Danfoss NL10MF Data sheet

Datasheets
NL10MF
Standard Compressor
R134a, 220-240V 50Hz & 208-230V 60Hz
General
Code number 105G6885
Approvals EN 60335-2-34, UL984, CCC
Compressors on pallet 80
Application
Application MBP
Frequency Hz 50 60
Evaporating temperature °C -20 to 15 -35 to 7.2
Max. condensing temperature continuous (short) °C 60 (70) 60 (70)
Max. winding temperature continuous (short) °C 125 (135) 125 (135)
Cooling requirements
Frequency Hz 50 60
Application
32°C F1F1F1F1–
38°C F
43°C F
Remarks on application:
Motor
Motor type RSIR/CSIR
LRA (rated after 4 sec. UL984), HST | LST A 16.1 13.1
Cut in Current, HST | LST A 16.1 17.1
Resistance, main | start winding (25°C) 6.1 17.5
F2 for 230-240V 50Hz nominal below -12°C evaporating temp.
CSIR strongly recommended for 60Hz
LBP MBP HBP LBP MBP HBP
1F1F1F1
1F1F1F1
S =Staticcoolingnormallysufcient
O = Oil cooling F1 = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) F2 = Fan cooling 3.0 m/s necessary
SG =Suctiongascoolingnormallysufcent
= not applicable in this area
Design
Displacement cm
Oil quantity (type) cm
Maximum refrigerant charge g 600
Free gas volume in compressor cm
Weight without electrical equipment kg 10.5
Dimensions
Height mm A 203
Suction connector location/I.D. mm | angle C 8.2 | 15°
material | comment Copper | Rubber plug
Process connector location/I.D. mm | angle D 6.2 | 25°
material | comment Copper | Rubber plug
Discharge connector location/I.D. mm | angle E 6.2 | 35°
material | comment Copper | Rubber plug
Oil cooler connector location/I.D. mm | angle F
material | comment
Connector tolerance I.D. mm ±0.09
Remarks:
3
3
3
320 (polyolester)
B 197
B1
B2
10.10
2360
© Danfoss | DCS (CC) | 2017.02
DEHC.ED.200.B7.02 | 1
EN 12900 Household (CECOMAF) 220V, 50Hz, fan cooling F
Danf already on order pro All trademarks in this material are property of the respec
1
Evap. temp. in °C -45 -40 -35 -30 -25 -23.3 -20 -15 -10 -6.7 -5 0 5 7.2 10 15 20
Capacity in W 266 346 441 513 554 687 843 919 1023 1231
Power cons. in W 251 286 323 347 360 397 435 451 472 509
Current cons. in A 2.06 2.15 2.25 2.33 2.37 2.50 2.65 2.72 2.81 2.98
COP in W/W 1.06 1.21 1.37 1.48 1.54 1.73 1.94 2.04 2.17 2.42
EN 12900 Household (CECOMAF) 220V, 60Hz, fan cooling F
1
Evap. temp. in °C -45 -40 -35 -30 -25 -23.3 -20 -15 -10 -6.7 -5 0 5 7.2 10 15 20
Capacity in W 109 166 233 258 312 406 518 603 650 807 989 1079
Power cons. in W 143 187 232 248 278 325 373 405 421 470 518 540
Current cons. in A 1.44 1.57 1.71 1.76 1.87 2.03 2.21 2.34 2.40 2.60 2.82 2.91
COP in W/W 0.76 0.89 1.00 1.04 1.12 1.25 1.39 1.49 1.54 1.72 1.91 2.00
ASHRAE MBP 220V, 50Hz, fan cooling F
1
Evap. temp. in °C -45 -40 -35 -30 -25 -23.3 -20 -15 -10 -6.7 -5 0 5 7.2 10 15 20
Capacity in W 293 382 487 567 6 11 758 930 1014 1129 1359
Power cons. in W 251 286 322 346 358 396 433 449 470 506
Current cons. in A 2.06 2.15 2.25 2.33 2.37 2.50 2.64 2.71 2.81 290
COP in W/W 1.17 1.33 1.51 1.64 1.71 1.92 2.15 2.26 2.40 2.68
ASHRAE MBP 220V, 60Hz, fan cooling F
1
Evap. temp. in °C -45 -40 -35 -30 -25 -23.3 -20 -15 -10 -6.7 -5 0 5 7.2 10 15 20
Capacity in W 122 184 258 285 344 448 571
Power cons. in W 144 188 232 248 278 325 372
Current cons. in A 1.44 1.57 1.71 1.76 1.87 2.03 2.21
COP in W/W 0.84 0.98 1.11 1.15 1.24 1.38 1.53
665 718 890 1092 1190
403 419 467 515 536
2.33 2.39 2.59 2.81 2.90
1.65 1.71 1.90 2.12 2.22
Accessories for NL10MF Figure Code number Test conditions
EN 12900/
CECOMAF
PTC starting device 6.3 mm spade connectors
4.8 mm spade connectors 103N0018 Ambient temperature 32°C 35°C
a1
103N0011 Condensing temperature 55°C 54.4°C
Starting relay 6.3 mm spade connectors a2 117U6022 Suction gas temperature 32°C 35°C
Start. capacitor 125 µF 6.3 mm spade connectors c 117U5018 Liquid temperature no subcooling 46.1°C
Cover b 103N2011
Cord relief d 103N1010 Mounting accessories Code number
Protection screen for PTC g 103N0476 Bolt joint for one comp. Ø: 16 mm 118-1917
Bolt joint in quantities Ø: 16 mm 118-1918
Snap-on in quantities Ø: 16 mm 118-1919
oss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
vided that such alterations can be made without subsequential changes being necessary eady agreed.
tive companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
2 |© Danfoss | DCS (CC) | 2017.02 DEHC.ED.200.B7.02
ASHRAE