Danfoss OP-HJZ, OP-HJM, OP-HGM, OP-HNU, OP-HRU User guide

...
Manual
Installation and maintenance condensing unit manual
OP-HJZ / HJM / HGM / HNU / HRU / HGZ / LJZ / LGZ
http://cc.danfoss.com
Manual
Contents
English version ....................................................................................................................4
Spanish version .................................................................................................................14
Model
Serial Number
Compressor:
Fan Motor:
Design Pressure:
Oil Type: Mineral
Housing for Outdoor use:
Danfoss Code
A
B
C
D
E
F
H
I
J K
L
G
OP-HJZ018D32Q
0012345AU0116
114N3209
R22, R404A, R507A,
R134a, R448A, R449A, R452A, R513A
Manual
Label
Installation & Maintenance
Picture 1 : Minimum mounting distances
A: Model and bar code
B: Unit code and bar code
C: Serial number and bar code
D: Compressor voltage & Locked rotor amps & Rated
load amps
E: Fan voltage & Full load amps
F: Min. circuit Ampacity
G: Max. Fuse size
H: Design pressure
I: Refrigerant
J: Oil type
K: Outdoor housing
L: Wiring diagram
AIR FLOW
IMPORTANT
L
[mm]
300 650 550 550
1-Installation and mainteneance of the condensing unit must be carried out by qualified personnel only. Follow these instructions and best practices on refrigeration engineering during installation, commissioning, maintenance and servicing tasks. 2-The condensing unit must only be used for its designed purposes and within its scope of application.
M
[mm]
N
[mm]
O
[mm]
3 - Under all circumstances, EN 378 (or any other applicable local safety regulation) requirements must be fulfilled. 4 - The condensing unit is delivered under nitrogen gas pressure (1 bar) and hence it cannot be connected as it is; refer to the “Installation” section for further details. 5 - The condensing unit must be handled with caution in a vertical position (maximum offset from the vertical: 15°).
3BC21808642813501-000201
Manual
Installation & Maintenance
Introduction
Handling and storage
Installation precautions
These instructions pertain to OPTYMA™ condensing units (R22, R404A, R507A, R134a, R448A, R449A, R452A, R513A) used for
• It is recommended not to open the packaging before the unit is at the final place for installation.
• Handle the unit with care. The packaging allows the use of a forklift or pallet jack for handling. Use appropriate and safe lifting equipment.
• Store and transport the unit in an upright position.
Do not braze if the condensing unit is under
pressure.
Never place the unit in a flammable
atmosphere.
Place the unit in such a way that it is not blocking or hindering walking areas, doors, windows or similar.
• Ensure adequate space around the unit for air
circulation and to open doors. Refer to picture 1 for minimal values of distance to walls.
• Avoid installing the unit in locations which are
daily exposed to direct sunshine for longer periods.
• Avoid installing the unit in aggressive and/or
dusty environments.
• Ensure a foundation with horizontal surface (less
than 3° slope), strong and stable enough to carry the entire unit weight and to eliminate vibrations and interference.
refrigeration systems. They provide necessary information regarding safety and proper usage of this product.
• Store the unit between -35 °C and 50 °C.
• Don’t expose the packaging to rain or corrosive atmosphere.
• After unpacking, check that the unit is complete and undamaged.
• The unit ambient temperature may not exceed 50 °C during off-cycle.
• Ensure that the power supply corresponds to the unit characteristics (see nameplate).
• When installing units for HFC refrigerants, use equipment specifically reserved for HFC refrigerants which was never used for CFC or HCFC refrigerants.
• Use clean and dehydrated refrigeration-grade copper tubes and silver alloy brazing material.
• Use clean and dehydrated system components.
• The suction piping connected to the compressor must be flexible in 3 dimensions to dampen vibrations. Furthermore piping has to be done in such a way that oil return for the compressor is ensured and the risk of liquid slug over in compressor is eliminated.
Installation
Leak detection
Vacuum dehydration
• The unit must be securely installed on a stable and rigid support, and fix from the beginning.
• It is recommended to install the unit on rubber grommets or vibration dampers (not supplied).
• Slowly release the nitrogen holding charge through the Schraeder port.
• Connect the unit to the system as soon as possible to avoid oil contamination from ambient moisture.
• Avoid material entering into the system while cutting tubes. Never drill holes where burrs cannot be removed.
Never pressurize the circuit with oxygen or dry
air. This could cause fire or explosions.
• Do not use dye for leak detection.
• Perform a leak detection test on the complete
system.
• Never use the compressor to evacuate the
system.
• Connect a vacuum pump to both the LP and HP
sides.
• Braze with great care using state-of-the-art techniques and vent piping with nitrogen gas flow.
• Connect the required safety and control devices. Remove the internal valve when using the Schraeder port for this.
• It is recommended to insulate the suction pipe up to the compressor inlet with 19 mm thick insulation.
• The maximum test pressure is 32 bar.
• When a leak is discovered, repair the leak and repeat the leak detection test.
• Pull down the system under a vacuum of 500 µm
Hg (0.67 mbar) absolute.
• Do not use an ohmmeter nor apply power to the
compressor while it is under vacuum as this may cause internal damage.
Manual
Installation & Maintenance
Electrical connections
Filling the system
• Switch off the system and isolate the main power supply.
• Ensure that power supply cannot be switched on during installation.
• All electrical components must be selected as per local standards and unit requirements.
• Refer to wiring diagram for electrical connections details.
• Ensure that the power supply corresponds to the unit characteristics and that the power supply is stable (nominal voltage ±10 % and nominal frequency ±2.5 Hz).
• Dimension the power supply cables according to unit data for voltage and current.
• Protect the power supply and ensure correct earthing.
• Wear protective stuff like goggles and protective gloves.
• Never start the compressor under vacuum. Keep the compressor switched off.
• Before charging the refrigerant, verify that the oil level is between “¼” and “¾” on the compressor oil sight glass. If additional oil is required, please refer to the compressor’s label for type of oil.
• Use only the refrigerant for which the unit is designed for.
• Fill the refrigerant in liquid phase into the condenser or liquid receiver. Ensure a slow
• Make the power supply according to local standards and legal requirements.
• The unit includes high and low-pressure switches which, when activated, cut the power supply to the compressor. Parameters for high and low-pressure cut-outs are to be adjusted by the installer, depending on the compressor model, refrigerant and application. For units with a 3-phase scroll compressor, correct phase sequence for compressor rotation direction shall be observed.
• Determine the phase sequence by using a phase meter to establish the phase order of line phases L1, L2 and L3.
• Connect line phases L1, L2 and L3 to main switch terminals T1, T2 and T3, respectively.
charging of the system to 4-5 bar for R22, R404A, R507A, R448A, R449A or R452A, and approx. 2 bar for R134a or R513A.
• Do not put liquid refrigerant through the suction line.
• It is not allow to mix additives with the oil and/or refrigerant
• The remaining charge is done until the installation has reached a level of stable nominal condition during operation.
• Never leave the filling cylinder connected to the circuit.
Verification before commissioning
Start-up
Use safety devices (such as safety pressure switches and mechanical relief valves) in compliance with both generally and locally applicable regulations and safety standards. Make sure that the devices are operational and properly set.
Check that the settings of high-pressure switches and relief valves don’t exceed the maximum service pressure of any system component.
• Never start the unit when no refrigerant is
charged.
• All service valves must be in the open position.
• Check compliance between unit and power
supply.
• Check that the crankcase heater is working.
• Check that the fan can rotate freely.
• Check that the protection sheet has been
removed from the backside of condenser.
• Balance the HP/LP pressure.
• Energize the unit. It must start promptly. If
the compressor does not start, check wiring conformity, voltage on terminals and sequence phase.
• Verify that all electrical connections are properly fastened and in compliance with local regulations.
• When a crankcase heater is required, it must be energized at least 12 hours before initial start-up and start-up after prolonged shut-down or belt type crankcase heaters.
• Eventual reverse rotation of a 3-phase compressor can be detected by the following phenomena: unit doesn’t start, the compressor doesn’t build up pressure, it has abnormally high sound level and abnormally low power consumption. In such case, shut down the unit immediately and connect the phases to their proper terminals.
• If the rotation direction is correct, the low­pressure gauge shall show a declining pressure and the high-pressure gauge shall show an increasing pressure.
5BC21808642813501-000201
Manual
Installation & Maintenance
Checks with running unit
Maintenance
• Check the fan rotation direction. Air must flow from the condenser towards the fan.
• Check current draw and voltage.
• Check suction superheat to reduce risk of slugging.
• When a sight glass is provided, observe the oil level at start and during operation to confirm that the oil level remains visible.
• Respect the operating limits.
• Check all tubes for abnormal vibration. Movements in excess of 1.5 mm require corrective measures, such as tube brackets.
• When needed, additional refrigerant in the
Always switch off the unit at main switch before
removing the fan panel.
Internal pressures and surface temperatures are
dangerous and may cause permanent injury.
Maintenance operators and installers require appropriate skills and tools. Tubing temperature may exceed 100 °C and therefore cause severe burns.
Ensure that periodic service inspections to ensure system reliability and as required by local regulations are performed. To prevent system related problems, following periodic maintenance is recommended:
• Verify that safety devices are operational and
properly set.
• Ensure that the system is leak tight.
• Check the compressor current draw.
• Confirm that the system is operating in a way
consistent with previous maintenance records and ambient conditions.
• Check that all electrical connections are still
adequately fastened.
• Keep the unit clean and verify the absence of
rust and oxidation on the unit components, tubes and electrical connections.
liquid phase may be added in the low-pressure side as far as possible from the compressor. The compressor must be operating during this process.
• Do not overcharge the system.
• Never release refrigerant to the atmosphere.
• Before leaving the installation site, carry out a general installation inspection regarding cleanliness, noise and leak detection.
• Record type and amount of refrigerant charge, as well as operating conditions as a reference for future inspections.
The condenser must be checked at least once a year for clogging and be cleaned if deemed necessary. Access to the internal side of the condenser takes place through the fan panel. Microchannel coils tend to accumulate dirt on the surface rather than inside, which makes them easier to clean than fin-&-tube coils.
• Switch off the unit at main switch before removing any panel from the condensing unit.
• Remove surface dirt, leaves, fibers, etc. with a vacuum cleaner, equipped with a brush or other soft attachment. Alternatively, blow compressed air through the coil from the inside out, and brush with a soft bristle. Do not use a wire brush. Do not impact or scrape the coil with the vacuum tube or air nozzle.
If the refrigerant system has been opened, the system has to be flushed with dry air or nitrogen to remove moisture and a new filter drier has to be installed. If evacuation of refrigerant has to be done, it shall be done in such a way that no refrigerant can escape to the environment.
Maintenance
Disposal
Always transmit the model number and serial number with any claim filed regarding this product. The product warranty may be void in following cases:
• Absence of nameplate.
• External modifications; in particular, drilling, welding, broken feet and shock marks.
• Compressor opened or returned unsealed.
• Rust, water or leak detection dye inside the compressor.
Danfoss recommends that condensing units and oil should be recycled by a suitable company at its site.
• Use of a refrigerant or lubricant not approved by Danfoss.
• Any deviation from recommended instructions pertaining to installation, application or maintenance.
• Use in mobile applications.
• Use in explosive atmospheric environment.
• No model number or serial number transmitted with the warranty claim.
Drawing 1A, version D32 (Reciprocating Compressor, 1 fan, Weiguang)
Drawing 1B, version D40 (reciprocating compressor, 1 fan, Weiguang)
Suction Line
Manual
Installation & Maintenance
Drawing 1A, version D32 (reciprocating compressor, 1 fan)
Front View Left View
Suction Line
Liquid line
Air ow
Suction Line
Power inlet
Liquid Line
Top View
X
Fixation
X
X
Suction Line Liquid Line
X
X
[mm]Y [mm]
Height H
[mm]
Depth D
[mm]
OP-HJ … 018D-022D 16 126 463 310 1000 OP-HJ … 028D-036D OP-HJ … 040D- 050D 688
14 174
538
420 1150
Drawing 1B, version D40 (reciprocating compressor, 1 fan)
Front View Left View
Length L
[mm]
Iso View
Suction Line
X
Y
Liquid line
L
Air ow
H
D
Liquid line
Top View
X
X
Fixation
OP-HJ … 018D-022D OP-LJ … 048D-068D OP-HJ … 028D-036D
OP-LJ … 108D-136D
X
X
X
[mm]Y [mm]
Height H
[mm]
Depth D
[mm]
16 126 463 310 1000
538
14 174
688
420 1150OP-HJ … 040D- 050D
Length L
[mm]
Suction Line
Liquid Line
Iso View
X
Y
H
L
D
7BC21808642813501-000201
Drawing 2A, version D32 (reciprocating compressor, 2 fan, Weiguang)
Suction Line
Drawing 2B, version D40 (reciprocating compressor, 2 fan, Weiguang)
Manual
Installation & Maintenance
Drawing 2A, version D32 (reciprocating compressor, 2 fan)
Front View
Suction Line
Liquid Line
Top View Iso View
Y Y
Left View
Suction Line
Air ow
Suction Line
H
Suction Line
Fixation
OP-HG … 064D-100D
OP-HG … 125D-160D 971
X1
[mm]
25 20 500
Liquid Line
X2
[mm]Y [mm]
Height H
[mm]
715
Drawing 2B, version D40 (reciprocating compressor, 2 fans)
Front View
Top View Iso View
Depth D
[mm]
800 120 0
Liquid Line
Suction Line
Length L
[mm]
Left View
L
Air ow
D
Liquid Line
Y
Fixation
X1
[mm]
X2
[mm]Y [mm]
OP-HG … 064D-100D
25 20 500
OP-LG … 215D-271D 715
Height H
[mm]
715
Y
Depth D
[mm]
800 120 0OP-HG … 125D-160D 971
Liquid Line
Suction Line
Length L
[mm]
H
L
D
Liquid Line
Loading...
+ 18 hidden pages