Multi Ejector solution incl. Multi Ejector Low
Pressure (LP 935/1435/1935) and AK-PC 782A
Application Guide | Low pressure lift ejector system
Contents1. General description ..........................................................................................................................................................3
1.1 System design with Low Pressure lift ejector ..............................................................................................3
1.2 Example system load ...........................................................................................................................................4
2.1 Select plant type ....................................................................................................................................................5
2.2 Suction group MT (Capacity control) .............................................................................................................6
2.3 HP control .................................................................................................................................................................7
2.4 Condenser fan control .........................................................................................................................................7
2.5 Receiver control .....................................................................................................................................................8
3. What is an ejector, and how does it work? ..........................................................................................................10
3.1 Danfoss Multi Ejector design ..........................................................................................................................10
3.2 Multi Ejector Capacity Control ....................................................................................................................... 11
3.3 How does the Multi Ejector solution work? .............................................................................................. 11
Application Guide | Low pressure lift ejector system
1. General description
1.1 System design with Low
Pressure lift ejector
Low pressure lift ejector systems are simpler
systems than high-pressure ejector systems,
because they do not need the parallel
compressor in order to work and give an energy
saving (see diagram on next page). In winter
time, the system works like a normal booster
system where the gas bypass valve controls the
receiver pressure with set pressure differential,
and the evaporation pressure is controlled by
adjusting the compressor capacity according to
the needed MT evaporators’ suction pressure.
The LP ejector can be considered as an add-on
to the standard system, however there are some
additional components, and a different control
strategy needs to be applied.
Below are the most important points to take
into account when designing such a system (see
diagrams on page 4):
Setpoints and operational modes
As described, an LP ejector system can operate
with two different modes: the standard mode in
low ambient temperatures and the ejector mode
in high temperatures. How it changes from one
mode to the other and the setpoint and signals
required for this are listed below:
• In the winter condition, the ejector is working
as a high-pressure valve and is not providing
any or not enough suction mass flow to put
the system into ejector operation. The system
is performing as a standard system, but with
receiver pressure controlled with a pressure
differential of 3 bar between the pressure
in the receiver (P-rec) and the common MT
evaporators’ suction line. The pressure signal
is coming from the sensor located before the
check valve (Po-MT). The pressure in the gas
cooler is controlled based on the refrigerant
outlet temperature (Sgc) and the optimum COP
algorithm.
• Ambient temperatures of 17 – 18 °C result in
24 – 25 °C out of the gas cooler measured by
the temperature sensor Sgc, corresponding
to gas cooler pressure 64 to 66 bar(a). At
ambient temperatures of 17 – 18 °C there is
enough expansion work in the system for the
LP ejector to take all the mass flow from the
MT evaporators and lift it to the receiver. Since
the gas bypass valve is controlled on the basis
of pressure difference between the receiver
and MT evaporator pressure, and not fixed
pressure, the valve will start to open more and
more. Setpoint for the valve would typically be
3 bar difference and if the ejector can provide
a higher lift, the gas bypass valve will be 100%
open.
Components
The system requires some additional
components. Additionally the design criteria for
some components are different:
• Gas Bypass Valves: It will be challenging
to have one valve fulfilling good control in
both Standard and Ejector mode. In the first
mode there is limited amount of gas released
to suction MT compressors with a constant
pressure difference of 3 bar, while in the second
At 23 – 25 °C out of the gas cooler, the ejector
starts to pump all gas from the MT evaporators
and lift to the receiver with a pressure lift of
approximately 3 bar. The consequence of this is
a better COP of the system. The higher suction
pressure will also result in higher mass flow in the
same compressor and thereby a first cost saving
due to a smaller installed capacity. The first cost
saving can be as much as 30% at high ambient
temperatures and 15% energy saving compared
to a booster system.
one (LP ejector mode) there is a large amount
of gas with a minimum possible pressure
drop; our solution is with 2 x Gas Bypass Valves
(GBV). GBV #1 is a standard one and works in
all conditions, and GBV #2 mounted in parallel
with big KV value operating when the system
turns into LP Ejector mode. The idea is to have
as little as possible pressure drop across the two
GBVs, as this pressure drop will count as loss to
the LP ejector’s recovered work.
• Another option is to use a 2-way ball valve
motor mounted in parallel to GBV #1 which
can give even better system performance as
the pressure drop in the gas bypass line will be
minimal.
• Pressure sensors: The reference sensor for
controlling MT compressors should be mounted
on the common MT evaporators’ suction line
“Po_MT”, before the check valve. In systems
with MT and LT evaporators it can happen
that the MT evaporator load drops below the
minimum MT compressor capacity which will
lead to pump down situation and possible
turning off of the MT compressors. On the other
hand, LT evaporators can have a load and LT
compressors will run. To protect LT compressors’
from high pressure cut-out, a new Psuc_MT
sensor is introduced. If the pressure exceeds
the set offset pressure, the Psuc_MT will
become reference sensor for controlling the MT
compressors.
• Electronic Expansion Valves and evaporators:
The LP ejector pressure lift is relatively low.
Therefore, the system needs to be designed
accordingly, and the EEV (Electronic Expansion
Valve) for MT evaporators should be selected
according to the system requirements and
limitation. The pressure losses in evaporator
and distributors should be investigated and
designed to be a portion of the minimum
pressure lift that the ejector can provide (3
bar). Larger evaporators and distributors
may provide too high pressure loss for the LP
system. If the losses in the evaporator are high,
then it should be ensured that the system
will operate with high pressure in the gas
cooler to provide adequate pressure lift. That
can either occur when there is high ambient
temperature or when Heat Recovery is activated
in the system. The pressure losses should be
considered in the selection of the EEV
• Compressors: Compressor selection is made
using the receiver pressure at the highest
ambient temperature (design condition). This is
Application Guide | Low pressure lift ejector system
1.2 Example system load
typically 6 – 7.5 bar higher than the evaporation
pressure and will yield smaller compressors
typically 20 – 30%, resulting in reduction of the
first cost of the system. The small compressor
steps in the system can be useful in the part
load situation during the cold periods.
Oil management
In booster/winter mode, the system has a safe
oil return, but when the system is in Ejector
mode, the oil will end in the receiver and will
stay there if no action is taken on it. There are
many ways to recover the oil and get it back to
the compressor. If the oil separator has a low
efficiency, the oil problem will be bigger. Part of a
safe oil return can be the LT compressors. The LT
compressors receive an oil-rich gas mixture from
the LT evaporators. The oil is passed through the
LT compressors and can be transferred to the MT
compressors as LT discharge is connected directly
to the MT compressor suction. However, as the LT
evaporators’ load varies during the year, sufficient
oil return cannot be expected. That depends on
the load ratio between the MT and LT compressor
capacity, the oil quantity in the system and the
efficiency of the oil separator.
To be certain, an oil recovery system is needed.
By using the second pressure differential
reference “DeltaP High” and a low oil level sensor
mounted on the oil receiver, the system can
be changed from LP Ejector mode to Standard
mode. This ensures that oil will return to the MT
compressors.
Danfoss
80.0
Pressure in receiver controlled by pressure differential.
Pressure in receiver result of LP ejector lift > 3 bar
Application Guide | Low pressure lift ejector system
1.3 Overall control strategy
and objectives
2. Configuration PC782A
The overall control objective is to maintain a
sufficiently low pressure difference between
the receiver pressure (Prec) and the evaporation
pressure (Po-MT) in order for the LP-ejector to lift
the total refrigerant flow from the refrigerated
cabinets up the receiver pressure level. The
designated MT-compressor will in this case
compress the gas (vapor) refrigerant directly from
the receiver. The pressure difference between
the sensors Prec and Po-MT, should however be
large enough for the injection valves to supply
the required refrigerant flow to the refrigerated
cabinets. If the motive energy for the ejector is
not big enough to perform the required pressure
lift, the check valve will open and the MT
In the PC782A, the LP-system is not considered as
a dedicated “Plant type” but rather a special case
of a booster system (without IT compressor). This
means that in order to support the LP-ejector
system, a number of configurations need to be
made in respectively: ”Select Plant Type”, “Suction
Group MT”, “HP-control”, “Receiver control” and
“I/O configuration”.
compressor will take the refrigerant flow directly
from the refrigerated cabinets (instead of the
ejector).
Note that in LP ejector mode, the check valve
restricts the flow direction from the compressor
suction port (Psuc-MT) towards the MT
evaporator outlet (Po-MT). This means that if the
suction pressure (Psuc-MT) increases, it cannot
be detected in the Po-MT measurement. It is
therefore important to device a control strategy
that keeps Psuc_MT in control as well.
In the section below the control strategy and
configuration of the PC782A to support the LPejector application will be described.
The LP-ejector system is considered a Booster/
One pack system without any IT compressors,
therefore it is only possible to configure the Delta
P control of the receiver from these plant type
selections: "One Pack + HP" and "Booster + HP".
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.