15.APPENDIX F - PARAMETERS FOR APPLICATION DEVELOPERS ...................118
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
vacon • 6Safety
9000.emf
13006.emf
9001.emf
9000.emf
9000.emf
9000.emf
9000.emf
9000.emf
9000.emf
1.SAFETY
This manual contains clearly marked cautions and warnings that are intended for your personal
safety and to avoid any unintentional damage to the product or connected appliances.
Please read the information included in cautions and warnings carefully.
The cautions and warnings are marked as follows:
= DANGER! Dangerous voltage
= WARNING or CAUTION
= Caution! Hot surface
1.1Danger
The components of the power unit are live when the drive is connected to mains
potential. Coming into contact with this voltage is extremely dangerous and may
cause death or severe injury.
The motor terminals U, V, W and the brake resistor terminals are live when the
AC drive is connected to mains, even if the motor is not running.
After disconnecting the AC drive from the mains, wait until the indicators on the
keypad go out (if no keypad is attached, see the indicators on the cover). Wait 5
more minutes before doing any work on the connections of the drive. Do not open
the cover before this time has expired. After expiration of this time, use a
measuring equipment to absolutely ensure that no
ensure absence of voltage before starting any electrical work!
The control I/O-terminals are isolated from the mains potential. However, the
relay outputs and other I/O-terminals may have a dangerous control voltage
present even when the AC drive is disconnected from mains.
Before connecting the AC drive to mains make sure that the front and cable
covers of the drive are closed.
During a ramp stop (see the Application Manual), the motor is still generating
voltage to the drive. Therefore, do not touch the components of the AC drive
before the motor has completely stopped. Wait until the indicators on the keypad
go out (if no keypad is attached, see the indicators on the cover). Wait additional 5
minutes before starting any work on the drive.
voltage is present.
Always
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
1
Safetyvacon • 7
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
1.2Warnings
The AC drive is meant for fixed installations only.
Do not perform any measurements when the AC drive is connected to the mains.
The earth leakage current of the AC drives exceeds 3.5mA AC. According to
standard EN61800-5-1, a reinforced protective ground connection must be
ensured. See Chapter 1.3.
If the AC drive is used as a part of a machine, the machine manufacturer is responsible for providing the machine with a supply disconnecting device (EN
60204-1).
Only spare parts delivered by the manufacturer can be used.
At power-up, power break or fault reset the motor will start immediately if the
start signal is active, unless the pulse control for
Start/Stop logic has been selected
Furthermore, the I/O functionalities (including start inputs) may change if
parameters, applications or software are changed. Disconnect, therefore, the
motor if an unexpected start can cause danger.
.
The motor starts automatically after automatic fault reset if the auto restart
function is activated. See the Application Manual for more detailed information.
Prior to measurements on the motor or the motor cable, disconnect the motor
cable from the AC drive.
Do not touch the components on the circuit boards. Static voltage discharge may
damage the components.
Check that the EMC level of the AC drive corresponds to the requirements of your
supply network.
Wear protective gloves when you do mounting, cabling or maintenance
operations. There can be sharp edges in the AC drive that can cause cuts.
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
1
vacon • 8Safety
13006.emf 13006.emf
1.3Earthing and earth fault protection
CAUTION!
The AC drive must always be earthed with an earthing conductor connected to the earthing terminal
marked with .
The earth leakage current of the drive exceeds 3.5mA AC. According to EN61800-5-1, one or more
of the following conditions for the associated protective circuit must be satisfied:
0)The protective conductor must have a cross-sectional area of at least 10 mm
Al, through its total run.
a)Where the protective conductor has a cross-sectional area of less than 10 mm
2
Al, a second protective conductor of at least the same cross-sectional area must be
mm
provided up to a point where the protective conductor has a cross-sectional area not less
than 10 mm
2
Cu or 16 mm2 Al.
b)Automatic disconnection of the supply in case of loss of continuity of the protective
conductor.
2
Cu or 1 6 mm2
2
Cu or 16
The cross-sectional area of every protective earthing conductor which does not form part of the
supply cable or cable enclosure must, in any case, be not less than:
-2.5mm
-4mm
2
if mechanical protection is provided or
2
if mechanical protection is not provided.
The earth fault protection inside the AC drive protects only the drive itself against earth faults in the
motor or the motor cable. It is not intended for personal safety.
Due to the high capacitive currents present in the AC drive, fault current protective switches may
not function properly.
Do not perform any voltage withstand tests on any part of the AC drive. There is
a certain procedure according to which the tests must be performed. Ignoring
this procedure can cause damage to the product.
NOTE! You can download the English and French product manuals with applicable safety,
warning and caution information from https://www.danfoss.com/en/service-and-support/.
REMARQUE Vous pouvez télécharger les versions anglaise et française des manuels produit
contenant l’ensemble des informations de sécurité, avertissements et mises en garde
applicables sur le site https://www.danfoss.com/en/service-and-support/.
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
1
CANopen option board OPTE6 - Generalvacon • 9
2.CANOPENOPTIONBOARD OPTE6 - GENERAL
2.1Overview
OPTE6 is a CANopen adapter board for VACON® AC drives. The board allows the AC drive to be
controlled by using the CANopen protocol. The board implements the AC drive profile with the
velocity mode.
The option board firmware implements the following protocol specifications:
• CiA-301 CANopen communication specification version 4.2
• CiA-402 CANopen Profile for Drives and Motion Controller version 3.2
Device: AC drive
Operation mode: velocity mode
• CiA-303-3 CANopen indicator specification, implemented by using 2 CANopen status led
indicators
2.2Software
2.2.1CAN
The CAN data link layer protocol is standardised in ISO 11898. The standard describes mainly the
data link layer composed of the logical link control (LLC) sub layer and the media access control
(MAC) sub layer, and some aspects of the physical layer of the OSI reference model.
2.2.2CANopen
CANopen is an application layer protocol on top of the CAN bus.
The protocol specification describes:
• Set of bit rates to support
• Network Management (NMT)
• Service data transmission (SDO)
• Process data transmission (PDO)
• Error message transmission (EMCY)
• Node status monitoring (heartbeat and node guarding)
• Identity information
• Parameter saving and restoring
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
2
vacon • 10CANopen protocol description
(1)
(2)(11)
(4)(5)(10)
(7)
(3)
(14)
(13)
(12)(8)(9)
Power on or hardware reset
Pre-operational
Initialisation
Operational
Stopped
11651_uk
3.CANOPENPROTOCOLDESCRIPTION
3.1NMT
NMT network management manages CANopen, and is a mandatory, common feature for all
devices. The protocol describes several node control services and the state machine.
1 = When the power is on, the NMT state is entered autonomously
2= The NMT state initialisation is finished, the NMT pre-operational state is entered
automatically
3 = NMT service starts with remote node indication or by local control
4 and 7 = NMT service enters pre-operational indication
5 and 8 = NMT service stops remote node indication
6 = NMT service starts remote node indication
9, 10 and 11 = NMT resets node indication
12, 13 and 14 = Indication of NMT service reset communication
Boot-up protocol
After anode starts, it will enter automatically into the pre-operational state. Always when this
transition occurs, a boot-up message is sent into the bus.
Table 1: Boot-up message
CAN IDLENGTHDATA0DATA1DATA2DATA3DATA4DATA 5DATA6DATA7
Figure 1. NMT state machine
0x700 +
Node ID
3
10
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
CANopen protocol descriptionvacon • 11
3.2Node control protocols
Protocol start remote node
The start remote node message sets the node(s) into operational state. See Figure 1. NMT state
machine. If the node ID in the message is set to ‘0’, the message affects all nodes (broadcast).
Table 2: Start remote node message
CAN IDLENGTHDATA0DATA1DATA2DATA3DATA4DATA5DATA6DATA7
0x00x20x1
NODE
ID
Protocol stop remote node
The stop remote node message sets the node(s) into stopped state. See Figure 1 NMT state
machine. If the node ID in the message is set to ‘0’, the message affects all nodes (broadcast). When
the node is in stopped state, it will not answer to SDO or PDO messages.
Table 3: Stop remote node message
CAN IDLENGTHDATA0DATA1DATA2DATA3DATA4DATA5DATA6DATA7
0x00x20x2
NODE
ID
Protocol enter pre-operational
The enter pre-operational message sets the node(s) into pre-operational state. See Figure 1. NMT
state machine. If the node ID in the message is set to ‘0’, the message affects all nodes (broadcast).
When the node is in pre-operational state, it will not answer to PDO messages.
Table 4: Enter pre-operational message
CAN IDLENGTHDATA0DATA1DATA2DATA3DATA4DATA5DATA6DATA7
0x00x20x80
NODE
ID
Protocol reset node
The reset node message makes the node(s) apply application reset. See Figure 1. NMT state
machine. Application reset sets the whole object dictionary back to the default or previously saved
values. If the node ID in the message is set to ‘0’, the message affects all nodes (broadcast). After
the node has made the application reset, it will enter the pre-operational state automatically from
the initialising state. This also creates a boot-up event and the boot-up message is sent after the
reset.
Table 5: Reset node message
CAN IDLENGTHDATA0DATA1DATA2DATA3DATA4DATA5DATA6DATA7
0x00x20x81
NODE
ID
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
3
vacon • 12CANopen protocol description
Protocol reset communication
The reset communication message makes the node(s) apply communication reset. See Figure 1.
NMT state machine. Communication reset does not affect the object dictionary values. If the node
ID in the message is set to ‘0’, the message affects all nodes (broadcast). After the node has made
the communication reset, it will enter the pre-operational state automatically from the initialising
state. This also creates a boot-up event and the boot-up message is sent after the reset.
Table 6: Reset communication message
CAN IDLENGTHDATA0DATA1DATA2DATA3DATA4DATA5DATA6DATA7
0x00x20x82
NODE
ID
3.3Error control protocols
It is not allowed to use guarding protocol and heartbeat protocol on one NMT slave at the same
time. If the heartbeat producer time is unequal 0, the heartbeat protocol is used.
3.3.1Heartbeat protocol
Heartbeat protocol defines the producer and consumer. The producer node sends its NMT status
that is then available for any consumer node. The consumer node is the receiver of heartbeat
messages. The producer node has a timing parameter that indicates how often the heartbeat
message should be sent. The consumer node has a relative parameter that indicates how often the
heartbeat message should be received. If the consumer does not receive the heartbeat message
within the time defined in the heartbeat object entry, an error event occurs.
Table 7: Node status description
ValueDescription
0x0Boot-up
0x4Stopped
0x5Operational
0x7FPre-operational
Table 8: Heartbeat message
CAN IDLENGTHDATA0DATA 1DATA2DATA3DATA4DATA 5DATA 6DATA7
0x700 +
Node ID
0x1Status
Table 9: Heartbeat-related objects in OD
IndexDescription
0x1016Consumer heartbeat time
0x1017Producer heartbeat time
0x1029Error behaviour
3
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
CANopen protocol descriptionvacon • 13
3.3.2Node guarding protocol
Node guarding protocol is a NMT master driver protocol, where the master sends a remote
transmission request, which is answered by the slave. The slave response includes one data byte
that consists of a NMT slave state, and a toggle bit that toggles every response.
NOTE! The CiA application note 802 recommends that the node guarding protocol should not be
used, because of different handling of RTR frames in CAN controllers.
OPTE6 option board does not have a hardware-triggered automatic response to the RTR frame. RTR
information is handled by software, and the response data always consists of updated information.
CAN IDLENGTHRTRDATA0DATA 1DATA2DATA3DATA4DATA 5DATA6DATA7
0x700 +
Node ID
Table 11: Node guarding response
CAN IDLENGTHDATA0DATA1DATA2DATA3DATA4DATA5DATA6DATA7
0x700 +
Node ID
0x01
0x1tStatus
Table 12: Node guarding slave status
Status
ValueDescription
0x4Stopped
0x5Operational
0x7FPre-operational
Table 13: Node guarding related objects in OD
IndexDescription
0x100CGuard time
0x100DLife time factor
3.3.3EMCY object
Option board works as an EMCY producer. The EMCY object is transmitted when a fault occurs in
the drive or option board. To switch off the EMCY producer, disable the EMCY COB-id by writing MSB
to 1 (object 0x1014).
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
3
vacon • 14CANopen protocol description
When an error occurs, the EMCY message is transmittedwith the current value of the error
registerand the error code is inserted into the pre-defined error field list. The newest error code is
always the first sub-index on the error field list. When all active errors are cleared, an empty EMCY
object is transmitted.
If a drive-internal fault occurs, the MSEF field contains the drive fault code. See the application and
user manual for possible fault codes. The ER field holds a bit coded value of the error type. See
object 0x1001 for more details.
Table 14: EMCY message
CAN IDLENGTHDATA0DATA1DATA2DATA3DATA4DATA5DATA6DATA7
0x80 +
Node ID
0x8 EEC ER MSEF
Table 15: EMCY message data fields
EECEmergency error code
ERError register value
MSEF
Manufacturer-specific
error code
Table 16: Used EMCY error codes and description MSEF fields
DATA0DATA1DATA2DATA3DATA4DATA5DATA6DATA7
0x0000
0x1000Drive fault codes
0x8110-
0x8120-
0x8130
ER
0x8140-
3: N umb er of remai ning error s ource s
3: Heartbeat consumer subindex
4: Heartbeat consumer node-ID
3
0x8210-
0x8220-
0x8240-
0x8250-
Table 17: Description and behavior of different error situations
EECDescriptionError behaviour Err LED
0x0000
0x1000
0x8120
Error Reset or No Error
Generic Error
CAN in Error Passive
Mode
If MSEF field is empty all error sources are cleared and drive
fault is cleared.
Drive fault codes have changed.-
EMCY is sent after CAN driver goes back to active state. This
also clears the fault.
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
Single flash
-
CANopen protocol descriptionvacon • 15
Table 17: Description and behavior of different error situations
Life Guard Error
0x8130
Heartbeat Error
0x8140Recovered from Bus-Off
0x8250
PDO timer expired
Error is reset when a RTR is received or either of the life
guard objects (0x100C, 0x100D) is written to zero.
Error is reset when a HB message is received by the HB consumer, or the consumer entry is changed (either Node-ID or
Heartbeat Time).
EMCY is sent after CAN driver goes back to active state. This
also clears the fault.
Error is cleared when a PDO is received (in expired PDO).
Double
flash
On
Quadruple
flash
All communication errors are reset if a reset command is given. This does not however reset drive
faults if there are active error sources.
EMCYs are also created in some cases, even though a fault is not created. These are for notification
only.
Table 18: Notification EMCY objects
EECDescription
0x8110CAN overrun (objects lost)
0x8210PDO not processed due to length error
0x8220PDO length exceeded
0x8240Unexpected SYNC data length
Table 19: EMCY-relate objects in OD
IndexDescription
0x1001Error register
0x1003
0x1014EMCY object COB-ID
Pre-definederror field
list
3.4SDO protocol
The Option board contains one SDO server. The SDO protocol provides a direct access to the object
entries of the object dictionary of the CANopen device. Each message is acknowledged by the
server. The protocol is mostly used to set and read parameters from the object dictionary at the
pre-operational state. Some objects have limitations for SDO usage at the operational state.
Up to four bytes can be transferred by using the expedited transfer, where the data fits into one CAN
message. For bigger than 4-byte object sizes, segmented transfer must be used. Optionally, block
transfer is also possible with bigger data types. Block transfer is most efficient with big data sizes.
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
3
vacon • 16CANopen protocol description
Table 20: SDO-related objects in OD
IndexDescription
0x1200
Some objects have limitations for SDO usage at the operational state. The following SDO abort
codes can be returned by OPTE6 option board.
Table 21. SDO abort codes
Abort codeDescription
0504 0001hClient/server command specifier not valid or unknown
0504 0005hOut of memory
0601 0000hUnsupported access to an object
0601 0002hAttempt to write a read only object
0602 0000hObject does not exist in the object dictionary
0604 0041hObject cannot be mapped to the PDO
0604 0042hThe number and length of the objects to be mapped would exceed PDO length
0604 0043hGeneral parameter incompatibility reason
0606 0000hAccess failed due to a hardware error
0607 0010hData type does not match, length of service parameter does not match
SDO server parameter
object
0609 0011hSub-index does not exist
0609 0030hInvalid value for parameter (download only)
0609 0031hValue of parameter written too high (download only)
0609 0032hValue of parameter written too low (download only)
0800 0020hData cannot be transferred or stored to the application
0800 0022h
0800 0024hNo data available
Data cannot be transferred or stored to the application because of the present
device state
3
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
CANopen protocol descriptionvacon • 17
3.5PDO protocol
Process data objects PDOs are used to transmit real-time data with no protocol overhead. Each
PDO has its mapping and communication parameter record.
There are two different types of PDOs. Transmit PDOs for producing data into network and Receive
PDOs for consuming data from network. OPTE6 board supports 5 receive and 5 transmit PDOs.
Each of rxPDO and txPDO mapping parameter record contains four (4) process data items. For
example, 0x01600 Receive PDO Mapping Parameter 1 contains following process data items:
• Mapping entry 1
• Mapping entry 2
• Mapping entry 3
• Mapping entry 4
All VACON
and AC drive. Using of 9-16 process data items requires Normal Extended Communication or Fast
Communication support from VACON
chapters:
• APPENDIX E - FIELDBUS OPTION BOARD COMMUNICATION
• APPENDIX F - PARAMETERS FOR APPLICATION DEVELOPERS
If master device assigns 16 process data items and VACON
items, then content of process data items 9-16 is ignored in VACON
®
AC drives supports transferring of eight (8) process data items between master device
®
AC drive. See details of communication modes in following
®
AC drive supports only 8 process data
®
AC drive.
Table 22: PDO-related objects in OD
IndexDescription
0x14001st rxPDO communication parameter record
0x14012nd rxPDO communication parameter record
0x14023rd rxPDO communication parameter record
0x14034th rxPDO communication parameter record
0x14045th rxPDO communication parameter record
0x16001st rxPDO mapping parameter record
0x16012nd rxPDO mapping parameter record
0x16023rd rxPDO mapping parameter record
0x16034th rxPDO mapping parameter record
0x16045th rxPDO mapping parameter record
0x18001st txPDO communication parameter record
0x18012nd txPDO communication parameter record
0x18023rd txPDO communication parameter record
0x18034th txPDO communication parameter record
0x18045th txPDO communication parameter record
0x1A001st txPDO mapping parameter record
0x1A012nd txPDO mapping parameter record
0x1A023rd txPDO mapping parameter record
0x1A034th txPDO mapping parameter record
0x1A045th txPDO mapping parameter record
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
3
vacon • 18CANopen protocol description
3.5.1PDO communication parameter record
PDO communication parameter record defines the COB-id, transmission type and how often the
PDO is transmitted. The fields can be modified during the pre-operational state.
COB ID determines whether the PDO is valid (active) and using 11-bit or 29-bit frames.
Table 24: COB ID
31 30 2928 1110 0
ValidReserved Frame
0x0000011-bit CAN-ID
29-bit CAN-ID
r/w
Table 25: COB ID data fields
Bit(s)ValueDescription
0PDO exists / enabled
Valid
1
ReservedxNot applicable
011-bit CAN-ID valid
Frame
120-bit CAN-ID valid
29-bit CAN-IDx
11-bit CAN-IDx
PDO does not exist /
disabled
29-bit CAN-ID of the CAN
extended frame
11-bit CAN-ID of the CAN
base frame
3
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
CANopen protocol descriptionvacon • 19
3.5.3Transmission type
Table 26: PDO transmission types
ValueDescription
0x00
0x01
0x02
0x03
0x04
......
0xF0
0xF1
......--
0xFB
0xFC
0xFD
0xFE
Synchronous (acyclic)
Synchronous (cyclic every sync)
Synchronous (cyclic every 2nd sync)
Synchronous (cyclic every 3rd sync)
Synchronous (cyclic every 4th sync)
Synchronous (cyclic every 240th sync)
Reserved
Reserved
RTR-only (synchronous)
RTR-only (Event-driven)
Event-driven (manufacturer-specific)
Receive
PDO
XX
X
1
X
1
X
1
X
1
X
1
X
1
--
--
-X
-X
XX
Transmit
PDO
X
X
X
X
X
X
0xFF
For receive PDO, each sync transmission mode equals the same. Each sync always activates the latest
1
Event-driven (device and application profile)
XX
received PDO value.
Synchronous means that the PDO is transmitted after the SYNC. The CANopen device starts
sampling the data with the reception of the SYNC. If the transmission mode of the PDO is acyclic,
the CANopen device gives an internal event, the sampling starts with the next SYNC and the PDO is
transmitted afterwards. If the transmission modeis cyclic, the sampling starts with the reception
of every SYNC, every second SYNC, every third SYNC etc. depending on the given value, and the PDO
is transmitted afterwards.
RTR-only means that the PDO is requested via RTR. If the transmission mode of the PDO is
synchronous, the CANopen device starts sampling with the reception of every SYNC and will buffer
the PDO. If the mode is event-driven, the CANopen device starts the sampling with the reception of
the RTR and transmits the PDO immediately.
Event-driven means that the PDO can be transmitted at any time based on the occurrence of the
internal event of the CANopen device. An event that triggers the OPTE6 transmission occurs when
the data mapped into the PDO is changed. Also, an event timer can be used to create transmit
events.
Inhibit time
For transmit PDOs, the inhibit time defines the minimum transmission interval, when 0xFE or 0xFF
transmission types are selected. For receive PDOs, the inhibit time is disabled. The inhibit time is
16bit unsigned value that is given as multiple of 100μs. Zero value means that the inhibit time is
disabled.
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
3
vacon • 20CANopen protocol description
Event timer
For a transmit PDO event, the timer defines the maximum interval between the transmissions, if
the transmission type is set to 0xFE or 0xFF.
For a receive PDO event, the timer activates the deadline monitoring. The deadline monitoring is
activated at the first received PDO. If the time between the after the last PDO received is longer
than defined in the event timer, a fault will occur.
Event timer is 16bit unsigned value that is given as multiple of 1ms. Zero value means that the event
timer is disabled.
NOTE: It is recommended to define non-zero Event timer value when using Event-driven
transmission type. By default Event timer value is zero, which together with Event-driven
transmission type means that OPTE6 CANopen transmits TPDO only when its data content changes.
In certain situations TPDO data content rarely or never changes. For example, when running zero
speed, TPDO1 data content (status word and actual speed) does not change after zero speed has
been reached.
Sync start value
Sync start value gives the possibility to compensate network peak traffic in case of sync
transmission mode.If the sync start value is zero, the normal sync behaviour for the PDO is used.
If the sync start value is greater than zero, the PDO waits for the SYNC message that contains the
counter value. When the counter value of a SYNC message equals the SYNC start value, the first
SYNC message is regarded as received. The sync start value must not be changed while the PDO
exists. See the SYNC message format in Table 30.
3.5.4PDO parameter mapping record
Each PDO consists of a maximum of 8 bytes of mapped data. To data map the PDO, use a
corresponding mapping record that consists of index, sub-index and the length of the mapped
object.
NOTE! All VACON
®
AC drives supports transferring of eight (8) process data items between master
device and AC drive. Read about usage of 9-16 process data items in Chapter 3.5.
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
CANopen protocol descriptionvacon • 21
To data map the PDOs, first disable the related PDO COB ID in the pre-operational state. In the
mapping structure, write the sub-index 0 to zero (number of mapped objects). Then write the
mapping structures on the mapping parameter record, starting from the sub-index 1. When you
have written all the necessary structures, write the sub-index 0 to correspond to the mapped
objects.
Example on how to write a dummy object to RPDO1 4th entry (when using Bypass mode) is explained
below:
Table 29. RPDO mapping example
Transfer data (hex)Interpretation
23 00 14 01
2F 00 16 00
23 00 16 04
2F 00 16 00
23 00 14 01
01 02 00 80Write RPDO1 COB-ID (1400:01) to invalid (0x8000 0201)
00 00 00 00 Write RPDO1 mapping number of entries (1600:00) to 0
10 00 06 00
Write RPDO1 4
th
entry (1600:04) to Dummy object (00060010)04 00 00 00Write RPDO1 mapping number of entries (1600:00) to 401 02 00 00Write RPDO1 COB-ID (1400:01) as valid (0x201)
3.6SYNC protocol
Sync protocol is used by PDOs when the transmission is synchronous. The sync object that is
defined by COB ID in the object 0x1005 triggers the transmission of the txPDOs, or activates the
previously received data of the rxPDO. At the default sync message the CAN-ID is 0x80. The sync
message is a zero-length message but optionally it can consist of an 8bit counter.
Table 30: SYNC message
CAN IDLENGTH
0x800x0
Table 31: SYNC message with counter
CAN IDLENGTHDATA0
0x800x1Counter
3.6.1SYNC with counter
When a counter is used in a sync message, the PDOs that have a defined sync start value compare
the value against the sync message counter. The sync producer counter will overflow after it
reaches the value defined in its ‘synchronous counter overflow value’ at the object 0x1019. Also, the
sync consumer has the object 0x1019even when the value itself is ignored. When the value of the
sync consumer is greater than zero, the sync counter handling and expecting of the sync messages
with counter are activated.
When the sync start value and the sync counter value match, the first sync message is regarded as
received.
The following figure shows an example of SYNC messaging, when the slave is configured with:
• 0x1019 - Synchronous counter 128
• 0x1800,2 - Transmission type = 2 (Cyclic, No. of SYNCs = 2)
• 0x1800,6 - Sync start value = 4
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
3
vacon • 22CANopen protocol description
(1) (2) (3)(4)(5) (6)(7) (8)
SYNC
time
txPDO
Figure 2. txPDO responses to SYNC messages
Table 32: Sync-related object in OD
IndexDescription
0x1005COB ID SYNC
0x1019Synchronous counter
0x1014EMCY object COB ID
0x14001st rxPDO communication parameter record
0x14012nd rxPDO communication parameter record
0x14023rd rxPDO communication parameter record
0x14034th rxPDO communication parameter record
0x14045th rxPDO communication parameter record
0x18001st txPDO communication parameter record
0x18012nd txPDO communication parameter record
0x18023rd txPDO communication parameter record
0x18034th txPDO communication parameter record
0x18045th txPDO communication parameter record
3
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
CANopen protocol descriptionvacon • 23
3.7Communication objects
3.7.10X1000 - Device Type
The device type object indicates basic information about the device, including the supported device
profile and the profile settings.
Table 33: 0x1000 Device type
IndexSub-indexValueNameData typeAccess
0x1000-0x00010192Device typeUNSIGNED32const
Value description:
0x0192 = 402 (Drive profile)
0x0001 = AC drive with PDO set for a generic drive device
3.7.20X1001 - Error Register
Error register indicates the active error code.
Table 34: 0x1001 Error register
IndexSub-indexValueNameData typeAccess
0x1001-0x0 Error registerUNSIGNED8ro
Table 35: Error register bit descriptions
BitMeaning
0Generic error
1Current
2Voltage
3Temperature
4Communication error (overrun, error state)
5Device profile-specific*
6Reserved*
7Manufacturer-specific*
* Not used/supported
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
3
vacon • 24CANopen protocol description
3.7.30X1003 - Pre-defined Error Field
Pre-defined error field is a list of errors signaled with an EMCY object, listing the error history of
up to 9 error entries. Sub-index 1 contains the latest error.
Table 36: 0x1003 Pre-defined error field
IndexSub-indexValueNameData typeAccess
00x0
10x0
0x1003
..........
90x0
Number of
errors
Sta ndard error
field
Sta ndard error
field
UNSIGNED8ro
UNSIGNED32
UNSIGNED32
ro
ro
3.7.40X1005 - COB ID SYNC
Defines the synchronisation message COB ID. Receiving the sync message causes actions in the
PDOs that have a synchronous transmission mode.
Table 37: 0x1005 COB ID sync
IndexSub-indexValueNameData typeAccess
0x1005-0x00000080COB ID syncUNSIGNED32r/w
3.7.50X100C - Guard Time
The object contains the guard time in milliseconds. As a default, guarding is disabled.
Table 38: 0x100C Guard time
IndexSub-indexValueNameData typeAccess
0x100C-0x0000Guard timeUNSIGNED16r/w
3.7.60X100D - Life Time Factor
Life time factor is used together with guard time, which is multiplied with the life time factor.
Table 39: 0x100D Guard time
IndexSub-indexValueNameData typeAccess
0x100D-0x00Guard timeUNSIGNED8r/w
Node life time = life time factor x guard time. If node life time is zero, guarding is disabled.
3
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
CANopen protocol descriptionvacon • 25
3.7.70X1014 - COB ID EMCY
The object defines the emergency message COB ID.
Table 40: 0x1014 COB ID EMCY
IndexSub-indexValueNameData typeAccess
0x1014-
0x00000080+
node id
COB ID EMCYUNSIGNED32r/w
Setting MSB (bit 31) to 1 will disable sending of EMCY messages.
3.7.80X1016 - Heartbeat Consumer Entries
The device can act as the heartbeat consumer. Up to 8 devices can be monitored, as defined in the
table below. If the heartbeat transmission delay of a defined node ID exceeds the heartbeat time,
the error behaviour is activated according to the error behaviour object.
Table 41: 0x1016 Heartbeat consumer entries
IndexSub-indexValueNameData typeAccess
00x08Number of entriesUNSIGNED8ro
10x0000 0000
20x0000 0000
30x0000 0000
Consumer heart beat
time 1
Consumer heart beat
time 2
Consumer heart beat
time 3
UNSIGNED32r/w
UNSIGNED32r/w
UNSIGNED32r/w
Consumer heart beat
time 4
Consumer heart beat
time 5
Consumer heart beat
time 6
Consumer heart beat
time 7
Consumer heart beat
time 8
UNSIGNED32r/w
UNSIGNED32r/w
UNSIGNED32r/w
UNSIGNED32r/w
UNSIGNED32r/w
0x1016
40x0000 0000
50x0000 0000
60x0000 0000
70x0000 0000
80x0000 0000
Table 42: Consumer heartbeat time entry
31 2423 1615 0
Not used, must be
zeroes.
Node ID Heartbeat time
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
3
vacon • 26CANopen protocol description
3.7.90X1017 - Producer Heartbeat Time
Heartbeat producer object consists of the time in milliseconds (ms) that it takes to transmit the
heartbeat message into the network. If the value is zero, the heartbeat is not used.
Table 43: 0x1017 Producer heartbeat time
IndexSub-indexValueNameData typeAccess
0x1017-0x0000
Table 44: Heartbeat message
CAN IDLENGTHDATA0
0x700 + node0x1Node state
Producer
heartbeat time
UNSIGNED16r/w
3.7.100X1018 - Identify Object
The object gives information about the option board
Table 45: 0x1018 Identify object
IndexSub-indexValueNameData typeAccess
00x04Number of entriesUNSIGNED8ro
10x90Vendor IDUNSIGNED32ro
0x1018
2-Product codeUNSIGNED32ro
3-Revision numberUNSIGNED32ro
4-Serial numberUNSIGNED32ro
3.7.110X1019 - Synchronous counter overflow value
The synchronous counter overflow value defines whether a counter is mapped into the SYNC message, as well as the highest value the counter can reach. 0 disables the sync counter.
Table 46: 0x1019 Synchronous counter
IndexSub-indexValueNameData typeAccess
0x1019-0x00
Synchronous
counter
UNSIGNED8r/w
3
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
CANopen protocol descriptionvacon • 27
3.7.120X1029 - Error behaviour
Error behaviour allows a change in the default error behaviour if there is a communication
error.
Table 47: 0x1029 Error behaviour
IndexSub-indexValueNameData typeAccessMinMax
00x01Number of entriesUNSIGNED8ro22
0x1029
10x00Communication errorUNSIGNED8r/w02
20x01Internal errorUNSIGNED8r/w11
Table 48: Error behaviour
ValueDescription
0Pre-operational
1No change in state
2Stopped
3..127Reserved
3.8Saving and restoring the object dictionary
CANopen defines a way of restoring the values in an object dictionary to the defaults and saving the
values if the modified values must be valid after the power cycle. The manufacturer-specific bypass
configuration can be restored to the object dictionary.
3.8.10X1010 Store parameter field
To save the object dictionary, use the object 0x1010 ‘Store Parameter Field’.
The option board only saves the parameters in the object dictionary with a command. Autonomous
saving is not supported. To save the parameters in the object dictionary,write the value 0x65766173
(ASCII “save”) into the sub-index by using the SDO protocol.
Table 49: 0x1010 Store parameter field
IndexSub-indexNameData typeAccess
0x1010
0
1Save all parametersUNSIGNED32r/w
Highest sub-index
supported
UNSIGNED8ro
3.8.20X1011 Restore default parameters
The object values of the object dictionary are restored to defaults by using the object 0x1011. Option
board supports restoring All parameters (sub index 1) and manufacturer-specific Bypass mode defaults (sub index 4).
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
3
vacon • 28CANopen protocol description
To restore parameters, write 0x64616F6C (ASCII "load") into the sub-index by using the SDO
protocol. Default object values are selected after reset. Restore all default parameter restores CiA402 default parameters (refer to Chapter 8.2.2.2). Bypass parameter set is described in Chapter 8.3.
Table 50: 0x1011 Restore default parameters
IndexSub-indexNameData typeAccess
0Highest sub-index supportedUNSIGNED8ro
Restore all default
parameters
Restore bypass parameter
set*
Restore Puller parameter
set
Restore Co-Extruder parameter set
UNSIGNED32r/w
UNSIGNED32
UNSIGNED32
UNSIGNED32
r/w
r/w
r/w
0x1011
1
4
5
6
* The bypassed set disables the CIA- 402 drive profile and resets the PDO mapping to the vendor specific
configuration. See Chapter 8.2 and Chapter 8.3 for more information.
3
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
Storing temperatureAs specified in drive specification (-40°C … 70°C)
Humidity0-95%, non-condensing, corrosive
Vibration and
electrical safety
EmissionC2 level, EN 61800-3 (2004)
ImmunityC2 level, EN 61800-3 (2004)
CAN Interface
500 VDC
As specified in drive specification (-10°C … 40°C)
EN 61800-5-1 (2007)
5… 15.8 Hz 1mm (peak)
15.8 ...150 Hz 1 G
Isolation
Protection
2500 V rms isolation with a less than
10-ns propagation delay
±8kV ESD IEC 61000-4-2 Contact
Discharge
±80V Fault Protection
greater than ±12V common Mode Range
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
4
vacon • 30 CANopen option board OPTE6 - technical data
4.2New features
The following table shows new major features that are added in the OPTE6 CANOpen option board's
firmware versions.
Table 52. OPTE6 CANopen firmware versions
New features
•Support for VACON
• Support for Fast Communication and 16 process data when installed to NXP
drive. See details in Chapter 14. APPENDIX E - FIELDBUS OPTION BOARD COMMUNICATION.
• Support for modifiable CANopen parameters and monitor values via keypad in
VACON
to/from keypad or PC tool. Functionality requires the following or newer AC drive
control firmware version:
-VACON
-VACON
• Support for CiA-420 EUROMAP extruder and puller. Note that this requires special AC drive application.
• Support for new 70CVB01605 hardware. Firmware can be used also with older
70CVB01124 hardware.
• Miscellaneous improvementsV007
• Miscellaneous improvementsV006
•Support for VACON
VACON
®
100 product family. CANopen parameters can also be stored and restored
®
100 INDUSTRIAL and 100 X: FW0072V029
®
100 FLOW: FW0159V018
®
20 X/CP and VACON® 20 drives.
®
NXP drive.
®
100 INDUSTRIAL, VACON® 100 FLOW, VACON® 100 X,
Firmware
version
V010
V009
V008
V005
4.3CAN cable
The recommended cables for installations are 4 wires twisted and a shielded cable with an
impedance of 120 Ohm. The network topology is a 2-wire bus line that is terminated at both ends by
resistors representing the characteristic impedance of the bus line. The typical CAN cable
impedance is 120 Ohm, and so for the termination resistors of ~120 Ohm must be used. For long
networks a higher resistor value must be used (150-300 Ohm).
Table 53. Bus parameter relation to cable length
Cable lengthMax bit rate [kbit/s]
0-40 m1000Max 70
100 m500
500 m100
1 km50
Max cable resistance
[m
Ω/m]
<60
<40
<26
4
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
Loading...
+ 90 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.