Installation Guide
Check valve
Type NRVT
Refrigerants: R744 (CO)
Temperature range (TS): -40 °C – 150 °C / -40 °F – 302 °F
020R9520
Max. working pressure (PS/MWP): 140 bar / 2031 psig
Warning:
This valve is UL certified for use in CO2(R744) systems only. The design pressure shall not be less than the
value outlined in section 9.2 of ANSI/ ASHRAE 15 for the refrigerant used in the system.
Only authorized persons are allowed to install this valve, as closing can cause build-up of excessive
pressure in the system.
020R9520
Possible orientations(hard spring)
Danfoss
It is possible vertical, horizontal or inclined mounting
Risk orientations(soft spring)
Brazing
Min. 5% Ag
Dry N2
Max. 150 °C / 302 °F
Danfoss
20-8016
oss
Internal leak risk orientations for soft spring
© Danfoss | Climate Solutions | 2022.02
45°
45°
AN400564784627en-000201 | 1