Installation and Instruction
PLRCA.PI.BX0.D1.01 / 520H3018
取 扱 説 明 書
Checked by drawn by date Name Catalog Number Drawing Number
NEV-L202DXF
NOV.2005
SSSSoooolllleeeennnnooooiiiidddd VVVVaaaallllvvvveeee
FFFFoooorrrr RRRReeeeffffrrrriiiiggggeeeerrrraaaannnntttt
VPV-L202D
NEV-202DXF
VPV-202DQ50
A-EV-33008
AAAA.... FFFFaaaaiiiilllluuuurrrreeee ttttoooo rrrreeeeaaaadddd aaaannnndddd ffffoooolllllllloooowwww aaaallllllll iiiinnnnssssttttrrrruuuuccccttttiiiioooonnnn ccccaaaarrrreeeeffffuuuullllllllyyyy bbbbeeeeffffoooorrrreeee iiiinnnnssssttttaaaalllllllliiiinnnngggg oooorrrr
ooooppppeeeerrrraaaattttiiiinnnngggg tttthhhhiiiissss ssssoooolllleeeennnnooooiiiidddd vvvvaaaallllvvvveeee ccccoooouuuulllldddd ccccaaaauuuusssseeee ppppeeeerrrrssssoooonnnnaaaallll iiiinnnnjjjjuuuurrrryyyy aaaannnndddd////oooorrrr pppprrrrooooppppeeeerrrrttttyyyy
ddddaaaammmmaaaaggggeeee.... SSSSaaaavvvveeee tttthhhheeeesssseeee iiiinnnnssssttttrrrruuuuccccttttiiiioooonnnnssss ffffoooorrrr ffffuuuuttttuuuurrrreeee uuuusssseeee....
BBBB NNNNOOOOTTTTEEEE FFFFOOOORRRR SSSSAAAAFFFFEEEETTTTYYYY
WWWWaaaarrrrnnnniiiinnnngggg
When removing the solenoid coil from the valve body, be sure to cut out the power supply as the coil
may burn.
Do not apply the different voltage from the voltage marked on the coil label.
It may cause burning or failure.
While power is on, do not touch the housing cover as personal injury may be caused.
(Coil heats up to 90℃)
Do not apply excessive force and/or any impact to the coil as it may cause valve failure, burn-out
and leakage trouble due to deformation.
Do not heat up the solenoid coil as the coil might be burn-out.
Do not put any inflammable thing around the coil as it could catch fire due to the coil heat.
CCCC SSSSPPPPEEEECCCCIIIIFFFFIIIICCCCAAAATTTTIIIIOOOONNNNSSSS
Min Bursting Press. 4.95 MPa {50.5/}(※1)
Max Working Press. 3.3 MPa {33.7/}(※1)
Min Operating Press Diff. 0 MPa {0 /}(※1,※2,※3)
Ambient Humidity 95%RH or less Coil insulation Class B molded
Fluid Fluorinated Refrigerant (Please contact Saginomiya when other kind of refrigerant is used.)
Fluid Temp. -30 to +120℃ Ambient Temp. -30 to +50℃
As explained in NOTE For SAFETY, coil may burn out at an abnormal condition. Use a suitable fuse.
To keep temperature of coil less than 130℃ taking ambient temperature,fluid temperature and exoergic of coil into
consideration.
Install coil place where do not splash with rain and drop water from condenser piping.
Do not use coil under the freezing condition.
Operating voltage may rise when internal part of the body is filled with "Liquid refrigerant" or in case there is
too much "Oil". Please confirm before using product.
We manuracture the product based on the specifications described in this drawing.Please check the safety and validity
in the product design in consideration that the product is conformed to the system or not when using.
EEEE FFFFEEEEAAAATTTTUUUURRRREEEE AAAANNNNDDDD AAAAPPPPPPPPLLLLIIIICCCCAAAATTTTIIIIOOOONNNN
These are a Solenoid Valves for Refrigerant circuit in various Refrigeration and Air conditioning equipment and
conforms to Refrigeration Safety Regulations.
NEV-L202DXF and VPV-L202D are small solenoid valves of the normally opened and the direct operated type.
NEV-202DXF and VPV-202DQ50 are small solenoid valves of the normally closed and the direct operated type.
These are the best for flow control of the fluorocarbon based refrigerant.
FFFF VVVVAAAALLLLVVVVEEEE SSSSEEEELLLLEEEECCCCTTTTIIIIOOOONNNN
Selecting most suitable valve for the equipment is important for better control.
Refer to the above mentioned brief specifications of this Solenoid Valve.
As for the following specification,there is a case different from indication of a product.
Airtight Pressure 3.3 MPa {33.7/}(※1)
6.23 MPa {63.5/}(※2,※3)
4.15 MPa {42.3/}(※2,※3)
※1・・・NEV-L202DXF,NEV-202DXF
※2・・・VPV-L202D
※3・・・VPV-202DQ50
Max Operating Press Diff. 2.06 MPa {21/} (※1,※2)
※ The above figure represents pressure at
4.15 MPa {42.3/}(※2,※3)
Note : SI unit {Metric unit}
2.8 MPa {28.6/}(※3)
Rated Voltage.
GGGG IIIINNNNSSSSTTTTAAAALLLLLLLLAAAATTTTIIIIOOOONNNN
<Before Installation>
Make sure that the supply voltage conforms to the voltage maked on the label.It may cause burning(or fuming)
of coil ,or malfunction if incorrect voltage is supplied.
Do not carry the valve with holding the lead wire only as it may cause coil burn-out.
Be careful to scratch flared part and or brazing point as it might cause leakage trouble.
Remove any foreign material or dust in the pipe as it may cause failure of the solenoid valve.
Mounting position should be in the following range.
・Keep enough space above the coil to allow service and maintenance.
゚
5
1
Valve Body
Grounding is required at a suitable position on the unit.
<Installation>
Ch eck the dir ectio n o f t he flu id w hen insta ll it. In sta ll i t a s s how n i n t he fig ure below s o t ha t
th e d ire ction of the a rr ow may bec ome the sam e.
Mounting of the Valve Body and Piping connection should be tightly fixed.
After connecting the Pipes, make air tight test.
Do not install a check valve at the inlet side as it may cause liquid sealing condition on the pipe inside and may
cause damage due to excessive pressure.
Be sure to cool the body while soldering the tubes in order to keep the body temp under 200℃.Soldering must be
carried out with the coil removed.It may cause valve leakage or malfunction.
Prior to solder the tubes,fill inside the valve with inactive gas(such as nitrogen or carbonic dioxide) in order to
avoid the generation of oxidescales.It may cause valve leakage or malfunction.
Be careful that water dose not enter into the pipe.
(Freeze up and Corrosion may cause to malfunction.)
Special attention is required not to apply excessive force of compression, tension or torsion against the
valve body as it may cause malfunction.
In case of removing or changing the direction of the coil,tighten the fixing screw(M4×7) at 1.47~1.96N・m
(15~20kgf・cm).If the screw is not tighten firmly,it may cause to be any noise or vibration.
<Operation>
Before removing the solenoid coil from the valve body, be sure to cut the power supply. If energizing the coil
itself while it is not assembled into the valve body, the coil may cause burn-out.
1
5
゚
Coil
IN
(NEV-202DXF,VPV-202DQ50)
MIN 50 mm
(NEV-L202DXF,VPV-L202D)
IN
2
HHHH MMMMAAAAIIIINNNNTTTTEEEENNNNAAAANNNNCCCCEEEE////IIIINNNNSSSSPPPPEEEECCCCTTTTIIIIOOOONNNN
In case of disassembling or inspection, please contact Saginomiya.
Before making a maintenance or inspection for the valve, be sure to cut the power supply.
IIII OOOOPPPPEEEERRRRAAAATTTTIIIIOOOONNNN CCCCHHHHEEEECCCCKKKK
Install the Product correctly and then check its operation to confirm collect function of the whole system.
JJJJ LLLLIIIIMMMMIIIITTTT OOOONNNN AAAAPPPPPPPPLLLLIIIICCCCAAAATTTTIIIIOOOONNNN
The product is not designed and manufactured for such equipment or system that is intended to be used
under such circumstances as to relate to human life. For application requieing specially high reliability,
please contact Company first.
KKKK SSSSCCCCOOOOPPPPEEEE OOOOFFFF WWWWAAAARRRRRRRRAAAANNNNTTTTYYYY
Unless otherwise agreed by the parties, warranty period of the Product shall be one year after delivery.
In case of failure attributable to the Company within such period, the Product shall be repaired or repaired or
replaced, provided that any one of followings are out of the warranty :
1.Improper handling or application by user
2.Modification or repair by other than the Company
3.Any failure to be caused by acts of God, fire, storm or the like, war,riot or the like and other causes beyond
the control of the parties concerned.
Warranty described in this paragraph means the warranty for the Product itself and does not include warranty for