a better grade of enclosure can be achieved when mounting the product in a special IP 55 enclosure.
The IP 55 enclosure is available for both single unit (060-033066) and dual unit (060-035066).
Ak0_0020
© Danfoss A/S (AC-DSL/MWA), 10 - 2006 DKRCC.PF.000.G1.02 / 520H1459 21
Fitter notes Pressure controls
Installation (cont.)
Placing of surplus capillary tube
The pressure connection of the control must always be tted to the pipe in such a way that liquid cannot collect in the bellows. This risk is present especially when:
the unit is located in a low ambient condition, e.g. in an air current,
the connection is made on the underside of the pipe.
Such liquid could damage the high-pressure control.
Consequently, compressor pulsation would not be damped and might give rise to contact chatter.
Surplus capillary tube can fracture if vibration occurs and might lead to complete loss of system charge. It is therefore very important that the following rules are observed:
When mounting direct on compressor: Secure the capillary tube so that the com­pressor/control installation vibrates as a whole. Surplus capillary tube must be coiled and bound.
Note:
According to EN rules it is not allowed to use capillary tube for connecting safety pressure controles. In such case a 1/4 inch tube is prescribed.
Al0_0009
Al0_0010
Setting
Low-pressure control
High-pressure control
Other types of mounting: Coil surplus capillary tube into a loose loop. Secure the length of capillary tube between compressor and loop to the compressor.
Secure the length of capillary tube between loop and pressure control to the base on which the pressure control is mounted.
In case of very strong vibrations, Danfoss steel capillary tubes with are connection are recommended: Code no. 0.5 m = 060-016666 Code no. 1.0 m = 060-016766 Code no. 1.5 m = 060-016866
KP pressure controls can be preset using a com­pressed air cylinder. Ensure that the change-over contacts are correctly connected for the required function.
Set the start pressure (CUT IN) on the range scale (A). Then set the dierential on the dierential scale (B). Stop pressure = CUT IN minus DIFF.
Set the stop pressure (CUTOUT) on the range scale (A). The set the dierential on the dierential scale (B). Start pressure = CUT OUT minus DIFF.
Remember: The scales are indicative only.
Al0_0011
Al0_0012
22 DKRCC.PF.000.G1.02 / 520H1459 © Danfoss A/S (AC-DSL/MWA), 10 - 2006
Fitter notes Pressure controls
Example with four compressors in parallel (R404A)
Setting LP for outdoor location
Indicative evaporating pressures (pe) for dierent types of systems
Medium: ice cream at –25°C, t0 –37°C,
Compressor CUT OUT CUT IN
p0 –0.5 bar, p suction line corresponding to 0.1 bar.
Each pressure control (e.g. KP 2) must be set individually in accordance with the following table.
The pressure control must be mounted in such a way that liquid cannot collect in the bellows.
If the compressor, condenser and receiver are situated outdoors, KP low pressure must be set to a “CUT IN” setting lower than the lowest occurring pressure (temperature around compressor) during winter operation. In this case, after longer standstill periods the pressure in the receiver determines the suction pressure.
Example:
Lowest occurring temperature around the compressor –20°C means, for R404A, a pressure of 1 bar. CUT IN must be set at –24°C (corre­sponding to 1.6 bar).
Al0_0013
Room temp. (tr) System type Dierence
+0.5°/+2°C Fan-cooled
meat cold room
+0.5°/+2°C Meat cold room with
natural air circulation
–1°/0°C Refrigeration meat
counter (open)
+2°/+6°C Milk cold room 14K 1.0 bar
0°/+2°C Fruit cold room
Vegetable chiller
–24°C Freezer 10K 1.6 bar
–30°C Ventilated deep
freeze room
–26°C Ice cream freezer 10K 1.4 bar
between te and t
media
10K 1.0 - 1.1 bar
12K 0.8 - 0.9 bar
14K 0.6 bar
6K 1.3 - 1.5 bar
10K 1 bar
Evaporating pressure (pe)
(air)
(R134a)
(R134a)
(R134a)
(R134a)
(R134a)
(R404A)
(R404A)
(R404A)
1 –0.05 bar 0.35 bar 2 0.1 bar 0.5 bar 3 0.2 bar 0.6 bar 4 0.35 bar 0.75 bar
RH
Setting of KP2/KP1
[%]
(cut in - cut out) D = Operating press. cont. S = Safety press. cont.
85 0.9 - 2.1 bar (D)
85 0.7 - 2.1 bar (D)
85 0.5 - 1.8 bar (D)
85 0.7 - 2.1 bar (D)
90 1.2 - 2.1 bar (D)
90 0.7 - 2.2 bar (S)
90 0.3 - 2.7 bar (S)
90 0.5 - 2.0 bar (S)
Pressure controls
Al0_0015
© Danfoss A/S (AC-DSL/MWA), 10 - 2006 DKRCC.PF.000.G1.02 / 520H1459 23
Fitter notes Pressure controls
Test of contact function
When the electrical leads are connected and the system is under normal operating pressure, the contact function can be tested manually.
Depending on the bellows pressure and setting, the test device must be pressed up or down.
Any reset mechanism becomes inoperative during the test.
On single units:
Use the test device at top left.
On dual units:
Use the test device on the left for low-pressure testing and the one at bottom right for high­pressure testing.
Warning! The contact function on a KP Pressure Control must never be tested by activating the device at top right. If this warning is ignored, the control may go out of adjustment. In the worst case function can be impaired.
Al0_0018
Al0_0019
On the KP 15 dual pressure control with optional automatic or manual reset on low-pressure and high-pressure side, automatic reset must be set when servicing is being carried out. The pressure control can then automatically restart. Remember, the original reset function must be set after servicing.
The pressure control can be protected against being set on automatic reset: Simply remove the washer controlling the reset function! If the unit is to be protected against tampering, the washer can be sealed with red lacquer.
Al0_0020
Low pressure Manual reset *) Automatic reset Automatic reset Manual reset
High pressure Manual reset *) Manual reset Automatic reset Automatic reset
*) Factory setting
Al0_0021
24 DKRCC.PF.000.G1.02 / 520H1459 © Danfoss A/S (AC-DSL/MWA), 10 - 2006
Fitter notes Pressure controls
The correct pressure control for your system
KP with solder connections can be used instead of are connections on hermetic systems.
In ammonia plant where KP pressure controls are used, they must be type KP-A. A connector with M10 × 0.75 – 1/ no. 060- 014166).
- 18 NPT (code
4
Al0_0006
Pressure controls
For refrigerating systems containing a large quantity of charge medium and where extra safety is desired/demanded (Fail-safe): Use KP 7/17 with double bellows. The system will stop if one of the bellows ruptures - without loss of charge.
For systems operating with low pressure on the evaporator side, and where the pressure control must regulate (not just monitor): Use KP 2 with a small dierential. An example where pressure control and thermo­stat are in series:
KP 61 regulates the temperature via compressor stop/start. KP 2 stops the compressor when suction pressure becomes too low.
KP 61: CUT IN = 5°C (2.6 bar) CUT OUT = 1°C (2.2 bar)
KP 2 low pressure: CUT IN = 2.3 bar CUT OUT = 1.8 bar
Al0_0002
Al0_0003
Al0_0004
© Danfoss A/S (AC-DSL/MWA), 10 - 2006 DKRCC.PF.000.G1.02 / 520H1459 25
Fitter notes Pressure controls
The correct pressure control for your system (cont.)
For systems where KP is activated occasionally (alarm) and for systems where KP is the signal source for PLC, etc.: Use KP with gold contacts; these give good contact at low voltages.
Al0_0005
26 DKRCC.PF.000.G1.02 / 520H1459 © Danfoss A/S (AC-DSL/MWA), 10 - 2006
Loading...