Danfoss OP-HPMP, OP-HPZP, OP-HPUS, OP-LPZP, OP-LPZS Installation guide

Instructions
Optyma™ Slim Pack
OP-HPMP/HPZP/HPUS/LPZP/LPZS
English / English p. 4
Español / Spanish p. 9
Português do Brasil / Brazilian Portuguese p. 14
1 | © Danfoss | DCS (CC)| 2017.03
Instructions
OP-HPMP019-28, OP-HPZP019-28, OP-HPUS015, LPZP048-68
525
327
861
626
OP-HPMP036-40, OP- HPZP036-40, OP-HPUS019-21
Ø8
361
51
30
Ø8
327
880
525
361
861
30
2 | © Danfoss | DCS (CC) | 2017.03
FRCC.PI.051.A1.ML
Instructions
OP-HPMP050-064, OP-HPZP050-064, OP-HPUS026-038,LPZP013-018
437
1283
525
Ø8
469
895
30
30
FRCC.PI.051.A1.ML
© Danfoss | DCS (CC) | 2017.03 | 3
Instructions
Instructions - Optyma™ Slim Pack
OP-HPMP/HPZP/HPUS/LPZP/LPZS
A
B
C
D
A: Model B: Code number C: Serial Number and bar code D: Supply voltage, Locked Rotor Ampere E: Housing Service Pressure F: Refrigerant G: Oil
E F
G
H
I J
H: Cable entry ports I: Suction port J: Liquid port K: Microchannel heat exchanger
L
N
M
O
K
Picture 1 : Minimum mounting distances
L
[mm]
250 650 550 550
Installation and servicing of the condensing units by qualied
personnel only. Follow these instructions and sound refrigeration engineering practice relating to installation, commissioning, maintenance and service.
M
[mm]
N
[mm]
O
[mm]
Picture 2
1 – Introduction These instructions pertain to Optyma™ Slim Pack
condensing units OP-HPMP, HPZP, HPUS, LPZP, LPZS (R507A, R404A, R134a, R22) used for refri­geration systems. They provide necessary infor­mation regarding safety and proper usage of this product The condensing unit includes following:
• Scroll/reciprocating compressor
• Microchannel heat exchanger
• Adjustable low Pressure switch
• Fix high pressures cartridge
• Service valves Suction/ liquid
• Weather proof housing
• Filter drier
• Cranckcase heater for compressor
• Receiver with stop valve
• Sight glass
• Phase sequence relay (scroll compressors)
• Fully pre-wired electrical panel (Contactor)
2 – Handling and storage
• It is recommended not to open the packaging before the unit is at the nal place for installation.
• Handle the unit with care. The packaging al­lows for the use of a forklift or pallet jack. Use appropriate and safe lifting equipment.
• Store and transport the unit in an upright position.
Picture 3
Picture 4
Mounting bolts (not supplied)
• Store the unit between -35°C and 50°C.
• Don’t expose the packaging to rain or corrosive atmosphere.
• After unpacking, check that the unit is com­plete and undamaged.
3 – Installation precautions
Do not braze as long the condensing unit is
under pressure.
Never place the unit in a ammable atmosphere Place the unit in such a way that it is not blocking
or hindering walking areas, doors, windows or similar.
• Ensure adequate space around the unit for air circulation and to open doors. Refer to picture1 for minimal values of distance to walls.
• Avoid installing the unit in locations which are daily exposed to direct sunshine for longer periods.
• Avoid installing the unit in aggressive and dus­ty environments.
• Ensure a foundation with horizontal surface (less than 3° slope), strong and stable enough to carry the entire unit weight and to eliminate vibrations and interference.
• The unit ambient temperature may not exceed 50°C during o-cycle.
• Ensure that the power supply corresponds to the unit characteristics (see nameplate).
• When installing units for HFC refrigerants, use
The condensing unit must only be used for its designed purpose(s) and within its scope of application.
Under all circumstances, the EN378 (or other applicable local safety regulation) requirements must be fullled.
The condensing unit is delivered under nitro­gen gas pressure (1 bar) and hence it cannot be connected as it is; refer to the «installation» section for further details.
The condensing unit must be handled with cau­tion in the vertical position (maximum oset from the vertical : 15°)
equipment specically reserved for HFC refri­gerants which was never used for CFC or HCFC refrigerants.
• Use clean and dehydrated refrigeration-grade copper tubes and silver alloy brazing material.
• Use clean and dehydrated system components.
• The suction piping connected to the compres­sor must be exible in 3 dimensions to dampen vibrations. Furthermore piping has to be done in such a way that oil return for the compres­sor is ensured and the risk of liquid slug over in compressor is eliminated.
4 – Installation
• The unit must be securely installed on a stable and rigid support, and xed from the begin­ning. See picture 2.
It is recommended to install the unit on rub-
ber grommets or vibration dampers (not sup­plied).
• Slowly release the nitrogen holding charge through the schrader port.
• Connect the unit to the system as soon as pos­sible to avoid oil contamination from ambient moisture.
• Avoid material entering into the system while cutting tubes. Never drill holes where burrs cannot be removed.
4 | © Danfoss | DCS (CC) | 2017.03
FRCC.PI.051.A1.02
Instructions
• Braze with great care using state-of-the-art tech­nique and vent piping with nitrogen gas ow.
• Connect the required safety and control de­vices. When the schrader port is used for this, remove the internal valve.
• It is recommended to insulate the suction pipe up to the compressor inlet with 19 mm thick insulation.
5 – Leak detection
Never pressurize the circuit with oxygen or
dry air. This could cause re or explosion.
• Do not use dye for leak detection.
• Perform a leak detection test on the complete system.
• The maximum test pressure is 32 bar.
• When a leak is discovered, repair the leak and repeat the leak detection.
6 – Vacuum dehydration
• Never use the compressor to evacuate the system.
• Connect a vacuum pump to both the LP & HP sides.
• Pull down the system under a vacuum of 500 μm Hg (0.67 mbar) absolute.
• Do not use a megohmmeter nor apply power to the compressor while it is under vacuum as this may cause internal damage.
7 – Electrical connections
• Switch o and isolate the main power supply.
• Ensure that power supply can not be switched on during installation.
• All electrical components must be selected as per local standards and unit requirements.
• Refer to wiring diagram for electrical connec­tions details.
• Ensure that the power supply corresponds to the unit characteristics and that the power supply is stable (nominal voltage ±10% and nominal frequency ±2,5 Hz).
• Dimension the power supply cables according to unit data for voltage and current.
• Protect the power supply and ensure correct earthing.
• Make the power supply according to local stan­dards and legal requirements.
The unit is equipped with high and low pressure switches, which directly cut the power supply to the compressor in case of activation. Parameters for high and low pressure cut outs should be set by installer considering compressor model, refrigerant and application. Units with Danfoss MLZ and LLZ compressors are also equipped with phase sequence relay to protect the unit against phase loss/sequence/ asymmetry and under-/over-voltage.
For units with a 3-phase scroll compressor, cor­rect phase sequence for compressor rotation direction shall be observed.
• Determine the phase sequence by using a phase meter in order to establish the phase orders of line phases L1, L2 and L3.
• Connect line phases L1, L2 and L3 to main swit­ch terminals T1, T2 and T3 respectively.
8 – Filling the system
• Wear protective stu like goggles and protec­tive gloves.
• Never start the compressor under vacuum. Keep the compressor switched o.
• Before charging the refrigerant, verify that the oil level is between ¼ and ¾ on the compressor oil sight glass. If additional oil is required please refer to the compressors label for type of oil.
• Use only the refrigerant for which the unit is designed for.
• Fill the refrigerant in liquid phase into the condenser or liquid receiver. Ensure a slow charging of the system to 4 – 5 bar for R404A /
R507A or R22 and approx. 2 bar for R134a.
• Do not put liquid refrigerant through suction line.
• It is not allowed to mix additives with the oil and/or refrigerant
• The remaining charge is done until the instal­lation has reached a level of stable nominal condition during operation.
• Never leave the lling cylinder connected to the circuit.
9 – Verification before commissioning
Use safety devices such as safety pressure switch and mechanical relief valve in compliance with both generally and locally applicable regu­lations and safety standards. Ensure that they are operational and properly set.
Check that the settings of high-pressure swit­ches and relief valves don’t exceed the maximum service pressure of any system component.
• Verify that all electrical connections are properly
fastened and in compliance with local regulations.
• When a crankcase heater is required, it must be
energized at least 12 hours before initial start­up and start-up after prolonged shut-down period.
10 – Start-up
• Never start the unit when no refrigerant is char-
ged.
• All service valves must be in the open position.
See picture 3.
• Check compliance between unit and power
supply.
• Check that the crankcase heater is working.
• Check that the fan can rotate freely.
• Check that the protection sheet has been re-
moved from the backside of condenser.
• Balance the HP/LP pressure.
• Energize the unit. It must start promptly. If
the compressor does not start, check wiring conformity, voltage on terminals and sequence phase.
• Eventual reverse rotation of a 3-phase com-
pressor can be detected by following phe­nomena; unit doesn’t start, the compressor doesn’t build up pressure, it has abnormally high sound level and abnormally low power consumption. In such case, shut down the unit immediately and connect the phases to their proper terminals.
• If the rotation direction is correct the low pres-
sure indication on the low pressure gauge shall show a declining pressure and the high pres­sure indication on the high pressure gauge shall show an increasing pressure.
11 – Check with running unit
• Check the fan rotation direction. Air must ow
from the condenser towards the fan.
• Check current draw and voltage.
• Check suction superheat to reduce risk of slug-
ging.
• When a sight glass is provided observe the oil
level at start and during operation to conrm that the oil level remains visible.
• Respect the operating limits.
• Check all tubes for abnormal vibration. Move-
ments in excess of 1.5 mm require corrective measures such as tube brackets.
• When needed, additional refrigerant in liquid
phase may be added in the low-pressure side as far away as possible from the compressor. The compressor must be operating during this pro­cess.
• Do not overcharge the system.
• Never release refrigerant to atmosphere.
• Before leaving the installation site, carry out
a general installation inspection regarding cleanliness, noise and leak detection.
• Record type and amount of refrigerant charge as well as operating conditions as a reference for future inspections.
12 – Maintenance
Always switch o the unit at main switch
before remove fan panel.
Internal pressure and surface temperature are dangerous and may cause permanent injury. Maintenance operators and installers require appropriate skills and tools. Tubing temperature may exceed 100°C and can cause severe burns.
Ensure that periodic service inspections to ensure system reliability and as required by local regulations are performed. To prevent system related problems, following Periodic maintenance is recommended:
• Verify that safety devices are operational and
properly set.
• Ensure that the system is leak tight.
• Check the compressor current draw.
• Conrm that the system is operating in a way
consistent with previous maintenance records and ambient conditions.
• Check that all electrical connections are still
adequately fastened.
• Keep the unit clean and verify the absence of
rust and oxidation on the unit components, tubes and electrical connections.
The condenser must be checked at least once a year for clogging and be cleaned if deemed necessary. Access to the internal side of the condenser takes place through the fan panel. Microchannel coils tend to accumulate dirt on the surface rather than inside, which makes them easier to clean than n-&-tube coils.
• Switch o the unit at main switch before re-
move any panel from the condensing unit.
• Remove surface dirt, leaves, bres, etc. with
a vacuum cleaner, equipped with a brush or other soft attachment. Alternatively, blow com­pressed air through the coil from the inside out, and brush with a soft bristle. Do not use a wire brush. Do not impact or scrape the coil with the
vacuum tube or air nozzle. If the refrigerant system has been opened, the system has to be ushed with dry air or nitrogen to remove moisture and a new lter drier has to be installed. If evacuation of refrigerant has to be done, it shall be done in such a way that no refri­gerant can escape to the environment.
13 - Warranty Always transmit the model number and serial num-
ber with any claim led regarding this product. The product warranty may be void in following cases:
• Absence of nameplate.
• External modications; in particular, drilling,
welding, broken feet and shock marks.
• Compressor opened or returned unsealed.
• Rust, water or leak detection dye inside the
compressor.
• Use of a refrigerant or lubricant not approved
by Danfoss.
• Any deviation from recommended instructions
pertaining to installation, application or main-
tenance.
• Use in mobile applications.
• Use in explosive atmospheric environment.
• No model number or serial number transmit-
ted with the warranty claim.
14 – Disposal Danfoss recommends that condensing
units and oil should be recycled by a suitable company at its site.
FRCC.PI.051.A1.03
© Danfoss | DCS (CC) | 2017.02 | 5
Instructions
Code N: HPMP, HPZP, LPZP
RC
230V 1~50-60Hz
L1 L2 1
13
5
F1
2 4
6
F2
F3
CR
CS
RL
1
2
5
CV
CV
a1
K
a2
2 PE
CP -COMPRESSOR / COMPRESOR CR -CAPACITOR MARCHA / RUN
CAPACITOR ARRANQUE / START
CS ­CV -CAPACITOR VENTILADOR / FAN
F -
FUSÍVEL / FUSIBLE / FUSE
K -CONTATOR / CONTACTOR
PH -
PRESSOSTATO ALTA PRESOSTATO ALTA PRESSURE SWITCH - HBP
PL -
PRESSOSTATO BAIXA PRESOSTATO BAJA PRESSURE SWITCH - LBP
RC -
RESISTÊNCIA CARTER CALENTADOR CARTER CRANKCASE HEATER
RL - RELE / RELAY
V -
VENTILADOR / FAN
R
S
P<
CP
V1
V2
PH
4
1
2
P<
PE
PL
№1
Code N: HPUS
CS
RL
5
PE
RC
CR
13
2 4
230V 1~ 50-60Hz
L1 L2 1
5
F1
6
F2
F3
CV
CV
a1
K
a2
2 PE
COMPRESSOR / COMPRESOR
CP ­CR -CAPACITOR MARCHA / RUN
CAPACITOR ARRANQUE / START
CS ­CV -CAPACITOR VENTILADOR / FAN
F -
FUSÍVEL / FUSIBLE / FUSE
K -CONTATOR / CONTACTOR
PH -
PRESSOSTATO ALTA PRESOSTATO ALTA PRESSURE SWITCH - HBP
PL -
PRESSOSTATO BAIXA PRESOSTATO BAJA PRESSURE SWITCH - LBP
RC -
1
2
RESISTÊNCIA CARTER CALENTADOR CARTER CRANKCASE HEATER
RL - RELE / RELAY
V -
VENTILADOR / FAN
C
S
R
CP
V1
V2
PH
4
1
2
P<
P<
PE
PL
6 | © Danfoss | DCS (CC) | 2017.03
№2
FRCC.PI.051.A1.02
Loading...
+ 13 hidden pages