Danfoss Optyma, Bluestar Installation guide [de]

Instructions
Condensing Units
Bluestar & Optyma™
English / English p. 2
Français / French p. 13
Deutsch / German p. 16
Polski / Polish p. 23
© Danfoss | DCS (CC) | 2016.11
FRCC.PI.050.A1.ML | 1
Instructions
Evaporating temperature (C°)
Ambient temperature (C°)
-15
-5
51520
HGZ R134a
-30 -20 -10 0
10
50
45
35
25
15
HGZ R404A - R507A
-15
-35
25 -30
50
45
35
25
15
LGZ R404A - R507A
-15
-5
510
50
45
35
25
15
MGZ R134a
-30 -20 -10 05
50
45
35
25
15
MGZ R404A - R507A
H
H
D
W
50 Hz W D H 60Hz MGZ 016-018-022-028 HGZ 018 LGZ 022 MGZ 032-036-040 HGZ 022-028-032 LGZ 028-040 MGZ 050-064-080 HGZ 040-050 - HGZ 036 LGZ 044-050 MGZ 100-125-144-160 HGZ 064-080-100 LGZ 088-100
700 500 392 MGZ 018-022
HGZ 018 LGZ 022
800 600 442 MGZ 028-032-036-040
HGZ 022-028 LGZ 028
1000 700 555 MGZ 050-064
HGZ 032-036-040-050 LGZ 044-050
1200 800 671 MGZ 080-100-125-144-160
HGZ 064-080-100 LGZ 088-100
HGZ 125-144-160 1500 870 975 HGZ 125-144-160
D
MBP application
50 Hz Compressor W D H MCZC030 MCZC038 MCZC048 MCZC054 MCZC060 MCZC068 MCZC086 MCZC096 MCZC108 MCZC121 MCZC136 MCZC171 MGZC215 MGZC242 MGZC271
MTZ18 MTZ22 MTZ28 MTZ32 MTZ36 MTZ40 MTZ51 MTZ57 MTZ65 MTZ73
MTZ81 MTZ100 MTZ125 MTZ144 MTZ160
500 620 451
630 650 605
755 700 656
900 900 759
1350 820 759
W
LBP application
50 Hz Compressor W D H LCQC048 NTZ048 500 620 451 LCQC068 LCQC096 LCQC108
NTZ068 NTZ096 NTZ108
630 650 605
LCQC136 NTZ136 755 700 656
LCQC215 LCQC271
NTZ215 NTZ271
900 900 759
LGQC048 NTZ048 700 500 392 LGQC068 LGQC096 LGQC108
NTZ068 NTZ096 NTZ108
800 600 442
LGQC136 NTZ136 1000 700 555
SH=10K
SH=10K Limited Superheat
SH=10K RGT=20°C
When MT compressors are used with R417A, the factory charged mineral oil 160P must be replaced by polyolester oil 160PZ.
2 | © Danfoss | DCS (CC) | 2016.11
Fig. 1
Instructions
1 x coil height Min. clearance: 2 x unit length
Fig.2
Fig.5
Fig.3
Fig.4
© Danfoss | DCS (CC) | 2016.11 | 3
Instructions
4 | © Danfoss | DCS (CC) | 2016.11
Instructions
Contents
1 - Introduction 2 - Transportation, storage 3 - Safety measures prior to assembly 4 - Assembly 5 - Leak detection 6 - Vacuum dehydration procedure 7 - Electrical connections 8 - Filling the system 9 - Verication before commissioning 10 - Start up 11 - Troubleshooting 12 - Maintenance 13 - Replacement 14 - User advisory
1 - Introduction
These instructions pertain to Bluestar condensing units used for refrigeration purposes. They are intended to provide necessary information regar­ding safety features and proper handling of this product.
Note that this is a general document for the en­tire range of condensing units; certain details therefore may not be applicable to the particular model you purchased. Please keep your manual and all relevant information handy for future re­ference.
• Equipment description: condensing units are available under dierent congurations. They incorporate a compressor and a fan-cooled condenser mounted on a base frame. In addi­tion, they may include a liquid receiver, a pres­sure switch, a connecting box and service valves.
• Approved list of refrigerants:
- The MCMC and MGMC product line (tted with Maneurop® MT compressors) can be used with R22 and R417A.
- The MCZC and MGZC product line (tted with Maneurop® MTZ compressors) can be used with R404A, R507A, R134a and R407C.
- The LCQC and LGQC product line (tted with Maneurop® NTZ compressors) can be used with R404A, R452A and R507A.
• Note that Maneurop® compressors are lled with lubricant before leaving the factory:
- The MT series with mineral oil (ref. 160P),
- The MTZ series with polyolester oil (ref. 160PZ),
- The NTZ series with polyolester oil (ref. 160Z). These lubricants must not be mixed with one another.
• Condensing units must only be used for their designed purpose(s) and within their scope of application (refer to Fig. 1).
Condensing units are delivered under ni­trogen gas pressure (between 1 and 2 bar) and hence cannot be connected as is; please refer to the «Assembly» section for further details.
Condensing units are not certied for mobile and explosion-proof applications. Any use of ammable refrigerant (e.g. hydrocarbons) or air is also strictly forbidden.
• Under all circumstances, the EN 378-2:2012 (or other applicable local regulation) requirement must be ful­lled.
When pressure tests are required on the sys­tem, they are to be performed by qualied per-
sonnel, in paying close attention to potential pressure-related hazards and heeding the pres­sure limits displayed on the compressor name­plate or in the application guidelines.
Modications or alterations to the compres­sor or receiver (such as brazing on the shell) not expressly approved by the party responsible for ensuring compliance could invalidate the user’s authorization to operate the equipment.
2 - Transportation, storage
• The condensing unit must be handled in the vertical position (maximum oset from the vertical: 15°). Should the unit be handled in an upside-down position, its performance may no longer be insured.
• Beware that all condensing unit handling must be carried out with extreme caution to avoid any shocks. Appropriate and safe lifting equipment is to be used during handling and unpacking. Be careful with the condenser’s front surface (note that the condenser side is indicated on the pac­kaging).
• Any damage noticed on either the packaging or the product itself upon reception should be indicated on a Customer Claim addressed to the shipping company. The same recommendation applies to all instances when transport instruc­tions have not been fully respected.
• Please review the safety instructions printed on the cardboard packaging before storage.
• Verify that the condensing unit is never stored in an ambient temperature of below -35°C (-31°F) or above 50°C (122°F).
• Ensure that the condensing unit and its packa­ging are not exposed to rain and/or a corrosive, ammable atmosphere.
3 - Safety measures prior to assembly
• All installation and servicing is to be performed by qualied personnel in compliance with all pertinent practices and safety procedures.
• The condensing unit must be located in a well-ventilated area; air ow through unit shall not be restricted in any way (refer to Fig.2). Make sure that the ambient temperature never ex­ceeds 50°C (122°F) during the o-cycle.
• For outdoor installations, provide a shelter or use a Danfoss condensing unit housing.
• Make certain that the condensing unit can be mounted onto a horizontal plane with a maxi­mum slope of 3°.
• Check that the condensing unit model corres­ponds to system specications (capacity, use of refrigerant, etc.).
• Verify that the power supply corresponds to compressor and fan motor characteristics (refer to the condensing unit nameplate for precision).
• Ensure that the refrigerant charging equip­ment, vacuum pumps, etc. for HFC refrigerant systems have been specically reserved for these refrigerants and never used with other CFC, HCFC refrigerants.
• Use only clean and dehydrated refrigera­tiongrade copper tubes as well as silver alloy brazing material.
• Verify that all system components are appro­priate (use of refrigerant, etc.), clean and dehy­drated before being connected to the comple­ted assembly.
Perform a check on the suction lines: horizontal sections are to be sloped downwards towards the compressor. Suction gas velocity must be high enough to provide for an adequate oil re­turn.This velocity must be within 8 to 12 m/s in vertical risers. In horizontal pipes, this velocity can decrease to 4 m/s. The use of U-trap and double-suction risers may be required on ver­tical sections, but not in excess of 4 m unless a second U-trap system has been tted (refer to Fig. 3). Suction line piping must be insulated in order to minimize the eects of superheating.
• The piping connected to the compressor must be congured on the basis of a exible 3-axis de­sign to dampen vibrations and designed in such a way as to prevent free liquid refrigerant migra­tion and drainage back to the compressor sump.
When installing a liquid receiver or any other pressure-containing component on the conden­sing unit, be sure that these components com­ply with the PED 2014/68/EU.
Make sure the installation is equipped with high-pressure safety components (e.g. pressure switch, pressure relief valve) to prevent against the bursting of pressure-containing components.
• Note that all local and regional regulations and safety standards, such as EN 378-2:2012, must be taken into account when designing, connecting and running the system.
4 - Assembly
The condensing unit’s time of exposure to the atmosphere during installation shall be held to a minimum. The condensing unit is tted with suction and liquid copper stubs equipped with shut-o valves to enable connection to the cir­cuit without ingress of air or moisture in the unit.
Opening the shut-o valves before connection will cause moisture contamination of the com­pressor lubricant.
• Rubber grommets can be installed under the condensing unit base frame, as shown in Fig 4, to prevent vibration interference from other operating equipment or machinery and to re­duce vibration transmission to the supporting structure.
Before opening the compressor connection ttings, it is mandatory to connect a 1/4” service hose to the Schrader tting on the compressor shell in order to gradually release the nitrogen holding charge.
• Ensure that no material enters into the system while cutting the tubing. Moreover, never drill holes in the pipe work after installation.
• Avoid are-type connections and exercise great care while brazing (use only state-of-the-art
© Danfoss | DCS (CC) | 2016.11 | 5
Instructions
practices); apply a nitrogen gas ow to prevent oxidation inside the tubing, especially when HFC refrigerants are being used. All brazing ma­terial is to contain a minimum of 5% silver.
• When brazing, protect the valves and all other unit components from torch heat damage (painted surfaces, gaskets, connecting box).
• Note that it is not necessary to remove com­pressor shut-o valves for connection to the system, hence no need to replace associated gaskets.
• Be sure to connect the required safety and control devices onto compressor shut-o valves or ttings.
• In case of oil return through the Schrader tting on the compressor shell, make sure the internal valve is removed.
5 - Leak detection
Never use oxygen or dry air in order to avoid the risk of re or explosion.
• Perform a leak detection test on the complete system by means of: a dry nitrogen pressure test, a mixture of nitrogen and the refrigerant to be used in the system, a helium leak test and/or a deep vacuum test.
• The test should be long enough in duration to ensure the absence of any slow leaks in the sys­tem.
• Use tools specically designed for detecting leaks.
• The low side test pressure must not exceed 1.1 x Ps pressure indicated on the compressor name­plate.
• For high side test pressure, do not exceed the pres­sure indicated on the condensing unit nameplate.
• Whenever the condensing unit is equipped with suction and liquid shut-o valves, these valves are to remain in the closed position while performing the leak test (condensing unit leak test already performed in the factory).
Do not use a megohmeter or apply power to the compressor while it is under vacuum, as this may cause motor winding damage (motor burn-out).
Do not use colored leak detection uids. Do not use chlorouorocarbon in leak testing sys­tems designed for HFC uids.
6 - Vacuum dehydration procedure
Whenever possible (if shut-o valves are pre­sent), the condensing unit must be isolated from the circuit. It is essential to connect the vacuum pump to both the LP & HP sides, in order to avoid dead-ending system parts.
Recommended procedure:
1) Once leak detection has been completed,
2) Pull down the system under a vacuum of 500 μm Hg (0.67 mbar).
3) When the vacuum level of 500 μm Hg has been reached, the system must be isolated from the pump.
4) A vacuum of 500 μm Hg (0.67 mbar) has to be reached and maintained for 4 hours. This pressure is to be measured in the refrigeration system, and not at the vacuum pump gauge.
If pressure increases, restart the leak-detection procedure (refer to the «Leak detection» section of this manual if necessary).
Vacuum pump: A two-stage vacuum pump with gas ballast valve (0,04-mbar standing vacuum) shall be used; its capacity is to be consistent with system volume. Never use the compressor as a vacuum pump. It is recommended to use large-diameter connec­tion lines and to connect these lines to the shut­o valves, rather than to the Schrader connec­tion. This recommendation allows avoiding excessive pressure losses.
Moisture level: At the time of commissioning, system moisture content may be as high as 100 ppm. During ope­ration, the liquid line lter dryer must reduce this level to < 20 ppm.
diagram located in the electrical box cover. For further details, refer to the condensing unit guidelines.
• Note that Maneurop® compressors tted on condensing units are protected against overhea­ting and overloading by an internal safety motor protector. However, an external manual reset overload is recommended for protecting the cir­cuit against over-current.
• The “must trip” value of this overload relay must be set in accordance with power line sizing and design and shall never exceed the “A max.” value stamped on the nameplate.
• On units equipped with an electrical box, all electrical connections (condenser fan motor, compressor motor, pressure control switch, crankcase heater, etc.) have already been wired at the factory. For single-phase compressors, start­and-run capacitors are included in the connec­ting box.
• The connecting box is equipped with screw type terminal blocks, for both power and control lines as well as earth terminals for grounding connections.
• All electrical components must be selected as per local standards and condensing unit compo­nent requirements.
8 - Filling the system
• Before charging the refrigerant, verify that the oil level is between 1/4 and 3/4 on the com­pressor oil sight glass and/or ensure that the oil charge of the original compressor is sucient as regards system dimension and piping design:
- An additional quantity of oil might be neces­sary for line lengths (back and forth) in excess of 20 m.
- In the event additional oil is required, use only an approved lubricant (refer to the «Intro­duction» section of this manual).
• Make sure the refrigerant used to ll the system is compatible with compressor design. Refer to the «Introduction» section of this manual for an approved list of refrigerants.
• Should a leak be discovered, proceed with re­pair steps and repeat the leak detection.
• When a deep vacuum leak detection test is se­lected, observe the following:
1) The level to reach is 500 μm Hg.
2) Wait 30 min.
3) If pressure increases rapidly, the system is not airtight. Locate and repair leaks. Restart the vacuum procedure, followed by steps 1, 2, etc.
4) If pressure increases slowly, the system contains moisture inside. Break the vacuum with nitrogen gas and restart the vacuum procedure, followed by steps 1, 2, etc.
5) Connect the compressor to the system by opening the valves.
6) Repeat the vacuum procedure, followed by steps 1, 2, etc.
7) Break the vacuum with nitrogen gas.
8) Repeat the vacuum procedure, steps 1, 2; a vacuum of 500 μm Hg (0.67 mbar) should be reached and maintained for 4 hours. This pres­sure is to be measured in the refrigeration sys­tem, and not at the vacuum pump gauge.
6 | © Danfoss | DCS (CC) | 2016.11
Additional notes:
• To improve moisture removal, the temperature of the system should not be lower than 10°C.
• A proper vacuum procedure is even more im­portant with HFC and polyolester lubricant than it has “traditionally” been with HCFC (R22) or CFC and mineral oil.
• For further details, please refer to TI 3-026.
Do not use a megohmeter or apply power to the compressor while it is under vacuum, as this may cause motor winding damage (motor burn­out).
7 - Electrical connections
• Make sure the main power supply to the sys­tem has been switched o and isolated, in ac­cordance with applicable regulations, before performing any electrical connection.
• Please refer to Figs 5 and 6 for typical wiring connections and examine the specic wiring
• Compressor switched o: the liquid refrigerant is charged into the condenser and/or liquid re­ceiver in the liquid phase (compulsory for refri­gerant blends).The charge must be asclose to the nominal system charge as possible in order to avoid both low pressure operations and ex­cessive superheating at start-up. Throughout this operation, both compressor service valves must remain closed.
• Remember that vapor-charging is only appro­priate for pure refrigerants, such as R22.
• To the extent possible, maintain the refrigerant charge below 2.5 kg per cylinder. Above this li­mit, install a system, such as a pump-down cycle or suction line accumulator, to prevent against liquid ood-back into the compressor.
• Be sure that the refrigerant charge is suitable for both winter and summer operations.
9 - Verification before commissioning
Ensure that all service valves are in the open
position before start-up. A closed discharge or
Instructions
suction service valve may cause serious damage to the compressor and/or compromise safety device operation, thereby resulting in potential injury to personnel.
• Check that all safety devices are operational and properly set (safety pressure switch set point, mechanical relief valve if necessary, etc.). Make sure that these devices comply with both generally - and locally - applicable regulations and standards (e.g. EN 378-2:2012).
• When using high-pressure switches or relief valves, the setting must not exceed maximum service pressure of any system component. Re­fer to the Application Guidelines for relevant condensing unit pressure safety limits.
• A low-pressure switch is recommended to prevent operation under vacuum. Use a mini­mum setting of 1.2 bar (absolute).
• Verify that all electrical connections are proper­ly fastened and in compliance with local safety regulations.
• A compressor crankcase heater is factory ins­talled, ensure that it has been energized for a minimum of 12 hours before initial start-up and/ or during prolonged shutdown periods.
10 - Start up
Never start the compressor in the absence of
a refrigerant charge.
• Do not bypass the LP or any other safety swit­ches during start-up
• Check current draw and voltage levels.
• Monitor the oil sight glass to ensure proper oil return to the compressor.After 2 to 4 hours of operations under established conditions, check the oil level and add oil if necessary (refer to TI bulletin 3-025). If oil return continues to perform poorly, further investigation of the piping design is required.
• In all cases, the application limits of the compressor must be respected; moreover, high superheat values lead to high discharge temperatures and decrease compressor capacity. The maximum discharge tem­perature is 130°C: operating ata higher temperature may result in refrigerant decomposition.
• Under steady-state operating conditions, check refrigerant piping or capillary tubes for abnor­mal vibrations (refrigeration line movement in excess of 1.5 mm necessitates corrective actions, pipe brackets, etc.).
• Ensure that refrigerant ow through the liquid line sight glass (when mounted) is adequate and that operating temperatures correspond with system specications.
• When needed, refrigerant may be added in the liquid phase, carefully throttling the refrigerant on the low-pressure side and as far as possible from the compressor.The compressor must be operating during this process.
Do not overcharge the system.
11 - Troubleshooting
Compressor failure to start: verify that the compressor is hooked up to the power supply; check the power lead connections and all sui­table capacitors on single-phase models. If these verications reveal no abnormality, control the motor windings with an ohmmeter. Note: when the internal motor protector has tripped out, it may take up to several hours to reset and restart the compressor.
• Compressor failure to build up pressure: check to make sure that all bypass valves in the system have not been opened. Also check that all solenoid valves are in their proper position. If the internal pressure relief valve is open, the compressor sump will be warm and the com­pressor will trip out on the motor protector. If this happens, it may take up to 2 or 3 hours to reset and automatically restart the compressor.
• Abnormal running noise on the system:
- Ensure the absence of any liquid ood-back to the compressor by means of measuring the return gas superheat and compressor sump temperature. The sump should be at least 10K above the saturated suction temperature under steady-state operating conditions.
- Check that the fans are running free and wit­hout vibration.
• The high-pressure switch trips out: check condenser operations (condenser cleanliness, fan operations, etc.). If above check out OK, the problem may be due to either refrigerant over­charging or the presence of a non-condensable (e.g. air, moisture) in the circuit.
• The low-pressure switch trips out: check eva­porator operations (coil cleanliness, fan opera­tions, water ow, water lter, etc.), liquid refrige­rant ow and pressure drops (solenoid valve, lter dryer, expansion valve, etc.), refrigerant charge.
• Low refrigerant charge: the correct refrige­rant charge is given by the liquid sight glass indication, the condenser delta T in relation to the refrigerant pressure tables (pressure-tempe­rature), the superheat and the sub-cooling, etc. (if additional charge is deemed necessary, refer to the «Filling the system» section).
• Compressor maximum short cycling: there must be a minimum delay of ve minutes between two compressor starts. DCC recom­mends the compressor should run at least two minutes after each start, and between each stop and start must be three minutes standstill. Only during pump down cycle, the compressor may run much shorter until the pumpdown pressure has been reached or when safety devices will prohibit compressor further operation.
12 - Maintenance
• Proper operations and maintenance of the condensing units serve to prevent against sys­tem-related problems.The following preventive maintenance checks, to be performed at regular intervals, are highly recommended:
- Control operating conditions (evaporating temperature, condensing temperature, com­pressor discharge temperature, temperature dierence on heat exchangers, superheat, sub-cooling). These conditions must always re­main within compressor operation limits.
- Verify that safety devices are operational and properly set.
- Check the compressor oil level and quality; this step may include an acid test, humidity check, spectrometer analysis, etc. whenever the oil becomes discolored.
- Ensure that the circuit is leak tight.
- Verify the proper operation of heat exchan­gers and, if necessary, clean them.
- Check that the fans are running free (without vibration) and current draw on the compressor motor as well as proper voltage balance between phases.
- Change the lter dryer when necessary.
- Check that all electrical connections are still adequately fastened.
- Make sure the condensing unit is clean and in good working order; verify the absence of rust or corrosion on components under pressure and electrical connections.
- Make sure the refrigerant charge is suitable for both winter and summer operation.
• Ensure that periodic in-service inspections re­quired by local regulations are performed.
13 - Replacement
Precaution must be taken when disconnec­ting any components, cutting or drilling holes in the tubing to ensure that no refrigerant under pressure is present in the system.
The refrigerant shall not be discharged direc­tly into the atmosphere; rather, it must be remo­ved using approved reclamation techniques and equipment and then safely stored, inaccordance with applicable legislation.
The presence of refrigerant vapor can displace air and lead to suocation. Proper ventilation is mandatory at all times when servicing the equip­ment.
A condensing unit component change must be carried out in compliance with local regulations.
• Make sure that the main power supply has been switched o.
• Before replacement, it is necessary to deter­mine the cause of failure and implement reme­dial action. If such analysis and repair are not performed, repetitive failure may occur. Note that an oil acidity test always proves helpful in­diagnosis when undertaking compressor repla­cement.
• Check that the replacement component has the same electrical and refrigeration perfor­mance characteristics as the original one.
• Whenever piping needs to be modied, please refer to the «Safety measures prior to assem- bly» section.
• For further details on replacement steps,refer to the previous sections of this manual.
Note: In the event of compressor motor failure, ush and clean the entire circuit before repla­cing the compressor in order to remove acids and contaminants. Systematically install a new lter dryer on the liquid line. Prior to this step (if ne­cessary), run the system for at least 2 hours with anti-acid cartridges (in such instances, the instal­lation of a suction lter might also be required). Af­ter an operating period of approximately 2 weeks,
© Danfoss | DCS (CC) | 2016.11 | 7
Instructions
check the level of oil acidity. If the oil acid test pro­ves positive, drain and replace the oil, replace the anti-acid liquid line lter dryer cartridges and the suction lter previously installed. Repeat oil and lter dryer replacements until the system is clean and acid-free.When there is no longer any sign of acidity, replace the anti-acid cartridges by the standard model and remove the suction strainer cartridge as required.
14 - User advisory
Insist that all service operations only be per­formed by qualied personnel.
The condensing unit tubing and compressor surface temperatures may exceed 100°C (212°F) and cause severe bodily burns. Special precau­tion must be taken when working around the compressor and refrigerant tubing. Moreover, a compressor in operation can generate very cold surface temperatures (as low as -45°C / -49°F), there by exposing personnel to the risk of free­zing burns.
Pressure inside the compressor and refrige­rant circuit can reach dangerously high levels (e.g. abnormal operation, re,…) leading to personnel injury if suddenly released; therefore, never drill, weld or cut the compressor shell and adjacent tubing (release of liquid refrigerant can cause ash freezing on exposed skin).
Even though fans are tted with safety guard it is recommended not to work on condenser while fans are running.
Be aware that the product warranty may be deemed null and void in the following cases:
• Modications to the unit, unless approved by Danfoss Commercial Compressors, absence of nameplate, broken or dented components, shock marks, etc...
• Compressor opened by the customer or re­turned unsealed (i.e. open discharge or suction ports),
• Presence of rust or water inside the condensing unit circuit,
• Addition of leak-detection uid in the compres­sor lubricant,
• Use of a refrigerant or lubricant not approved by Danfoss Commercial Compressors.,
• Any deviation from recommended instructions­pertaining to installation, application or mainte­nance,
• Use in mobile applications (boats, trains, truc­ks,etc.) or under explosive atmospheric conditions.
The date of production of the condensing unit is indicated on the nameplate. Ensure that the model and serial number information is always transmitted with any claim led regarding this product.
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specications already agreed. All trade­marks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
8 | © Danfoss | DCS (CC) | 2016.11
Instructions
Temperature évaporée (C)
Temperature ambiante (C)
-15
-5
51520
HGZ R134a
-30 -20 -10 0
10
50
45
35
25
15
HGZ R404A - R507A
-15
-35
25 -30
50
45
35
25
15
LGZ R404A - R507A
-15
-5
510
50
45
35
25
15
MGZ R134a
-30 -20 -10 05
50
45
35
25
15
MGZ R404A - R507A
Plage d'application MBP
T evap (C)
Plage d'application LBP
H
H
D
W
50 Hz W D H 60Hz MGZ 016-018-022-028 HGZ 018 LGZ 022 MGZ 032-036-040 HGZ 022-028-032 LGZ 028-040 MGZ 050-064-080 HGZ 040-050 - HGZ 036 LGZ 044-050 MGZ 100-125-144-160 HGZ 064-080-100 LGZ 088-100
700 500 392 MGZ 018-022
HGZ 018 LGZ 022
800 600 442 MGZ 028-032-036-040
HGZ 022-028 LGZ 028
1000 700 555 MGZ 050-064
HGZ 032-036-040-050 LGZ 044-050
1200 800 671 MGZ 080-100-125-144-160
HGZ 064-080-100 LGZ 088-100
HGZ 125-144-160 1500 870 975 HGZ 125-144-160
50 Hz
MCZC030 MCZC038 MCZC048 MCZC054 MCZC060 MCZC068 MCZC086 MCZC096 MCZC108 MCZC121 MCZC136 MCZC171 MGZC215 MGZC242 MGZC271
D
Application MBP
Compres-
MTZ18 MTZ22
seur
W D H
500 620 451
MTZ28 MTZ32 MTZ36
630 650 605
MTZ40 MTZ51 MTZ57
755 700 656 MTZ65 MTZ73 MTZ81
900 900 759
MTZ100 MTZ125 MTZ144
1350 820 759
MTZ160
W
Application LBP
Compres-
50 Hz
seur
W D H
LCQC048 NTZ048 500 620 451 LCQC068 LCQC096 LCQC108
NTZ068 NTZ096 NTZ108
630 650 605
LCQC136 NTZ136 755 700 656
LCQC215 LCQC271
NTZ215 NTZ271
900 900 759
LGQC048 NTZ048 700 500 392 LGQC068 LGQC096 LGQC108
NTZ068 NTZ096 NTZ108
800 600 442
LGQC136 NTZ136 1000 700 555
Lorsque les compresseurs MT sont utilisés avec du R417A, l’huile minérale remplie en usine 160P doit être remplacée par de l’huile polyolester 160PZ.
46
43
38
T amb (C)
32
R404A/R507A
SH=10K
28
-30 -25 -20 -15 -10 -5 0510
Fig. 1
46
43
38
SH=10K Surchaue limitée
SH=10K RGT=20°C
T amb (C)
32
27
-45 -40 -35 -30 -25 -20 -15 -10
T evap (C)
R404A/R507A
© Danfoss | DCS (CC) | 2016.11 | 9
Loading...
+ 20 hidden pages