Danfoss Planning Underfloor Heat Compendium

MAKING MODERN LIVING POSSIBLE
Planning Underfloor Heat
DANFOSS HEATING SOLUTIONS Handbook
Handbook Planning Underfloor Heat
Planning criteria
Standards for underfloor heating
Essential requirements for all calculations:
• Detailed plan of building, construction of outer walls, and size and type of windows. These data are essential for calculation of the heating load in accordance with EN 12831.
• Information on the type of ooring and its
thermal resistance R
dependent on the oor construction, particularly
, since the heat output is
λ,B
that over screed (in accordance with EN 1264 a
thermal resistance of R
living rooms is specied, in bathrooms R
m2 K/W. Other values up to a maximum of 0.15 m2 K/W are to be separately agreed.) R m2 K/W.
= 0.1 m2 K/W R
λ,B
λ,B
for
λ,B
= 0.0
λ,B
= 0.0
• Building plans, building drawings and all room data have to be shown. After the calculations, the pipe layout and data are included in the building plan.
• Danfoss forms for calculations.
The following standards have to be observed when planning and installing oor heating:
EN 1991 Action on structures
EN 1264 Underoor Heating, Systems and
Components
Changes in building methods over the last few decades have brought about lower requirements for heating homes, so that Danfoss underoor heating can meet respective heating requirements for even physiologically acceptable surface tem­peratures. In some rooms, such as bathrooms, additional heating may be necessary, as areas under bath and shower cannot be heated and a higher temperature is required (24° C instead of 20° C). In such rooms the underoor heating maintains the temperature in the oor while other heat comes from sources such as wall heating, heated towel rails, etc.
EN 13813 Screed Material and Floor Screeds
Local building regulations.
Professional information on interface
co-ordination when planning heated underoor constructions (ref: BVF).
Estimated pre-calculations
DIN 4109 Sound Insulation in the Building Industry
ISO EN 140-8 Measurement of sound insulation in buildings and building elements
The output tables of Danfoss SpeedUp and Basic heating systems show output values for various room temperatures as well as the temperatures of the central heating water in relation to dierent oor nishes. These tables give calculations of the mean central heating water temperature with which to run the underoor heating in order to achieve the desired output.
EN 1264 is crucial for the construction of under­oor heating. With the inclusion of EN 13813
‘Screed Material and Floor Screeds’ three Basic
Danfoss constructions are possible.
The required excess heat source temperature determines the supply temperature which is described in more detail in the chapter ‘Calculating the supply Temperature’. The heat ow densities are distributed evenly over the edge and comfort zones. The main central heating water tempera­ture is determined by the type of installation (see output tables).
2
VGCTC202 © Danfoss 06/2009
max 29°C
W
Handbook Planning Underfloor Heat
Standard heating load of an underfloor heated room
Thermal insulation to avoid downward heat loss
When making calculations for Danfoss underoor heating the standard heat load Q essential. For underoor heating in multi-storey
of the room is
N,f
buildings the heat gain of the shared oor can be included into the calculations if there are no restrictions on the work. The heat output QH is generally calculated from the standard heat load of an underoor heated room Q accordance with EN 4701 Part 3.
plus an extra calculation allowance in
H,f
QH = (1 + x)* Q
N,f
It is important to consider the thermal resistance of the insulation below the underoor heating so that the heat of the underoor heating radiates mainly upwards. In accordance with EN 1264, Part 4 there are three dierent kinds of oor/storey constructions and various minimum heat resistances.
Thermal Insulation R
A above rooms with similar use 0.75 m2 K / W
B above rooms with dierent
use*, unheated rooms (e.g. cellar) and on ground oor
C above external air (-15°C) (e.g.
garages, passage ways)
* e.g. rooms above commercially used premises
1.25 m
2.00 m
Ins, min
2
2
K / W
K / W
Q
: Standard heating load of an underoor
N,f
heated room [W]
QH: Heat output calculation
If the heating system, such as an underoor system, can raise the heat output by raising the heat source temperature the extra allowance is is zero. Thus the calculated temperature output equals the standard heat load of an underoor heated room.
The heat resistance R
layer is calculated as follows:
R
with a single insulation
λ.ins
S
=
λ,ins
λ
ins
ins
with: S
: eective insulation thickness [m]
ins
λ
: thermal conductivity [W/m K]
ins
Maximum surface temperature Θ
Fmax
Fluctuation in temperature (W)
In accordance with EN 1264 maximum surface temperatures for phsysiological reasons are set
as follows:
Comfort zone: 29° C Edge zone: 35° C Bathrooms: ti + 9° C = 33° C
Standard room temperatures of 20 or 24° C in bathrooms result in a dierence in surface
The position of the heating pipe can further inuence the output. Depending on the position, varying surface temperatures can occur. Output is higher above the pipes than in between. The dierence between the maximum and minimum surface temperatures is called uctuation (W).
W = θ
F max
- θ
F min
Larger distances between pipes cause larger uctuation. Lower lying pipes slow down the heating sy stem but the ‘ long w ay’ to the sur fac e dis tribu tes the temperature evenly, the uctuation remains small. Since the maximum oor temperature must not be exceeded, larger uctuation causes greater loss in output than a smaller uctuation. In the rst
temperature and room temperature of 9K (in comfort zones and bathrooms) or 15K (in edge zones). Limiting the surface temperature has the eect of limiting the heat output of the underoor heating. It is an important factor when deciding whether to choose additional heating. However, with modern insulation the heat output in underoor heating is sucient in 99 of 100 cases.
case, average oor temperature is signicantly lower than the maximum permitted temperature.
VGCTC202 © Danfoss 06/2009
3
Handbook Planning Underfloor Heat
1 2 5 20 K
W/m²
200
100
50
30
20
10
Characteristic base line
The Characteristic base line shows the relation­ship between the heat ow density and the surface temperature (surface temperature minus room temperature) when the heated area is evenly heated (uctuation = 0).
Heat output q
Mean surface temperature difference
With a surface temperature of 9K above room temperature an output of approx. 100W/m2 is achieved, with an excess temperature of 15K a heat output of approx. 175 W/m2.
Since the characteristic base line has idealised physical parameters and is valid independent of the system, no system, kept at the maximum permitted surface temperature, can reach an output of more than 100 W/m2 or 175 W/m2 in edge zones. Consequently the specic heat output q of the oor surface depends on the dierence between room and surface temperatures as well as the transferability. The latter is dependent on the room data, including the needs to air the room and is described as heat transfer coecient α here 11.1 W/m2K.
q = α
(θF - θi)
ges
ges
θF = Floor temperature °C
θi = Room temperature °C
Example:
At a room temperature of 20° C and a oor temperature of 27° C a heat output of
q = 11.1 W/m2 K * 7°K (27° C - 20° C) = 77.7 W/m2 would be achieved.
Heat source temperature
Installation types
The mean heat source temperature is a rm component of many calculations. It is calculated from the mean value of the supply and return temperatures:
θm = θi + Δθ
H
The heating system Danfoss Basic comprises two dierent installation types in edge zones and three in comfort zone areas.
System Possible pipe distance in cm
BasicRail 8.8 (mean)
BasicRail 12 (mean)
BasicRail 20
BasicRail 25
BasicRail 30
BasicGrip and BasicClip 10
BasicGrip and BasicClip 15
BasicGrip and BasicClip 20
BasicGrip and BasicClip 25
BasicGrip and BasicClip 30
SpeedUp and SpeedUp Eco 12.5
SpeedUp and SpeedUp Eco 25
with:
ΔθH: Excess Heat Source Temperature
θi: Standard - Inside Temperature θm: Heat Source Temperature
The SpeedUp and SpeedUp Eco heating systems has installation types for the edge and comfort zones. They dier in pipe distance.
4
VGCTC202 © Danfoss 06/2009
Handbook Planning Underfloor Heat
Heat output curve Limiting curve
Calculated heat flow density
The heat output and the uctuation of the surface temperature are dependent on several factors:
• Floor surface temperature
• Room temperature
• Pipe distances
• Thickness and thermal conductivity of the load bearing panels
• Lateral heat output
• Thermal resistance of oor nish
• Composition of the layers
In accordance with EN 1264 all factors combine into the following equation heat ow density q:
q = KH + Δθ
H
with:
q: Heat output [W/m2]
KH: Equivalent heat transfer coecient [W/m2 K]
(ocial DIN check)
ΔθH: Excess heat source temperature
When doing the calculations for underoor heating, the calculated heat ow density is to be worked out as follows in accordance with DIN EN 1264, Part 3 :
Q
q
=
des
N,f
A
F
with: q
Calculated heat ow density [W/m2]
des
Q
Standard-heat load of an underoor heated
N,f
room [W]
AF Floor area to be heated [m2]
The heat output achieved from underoor heating is
QF = q * A
F
with:
Δθ
H
θ
- θ
=
V
R
- θ
θ
V
θR - θ
i
i
In
with: θV: Supply temperature θR: Return temperature θi: Standard-inside temperature
When keeping to maximum permitted tempera­tures, the above factors will give, apart from uctuation, limiting curves (calculated according to EN 1264, Part 2). The intersections indicate the heat ow limits and the limits to excess heat source temperatures.
The data for the heat ow densities of the edge zones or comfort zones qR and qA can be calcu­lated from the output diagrams where the excess temperature of the heat source applies. The approved threshold of the heat ow density (intersection of curves with limiting curve) must not be exceeded. The approved density depends on the thermal resistance of the oor covering and the construction type. If one value of the calculated and distributed heat ow density (qR/qA) is above the threshold heat ow density, the threshold density rather than the heat ow density applies. The resulting decrease in excess heat source temperature also reduces the heat ow density of the other combination type of installation. If the standard heat load of a room heated with underoor heating is greater than the heat output of the underoor heating, additional heating for the shortfall should be considered. Q
N,f
- QF.
with: q
Calculated heat ow density
des
Q
Standard-heat load of an underoor heated
N,f
room
AF Floor area to be heated
where q is evenly distributed over the edge zone (maximum 1 m wide) and the comfort zone:
A
R
q =
VGCTC202 © Danfoss 06/2009
A
* qR+
F
A
A
* q
A
A
F
5
Handbook Planning Underfloor Heat
Calculation of excess supply temperature
The calculated supply temperature for a room with the highest calculated heat ow density is assigned q thermal resistance for oor cover of R K/W. Higher values for R account. Bathrooms will have R The dierential temperature σ for the room to be
(except bathrooms) and given a
max
have to be taken into
λ,B
λ,B
= 0.0 m2 K/W.
λ,B
= 0.10 m2
calculated is dened as σ = 5 K. The installation type is chosen so that q max fully achieves the threshold heat ow density indicated in the limiting curve. The maximum permitted excess ow temperature is
Δθ
V, des
≤ Δθ
when
H, des
+
σ
Δθ
σ
2
≤ 0.5:
H
with Δθ
H, des
≤ Δθ
H, G
otherwise:
Δθ
V, des
= Δθ
H, des
σ
+
+
2 (12 Δθ
2
σ
)
H, des
In all other rooms which are operating on calculated ow temperatures the dierential temperature is calculated as follows, as long as
the relation:
σ
j
< 0.5
Δθ
H, j
is:
Δθ
: Excess heat source temperature of each room j
H,j
with:
σ j = 2 * [(Δθ
V, des
) – Δθ
]
H,j
otherwise:
4(Δθ
- Δθ
σ j = 3 * Δθ
*
H, j
[√
1+
V, des
3 * Δθ
)
H, j
-1
H, j
]
Calculation heat source temperature
For calculating the size of the circulating pump the mass ow rate is determined as mH (ow rate of heating water in kg/s). It is independent of the total output (oor heating output, and heat losses to other rooms) as well as dierential temperature.
mH =
* q
A
F
σ * C
R
1 +
(
W
R
- θ
θ
o
i
q * R
u
)
u
+
u
with CW = 4190 J/kgK
The partial heat transfer resistance of the oor
construction Ro (upwards) encompasses both the
thermal conductivity and thermal resistance upwards:
1
Ro =
with1= 0.093 m2 K/W
+ R
α λ
α
S
u
+
λ ,B
u
The sum of the downwards thermal conductivity and downwards thermal resistances is:
Ru = R
λ, ins
with R
+ R
λ, oor
= 0.17 m2 K/W
α, oor
+ R
λ, render
+ R
α, oor
The mass ow rate mH can also be expressed when converted as the ow rate VH:
m
VH =
with ρ = 0.998 kg/dm
H
ρ
3
To determine the ow rate of a heating circuit the ow rate of the room VH must be divided by the number of heating circuits:
V
VHK =
Number of heating circuits
H
6
VGCTC202 © Danfoss 06/2009
Handbook Planning Underfloor Heat
Pressure loss
For the calculations and size of the circulating pump it is important to calculate pressure loss. In order to calculate pressure loss the total length of the pipes IHK and supply and returns have to be determined. Here it is important that the length of the supply and return pipes FEED is double the distance of room to manifold (supply and return). Depending on the laying type the following
values are relevant:
lH = Pipe length of edge zone layout plan * AR
+ Pipe length of comfort zone layout plan * A
The mean length of the heating circuit IHK is calculated thus:
I
IHK = FEED +
Here it must be mentioned that the area layout and the number of heating circuits are determined by the type of screed, i.e. the heating circuits must be compatible with the screed sections.
Number of heating circuits
(
H
A
)
The pressure loss diagram (cf. pressure loss diagram for Danfoss composite pipe) shows, via ow rate per heating circuit V resistance as pressure loss Δp per m. To calculate the total loss of a heating circuit, this value has to be multiplied by the length of the heating circuit.
ΔpHK = Δp * l
Individual heating circuits have dierent lengths and dierential temperatures and show dierent loss of pressure. Pressure compensation ensures that all heating circuits are supplied with sucient water. The ow adjustment is made on the return valve by determining the ow per minute (i.e. the volume ow [l/h] of the individual heating circuits is divided by 60 [min.]).
The total water volume within an underoor heat­ing system is calculated by the length of all heating circuits IHK multiplied by a factor of 0.113 (l/m).
, the pipe friction
HK
HK
Correlation between flow rate, pressure loss and differential temperature:
Threshold values
The smaller the dierential temperature:
• the higher the volume ow
• the higher the ow speed of the medium and
• the higher the pressure loss
• The maximum supply temperature must not exceed 55° C for wet cement and calcium sulphate (CAF) screed
• Heating circuits should not be longer than
100 m, 110 m maximum.
• The optimum length is 120 m.
• Pressure loss of 250 mbar must not be exceeded since the circulating pump, apart from maintaining the pressure head, has to cope with pressure losses in the heating circuits and in the whole system (in manifold, its valves, supply and return pipes, mixing valves, etc.).
• The maximum supply must not exceed 50° C
for gypsum plaster.
Raising the dierential temperature causes a reduction in ow rate.
VGCTC202 © Danfoss 06/2009
7
Handbook Planning Underfloor Heat
Floor Heating Quick Planner
Quick and easy dimensioning of the floor heating system
The proper dimensions for oor heating systems can be calculated in a matter of minutes by using the Internet-based Danfoss Floor Heating Dimensioning Programme. With a few, basic inputs, this easy-to-use software will provide all the necessary information regarding
system design, product selection, and commis­sioning. This makes the Danfoss Floor Heating Dimensioning Programme a very valuable tool in both the bidding and the implementation phases.
8
VGCTC202 © Danfoss 06/2009
Loading...