PLUS+1® Compliant Function Block Library—Filter Function Blocks
Contents
Risk Reduction
Design, Test, and Secure to Reduce Risks................................................................................................................................4
Function Block Connections.........................................................................................................................................................7
Function Block Connections...................................................................................................................................................... 11
Status Logic......................................................................................................................................................................................11
Identical Function Blocks Need Different Namespace Values to Successfully Compile...................................... 11
Function Block Connections...................................................................................................................................................... 15
Status Logic......................................................................................................................................................................................15
Identical Function Blocks Need Different Namespace Values to Successfully Compile...................................... 15
Function Block Connections...................................................................................................................................................... 21
Status Logic......................................................................................................................................................................................22
Split and Dwell Tm Values.......................................................................................................................................................... 23
Sft Strt and Sft End Values...........................................................................................................................................................27
Identical Function Blocks Need Different Namespace Values to Successfully Compile...................................... 29
Function Block Connections...................................................................................................................................................... 34
Function Block Values.................................................................................................................................................................. 35
Identical Function Blocks Need Different Namespace Values to Successfully Compile...................................... 35
Danfoss | January 201911062070 | AQ00000101en-000102 | 3
User Manual
PLUS+1® Compliant Function Block Library—Filter Function Blocks
Risk Reduction
Design, test, and secure applications that you develop to reduce risks of personal injury and equipment
damage.
Design, Test, and Secure to Reduce Risks
Applications created with PLUS+1® GUIDE typically control equipment such as tractors, cranes, and
harvesters.
Using heavy, powerful, and mobile off-road equipment always involves the risk of personal injury and
equipment damage, even when this equipment is operating under normal operating conditions.
Abnormal operating conditions greatly increase the risk of personal injury and equipment damage.
The PLUS+1® program has no automatic protections against these risks. The tool has no protection
against the risks that result from bugs in the tool software, errors in the tool manual, or incompatibilities
between software versions of the tool.
You must:
•
Design your application to reduce these risks.
•
Test your application to reduce these risks.
•
Secure your application against unauthorized changes in its operating parameters to reduce these
risks.
Design
Test
As you design your application, you must include the fault checking and the error handling needed to
reduce risks in normal and abnormal operating conditions.
Consider the following when developing fault checking and error handling for your PLUS+1® GUIDE
application:
•
How the machine is normally used.
•
Possible operator errors and their consequences.
•
Industry safety standards and legal requirements.
•
Input and output failures and their consequences. These failures can include:
Joystick, sensor, and other inputs suddenly going to ±100 % or to 0 %.
‒
Joystick, sensor, and other inputs suddenly going to ±100 % or to 0 %.
‒
Outputs that control machinery direction, speed, and force suddenly changing direction or going
‒
to ±100 % or to 0 %.
Decide how likely each failure is. The more likely a failure, the more you need to protect against
the consequences of the failure.
•
The sequence of events and consequences of a fault or error.
•
The sequence of events and consequences of an emergency stop.
After creating an application, you are responsible for testing the application.
Download your application to hardware and test its operation under both normal and abnormal
operating conditions. Make sure:
•
Individual inputs produce expected outputs.
•
Fault handling and error checking work as designed.
You must repeat your tests when you make configuration, calibration, or software changes to the
application.
PLUS+1® Compliant Function Block Library—Filter Function Blocks
Risk Reduction
Secure
You have the responsibility to secure your application against unauthorized changes.
Always use the PLUS+1® GUIDE program’s Toolkey feature to restrict access to your application’s
operating parameters.
•
Without Toolkey protection, there is an increased risk that unauthorized personnel could use the
PLUS+1® Service Tool program to change your application’s operating parameters.
Changes in your application’s operating parameters might cause unexpected machinery movement
that results in personal injury and equipment damage.
•
Toolkey protection reduces the risk that unauthorized personnel could use the PLUS+1® program to
change your application’s operating parameters.
Refer to How to Use the Toolkey to Restrict Service Tool Access to Application Values in the PLUS+1—How-to
chapter of the PLUS+1 GUIDE User Manual (Danfoss part 10100824).
PLUS+1® Compliant Function Block Library—Filter Function Blocks
Exp_Filter Function Block
IEC 61508-3 Annex D Supplemental Information
The following table provides IEC 61508-3 Annex D supplemental information.
Item
Function block nameExp_Filter
Function block version4.0.
Function block development
environment
Compatible hardware
Function block developed in
compliance with
Competence required of
function block integrator
Contacting Danfoss
Description
PLUS+1® GUIDE version 8.1 and later.
Verified in the PLUS+1® GUIDE compile process.
When the PLUS+1® GUIDE compiler finds a function block that is incompatible with hardware, it aborts the compile
process and logs an error message. The error message gives the location of the function block and states “Error 80:
component not supported in hwd.”
Danfoss Software Product Development Process (PDP), which includes ISO 9001 and IEC 61508-3 standards.
The knowledge, competence, and training required to:
Understand this manual.
•
Use the PLUS+1® GUIDE program to develop a machine control application.
•
Follow quality software practices to develop a machine control application.
PLUS+1® Compliant Function Block Library—Filter Function Blocks
Median_Filter Function Block
Function Block Connections
Connections made with the Median_Filter function block are described.
ItemDescription
1
2Sets the interval between consecutive input samples.
3Sets the number of sample used in the calculation of the middle value.
4The signal to be filtered.
5Outputs a bus with all of the function block's input and output signals.
6Reports the status of the function block.
7The Input signal after filtering.
True—include the function block’s built-in Advanced Checkpoint with Namespace in the compiled LHX download file.
•
False—exclude the function block’s built-in Advanced Checkpoint with Namespace components from the compiled LHX download file.
•
Status Logic
This topic describes how status logic is indicated for the function block.
StatusHex
Invalid setup.0x80081000
*
Bit 16 set to 1 identifies a standard Danfoss status or fault code.
*
Binary Cause
Smpl Nmbr input is greater than
7.
LoopTm input is out of range.
ResponseCorrection
The function block clamps its
Smpl Nmbr input at 7,
The function block clamps its
LoopTm input at 1,
Identical Function Blocks Need Different Namespace Values to Successfully Compile
If you use the same function block more than once in an application, you must change each function
block’s namespace value to avoid compiler errors.
All function blocks contain Advanced Checkpoint with Namespace components that enable the PLUS+1
Service Tool to read block input and output values.
Some function blocks contain non-volatile memory components that store function block operating
parameters.
Both these components use memory names (“aliases”) to allocate memory. Identical memory names
cause compiler errors.
The namespace value adds a unique prefix to each component name to avoid errors. Keep each
namespace value short to save controller memory.
PLUS+1® Compliant Function Block Library—Filter Function Blocks
Median_Filter Function Block
IEC 61508-3 Annex D Supplemental Information
The following table provides IEC 61508-3 Annex D supplemental information.
Item
Function block nameMedian_Filter
Function block version4.0.
Function block development
environment
Compatible hardware
Function block developed in
compliance with
Competence required of
function block integrator
Contacting Danfoss
Description
PLUS+1® GUIDE version 8.1 and later.
Verified in the PLUS+1® GUIDE compile process.
When the PLUS+1® GUIDE compiler finds a function block that is incompatible with hardware, it aborts the compile
process and logs an error message. The error message gives the location of the function block and states “Error 80:
component not supported in hwd.”
Danfoss Software Product Development Process (PDP), which includes ISO 9001 and IEC 61508-3 standards.
The knowledge, competence, and training required to:
Understand this manual.
•
Use the PLUS+1® GUIDE program to develop a machine control application.
•
Follow quality software practices to develop a machine control application.
Danfoss | January 201911062070 | AQ00000101en-000102 | 13
User Manual
PLUS+1® Compliant Function Block Library—Filter Function Blocks
Average_Filter Function Block
The Average_Filter function block conditions a signal by outputting the average of the most current
sampling of input.
Up to 128 samples can be used with a configurable interval between each sample for calculating the
average.
Typical uses for this function block include:
Reducing random signal noise on an analog input.
•
Slowing down the response in a digital control.
•
Smoothing and slowing a changing signal to present the signal in a readable format for a display
•
application.
Note that while an increase in the sample time or sample number can reduce signal noise, it can also
reduce the response of the system.
Inputs
The inputs to the Average_Filter function block are described.
Use only the data types specified in this table. Other data types cause compiler errors.
ItemTypeRangeDescription
ChkPtBOOL——
TolU160–65,535Tol (Tolerance) sets the allowed difference between the function block's Input and Output values.
Smpl TmU160–65,535Smpl Tm (Sample Time) sets the interval between consecutive input samples.
Smpl NmbrU80–128Smpl Nmbr (Sample Number) sets the number of samples used in the average calculation.
InputS16-32,768–32,767The signal to be filtered.
True—include the function block’s built-in Advanced Checkpoint with Namespace in the compiled
•
LHX download file.
False—exclude the function block’s built-in Advanced Checkpoint with Namespace components
•
from the compiled LHX download file.
The function block resets its Output to equal its Input when the difference between its Input and
Output values becomes greater than the Tol value.
A 0 Tol value disables this option.
When the Smpl Tm is:
•
Equal to zero, the function block bypasses the filter function.
•
Less than the Loop Tm (OS.ExecTime), the function block uses the Loop Tm as its Smpl Tm.
1000 = 1000 ms.
The function block bypasses the filter function when the Smpl Nmbr equals zero.
PLUS+1® Compliant Function Block Library—Filter Function Blocks
Average_Filter Function Block
Outputs
The outputs of the Mov_Avg function block are described.
ItemTypeRangeDescription
IO
StatusU16——Reports the status of the function block.
OutputS16-32,768–32,767The Input signal after filtering.
Function Block Connections
Bus——Outputs a bus with all of the function block's input and output signals.
This bus provides a convenient way to distribute this function block's signals to your application.
This output follows the standard bitwise scheme described in the Status Logic topic.
Connections made with the Mov_Avg function block are described.
ItemDescription
1
2Sets the allowed difference between the function block's Input and Output values.
3Sets the interval between consecutive input samples.
4Sets the number of samples used in the average calculation.
5The signal to be filtered.
6Outputs a bus with all of the function block's input and output signals.
7Reports the status of the function block.
8The Input signal after filtering.
True—include the function block’s built-in Advanced Checkpoint with Namespace in the compiled LHX download file.
•
False—exclude the function block’s built-in Advanced Checkpoint with Namespace components from the compiled LHX download file.
•
Status Logic
This topic describes how status logic is indicated for the function block.
*
StatusHex
Invalid setup.0x8008
*
Bit 16 set to 1 identifies a standard Danfoss status or fault code.
Binary Cause
1000
Loop Tm (OS.ExecTime) out
•
of range.
Smpl Nmbr > 128.
•
ResponseCorrection
The function block's Output
equals Input.
Identical Function Blocks Need Different Namespace Values to Successfully Compile
If you use the same function block more than once in an application, you must change each function
block’s namespace value to avoid compiler errors.
All function blocks contain Advanced Checkpoint with Namespace components that enable the PLUS+1
Service Tool to read block input and output values.
Some function blocks contain non-volatile memory components that store function block operating
parameters.
Return the Loop Tm
(OS.ExecTime) value to within
its 1–65535 range.
PLUS+1® Compliant Function Block Library—Filter Function Blocks
Average_Filter Function Block
IEC 61508-3 Annex D Supplemental Information
The following table provides IEC 61508-3 Annex D supplemental information.
Item
Function block nameAverage_Filter.
Function block version4.0.
Function block development
environment
Compatible hardware
Function block developed in
compliance with
Competence required of
function block integrator
Contacting Danfoss
Description
PLUS+1® GUIDE version 8.1 and later.
Verified in the PLUS+1® GUIDE compile process.
When the PLUS+1® GUIDE compiler finds a function block that is incompatible with hardware, it aborts the compile
process and logs an error message. The error message gives the location of the function block and states “Error 80:
component not supported in hwd.”
Danfoss Software Product Development Process (PDP), which includes ISO 9001 and IEC 61508-3 standards.
The knowledge, competence, and training required to:
Understand this manual.
•
Use the PLUS+1® GUIDE program to develop a machine control application.
•
Follow quality software practices to develop a machine control application.
Danfoss | January 201911062070 | AQ00000101en-000102 | 17
User Manual
PLUS+1® Compliant Function Block Library—Filter Function Blocks
Soft_Ramp Function Block
Use the Soft_Ramp function block to provide a smooth transition from one value to another.
The Soft_Ramp and the Time_Ramp function blocks output similar ramps. The ramps differ in that the
Soft_Ramp function block adds soft acceleration and deceleration to its ramp.
A typical use for this function block is in propel applications that require smooth starting and stopping.
Note that the:
Inc Tm parameter determines the ramp rate when the output increases in magnitude away from
•
zero.
Dec Tm parameter determines the ramp rate when the output decreases in magnitude towards zero.
•
These parameter characteristics may cause a transition from one ramp rate to another when the Output
crosses zero even if the Split input is false.
Danfoss | January 201911062070 | AQ00000101en-000102 | 19
User Manual
PLUS+1® Compliant Function Block Library—Filter Function Blocks
Soft_Ramp Function Block
Inputs
The inputs to the Soft_Ramp function block are described.
Use only the data types specified in this table. Other data types cause compiler errors.
ItemTypeRangeDescription
ChkPt
SplitBOOL——Sets how the function block handles transitions between positive and negative outputs.
ResetBOOL——
Reset ValS16-32768–32767
Dwell TmU160–65535The time that the function block holds the Output at zero when it transitions this output between
MaxS16-32768–32767The most positive allowed Output value.
MinS16-32768–32767The most negative allowed Output value.
Sft StrtU160–10000Sft Strt (Soft Start) sets the portion of the Output ramp to which the function block applies a gradual,
Sft EndU160–10000Sft End (Soft End) sets the portion of the Output ramp to which the function block applies a gradual,
RangeU160–65535The amount by which the function block changes its Output in the Inc Tm or Dec Tm.
Dec TmU160–65535Dec Tm (Decrement Time) sets the time that it takes for the function block to decrease the absolute
Inc TmU160–65535Inc Tm (Increment Time) sets the time that it takes for the function block to increase the absolute value
InputS16-32768–32767The signal to be filtered.
BOOL——
True—include the function block’s built-in Advanced Checkpoint with Namespace in the compiled
•
LHX download file.
False—exclude the function block’s built-in Advanced Checkpoint with Namespace components
•
from the compiled LHX download file.
T—The Output ramps to a stop at zero before crossing zero.
F—The Output only ramps to a stop when it reaches the Input value.
True—Output value equals the Reset Val.
•
Use at the startup of an application to preload the Output to a non-zero value.
False—The function block applies normal filtering to the Output.
•
The value that the function block applies to its Output when its Reset input goes true.
positive and negative values.
soft-start acceleration profile. Set as percent.
Total Sft values should be less than 10000 (100.00%).
10,000 = 100.00%.
soft-end deceleration profile. Set as percent.
Total Sft values should be less than 10000 (100.00%).
10000 = 100.00%.
Example: A function block with a Range value of 10000 and a Dec Tm of 500 ms takes 500 ms to
decrease its Output value by 10000.
value of its Output by the Range value.
Example: A function block with a Dec Tm of 500 ms and a Range value of 10000 takes:
500 ms to decrease its Output from 10000 to 0.
•
500 ms to decrease its Output from -10000 to 0.
•
1000 = 1000 ms.
of its Output by the Range value.
Example: A function block with a Inc Tm of 500 ms and a Range value of 10000 takes:
PLUS+1® Compliant Function Block Library—Filter Function Blocks
Soft_Ramp Function Block
Function Block Connections
Connections made with the Soft_Ramp function block are described.
ItemDescription
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
True—include the function block’s built-in Advanced Checkpoint with Namespace in the compiled LHX download file.
•
False—exclude the function block’s built-in Advanced Checkpoint with Namespace components from the compiled LHX download file.
•
•
T—The Output ramps to a stop at zero before crossing zero.
•
F—The Output only ramps to a stop when it reaches the Input value.
True—Output value equals the Reset Val.
•
False—The function block applies normal filtering to the Output.
•
The value that the function block applies to its Output when its Reset input goes true.
The time that the function block holds the Output at zero when it transitions this output between positive and negative values.
The most positive allowed Output value.
The most negative allowed Output value.
Sets the portion of the Output ramp to which the function block applies a gradual, soft-start acceleration profile. Set as percent.
Sets the portion of the Output ramp to which the function block applies a gradual, soft-end deceleration profile. Set as percent.
The amount by which the function block changes its Output in the Inc Tm or Dec Tm.
Sets the time that it takes for the function block to decrease the absolute value of its Output by the Range value.
Sets the time that it takes for the function block to increase the absolute value of its Output by the Range value.
The signal to be filtered.
Outputs a bus with all of the function block's input and output signals.
Reports the status of the function block.
Reports the faults of the function block.
True—The absolute value of the Output is decreasing.
•
False—The absolute value of the Output is not decreasing.
•
True—The Output value equals the Input value.
•
False—The Output value does not equal the Input value.
PLUS+1® Compliant Function Block Library—Filter Function Blocks
Soft_Ramp Function Block
IEC 61508-3 Annex D Supplemental Information
The following table provides IEC 61508-3 Annex D supplemental information.
Item
Function block nameSoft_Ramp
Function block version4.0.
Function block development
environment
Compatible hardware
Function block developed in
compliance with
Competence required of
function block integrator
Contacting Danfoss
Description
PLUS+1® GUIDE version 8.1 and later.
Verified in the PLUS+1® GUIDE compile process.
When the PLUS+1® GUIDE compiler finds a function block that is incompatible with hardware, it aborts the compile
process and logs an error message. The error message gives the location of the function block and states “Error 80:
component not supported in hwd.”
Danfoss Software Product Development Process (PDP), which includes ISO 9001 and IEC 61508-3 standards.
The knowledge, competence, and training required to:
Understand this manual.
•
Use the PLUS+1® GUIDE program to develop a machine control application.
•
Follow quality software practices to develop a machine control application.
Danfoss | January 201911062070 | AQ00000101en-000102 | 31
User Manual
PLUS+1® Compliant Function Block Library—Filter Function Blocks
Time_Ramp Function Block
Use the Time_Ramp function block to provide a slower transition from one value to another.
For a given change in Input, the Output changes at a rate specified by the given range and times.
Typical uses for this function block include:
Limiting the rate of change for a propel command.
•
Filtering an input signal.
•
This function block limits linear rates. Consider using the Soft_Ramp function bock if the output
transitions provided by this function block are too aggressive.
PLUS+1® Compliant Function Block Library—Filter Function Blocks
Time_Ramp Function Block
Inputs
The inputs to the Time_Ramp function block are described.
Use only the data types specified in this table. Other data types cause compiler errors.
ItemTypeRangeDescription
ChkPtBOOL——
ResetBOOL——
Rest ValueS16-32768–32767The value that the function block applies to its Output when its Reset input goes true.
RangeU160–65535The amount by which the function block changes its Output in the Inc Tm or Dec Tm.
Dec TmU160–65535Dec Tm (Decrement Time) sets the time that it takes for the function block to decrease the absolute
Inc TmU160–65535Inc Tm (Increment Time) sets the time that it takes for the function block to increase the absolute value
InputS16-32768–32767The signal to be filtered.
True—include the function block’s built-in Advanced Checkpoint with Namespace in the compiled
•
LHX download file.
False—exclude the function block’s built-in Advanced Checkpoint with Namespace components
•
from the compiled LHX download file.
True—Output value equals the Reset Val.
•
Use at the startup of an application to preload the Output to a non-zero value.
False—The function block applies normal filtering to the Output.
•
Example: A function block with a Range value of 10000 and a Dec Tm of 500 ms takes 500 ms to
decrease its Output value by 10000.
value of its Output by the Range value.
Example: A function block with a Dec Tm of 500 ms and a Range value of 10000 takes:
500 ms to decrease its Output from 10000 to 0.
•
500 ms to decrease its Output from -10000 to 0.
•
1000 = 1000 ms.
of its Output by the Range value.
Example: A function block with a Inc Tm of 500 ms and a Range value of 10000 takes:
500 ms to increase its Output from 0 to 10000.
•
500 ms to increase its Output from 0 to -10000.
•
1000 = 1000 ms.
Outputs
The outputs of the Time_Ramp function block are described.
This function block has no Status or Fault outputs.
ItemTypeRangeDescription
IOBus——Outputs a bus with all of the function block's input and output signals.
This bus provides a convenient way to distribute this function block's signals to your application.
DecBOOL——
PasvBOOL——
OutputS16-32768–32767The Input signal after filtering.
Danfoss | January 201911062070 | AQ00000101en-000102 | 33
True—The absolute value of the Output is decreasing.
•
False—The absolute value of the Output is not decreasing.
•
True—The Output value equals the Input value.
•
False—The Output value does not equal the Input value.
•
User Manual
PLUS+1® Compliant Function Block Library—Filter Function Blocks
Time_Ramp Function Block
Function Block Connections
Connections made with the Time_Ramp function block are described.
ItemDescription
1
2
3
4
5
6
7
8
9
10
11
True—include the function block’s built-in Advanced Checkpoint with Namespace in the compiled LHX download file.
•
False—exclude the function block’s built-in Advanced Checkpoint with Namespace components from the compiled LHX download file.
•
True—Output value equals the Reset Val.
•
False—The function block applies normal filtering to the Output.
•
The value that the function block applies to its Output when its Reset input goes true.
The amount by which the function block changes its Output in the Inc Tm or Dec Tm.
Sets the time that it takes for the function block to decrease the absolute value of its Output by the Range value.
Sets the time that it takes for the function block to increase the absolute value of its Output by the Range value.
The signal to be filtered.
Outputs a bus with all of the function block's input and output signals.
True—The absolute value of the Output is decreasing.
•
False—The absolute value of the Output is not decreasing.
•
True—The Output value equals the Input value.
•
False—The Output value does not equal the Input value.
PLUS+1® Compliant Function Block Library—Filter Function Blocks
Time_Ramp Function Block
Function Block Values
The following figure shows how the Inc Tm (Increment Time), Dec Tm (Decrement Time) and Range
values shape the ramps output by the Time_Ramp function block.
Identical Function Blocks Need Different Namespace Values to Successfully Compile
If you use the same function block more than once in an application, you must change each function
block’s namespace value to avoid compiler errors.
All function blocks contain Advanced Checkpoint with Namespace components that enable the PLUS+1
Service Tool to read block input and output values.
Some function blocks contain non-volatile memory components that store function block operating
parameters.
Both these components use memory names (“aliases”) to allocate memory. Identical memory names
cause compiler errors.
The namespace value adds a unique prefix to each component name to avoid errors. Keep each
namespace value short to save controller memory.
PLUS+1® Compliant Function Block Library—Filter Function Blocks
Time_Ramp Function Block
IEC 61508-3 Annex D Supplemental Information
The following table provides IEC 61508-3 Annex D supplemental information.
Item
Function block nameTime_Ramp
Function block version4.0.1
Function block development
environment
Compatible hardware
Function block developed in
compliance with
Competence required of
function block integrator
Contacting Danfoss
Description
PLUS+1® GUIDE version 8.1 and later.
Verified in the PLUS+1® GUIDE compile process.
When the PLUS+1® GUIDE compiler finds a function block that is incompatible with hardware, it aborts the compile
process and logs an error message. The error message gives the location of the function block and states “Error 80:
component not supported in hwd.”
Danfoss Software Product Development Process (PDP), which includes ISO 9001 and IEC 61508-3 standards.
The knowledge, competence, and training required to:
Understand this manual.
•
Use the PLUS+1® GUIDE program to develop a machine control application.
•
Follow quality software practices to develop a machine control application.
2800 East 13th Street
Ames, IA 50010, USA
Phone: +1 515 239 6000
Danfoss
Power Solutions Trading
(Shanghai) Co., Ltd.
Building #22, No. 1000 Jin Hai Rd
Jin Qiao, Pudong New District
Shanghai, China 201206
Phone: +86 21 3418 5200
Products we offer:
Comatrol
www.comatrol.com
Turolla
www.turollaocg.com
Hydro-Gear
www.hydro-gear.com
Daikin-Sauer-Danfoss
www.daikin-sauer-danfoss.com
DCV directional control
•
valves
Electric converters
•
Electric machines
•
Electric motors
•
Hydrostatic motors
•
Hydrostatic pumps
•
Orbital motors
•
PLUS+1® controllers
•
PLUS+1® displays
•
PLUS+1® joysticks and
•
pedals
PLUS+1® operator
•
interfaces
PLUS+1® sensors
•
PLUS+1® software
•
PLUS+1® software services,
•
support and training
Position controls and
•
sensors
PVG proportional valves
•
Steering components and
•
systems
Telematics
•
Danfoss Power Solutions is a global manufacturer and supplier of high-quality hydraulic and
electric components. We specialize in providing state-of-the-art technology and solutions
that excel in the harsh operating conditions of the mobile off-highway market as well as the
marine sector. Building on our extensive applications expertise, we work closely with you to
ensure exceptional performance for a broad range of applications. We help you and other
customers around the world speed up system development, reduce costs and bring vehicles
and vessels to market faster.
Danfoss Power Solutions – your strongest partner in mobile hydraulics and mobile
electrification.
Go to www.danfoss.com for further product information.
We offer you expert worldwide support for ensuring the best possible solutions for
outstanding performance. And with an extensive network of Global Service Partners, we also
provide you with comprehensive global service for all of our components.
Local address:
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alterations can be made without subsequent changes being necessary in specifications already agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.