Liquid level regulating valves
Type PMFL / PMFH and SV
For modulating liquid level control in refrigeration,
freezing and air conditioning plant
For modulating liquid level control in
refrigeration, freezing and air conditioning
plant, a system comprising a liquid level
regulating valve type PMFL or PMFH, controlled
by a pilot oat valve type SV, is used.
PMFL and SV systems are used on the
evaporator side. PMFH and SV systems are used
on the condenser side.
The system is suitable for use with ammonia or
uorinated refrigerants. The PMFL and PMFH
can be used in liquid lines to or from
• evaporators
• separators
• intermediate coolers
• condensers
• receivers
Modulating liquid level regulation provides
liquid injection that is proportional to the
actual capacity. This gives a constant amount of
ashgas, thus ensuring stable regulation and
economic operation because variations in
pressure and temperature are held to a
minimum.
AI242086443737en-001001
Liquid level regulating valves, Type PMFL / PMFH and SV
Features
• Applicable to HCFC, HFC and R717 (Ammonia)
• PMFL / PMFH are based on PM valve family housings
• Same ange programme as for PM valve series
• Valve housing in low temperature cast iron (spherical) - EN GJS 400-18-LT
• Manual operation possible
• Position indicator available
• Pressure gauge connection to monitor inlet pressure
• Simple installation
• Main valve top cover can be located in any position without aecting the function
• Classication: DNV, CRN, BV, EAC etc. To get an updated list of certication on the products please contact your
local Danfoss Sales Company
C/w normal (factory mounted) spring set, subcooling 0 – 8 K ~ 0 – 14 F
Pressure
dierence (Dp) over PMFL in bar or psi
< 5 bar
5 – 8 bar
8 – 10 bar
10 – 12 bar
> 12 bar
< 72 psi
72 – 116 psi
116 – 145 psi
145 – 174 psi
> 174 psi
80
No tension
2 – 3
3 – 4.5
4.5 – 6
ca. 7
125
No tension
3 – 5
5 – 7
7 – 9
ca. 10
200
No tension
3 – 5
5 – 7
7 – 9
ca. 10
300
No tension
4 – 6
6 – 9
9 – 12
ca. 14
PMFL
C/w strong spring set, subcooling 8 – 40 K ~ 14 – 72 F
Pressure
dierence (Dp) over PMFL in bar or psi
6 – 9 bar
> 9 bar
87 – 131 psi
> 131 psi
80
4
Max. tension
125
6
Max. tension
Liquid level regulating valves, Type PMFL / PMFH and SV
Functions
PMFL
Figure 1: PMFL
When the liquid level inside the oat drops, the oatorice opens. This relieves the higher pressure, ps, acting on
the servo piston to the low pressure side causing the PMFL to open. Variations in liquid level will result in variations
in pressure over the piston and variation in the amount of liquid injected. It is important to choose the correct
spring set when designing the plant. The spring set should be selected from the table below:
Table 1: Subcooling
The setting spindle, pos. 60, has not been set from factory. It is imperative that the setting spindle is adjusted before
the valve is put into operation. The outer spring, pos. 23, is preset and the inner spring, pos. 43, is adjusted when
turning the spindle. The following tables shows the adjustment of the inner spring in number of turns of the spindle
as a function of valve size, spring type and pressure dierence:
C/w stong spring set, subcooling 8 – 40 K ~ 14 – 72 F
Pressure dierence (Dp) over PMFL in bar or psi
6 – 16 bar
87 – 232 psi
300
Spring must always be set to max. tension
PMFL
C/w weak spring set, low pressure plants
Pressure dierence (Dp) over PMFL in bar or psi
1.2 – 1.8 bar
1.8 – 2.5 bar
2.5 – 3 bar
3 – 4 bar
17 – 26 psi
26 – 36 psi
36 – 43 psi
43 – 58 psi
80
No tension
3 – 4
4 – 6
Max. tension
125
No tension
4 – 6
6 – 8
Max. tension
200
No tension
4 – 6
6 – 8
Max. tension
300
No tension
5 – 7
5 – 7
Max. tension
From compressor
To compressor
From evaporator
Condenser
Alarm
Alarmfloat switch
Throughtype receiver
Liquid level
Overflow
valve
Filter
Oil drainvalve
Toevaporator
Liquid level regulating valves, Type PMFL / PMFH and SV
Table 4: PMFL
Table 5: PMFL
Figure 2: PMFL function example
The values for spindle turns are an indication for an initial setting only. If a position indicator is used, a more precise
modulation can be achieved when ne tuning the valve setting. If the PMFL is not opening fully, the spring tension
must be reduced. If the PMFL is operating in a ON / OFF function, the spring tension should be increased. The
condenser pressure will have an eect on the ne tuning and large variations in condensing pressure might call for
readjustment. The subcooling is measured just before the PMFL and the pressure dierence is for the valve only
excluding piping and armatures.
The PMFL can be used together with SV 4 as a pilot valve.
The orices determines the Kv (Cv) value of the pilot and the following table can be used as an initial selection guide:
Liquid level regulating valves, Type PMFL / PMFH and SV
Table 6: PMFL
The nal choice of orice may vary depending on refrigerant and pressure levels. Smaller pressure levels needs a
bigger orice. Pressure dierence levels below 3 bar (43 psi) need SV 4 – 6 with Ø3 mm orice.
SV oats for PMFL
SV 4 can be used for PMFL low pressure control system. The oat must be connected as shown.
Figure 3: SV oats for PMFL
NOTE:
Only one inlet connection possible for SV 4.
PMFH
Figure 4: PMFH
If the liquid level inside the SV oat rises, the oatorice opens and relieves pressure through the pilot line to the
top of the PMFH, increasing the pressure, ps, moving the pushrod downwards and opening the PMFH. The pilot line
is connected in the topcover at SI. Override of the pilot signal can be made by using an EVM valve at SII. It is
important to choose the correct spring set when designing the plant. The spring set should be selected from the
table below:
Liquid level regulating valves, Type PMFL / PMFH and SV
Table 7: spring set selection
The PMFH can be used together with either SV 1 or 3 with the SV mounted with the bleed valve downwards, refer to
the drawing below. This reverses the opening so that rising oat opens the orice.
Figure 5: PMFH function example
NOTE:
High pressure oat system (for explanatory purposes only)
SV 1 - 3
SV 1 – 3 oat has 2 dierent pilot connections: S-port (series connection with PMFH) or P-port (parallel connection
with the PMFH).
P-port:
When using the P-port, it is possible to force open the PMFH valve to a fully open position. This is practical for
service purposes or to conrm if the oat has sucient capacity for the PMFH and the operating conditions.
However, when P-port connection is used it is possible to overll a system due to constant bleeding or unautorised
tampering. In this case, it is advisable to introduce a shut o when the liquid level reaches a preset point. Shut o
can be done via an electrical switch if an EVM valve is mounted in the SII port in the top of the PMFH. It is only
advisable to use the P-port at low pressure dierence.
S-port:
The S-port oers the advantage of a preorice which divides the pressure drop and any wear possibility due to
cavitation. S-port connection must be used at high pressure dierences, dp > 10 bar (145 psi). The Kv (Cv) value of
the SV is higher using P-port than using S-port. A higher P-band can thus be obtained.
Liquid level regulating valves, Type PMFL / PMFH and SV
Media
Refrigerants
Applicable to HCFC, HFC and R717 (Ammonia).
New refrigerants
Danfoss products are continually evaluated for use with new refrigerants depending on market requirements.
When a refrigerant is approved for use by Danfoss, it is added to the relevant portfolio, and the R number of the
refrigerant (e.g. R513A) will be added to the technical data of the code number. Therefore, products for specic
refrigerants are best checked at store.danfoss.com/en/, or by contacting your local Danfoss representative.
Liquid level regulating valves, Type PMFL / PMFH and SV
Product specication
Pressure and temperature
Table 8: Pressure and temperature data
NOTE:
Max. working pressure is limited to
MWP = 21 bar when media temperatures are:
below -20 °C for valves made of GGG-40.3 and
below -10 °C for valves made of GG-25.
Δtsub = tc - tl = 30 °C - 20 °C = 10 K
Calculations do not take into account pressure loss in pipelines.
Pressure drop across valve
Δp = p
c
- pe = 11.9 - 2.9 bar = 9 bar
Correction factor for 10 K subcooling
0.98
Corrected capacity
600 kW × 0.98 = 588 kW
Liquid level regulating valves, Type PMFL / PMFH and SV
PMFH
Figure 7: PMFH
Sizing
Sizing example for PMFL
Table 9: Sizing example for PMFL
NOTE:
The corrected capacity can be found in the capacity table. It will be seen from the table that valve type PMFL 80-4
should be chosen. Refering to “ordering table”, code number 027F0053 can be found. For details of anges,
accessories and pilot valve, see Ordering section.
Since Δp = 9 bar and Δt
set must be used. The pilot line is connected to SV at connection S. In the ordering table the code number for the
spring set can be found: 027F0118.
= 10 K, it will be seen from the “C/w strong spring set” for PMFL that a “STRONG” spring
Δtsub = tc - tl = 30 °C - 20 °C = 10 K
Calculations do not take into account pressure loss in pipelines.
Pressure drop across valve
Δp = pc - pe = 11.9 - 2.9 bar = 9 bar
Correction factor for 10 K subcooling
0.98
Corrected capacity
2200 kW × 0.98 = 2156 kW
∆t K24101520253035404550k
1.0110.98
0.96
0.94
0.92
0.91
0.89
0.87
0.86
0.85
∆t K24101520253035404550k
1.0110.96
0.93
0.9
0.87
0.85
0.83
0.8
0.78
0.77
DANFOSS27F692_08-2017
M24 × 1.5
KW 32
G3/8A
AF 22
∅6.5 / ∅10
Liquid level regulating valves, Type PMFL / PMFH and SV
Sizing example for PMFH
Table 10: Sizing example for PMFH
NOTE:
The corrected capacity can be found in the capacity table. It will be seen from the table that valve type PMFH 80-7
should be chosen. In the ordering table the code number for the valve can be found: 027F3060 for CE-approved
valve. For details of anges, accessories and pilot valve, see Ordering section.
Correction factors
When dimensioning, multiply the evaporator capacity by a correction factor k dependent on the subcooling Δt
just ahead of the valve. The corrected capacity can then be found in the capacity table.
Liquid level regulating valves, Type PMFL / PMFH and SV
Ordering
Table 16: Rated capacity in kW (1 kW = 0.284 TR)
NOTE:
The rated capacity is given at
Evaporating temperature te = 5 °C,
Condensing temperature tc = 32 °C and
Liquid temperature tl = 28 °C.
Figure 10: Main valveFigure 11: Main valve
Table 17: Main valve
NOTE:
The code nos. stated apply to main valves type PMFL or PMFH incl. ange gaskets, ange bolts, blanking plug and
pilot connection with Ø6.5 / Ø10 mm weld nipple.
The PMFL / PMFH valves are approved and CE marked in accordance with Pressure Equipment Directive 97/23/EC. For further details / restrictions - see Installation guide.
PMFL / PMFH-valves
(1)
Nominal bore
DN≤ 25 (1 in.)
DN 32-125 mm (1
1
⁄4 - 5 in.)/
DN 150 mm (6 in.)
Classied for
Fluid group I
Catagory
Article 3, paragraph 3
II
III
Liquid level regulating valves, Type PMFL / PMFH and SV
Certicates, declarations, and approvals
The list contains all certicates, declarations, and approvals for this product type. Individual code number may have
some or all of these approvals, and certain local approvals may not appear on the list.
Some approvals may change over time. You can check the most current status at danfoss.com or contact your local
Danfoss representative if you have any questions.
Danfoss oers a wide range of support along with our products, including digital product information, software,
mobile apps, and expert guidance. See the possibilities below.
The Danfoss Product Store
The Danfoss Product Store is your one-stop shop for everything product related—no matter where
you are in the world or what area of the cooling industry you work in. Get quick access to essential
information like product specs, code numbers, technical documentation, certications, accessories,
and more.
Start browsing at store.danfoss.com.
Find technical documentation
Find the technical documentation you need to get your project up and running. Get direct access to
our ocial collection of data sheets, certicates and declarations, manuals and guides, 3D models
and drawings, case stories, brochures, and much more.
Start searching now at www.danfoss.com/en/service-and-support/documentation.
Danfoss Learning
Danfoss Learning is a free online learning platform. It features courses and materials specically
designed to help engineers, installers, service technicians, and wholesalers better understand the
products, applications, industry topics, and trends that will help you do your job better.
Create your Danfoss Learning account for free at www.danfoss.com/en/service-and-support/learning.
Get local information and support
Local Danfoss websites are the main sources for help and information about our company and
products. Find product availability, get the latest regional news, or connect with a nearby expert—all
in your own language.
Find your local Danfoss website here: www.danfoss.com/en/choose-region.
Spare Parts
Get access to the Danfoss spare parts and service kit catalog right from your smartphone. The app
contains a wide range of components for air conditioning and refrigeration applications, such as
valves, strainers, pressure switches, and sensors.
Download the Spare Parts app for free at www.danfoss.com/en/service-and-support/downloads.
Coolselector®2 - nd the best components for you HVAC/R system
Coolselector®2 makes it easy for engineers, consultants, and designers to nd and order the best
components for refrigeration and air conditioning systems. Run calculations based on your operating
conditions and then choose the best setup for your system design.
Download Coolselector®2 for free at coolselector.danfoss.com.
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its
products without notice. This also applies to products already on order provided that such alterations can be made without subsequential
changes being necessary in specications already agreed. All trademarks in this material are property of the respective companies. Danfoss and
the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.