Danfoss OP-HPMD031-043-054, OP-HPMD063-068 User Manual

Instructions
Optyma™ Pack OP-HPMD
L
MADE IN INDIA
A
OP-HPMD031AWW00G
Code no.:
B
Application
C
Refrigerant
D
M.W.P. HP
E
LP (1) 7 bar Voltage 230V3N~/50Hz
F
LRA 40 12MCC
Serial No.
G
Barcode Serial No:
A: Model B: Code number C: Application, Protection D: Refrigerant E: Housing Service Pressure F: Supply voltage, Locked Rotor Ampere,
Maximum Current Consumption
G: Serial Number and bar code
Picture 2
114X9101
HBP (1) R22 (1) 25 bar
123456CG0514
IP54
(2) (2)
118UXXXX
H: Cable entry ports I: Suction port J: Liquid port K: Coil guard
Mounting bolts
Picture 3
N
M
Picture 1 : Minimum mounting distances
L
[mm]
250 650 550 550
Installation and servicing of the condensing units by qualified
personnel only. Follow these instructions and sound refrigeration engineering practice relating to installation, commissioning, maintenance and service.
The condensing unit must only be used for its designed purpose(s) and within its scope of application.
Under all circumstances, the applicable local safety regulation) requirements must be fulfilled.
The condensing unit is delivered under nitro­gen gas pressure (1 bar) and hence it cannot be connected as it is; refer to the «installation» section for further details.
The condensing unit must be handled with cau­tion in the vertical position (maximum offset from the vertical : 15°)
M
[mm]
N
[mm]
O
O
[mm]
1 – Introduction
These instructions pertain to Optyma condensing units OP-HPMD (R22) used for re­frigeration systems. They provide necessary in­formation regarding safety and proper usage of this product. The condensing unit includes following:
version W00
• Reciprocating compressor
• Fin-Tube heat exchanger
• Cartridge pressure switches
• Discharge gas thermostat (DGT)
• Service valves suction/ liquid
• Weather proof housing
2 – Handling and storage
• It is recommended not to open the packaging be­fore the unit is at the final place for installation.
• Handle the unit with care. The packaging al­lows for the use of a forklift or pallet jack. Use appropriate and safe lifting equipment.
• Store and transport the unit in an upright position.
• Store the unit between -35°C and 50°C.
• Don’t expose the packaging to rain or corrosive atmosphere.
• After unpacking, check that the unit is com-
TM
Pack
© Danfoss | DCS (CC) | 2018.11
plete and undamaged.
3 – Installation precautions
Do not braze as long the condensing unit is
under pressure.
Never place the unit in a flammable atmosphere Place the unit in such a way that it is not blocking
or hindering walking areas, doors, windows or similar.
• Ensure adequate space around the unit for air circulation and to open doors. Refer to picture1 for minimal values of distance to walls.
• Avoid installing the unit in locations which are daily exposed to direct sunshine for longer periods.
• Avoid installing the unit in aggressive and dusty environments.
• Ensure a foundation with horizontal surface (less than 3° slope), strong and stable enough to carry the entire unit weight and to eliminate vibrations and interference.
• The unit ambient temperature may not exceed 50°C during off-cycle.
• Ensure that the power supply corresponds to the unit characteristics (see nameplate).
• Use clean and dehydrated refrigeration-grade copper tubes and silver alloy brazing material.
• Use clean and dehydrated system components.
• The suction piping connected to the compres­sor must be flexible in 3 dimensions to dampen vibrations. Furthermore piping has to be done in such a way that oil return for the compres­sor is ensured and the risk of liquid slug over in compressor is eliminated.
4 – Installation
• The installation in which the condensing unit is ins­talled must comply to EEC Pressure directive (PED) no. 2014/68/EU. The condensing unit itself is not a ”unit” in the scope this directive. Under all circum­stances local safety regulations must be fulfilled.
• The unit must be securely installed on a stable and rigid support, and fixed from the begin­ning. See picture 2.
It is recommended to install the unit on rub- ber grommets or vibration dampers . Rubber pads with mounting bolts are supplied.
• Slowly release the nitrogen holding charge through the schrader port.
• Connect the unit to the system as soon as possible to avoid oil contamination from ambient moisture.
• Avoid material entering into the system while cutting tubes. Never drill holes where burrs cannot be removed.
AN294425350971en-000101 | 1
Instructions
• Braze with great care using state-of-the-art tech­nique and vent piping with nitrogen gas flow.
• Connect the required safety and control de­vices. When the schrader port is used for this, remove the internal valve.
• It is recommended to insulate the suction pipe up to the compressor inlet with 19 mm thick insulation.
5 – Leak detection
Never pressurize the circuit with oxygen or
dry air. This could cause fire or explosion.
• Do not use dye for leak detection.
• Perform a leak detection test on the complete system.
• The maximum test pressure is 28 bar.
• When a leak is discovered, repair the leak and repeat the leak detection.
6 – Vacuum dehydration
• Never use the compressor to evacuate the system.
• Connect a vacuum pump to both the LP & HP sides.
• Pull down the system under a vacuum of 500 μm Hg (0.67 mbar) absolute.
• Do not use a megohmmeter nor apply power to the compressor while it is under vacuum as this may cause internal damage.
7 – Electrical connections
• Switch off and isolate the main power supply.
• Ensure that power supply can not be switched on during installation.
• All electrical components must be selected as per local standards and unit requirements.
• Refer to wiring diagram for electrical connec­tions details.
• Ensure that the power supply corresponds to the unit characteristics and that the power supply is stable (nominal voltage ±10% and no­minal frequency ±2,5 Hz).
• For safe working under compressor specifica­tion, unit is equipped with discharge gas ther­mostat (DGT), which directly cut the power supply to the compressor in case of activation (Activates at 130 ±5 °C and deactivates at 105 ±10 °C discharge gas temperature. Make sure that discharge gas thermostat is properly connected as per wiring diagram (Refer DGT in WD1 and WD2)
• Dimension the power supply cables according to unit data for voltage and current.
• Protect the power supply and ensure correct earthing.
• Make the power supply according to local stan­dards and legal requirements.
The unit is equipped with high and low pressure switches, which directly cut the power supply to the compressor in case of activation.
• Determine the phase sequence by using a phase meter in order to establish the phase or­ders of line phases L1, L2 and L3.
• Connect line phases L1, L2 and L3 to main swit­ch terminals T1, T2 and T3 respectively.
8 – Filling the system
• Wear protective stuff like goggles and protec­tive gloves.
• Never start the compressor under vacuum. Keep the compressor switched off.
• Before charging the refrigerant, verify that the oil level is between ¼ and ¾ on the compressor oil sight glass. If additional oil is required please refer to the compressors label for type of oil.
• Use only the refrigerant for which the unit is designed for.
• Fill the refrigerant in liquid phase into the condenser or liquid receiver.
• Ensure a slow charging of the system to 4 – 5 bar for R22.
• Do not put liquid refrigerant through suction line.
• It is not allowed to mix additives with the oil and/or refrigerant
• The remaining charge is done until the instal­lation has reached a level of stable nominal condition during operation.
• Never leave the filling cylinder connected to the circuit.
9 – Verification before commissioning
Use safety devices in compliance with both generally and locally applicable regulations and safety standards.
• Verify that all electrical connections are properly
fastened and in compliance with local regulations.
• When a crankcase heater is required, it must be
energized at least 12 hours before initial start­up and start-up after prolonged shut-down pe­riod.
10 – Start-up
• Never start the unit when no refrigerant is
charged.
• All service valves must be in the open position.
See picture 3.
• Check compliance between unit and power
supply.
• Check that the crankcase heater is working.
• Check that the fan can rotate freely.
• Check that the protection sheet has been re-
moved from the backside of condenser.
• Balance the High Pressure / Low Pressure.
• Energize the unit. It must start promptly. If
the compressor does not start, check wiring conformity, voltage on terminals and sequence phase.
11 – Check with running unit
• Check the fan rotation direction. Air must flow
from the condenser towards the fan.
• Check current draw and voltage.
• Check suction superheat to reduce risk of slug-
ging.
• When a sight glass is provided observe the oil
level at start and during operation to confirm that the oil level remains visible.
• Respect the operating limits.
• Check all tubes for abnormal vibration. Move-
ments in excess of 1.5 mm require corrective measures such as tube brackets.
• When needed, additional refrigerant in liquid
phase may be added in the low-pressure side as far away as possible from the compressor. The compressor must be operating during this pro­cess.
• Do not overcharge the system.
• Never release refrigerant to atmosphere.
• Before leaving the installation site, carry out
a general installation inspection regarding cleanliness, noise and leak detection.
• Record type and amount of refrigerant charge
as well as operating conditions as a reference for future inspections.
12 – Maintenance
Always switch off the unit at main switch be­fore remove fan panel.
Internal pressure and surface temperature are dangerous and may cause permanent injury. Maintenance operators and installers require appropriate skills and tools. Tubing temperature may exceed 100°C and can cause severe burns.
Ensure that periodic service inspections to ensure system reliability and as required by local regulations are performed. To prevent system related problems, following Periodic maintenance is recommended:
• Verify that safety devices are operational and
properly set.
• Ensure that the system is leak tight.
• Check the compressor current draw.
• Confirm that the system is operating in a way
consistent with previous maintenance records and ambient conditions.
• Check that all electrical connections are still adequately fastened.
• Keep the unit clean and verify the absence of rust and oxidation on the unit components, tubes and electrical connections.
The condenser must be checked at least once a year for clogging and be cleaned if deemed necessary. Access to the internal side of the condenser takes place through the fan panel.
• Switch off the unit at main switch before re­move any panel from the condensing unit.
• Remove surface dirt, leaves, fibres, etc. with a vacuum cleaner, equipped with a brush or other soft attachment. Alternatively, blow com­pressed air through the coil from the inside out, and brush with a soft bristle. Do not use a wire brush. Do not impact or scrape the coil with the vacuum tube or air nozzle.
If the refrigerant system has been opened, the system has to be flushed with dry air or nitrogen to remove moisture and a new filter drier has to be installed. If evacuation of refrigerant has to be done, it shall be done in such a way that no refri­gerant can escape to the environment.
13 - Warranty
Always transmit the model number and serial nu­mber with any claim filed regarding this product. The product warranty may be void in following cases:
• Absence of nameplate.
• External modifications; in particular, drilling, welding, broken feet and shock marks.
• Compressor opened or returned unsealed.
• Rust, water or leak detection dye inside the compressor.
• Use of a refrigerant or lubricant not approved by Danfoss.
• Any deviation from recommended instructions pertaining to installation, application or main­tenance.
• Use in mobile applications.
• Use in explosive atmospheric environment.
• Working above specified envelope mentioned (Maximum Ambient temperature 45 °C)
• No model number or serial number trans­mitted with the warranty claim.
14 – Disposal
Danfoss recommends that condensing units and oil should be recycled by a suitable company at its site.
2 | AN294425350971en-000101
© Danfoss | DCS (CC) | 2018.11
Loading...
+ 2 hidden pages