Danfoss VLT 6000 HVAC, VLT 8000 AQUA, LonWorks Option Card Instruction Manual

Drives Solutions
www.danfoss.com/drives
Instruction manual
Lonworks FTP
VLT® 5000 / 6000 HVAC / 8000 AQUAVLT
LonWorks® FTP Option Card
Instruction Manual
2
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
DANGER
!
Rotating shafts and electrical equipment can be hazardous. Therefore, it is strongly recommended that all electrical work conform to the National Electrical Code (NEC) and all local regulations. Installation, start-up and maintenance should be performed only by qualified personnel.
Factory recommended procedures, included in this manual, should be followed. Always disconnect electrical power before working on the unit.
Although shaft couplings or belt drives are generally not furnished by the manufacturer, rotating shafts, couplings and belts must be protected with securely mounted metal guards that are of sufficient thickness to provide protection against flying particles such as keys, bolts and coupling parts. Even when the motor is stopped, it should be considered “alive” as long as its controller is energized. Automatic circuits may start the motor at any time. Keep hands away from the output shaft until the motor has completely stopped and power is disconnected from the controller.
Motor control equipment and electronic controls are connected to hazardous line voltages. When servicing drives and electronic controls, there will be exposed components at or above line potential. Extreme care should be taken to protect against shock. Stand on an insulating pad and make it a habit to use only one hand when checking components. Always work with another person in case of an emergency. Disconnect power whenever possible to check controls or to perform maintenance. Be sure equipment is properly grounded. Wear safety glasses whenever working on electric control or rotating equipment.
Safety Guidelines
1. The drive must be disconnected from the AC line before any service work is done.
2. The Stop/Off key on the local control panel of the drive
Touching electrical parts may be fatal – even after equipment has been disconnected from AC line. To be sure that capacitors have fully dis­charged, wait 14 minutes after power has been removed before touching any internal component.
DANGER
!
does not disconnect the equipment from the AC line and is not to be used as a safety switch.
3. Correct protective grounding of the equipment must be established. The user must be protected against supply voltage and the motor must be protected against overload in accordance with applicable national and local regulations.
4. Ground currents are higher than 3 mA.
Warnings Against Unintended Start
1. While the drive is connected to the AC line, the motor can be brought to a stop by means of external switch closures, serial bus commands or references. If personal safety considerations make it necessary to ensure that no unintended start occurs, these stops are not sufficient.
2. During programming of parameters, the motor may start. Be certain that no one is in the area of the motor or driven equipment when changing parameters.
3. A motor that has been stopped may start unexpectedly if faults occur in the electronics of the drive, or if an overload, a fault in the supply AC line or a fault in the motor connection or other fault clears.
4. If the Local/Hand key is activated, the motor can only be brought to a stop by means of the “Stop/Off” key or an external safety interlock.
NOTE: It is responsibility of user or person installing drive to provide proper gr ounding and branch circuit protection for incoming power and motor overload according to National Electrical Code (NEC) and local codes.
The Electronic Thermal Relay (ETR) is UL listed. VLTs provide Class 20 motor overload protection in accordance with the NEC in single motor applications, when VLT 6000/8000 parameter 117 (VLT 5000 parameter 128) is set for ETR Trip 1 and parameter 105 is set for rated motor (nameplate) current.
3
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
Table of Contents
Overview
Introduction............................................................................................. 5
About This Manual .................................................................................. 5
Assumptions ........................................................................................... 5
What Y ou Should Already Know ............................................................ 5
References .............................................................................................. 5
LonW orks Overview................................................................................ 6
LON Concept........................................................................................... 6
Applications ............................................................................................ 6
VLT LonWorks Option Card.................................................................... 7
Node Arrangements................................................................................ 7
Message Passing .................................................................................... 7
Collision Detection ................................................................................. 8
Network Management............................................................................. 8
Routers and Bridges............................................................................... 9
Installation
Wiring Installation................................................................................... 10
Card Installation...................................................................................... 1 0
T ools Required........................................................................................ 10
VL T LonWorks Option Car d.......................................................................11
Installation Instructions ......................................................................... 12
Network Initialization of LonW orks Option Card ................................... 19
Resource files .......................................................................................... 19
Free T opology Network Configuration
Free T opology Network Configuration .................................................. 20
Network T ermination Option .................................................................. 21
Terminator and Service Switch Locations ............................................ 21
System Performance .............................................................................. 22
System Specifications ............................................................................ 22
T ransmission Specifications.................................................................. 22
Free T opology Specifications ................................................................. 22
Doubly-terminated Bus Topology Specifications ................................. 22
Diagnostic LEDs
LonW orks Card Diagnostic LEDs ........................................................... 23
Status LED ............................................................................................... 23
Service LED ............................................................................................. 23
Service LED Patterns and Descriptions ................................................. 24
4
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
Interface/Network V ariables
VLT Adjustable Frequency Drive
and LonWorks Netw ork Configuration ................................................... 25
Network Drive Control Input ................................................................... 26
Drive Feedback to Network ..................................................................... 29
Drive Status Bit Definitions..................................................................... 31
Network Timer Functions ....................................................................... 33
VL T P arameter Access ............................................................................ 34
Parameter Access Error Codes............................................................... 35
Parameter Access Command and Response Examples........................ 35
Standard Object Support ........................................................................ 37
Alarm Descriptions.................................................................................. 38
Parameters
Parameter List ......................................................................................... 39
Parameter Description............................................................................. 39
5
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
This manual is intended to be used for both instruction and reference. It only briefly touches on the basics of the LonWorks protocol whenever it is necessary for gaining an understanding of the LonWorks profile for drives and the LonWorks Option Card for the Adjustable frequency drive.
This manual is also intended to serve as a guideline when you specify and optimize your
Introduction
About This Manual
What Y ou Should Already Know
Assumptions
This manual provides comprehensive instructions on the installation and set up of the LonWorks Option Card for the VLT 5000,
VLT 6000 and the VLT 8000 Adjustable
Frequency Drive to communicate over a LonWorks network.
For specific information on installation and operation of the adjustable frequency drive, refer to the VLT 5000 Installation, Operation
and Instruction Manual , VLT 6000 Installation,
Operation and Instruction Manual or VLT8000 Installation, Operation and Instruction Manual.
Portions of this manual are printed with the permission of the Echelon Corporation and the National Electrical Contractors Association of the USA (NECA).
Echelon®, LonTalk®, Neuron® and LonWorks
®
are registered trademarks of the Echelon Corporation. VLT® is a registered trademark of Danfoss Inc.
The Danfoss LonWorks Option Card is designed to communicate with any controller node that supports the interfaces defined in
this document. It is assumed that you have full knowledge of the capabilities and limitations of the controller node.
This manual assumes that you have a controller node that supports the interfaces in this document and that all the requirements stipulated in the controller node, as well as
the Adjustable Frequency Drive, are strictly observed along with all limitations therein.
communication system. Even if you are an experienced LonWorks programmer, we suggest that you read this manual in its entirety before you start programming, since important information can be found in all sections.
References
LonMaker™ for Windows® User's Guide.
VLT® 5000 Installation, Operation and Instruction Manual
(Referred to as the VLT Instruction Manual in this document.)
VLT® 6000 Installation, Operation and Instruction Manual
(Referred to as the VLT Instruction Manual in this document.)
VLT ® 8000 Installation, Operation and Instruction Manual
(Referred to as the VLT Instruction Manual in this document.)
6
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
LON Concept
LonWorks Overview
Applications
LonWorks is both an existing standard and hardware developed by Echelon Corporation. Echelon's stated goal is to establish a com­modity solution to the presently daunting problems of designing and building control networks.
The result is LonMark Interoperability which makes it possible for independent network devices to operate together over a LonWorks network. The LonMark program was developed to address interoperability issues. As a result, the LonMark Interoperability Association Task Groups (LonUsers Groups) were developed. The task groups determine that each device on the network has an object definition, create
The LonWorks communications structure is similar to that of a local area network (LAN) in that messages are continually exchanged between a number of processors. A LonWorks system is a determined local operating network (LON). LON technology offers a means for integrating various distributed systems that perform sensing, monitoring, control, and other automated functions. A LON allows these intelligent devices to communicate with one another through an assortment of communications media using a standard protocol.
LON technology supports distributed, peer­to-peer communications. That is, individual
network devices can communicate directly with one another without need for a central control system. A LON is designed to move sense and control messages which are typically very short and which contain commands and status information that trigger actions. LON performance is viewed in terms of transactions completed per second and response time. Control systems do not need vast amounts of data, but they do demand that the messages they send and receive are absolutely correct. The critical factor in LON technology is the assurance of correct signal transmission and verification.
An important LonWorks benefit is the network’s ability to communicate across different types of transmission media. The NEURON chip is the heart of the LonWorks system. The NEURON chip's commu­nication port allows for the use of transceivers for other media (such as coax and fiber optic) to meet special needs.
LonWorks control devices are called nodes. Physically, each node consists of a NEURON chip and a transceiver. With proper design, the nodes become building blocks that can
be applied to control a variety of tasks, such as lighting or ventilating, integrating a variety of communications media.
The tasks which the nodes perform are determined by how they have been connected and configured. Because hardware design, software design, and network design may be independent in a LonWorks-based system, a node’s function can be programmed to accommodate the networks in which it will be used.
standards and models to be used by particular applications and create a common platform for presenting data. A standard network variable type (SNVT) facilitates interoperability by providing a well defined interface for communication between devices made by different manufacturers. The VLT Adjustable Frequency Drive supports the node object and controller standard object definitions of LonMark Interoperability.
Customers are currently using LonWorks for process control, building automation, motor control, elevator operation, life safety systems, power and HVAC distribution and similar intelligent building applications.
7
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
Message Passing
Node Arrangements
LonWorks nodes can be addressed either individually or in groups. A group can contain up to 64 nodes, and one LonWorks network can support 255 groups. Furthermore, any node can be part of 15 different groups. A subnet, very similar to a group, can contain 127 nodes. A domain is the largest arrangement of nodes with a single domain able to handle 255 subnets. Thus a domain can handle 32,385 separate nodes. A single node may be connected to no more than two domains.
The group structure has the advantage of allowing a number of nodes to be reached at only one address. This method reduces the
record keeping inside each chip to a minimum, allowing faster operation. However, high efficiency individual addressing can be done at all levels of a LonWorks system. The address table of a node contains entries for the group type and size and tells the node how many acknowledgments to expect when it sends a message. It also tells the NEURON chip which domain to use and the node group member number, which identifies an acknowledgment as coming from the node. The address also contains a transmit timer, a repeat timer, a retry counter, a receive timer, and the group ID.
There are a number of trade-offs between network efficiency, response time, security, and reliability. Generally, LonWorks defaults to the greatest degree of safety and verification for all communications over the LON network. The LonTalk protocol, built into the chips, is the operating system that coordinates the LonWorks system. It offers four basic types of message service.
The most reliable service is acknowledged (or end-to-end acknowledged service), where a message is sent to a node or group of nodes and individual acknowledgments are ex­pected from each receiver. If an acknowledgment is not received from all des­tinations, the sender times out and re-tries the transaction. The number of retries and time-out duration are both selectable. Ac-
VLT LonWorks Option Card
The Danfoss VLT LonWorks option card is comprised of a control card with a NEURON chip and a memory card. When installed into the VLT adjustable frequency drive, the unit enables the drive to communicate with other devices on the LON. The VLT drive is designed to provide precision control of standard induction electrical motors. The drive receives three reference signals along with start/stop and reset commands from the network. The drive also receives a 16-bit control word that provides full operational control of the drive. (See Network Drive Control Input for additional details.)
In response, the drive provides 16 output network variables containing important drive and motor data. (See Drive Feedback to Network.) Output to the network includes drive status, current, voltage, motor and inverter thermal status, and alarms and warnings.
LonWorks supports many different types of transmission media. A LonWorks network physical layer option can be transformer coupled twisted pair (78 kbps and 1.25 Mbps), free topology, link power, power line, RF, RS-485, fiber optic, coaxial, or infrared.
The VLT LonWorks option supports four transmission media with three versions of the VLT LonWorks option card. The VLT LonWorks option card versions are:
1. Free topology, which also operates on a link power network.
2. 78 kbps transformer coupled twisted pair.
3. 1.25 Mbps transformer coupled twisted pair.
A router is required to interface to a LonWorks network when not supported by one of the three option card versions.
8
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
Collision Detection
Network Management
Depending on the level of a given application, a LonWorks network may or may not require the use of a network management node. A network management node performs management functions, such as:
Find unconfigured nodes and download their network addresses.
Stop, start, and reset node applications.
Access node communication statistics.
Configure routers and bridges.
Download new applications programs.
Extract the topology of a running
network.
The LonTalk protocol uses a unique collision avoidance algorithm which allows an overloaded channel to carry near to its maximum capacity, rather than reducing its throughput due to excessive collisions between messages. When using a communications medium that supports collision detection, such as twisted pair, the LonTalk protocol can optionally cancel transmission of a packet as soon as a collision is detected by the transceiver. This option
allows the node to immediately retransmit any packet that has been damaged by a collision. Without collision detection, the node would wait the duration of the retry time to notice that no acknowledgment was received. At that time it would retransmit the packet, assuming acknowledge or request/response service. For unacknowledged service, an undetected collision means that the packet is not received and no retry is attempted.
knowledgments are generated by the network host processor without intervention of the ap­plication. Transaction IDs are used to keep track of messages and acknowledgments so that the application does not receive dupli­cate messages.
An equally reliable service is request/response, where a message is sent to a node or group of nodes and individual responses are ex­pected from each receiver. Incoming messages are processed by the application on the receiving side before a response is generated. The same retry and time-out op­tions are available as with acknowledged service. Responses may include data, so that this service is particularly suitable for remote procedure call or client/server applications.
Next in reliability is unacknowledged repeated. Messages are sent multiple times to a node or a group of nodes with no response expected. This service is typically used when broadcasting to large groups of nodes when traffic generated by all the responses would overload the network.
The final method in reliability is unac- knowledged, where a message is sent once to a node or group of nodes and no response is expected. This option is typically used when the highest performance is required, network bandwidth is limited, and the application is not sensitive to the loss of a message.
Message Passing (continued)
9
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
Routers and Bridges
A router (or bridge) is a special node that consists of two connected NEURON chips, each connected to a separate channel (see figure below). Routers and bridges pass packets back and forth between these channels. There are four types of routers. A repeater is the simplest form of router, simply forwarding all packets between the two channels. A bridge simply forwards all packets which match its domains between the two channels. Using a bridge or repeater, a subnet can exist across multiple channels. A learning router monitors the network traffic and learns the network topology at the domain/subnet level. The learning router then uses its knowledge to selectively route packets between channels. Like a learning router, a configured router selectively routes packets between channels by consulting internal routing tables. Unlike a learning router, the contents of the internal routing tables are specified using network management commands.
Initially, each router sets its internal routing tables to indicate that all subnets could lie on either side of the router. Suppose that node 6, in the figure below, generates a message bound for node 2. Learning router 1 initially picks up the message. It examines the source subnet field of the message and notes in its internal routing tables
Learning Routers
Source: Echelon Corp.
that subnet 2 lies below it. The router then compares the source and destination subnet IDs and, since they are different, the message is passed on. Meanwhile, learning router 2 also passes the message on, making an appropriate notation in its internal routing tables regarding the location of subnet 2.
Suppose now that node 2 generates an acknowledgment. This acknowledgment is picked up by learning router 1, which now notes the location of subnet 1. Learning router 1 examines its internal routing tables, and, noting that subnet 2 lies below, passes the message on. When the message appears on subnet 2, it is noted by both node 6 (the destination) and learning router 2. Learning router 2 does not pass it on but merely notes that subnet 1, like subnet 2, lies somewhere above. Learning router 2 will not learn of the existence or location of subnet 3 until a message is originated from there. Subnets cannot cross routers. While bridges and repeaters allow subnets to span multiple channels, the two sides of a router must belong to separate subnets. Since routers are selective about the packets they forward to each channel, the total capacity of a system can be increased in terms of nodes and connections.
9 10 11 12
1 2 3 4
5 6 7 8
R
R
Channel
Channel
Channel
Subnet 1
Subnet 3
Subnet 2
Learning Router 1
Learning Router 2
10
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
Wiring Installation
VLT adjustable frequency drive contains dangerous voltages when connected to line power. After disconnecting from line, wait at least 14 minutes before touching any electrical com­ponents.
Only a competent electrician should carry out electrical installation. Improper installation of motor or VLT can cause equipment failure, serious injury or death. Follow this manual, National Electrical Code (USA) and local safety codes.
WARNING
!
CAUTION
!
CAUTION
!
Electronic components of VLT adjustable frequency drives are sensitive to electrostatic dis­charge (ESD). ESD can reduce performance or destroy sensitive electronic components. Follow proper ESD procedures during installation or servicing to prevent damage.
It is responsibility of user or installer of VLT adjustable frequency drive to provide proper grounding and motor overload and branch protection according to National Electrical Code (USA) and local codes.
DANGER
!
WW
WW
W
iringiring
iringiring
iring The adjustable frequency drive generates a carrier frequency with a pulse frequency between 3 kHz and 14 kHz. This results in radiated frequency noise from the motor cables. It is very important that the LonWorks cable be isolated as much as possible from the drive output cabling to the motor. Use shielded wire rather than twisted-pair. Do not run LonWorks cabling and motor cables in parallel or in close proximity to one another. Ensure that the drive is properly grounded.
The following section describes the installation procedures for the LonWorks option card (see following illustration). For additional information on installation and operation of the VLT adjustable frequency drive, refer to the VLT Instruction Manual.
Card Installation
Tools Required
Flat-head screw driver Torx T-10 screw driver Torx T-20 screw driver
11
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
VLT LonWorks Option Card
(Free T opology Model)
LEDs
Terminal Connector
Service Pin Switch SW1
Mounting Hole
LEDs
Terminal Connector
Service Pin Switch SW3
Terminator Switch
Ribbon Cable Socket (to Memory Board)
Ribbon Cable Socket (to Control Board)
Memory Board
Ribbon Cable Socket (to drive control board)
LonWorks Control Board
Host Chip
Drive Memory
12
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
Installation Instructions
1. Access to Control Card Cassette
Remove control wiring by unplugging connector terminals (A).
Remove grounding clamps (B) by removing two screws holding each in place. Save screws for reassembly.
Loosen two captive screws (C) securing cassette to chassis.
2. Disconnect Control Card Cassette
IP20/NEMA 1 and Bookstyle
Remove Local Control Panel (LCP) by pulling out from top of display (A) by hand. LCP connector on panel back will disconnect.
Remove protective cover by gently prying with a screw driver at notch (B) and lift cover out of guide pin fittings.
IP54/NEMA 12
Open front panel of drive by loosening captive screws and swing open.
Disconnect Local Control Panel (LCP) cable from drive control card.
(A)
(B)
(A)
(B)
(C)
13
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
Lift control card cassette from bottom.
Unplug two ribbon cables (A) and (B)
from control board.
Unhinge cassette at top to remove.
3. Remove Cassette and Ribbon Cables
NOTE Ribbon cables will need to be reconnected to same connec­tions from which removed.
4. Chassis Ground Connections
Location of holes to mount grounding strips can vary with drive configuration. When applicable, remove mounting screws and washers located in chassis using Torx T-20 screw driver and save for reassembly. Otherwise, grounding strips attach with screws and washers provided, as shown in step 5.
NOTE Ground strips are used on 208 V drives of 22 kW (30 HP) or less and on 460 V drives of 45 kW (60 HP) or less. For all other drives, go to step 6.
(A)
(B)
14
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
Align ground strips over screw holes. Strip with fewest contact points mounts on cable side of chassis. Tabs on grounding strips point toward outside of chassis.
Replace screws removed in step 4 and add additional screws and washers provided, as necessary. Tighten to
0.9 Nm (8 in-lbs) using Torx T-20 screw driver.
5. Install Chassis Ground Connections
Ground Strips
Attach ribbon cables between LonWorks control card and memory card.
Be sure exposed wire portion of ribbon cable (A) is facing front of socket (B). Do not remove blue insulation covering end of ribbon cable.
Pull up collar (C) of ribbon cable socket, insert cable and push collar closed.
Repeat procedure for all ribbon cables.
IP20/NEMA 1 and IP54/NEMA 12
Remove terminal connector from terminal block (D) and connect to terminal block (E) at this time for ease of access.
6. Install Ribbon Cables between Option Cards
(D)
(E)
15
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
Insert edge of LonWorks cards into slot in side of cassette and align screw holes.
9. Insert LonWorks Card
Route ribbon cables from LonWorks memory card through slot at side of control board cassette.
8. Ribbon Cable Routing
7. Remove LCP Cradle
IP20/NEMA 1 and Bookstyle
Carefully push in tabs at corners of LCP cradle to release clips. Pull out to disengage clips and lift cradle free.
16
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
11. Install Ribbon Cable on VLT Control Board
Be sure not to twist or crimp ribbon cables.
Insert cables into corresponding sockets and fasten in accordance with directions in step 5.
IP20/NEMA 1 and Bookstyle
Insert cradle clips into holes in cassette.
Push down on cradle to snap it into
place.
12. Install LCP Cradle
Secure LonWorks card with 3 self-tapping screws and washers provided using Torx T-10 screw driver. Tighten to 8 in-lbs (0.9 Nm).
10. Secure LonWorks Card
17
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
Connect ribbon cables.
Connect control card cassette to hinge
at top of drive and fit into chassis.
14. Install Ribbon Cables
NOTE Ribbon cables must be recon­nected to same connections from which removed.
IP20/NEMA 1 and IP54/NEMA 12
Spring tension clip (A) is used as a cable strain relief and ground point for shielded cable.
Insert clip through inner wall of chassis at slot provided.
Compress spring into clip at outer wall of chassis.
13. Install Spring Tension Clip
(A)
18
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
15. Install Control Card Cassette
16. Plug in Terminal Connector
NOTE Shielded cable is recommended. Ground shielded cable at spring tension clip location or ground at cable clamp by removing cable insulation at contact point. Do not use connector terminal 61.
Fasten control card cassette by alternately tightening two captive screws (A). Tighten to 0.9 Nm (8 in-lbs).
Route control wires through clamp fasteners (B) and secure clamps with two screws.
Connect control terminals (C) by firmly pressing them into connector receptacles.
(A)
(B)
(C)
Connect signal wire NET A to terminal 79 and NET B to 80 of terminal connector. (In free topology model, connections can be reversed.)
IP20/NEMA 1 and IP54/NEMA 12
Plug network connector into terminal block at side of control card cassette.
Insert LonWorks cable between inner wall of chassis and spring tension clip.
Bookstyle
Remove knockout from top of drive (A).
Route control wires through clamp
fasteners (B) on cable plate and secure clamps with screws. Tighten to 0.9 Nm (8 in-lbs).
Secure cable plate to drive with screws and screw holes provided. Tighten to
0.9 Nm (8 in-lbs).
Plug network connector (C) into terminal block at top of control card cassette.
(A)
(B)
(C)
Shield 61
NET B 80
NET A 79
79
80
61
19
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
Network Initialization of LonW orks Option Card
Resource files
A LonMark interface file (.XIF extension) provides the host processor with device information. With this, it is possible to design a LonWorks network without the adjustable frequency drive being physically present.
The resource files (VLTLON.XIF and DanfossVSD_03.*) can be downloaded from the Internet site www.danfoss.com/drives.
Echelon Corporation has also developed a set of free plug-ins available through their web site at www.echelon.com/plugin/default.htm. Also intended for network design, these plug-ins provide easy access to screens which simplify the process of manually setting up the drive, testing, and monitoring operation.
The LonWorks option card contains a NEURON chip with a unique address. After hardware installation, initialize the LonWorks option card. Addressing nodes on the LonWorks network is performed at installation time by an installation tool or network management tool. Addressing requires the retrieval of a node’s NEURON ID. The NEURON ID is a 48 bit number that identifies every manufactured NEURON chip. There are several methods by which the network software will initialize the drive automatically. The network can recognize the drive without action beyond proper installation. The card is then ready to be programmed for network operation. The VLT LonWorks option supports three additional methods of addressing a node:
1. Service Pin - There are two momentary-contact service switches that send the NEURON ID over the network. If the network software prompts the action, press
either service pin (SW1 or SW3) to transmit the NEURON ID over the network. The service pin locations are shown in the illustration in Terminator and Service Switch Locations in this manual.
2. Query and Wink - The LonWorks option card is shipped with a domain of “0” and subnet of 1. Upon receiving the wink command, the on-board green status LED flashes so that the installer can locate the node. The chip sends out its Neuron ID over the network in response to the query command.
3. NEURON ID Label - The VLT LonWorks option card has a NEURON ID label that displays the NEURON ID as a 12 digit hexadecimal number. The installer can manually enter the NEURON ID during installation.
The drive may also be added to the network upon initialization.
The VLT LonWorks network interface consists of SNVTs and SCPT. The SNVTs support the LonMark Controller Profile along with VLT configuration, control and moni­toring capabilities. Any combination of SNVTs can be used to operate the VLT.
We also support the Functional Profile for Variable Speed Drives version 1.1 from the LonMark organisation.This profile defines a set of Network variables (SNVT) and configuration properties (SCPT).
20
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
Free Topology Network Configuration
The Free Topology Transceiver (FTT) system is designed to support free topology wiring and accommodates bus, star, loop or any combination of these topologies. The FTT transceiver located on the VLT LonWorks
option card provides I/O functions. Flexible wiring capability simplifies system installation and makes it easy to add nodes for system expansion. The figures below represent five network topologies.
TERMINATION
TERMINATION
TERMINATION
TERMINATION
TERMINATION
TERMINATION
Singly Terminated Bus Loop
Doubly Terminated Bus Loop
Star Topology
Mixed Topology
Loop Topology
Loop Topology
Mixed Topology
21
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
Network Termination Option
Terminator and Service Switch Locations
The option of using termination on the LonWorks card is provided. The option card has a termination resistor built-in which is activated by the terminator switches. Use of the terminator is optional, depending upon the
network configuration. If termination is provided elsewhere in the network, the termination function should be OFF. Terminator switches position functions are provided in the table below.
Switch P osition Functions
TT
TT
T
erminationermination
erminationermination
ermination
Pos 1Pos 1
Pos 1Pos 1
Pos 1
Pos 2Pos 2
Pos 2Pos 2
Pos 2
No termination Net Term OFF Net Term OFF
(Factory setting) (Factory setting) Single termination Net Term ON Net Term OFF Double termination Net Term ON Net Term ON
TT
TT
T
erminator Switcheserminator Switches
erminator Switcheserminator Switches
erminator Switches
Service Pin SwitchService Pin Switch
Service Pin SwitchService Pin Switch
Service Pin Switch
Service Pin SwitchService Pin Switch
Service Pin SwitchService Pin Switch
Service Pin Switch
OFF
1
2
Free T opology LonWorks Control Card
22
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
System Performance
Up to 64 FTT-10 transceivers, or 128 LPT-10 transceivers, are allowed per network segment.
Both types of transceivers may be used on a given segment, provided that the following constraint is met:
(2 x number of FTT-10 transceivers) +
(number of LPT-10 transceivers) 128.
System Specifications
Free topology system specifications and transmission specifications are described below. Both specifications should be met to ensure proper operation.
The transmission specification depends on such factors as resistance, mutual capacitance and the velocity of propagation.
The system designer may choose from a variety of cables, depending on cost, availability, and desired performance. Performance may vary with cable type. Contact Echelon for cable types and the characterization of system performance.
Note that the following specifications arNote that the following specifications ar
Note that the following specifications arNote that the following specifications ar
Note that the following specifications ar
e for onee for one
e for onee for one
e for one
network segment. Multiple segments may benetwork segment. Multiple segments may be
network segment. Multiple segments may benetwork segment. Multiple segments may be
network segment. Multiple segments may be combined using rcombined using r
combined using rcombined using r
combined using r
epeaters to increpeaters to incr
epeaters to increpeaters to incr
epeaters to incr
ease theease the
ease theease the
ease the
number of nodes and distance.number of nodes and distance.
number of nodes and distance.number of nodes and distance.
number of nodes and distance.
T ransmission Specifications
Free Topology nodes run at 78 kbps transmission speeds.
Doubly­Terminated Bus Topology Specifications
Free Topology Specifications
The average temperature of the wire must not exceed 55° C (131° F), although individual segments of wire may be as hot as 85° C (185° F).
Danfoss recommends the use of shielded LonWorks communication cable for instance Belden 8719. See also section 12 Plug in terminal Connector.
Cable Specifications
Maximum bus length forMaximum bus length for
Maximum bus length forMaximum bus length for
Maximum bus length for
Maximum bus length forMaximum bus length for
Maximum bus length forMaximum bus length for
Maximum bus length for
segments withsegments with
segments withsegments with
segments with
segments with both FTTsegments with both FTT
segments with both FTTsegments with both FTT
segments with both FTT
-10-10
-10-10
-10
FTTFTT
FTTFTT
FTT
-10 transceivers only-10 transceivers only
-10 transceivers only-10 transceivers only
-10 transceivers only
and LPTand LPT
and LPTand LPT
and LPT
-10 transceivers-10 transceivers
-10 transceivers-10 transceivers
-10 transceivers
Belden 85102 2700 m / 8858 ft 2200 m / 7217 ft Belden 8471 2700 m/ 8858 ft 2200 m / 7217 ft Level IV, 22AWG 1400 m / 4593 ft 1150 m / 3772 ft JY (St) Y 2x2x0.8 900 m / 2952 ft 750 m / 2460 ft
MaximumMaximum
MaximumMaximum
Maximum
MaximumMaximum
MaximumMaximum
Maximum
node-to-node distancenode-to-node distance
node-to-node distancenode-to-node distance
node-to-node distance
total wirtotal wir
total wirtotal wir
total wir
e lengthe length
e lengthe length
e length
Belden 85102 500 m / 1640 ft 500 m / 1640 ft Belden 8471 400 m / 1312 ft 500 m / 1640 ft Level IV, 22AWG 400 m / 1312 ft 500 m / 1640 ft JY (St) Y 2x2x0.8 320 m / 1050 ft 500 m / 1640 ft
23
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
The Status LED patterThe Status LED patter
The Status LED patterThe Status LED patter
The Status LED patter
ns arns ar
ns arns ar
ns ar
e:e:
e:e:
e:
ONON
ONON
ON
There is power on the board but there has not been any communication to an input network variable in the last 2 seconds.
Flashing 10 times per secondFlashing 10 times per second
Flashing 10 times per secondFlashing 10 times per second
Flashing 10 times per second
There is regular network communication to the VLT's input network variables.
Flashing intermittentlyFlashing intermittently
Flashing intermittentlyFlashing intermittently
Flashing intermittently
There is network communication to the VLT's input network variables but input network variables are received at a period greater than 2 seconds.
Flashing 5 times per secondFlashing 5 times per second
Flashing 5 times per secondFlashing 5 times per second
Flashing 5 times per second
The response to the network management Wink command. The VLT LonWorks node must be reset to leave the wink state.
OFFOFF
OFFOFF
OFF
No power on board or hardware fault.
LonWorks Card Diagnostic LEDs
The LonWorks board includes two LEDs to display the communication status of the board, display the state of the NEURON chip, and respond to the network management
wink command. The onboard LEDs are the Service LED (LED 1, red) and the Status LED (LED 2, green).
Status LED
Service LED
The Service LED displays the state of the NEURON chip. The following table shows the Service LED patterns for various states and defines their meaning.
LEDsLEDs
LEDsLEDs
LEDs
24
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
Service LED Patterns and Descriptions
Service LED Pattern Descriptions
LED Pattern Operation Description
Continuously ON Power-up of Neuron 3120xx
chip-based node or Neuron 3150 chip-based node with any PROM
Use EEBLANK and follow reinitialization procedure.
Continuously OFF Power-up of Neuron 3120xx
chip-based node or Neuron 3150 chip-based node with any PROM
Indicates bad node hardware.
ON for one second at power-up followed by approximately 2 seconds OFF, then stays ON
Power-up/Reset May be caused by Neuron chip
firmware when mismatch occurs in application checksum.
Indicates watchdog timer resets occurring.
Possible corrupt EEPROM.
For Neuron 3150 chip-based node, use EEBLANK and follow reinitialization procedure.
Flashing at 1 second intervals Anytime Indicates node is unconfigured
but has an application. Proceed with loading node.
Brief flash at power-up. OFF duration approximately 10 seconds after which stays ON
Using EEBLANK or Neuron 3150 chip-based node
Indicate completion of blanking process.
Brief flash at power-up. OFF duration approximately 1 to 15 seconds, depending on application size and system clock. LED then begins flashing at 1 second intervals.
First power-up with new PROM on Neuron 3150 chip­based custom node. Unconfigured firmware state exported.
Indicates unconfigured state.
Brief flash at power-up followed by OFF
Node is configuring and running normally.
Short flash every 3 seconds Anytime
25
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
The VLT LonWorks option card supports LonMark network design to improve interoperability. The Controller Object contains the VLT Adjustable Frequency Drive profile.
The configuration parameters are network variable inputs to the VLT. Configuration of parameters needs setting only one time, usually at installation.
VLT 5000 parameters are shown in parenthesis, where applicable.
Configurations properties
(Nci)
Function SNVT type Variable Name Units VLT 6000/8000 VLT 5000
parameter parameter
Nom. motor freq.
1)
SNVT_freq_hz nciNmlFreq 1 Hz 104 104
Nom. motor rpm
1)
SNVT_rpm nciNmlSpeed 1 rpm 106 106
Min. frequency
1)
SNVT_lev_percent nciMinSpeed 0.005% 201 201
Max. frequency
1)
SNVT_lev_percent nciMaxSpeed 0.005% 202 202
Ramp up time 1
1)
SNVT_time_sec NciRampUpTime 1 sec 206 207
Ramp down time 1
1)
SNVT_time_sec NciRampDownTime 1 sec 207 208
Heart beat time
1)
SNVT_time_sec NciSndHrtBt 0.1 sec - -
1)
Part of the LonMark Functional Profile for
Variable Speed Drive 6010 version 1.1
When the NciSndHrtBt time is active it will sent the following variables:
nvoDrvCurnt
nvoDrvSpeed
nvoDrvVolt
nvoDrvPwr
Please note that nciNmlFreq and nciNmlSpeed can only be written to when the VLT frequency converter is stopped.
(EDIT SETUP SELECT)
NOTE
Please note that writing to Configuration properties will be stored in the Non-Volatile memory. Continous writing to Configuration properties may damage the Non-Volatile memory.
26
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
Network Variable Inputs to VLT
Network Drive Control
Input
The most common functions for controlling the VLT Adjustable Frequency Drive from the LonWorks network are made readily available. Those functions and their descriptions are presented in the table below. The control word function accesses additional drive capabilities for network control.
The choice of open loop or closed loop operation of the drive is selected in parameter 100, Configuration.
Using nviRefPcnt, the drive's reference is expressed as a percentage of the reference range. The range is set using parameters 204, Min. Reference and 205, Max. Reference. In open loop operation, reference represents the drive's desired output speed. In this case, set Min. Reference to 0 Hz and Max. Reference equal to Max. Frequency in parameter 202.
In closed loop operation, reference represents the desired setpoint. It is recommended that parameters 204 and 205 be set equal to parameters 201, Min. Frequency and 202,
Max. Frequency.
Start/Stop and Reset fault
SNVT_lev_disc. ST_OFF and ST_NUL are interpreted as low or “0.” ST_LOW, ST_MED, ST_HIGH, and ST_ON are interpreted as high or 1.
NOTE To optimize netw ork performance and for proper drive operation, use only one of following input reference commands.
Reference 1
Network variable nviRefPcnt is a signed value. It represents the desired percentage of the VLT drive's reference range.
Range: -163.840 - 163.835.
All references provided to the drive are added to the total reference value. If reference is to be controlled by the LonWorks bus only, ensure that all other reference inputs are zero. This means that digital input terminals and analog input terminals should not be used for reference signals. The default setting (0%) should be maintained for preset references in parameters 211 (215) through 214 (218). Also, in closed loop operation, the default setting (0.0) should be maintained for drive setpoints in parameters 418 (215) and 419 (218).
Function SNVT type Variable Name Units VLT 6000/8000 VLT 5000
parameter parameter
Start/Stop SNVT_lev_disc nviStartStop Boolean 104 104
*Reset fault SNVT_lev_disc nviResetFault Boolean - -
Reference 1 SNVT_lev_percent nviRefPcnt 0.005% - ­Reference 3 SNVT_freq_hz nviRefHz 0.1 Hz - -
Control word SNVT_state nviControlword 16 Boolean - -
Drive Speed Setpoint
1)
SNVT_switch NviDrvSpeedStpt - Ctrw. + Ref. Ctrw. + Ref. Setpoint 1 SNVT_lev_percent NviSetpoint1 0.01% 418 215 Setpoint 2 SNVT_lev_percent NviSetpoint2 0.01% 419 216 Bus feedback1 SNVT_lev_percent NviFeedback1 0.01% 535 ­Bus feedback2 SNVT_lev_percent NviFeedback2 0.01% 536 -
* Reset on a transition from 0 to 1. A 0 must be sent after reset to enable the next reset.
1)
Part of the LonMark Functional Profile for
Variable Speed Drive 6010 version 1.1
27
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
Bit
BitBit
Bit 1111 00
0000
00 ON 1
ON 1ON 1
ON 1
01
0101
01 ON 2
ON 2ON 2
ON 2
02
0202
02 ON 3
ON 3ON 3
ON 3
03
0303
03 Enable
EnableEnable
Enable
04
0404
04 Ramp
RampRamp
Ramp
05
0505
05 Ramp Enable
Ramp EnableRamp Enable
Ramp Enable
06
0606
06 Start
StartStart
Start
07
0707
07 Reset
ResetReset
Reset
08
0808
08 ON
ONON
ON
09
0909
09 ON
ONON
ON
10
1010
10 Valid
ValidValid
Valid
11
1111
11 Slow down
Slow downSlow down
Slow down
12
1212
12 Catch up
Catch upCatch up
Catch up
13
1313
13 14
1414
14 15
1515
15 Reversing
ReversingReversing
Reversing
Bit
BitBit
Bit Setting
SettingSetting
Setting 00001
11
1
00
0000
00 0000Preset Ref. LSB
Preset Ref. LSBPreset Ref. LSB
Preset Ref. LSB
01
0101
01 0000Preset Ref. MSB
Preset Ref. MSBPreset Ref. MSB
Preset Ref. MSB
02
0202
02 1111DC Brake
DC BrakeDC Brake
DC Brake no DC Brake
no DC Brakeno DC Brake
no DC Brake
03
0303
03 0000Coast Stop
Coast StopCoast Stop
Coast Stop no Coast Stop
no Coast Stopno Coast Stop
no Coast Stop
04
0404
04 1111Quick Stop
Quick StopQuick Stop
Quick Stop no Quick Stop
no Quick Stopno Quick Stop
no Quick Stop
05
0505
05 1111 Freeze Freq.
Freeze Freq.Freeze Freq.
Freeze Freq. no Freeze Freq.
no Freeze Freq.no Freeze Freq.
no Freeze Freq. nviStartStop
nviStartStopnviStartStop
nviStartStop nviResetFault
nviResetFaultnviResetFault
nviResetFault
06
0606
06 0000Ramp Stop
Ramp StopRamp Stop
Ramp Stop Start
StartStart
Start Bit
BitBit
Bit 00001
11
10
00
01
11
1 Description
DescriptionDescription
Description
07
0707
07 0000no Reset
no Resetno Reset
no Reset Reset
ResetReset
Reset 00
0000
00 00000
00
00
00
0Preset Ref LS
B
Preset Ref LSBPreset Ref LS
B
Preset Ref LSB
08
0808
08 0000no Jog
no Jo gno Jo g
no Jo g Jog
JogJog
Jog 01
0101
01 00000
00
00
00
0Preset Ref MSB
Preset Ref MSBPreset Ref MSB
Preset Ref MSB
09
0909
09 0000 no function
no functionno function
no function 02
0202
02 11111
11
11
11
1No DC Brake
No DC BrakeNo DC Brake
No DC Brake
10
1010
10 1111 see Parm. 805
see Parm. 805see Parm. 805
see Parm. 805 03
0303
03 11111
11
11
11
1No Coast Stop
No Coast StopNo Coast Stop
No Coast Stop
11
1111
11 0000 Relay 1 OFF
Relay 1 OFFRelay 1 OFF
Relay 1 OFF Relay 1 ON
Relay 1 ONRelay 1 ON
Relay 1 ON 04
0404
04 11111
11
11
11
1 No Quick Stop
No Quick StopNo Quick Stop
No Quick Stop
12
1212
12 0000 Relay 2 OFF
Relay 2 OFFRelay 2 OFF
Relay 2 OFF Relay 2 ON
Relay 2 ONRelay 2 ON
Relay 2 ON 05
0505
05 11111
11
11
11
1 No Freeze Freq.
No Freeze Freq.No Freeze Freq.
No Freeze Freq.
13
1313
13 0000 Setup LSB
Setup LSBSetup LSB
Setup LSB 06
0606
06 00001
11
10
00
0Start
StartStart
Start
14
1414
14 0000Setup MSB
Setup MSBSetup MSB
Setup MSB 07
0707
07 00000
00
01
11
1 Reset
ResetReset
Reset
15
1515
15 0000no Reversing
no Reversingno Reversing
no Reversing Reversing
ReversingReversing
Reversing 08
0808
08 00000
00
00
00
0Jog
JogJog
Jog
09
0909
09 00000
00
00
00
0 No function
No functionNo function
No function
10
1010
10 11111
11
11
11
1Bit 10
Bit 10Bit 10
Bit 10
11
1111
11 00000
00
00
00
0 Relay 1 On
Relay 1 OnRelay 1 On
Relay 1 On
12
1212
12 00000
00
00
00
0 Relay 2 On
Relay 2 OnRelay 2 On
Relay 2 On
13
1313
13 00000
00
00
00
0 Setup LSB
Setup LSBSetup LSB
Setup LSB
14
1414
14 00000
00
00
00
0Setup MSB
Setup MSBSetup MSB
Setup MSB
15
1515
15 00000
00
00
00
0 Reversing
ReversingReversing
Reversing
No value is written to the control word
No value is written to the control word
No value is written to the control word
No value is written to the control word
OFF 3
OFF 3OFF 3
OFF 3
OFF 2
OFF 2OFF 2
OFF 2
OFF 1
OFF 1OFF 1
OFF 1
0000
Ram
p
sto
p
Ramp sto
p
Ramp sto
p
Ramp sto
p
Freeze out freq.
Freeze out freq.Freeze out freq.
Freeze out freq.
Quick stop
Quick stopQuick stop
Quick stop
Motor coastin
g
Motor coastin
g
Motor coastin
g
Motor coastin
g
No function
No functionNo function
No function
Setu
p
1 (LSB
)
Setup 1 (LSB
)
Setup 1 (LSB
)
Setup 1 (LSB
)
Setup 2 (MSB)
Setup 2 (MSB)Setup 2 (MSB)
Setup 2 (MSB)
No function
No functionNo function
No function
Jog 1 OFF
Jog 1 OFFJog 1 OFF
Jog 1 OFF
Jo
g
2 OFF
Jo
g
2 OFFJog 2 OFF
Jo
g
2 OFF
Data not valid
Data not validData not valid
Data not valid
No function
No functionNo function
No function
1111
16
1616
16
8888 4444 2222
256
256256
256 128
128128
128
64
6464
64 32
3232
32
32768
3276832768
32768
Value
ValueValue
Value
16384
1638416384
16384
8192
81928192
8192 4096
40964096
4096 2048
20482048
2048 1024
10241024
1024
512
512512
512
No function
No functionNo function
No function
Control Word Bit Descriptions
for Coast Stop
Network Drive Control Input
(continued)
Reference 2
Network variable nviRefRads is a signed value. A negative value is interpreted as zero. It represents the desired output frequency of the drive in radians/second in open loop. It is rarely used in closed loop.
Range: -3276.8 - 3276.7.
Reference 3
Network variable nviRefHz is an unsigned value. It represents the output frequency of the drive in Hz in open loop. It is rarely used in closed loop mode.
Range: 0 - 6553.5.
Control Word
The input network variable nviControlWord is a 16-bit word that provides additional operational control of the drive, as listed in the table below. The settings shown represent the Coast Stop command
NOTE Drive always stops and ignores serial bus commands to run when OFF/STOP or STOP/RESET function is activated from drive keypad.
Start/Stop and Fault Reset Control W ord
Bit Descriptions
VLT 5000 parameters are shown in parenthesis, where applicable.
The VLT 5000 allows the choice between two control word profiles, selected in parameter 512, Telegram Profile. The table below defines the Profidrive control word used for transmitting commands to the drive using the Profibus protocol.
The equivalent control word bit settings to start and stop the drive (nviStartStop) and to reset after a fault (nviResetFault) are described in the table below.
Profidrive Control W or d Bit
Descriptions
28
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
Precedence of the stop commands is:
1. Coast stop
2. Quick stop
3. DC brake stop
4. Ramp stop
Coast stop
The drive output stops immediately and the motor coasts to a stop.
Drive display show UN.READY (unit ready) when coast stop is active.
Drive cannot run in any mode.
Parameter 503 (502),
Coasting stop, determines interaction with input 27.
Quick stop
The drive output frequency ramps down to 0 Hz according to time set in parameter 207 (212), Ramp Down Time.
Drive display shows STOP.
Drive cannot run in AUTO
mode but can run in HAND mode.
DC brake stop
The drive brakes the motor to a stop using DC injection braking.
Parameters 114 (125) and 115 (126) determine amount and time of DC current applied for braking.
Drive display shows DC STOP.
Drive cannot run in AUTO
mode but can run in HAND mode.
Parameter 504, DC Brake, determines interaction with input 27.
Drive Speed Setpoint
With this input variable it is possible to give the Drive a Start/stop signal and a reference.
StateState
StateState
State
Ref. valueRef. value
Ref. valueRef. value
Ref. value
CommandCommand
CommandCommand
Command 0 - Stop 1 0 Run, Ref. = 0% 1 0-100% Run, Ref. = 0-100% 0xFF - Auto (invalid)
Default is Auto.
Ramp stop
The drive output frequency ramps down to 0 Hz according to time set in parameter 207, Ramp Down Time.
Factory setting is 60 sec for fan applications and 10 sec for most pump applications.
Drive display shows STAND BY.
Drive can run in HAND mode or
AUTO through a digital input command.
Parameter 505, Start, determines interaction with input 18.
29
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
Drive Feedback to Network
The VLT LonWorks option provides 16 output variables to the network containing important drive and motor feedback data. Feedback data is sent when there is a change in value. The VLT LonWorks option will only transmit bound network variables. Since some data changes continuously, the transmission rate of those variables is limited. Min send time specifies the minimum time between transmissions of variables.
The Drive Outputs (1, 2, or 3) will have a maximum time between transmission set by the Max send time. This function acts as a transmit heartbeat and allows a controller node to determine the health of the controller/VLT connection. The Max send time function is disabled when the configuration network variable nciMaxsendT is not configured or is set to 0.
Network Variable Outputs from VLT
Function SNVT type Variable Name Units Max Min Drive status SNVT_state nvoDrvStatus 16 Boolean N A N A Drive output 1 SNVT_lev_percent nvoOutputPcnt 0.005% 163.835
163.840
Current
1)
SNVT_amp nvoDrvCurnt 0.1 amps 3276.7 0 Energy SNVT_elec_kwh nvoDrvEnrg 1 kWh 65,535 0 Power
1)
SNVT_power_kilo nvoDrvPwr 0.1 kW 6553.5 0 Statusword SNVT_state nvoStatusWord 16 Boolean NA NA
Drive output 3 SNVT_freq_hz nvoOutputHz 0.1 Hz 6553.5 0
Output voltage SNVT_volt nvoVoltage 0.1 V 3276.7 –3276.8 Digital input SNVT_state nvoDigitlInput 16 Boolean NA NA Alarm SNVT_state nvoAlarmWord 16 Boolean NA N A Warning 1 SNVT_state nvoWarning1 16 Boolean N A N A Warning 2 SNVT_state nvoWarning2 16 Boolean N A N A DC voltage SNVT_volt nvoDCVolt 0.1 V 3276.7 0
Motor therm. Status SNVT_lev_cont nvoTempMtr 0.5 % 100 0
Inverter therm. Status SNVT_lev_cont nvoTempInvrtr 0.5 % 100 0
Analog input SNVT_volt nvoAnalog1 0.1 V 10 0 Term. 53 Analog input SNVT_volt nvoAnalog2 0.1 V 10 0 Term. 54 Analog input SNVT_amp_mil nvoAnalog3 0,1 mA 20 0 Term. 60 Running hours
1)
SNVT_time_hour nvoDrvRunHours 1 Hour 65534 0 Feedback SNVT_lev_percent nvoFeedback 0.01% 100.000 0 Frequency SNVT_freq_hz nvoOutputHz1 0.1 Hz 6553.5 0 Drive speed
1)
SNVT_lev_percent nvoDrvSpeed 0.01% 100 0 Output voltage
1)
SNVT_volt nvoDrvVolt 0.1 V 3276.7 0
VLT 5000 parameters are shown in parenthesis, where applicable.
1)
Part of the LonMark Functional Profile for
Variable Speed Drive 6010 version 1.1
30
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
Drive status
NvoDrvStatus, nvoStatusWord, nvo­DigitalInput, nvoAlarmWord, nvoWarning1 and nvoWarning2 are all 16 bit Boolean values using the SNVT_state variable type. Individual bits represent specific drive status states. The tables provided in Drive Status Bit Definitions define each bit.
Drive output 1
Network variable nvoOutputPcnt provides an analog indication of drive operation. In open loop, this is the drive output frequency in percentage within the reference range. To avoid negative numbers, or numbers above 100%, set parameter 204, Min. Reference to 0 Hz, and parameter 205, Max. Reference equal to parameter 202, Max. Frequency.
In closed loop, this is the drive's feedback signal within the reference range. For best operation, set Min. Reference to equal parameter 413 (414), Min. Feedback, and
Max. Reference to equal parameter 414 (415), Max. Feedback.
Drive output 2 and Drive Output 3
Output 2 is useful in open loop to report the drive's output frequency in rad/sec. Output 3 in open loop reports the drive's output in Hz. Note that in closed loop nvoOutputHz will report the actual Feedback and not the output frequency. For best results, set Min. Reference to 0 Hz and Max. Reference equal to Max. Frequency. These variable are rarely used in closed loop.
31
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
Bit Value 0 1 Bit Value 0 1
00 32768 33 OFF 33 ON 00 32768 01 16384 32 OFF 32 ON 01 16384 02 8192 29 OFF 29 ON 02 8192 03 4096 27 OFF 27 ON 03 4096 04 2048 19 OFF 19 ON 04 2048 05 1024 18 OFF 18 ON 05 1024 06 512 17 OFF 17 ON 06 512 07 256 16 OFF 16 ON 07 256 08 128 no function 08 128 09 64 no function 09 64 10 32 no function 10 32 11 16 no function 11 16 12 8 no function 12 8 13 4 no function 13 4 Stopped Running 14 2 no function 14 2 No Warning Warning 15 1 no function 15 1 no Alarm Alarm
Bit Value 0 1 Bit Value 0 1
00 32768 Alarm Ctrl. Ready 00 32768 normal Unknown Fault 01 16384 Alarm Drive Ready 01 16384 normal Trip Lock 02 8192 Safety Open Safety Closed 02 8192 normal AMA Fault 03 4096 No Alarm Alarm 03 4096 normal HPFB Timeout 04 2048 04 2048 normal RS-485 Timeout 05 1024 05 1024 normal ASIC Fault 06 512 06 512 normal Short circuit 07 256 no Warning Warning 07 256 normal SMPS Fault 08 128 Not at Ref. at Ref. 08 128 normal Ground Fault 09 64 Hand Mode Auto Mode 09 64 normal Overcurrent 10 32 Fr. Range Warn Freq. in Range 10 32 normal Current limit 11 16 Stopped Running 11 16 normal Mtr. Thermistor 12 8 no used 12 8 normal Motor thermal 13 4 normal V oltage Warn. 13 4 normal Undervoltage 14 2 normal Current lim. 14 2 normal Overvoltage 15 1 normal Therm. Warning 15 1 normal In. Phase loss
Bit Value 0 1 Bit Value 0 1
00 32768 normal Ref. High 00 32768 normal Autoramping 01 16384 normal Ctrl. Crd. Fault 01 16384 normal Start Delay 02 8192 normal Pwr. Crd. Fault 02 8192 normal Sleep Boost 03 4096 normal HPFB Timeout 03 4096 normal Sleep 04 2048 normal RS-485 Timeout 04 2048 normal AMA Done 05 1024 normal Overcurrent 05 1024 normal AMA Running 06 512 normal Current limit 06 512 normal Rev. Start 07 256 normal Thermistor O.T. 07 256 no Ramp Ramping 08 128 normal Motor O.T. 08 128 Forward Reverse 09 64 normal Inverter O.T. 09 64 not at Ref. at Reference 10 32 normal U.V. Alarm 10 32 Stopped Running 11 16 normal O.V. Alarm 11 16 Remote Ref. Local Ref. 12 8 normal U.V. Warning 12 8 normal OFF (HOA) 13 4 normal O.V. Warning 13 4 Auto Start/stop Hand 14 2 normal Input Phase Loss 14 2 normal Run Request 15 1 normal Live Zero 15 1 Run Permission no Run Perm.
no function
not used not used not used
no function no function no function no function
no function no function no function no function
no function no function no function no function
VLT 6000/8000 Drive Status Bit Definitions
nvoWarning1 nvoWarning2
nvoStatusWord nvoAlarmWord
nvoDigitalInput
nvoDrvStatus
32
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
Bit Value 0 1 Bit Value 0 1 00 32768 33 OFF 33 O N 00 32768
01 16384 32 OFF 32 O N 01 16384 02 8192 29 O FF 29 ON 02 8192 03 4096 27 O FF 27 ON 03 4096 04 2048 19 O FF 19 ON 04 2048 05 1024 18 O FF 18 ON 05 1024 06 512 17 OFF 17 ON 06 512 07 256 16 OFF 16 ON 07 256 08 128 no function 08 128 09 64 no function 09 64 10 32 no function 10 32 11 16 no function 11 16 12 8 no function 12 8 Remote Local 13 4 no function 13 4 Stopped Running 14 2 no function 14 2 No Warning Warning 15 1 no function 15 1 no Alarm Alarm
Bit Value 0 1 Bit Value 0 1 00 32768 Alarm Ctrl. Ready 00 32768 normal Brake Test fail 01 16384 Alarm Drive Ready 01 16384 normal Trip Lock 02 8192 Safety Open Safety Closed 02 8192 normal AMA Fault 03 4096 No Alarm Alarm 03 4096 normal AMA OK 04 2048 04 2048 normal Power Up Fault 05 1024 05 1024 normal ASIC Fault 06 512 06 512 normal HPFB Timeout 07 256 no Warning Warning 07 256 normal RS-485 Timeout
08 128 Not at Ref. at Ref. 08 128 norma l Short circuit 09 64 Local Bus Control 09 64 normal Power Fault 10 32 Fr. Range Warn Freq. in Range 10 32 normal Ground Fault 11 16 Stopped Running 11 16 normal Over current 12 8 no used Stall, Autostart 12 8 normal Torque limit 13 4 normal Voltage Warn. 13 4 normal Motor Thermal 14 2 normal Current lim. 14 2 normal Motor Overload 15 1 normal Therm. Warning 15 1 normal Inverter Overload
Bit Value 0 1 Bit Value 0 1 00 32768 normal Brake Test Fault 00 32768 normal Ramping
01 16384 normal Ctrl. Crd. Fault 01 16384 normal AMT 02 8192 normal Pwr. Crd. Fault 02 8192 norma l Start Fwd/Rev 03 4096 normal HPFB Timeout 03 4096 normal Slow down 04 2048 normal RS-485 Timeout 04 2048 norma l Catch up 05 1024 normal Overcurrent 05 1024 normal FB High 06 512 norma l Torque limit 06 512 normal FB Low 07 256 norma l Thermistor O.T. 07 256 normal Current High 08 128 norma l Motor O.T. 08 128 normal Current Low 09 64 normal Inverter O.T. 09 64 normal Freq. High 10 32 normal U.V. Alarm 10 32 normal Freg. Low 11 16 normal O.V. Alarm 11 16 norma l Brake Test OK 12 8 normal U.V. Warning 12 8 normal Braking Max. 13 4 normal O .V. Warning 13 4 norma l Braking 14 2 normal Input Phase Loss 14 2 norma l Discharge OK 15 1 normal No motor 15 1 norma l Out Freq. Range
not used not used not used
no function no function no function no function
no function no function no function no function
no function no function no function no function
nvoDigitalInput
nvoD rvStatus
nvoStatusWord
nvoWarning1
nv oAlarmWord
nvoWarning2
VLT 5000 Drive Status Bit Definitions
33
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
Min send time
Sets the minimum period between transmissions for all output network variables, using the network variable nciMinSendT. This function is used to keep the transmission of variables that change continuously from dominating the network communication.
Max receive time
This drive function is replaced by the value set in parameter 803, Bus Time Out. The LonWorks option will initiate bus time out activities when the time set in parameter 803 expires without receiving an input network variable directed to the drive. This acts like a LonWorks receive heartbeat. The action taken by the drive is determined by the setting selected in parameter 804, Bus time out function. See the parameter description section of this manual. The value of nciMaxReceiveT has no effect on the operation of the drive.
Network Timer Functions
Max send time
This function sets the maximum time between transmissions for the network variables Drive Output 1, 2, and 3 using the configuration network variable nciMaxSendT. It can be used by the controller to monitor the health of the VLT and controller connection. It acts like a LonWorks send heartbeat.
The Max send time function is disabled when nciMaxSendT is not configured or set to “0.”
Function SNVT Variable Units Max Min Default
type Name
Min send SNVT nciMin- time 0 days 0 days 0 days time _elapsed SendT 0 hours 0 hours 0 hours
_tm 1 min 0 min 0 min
5 sec 0 sec 0 sec 535 msec 100 msec
1
500 msec
30 msec
2
Max SNVT nciMax- time 0 days 0 days 0 days receive _elapsed ReceiveT 18 hours 0 hours 0 hours time _tm 12 min 0 min 0 min
15 sec 1 sec 0 sec 0 msec 0 msec 0 msec
(Off)
Max SNVT nciMax- time 0 days 0 days 0 days send _elapsed SendT 0 hours 0 hours 0 hours time _tm 1 min 0 min 0 min
5 sec 0 sec 0 sec 535 msec 100 msec
1
0 msec
30 msec
2
(Off)
1
78 kbps transformer coupled twisted pair and 78 Kbps free topology transceiver models.
2
1.25 Mbps transformer coupled twisted pair transceiver model.
Network Timer Functions
34
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
A controller node can monitor or modify any VLT parameter by supporting the Parameter
access command and the Parameter access response functions. These functions allow a
controller complete access to the features of the VLT and the ability to configure drives with predefined settings, using the network variables nviParamCmd and nvoParamResp.
The following definitions describe how the fields of SNVT_preset are used by the VLT LonWorks option:
Learn
This field contains the function code for the VLT. The values for this field are:
LN_RECALL (0), LN_LEARN_CURRENT (1), LN_LEARN_VALUE (2), and LN_REPORT_VALUE (3).
LN_RECALL (0) and LN_REPORT_VALUE (3) are interpreted as read commands.
LN_LEARN_CURRENT (1) and LN_LEARN_VALUE (2) are interpreted as write commands.
Any other value in this field will result in an error message in the Parameter access
response.
Selector
This field contains the VLT parameter number, written in decimal notation, that is to be written or read. Requests for undefined parameters will result in an error message in the Parameter access esponse.
VLT Parameter Access
The controlling device should compare the parameter number of the response message to the requested parameter number to determine that the information received is the requested information and not a response to another controller or from another VLT.
Value
This array contains the parameter information to and from the VLT. All VLT parameters use 16 bit signed or unsigned values. The most significant 2 hex bytes of data will be stored in value [0] and the least significant 2 hex bytes of data will be stored in value [3]. In the event of an error message, the VLT will send 0xff in value [0] and an error code in value [3]. The error codes are defined in the section Parameter Access Error Codes in this manual.
NOTE
Consult
Conversion Index
in
the VLT Instruction Manual
parameter table for correct conversion factor for reading and writing to and from drive.
Day, Hour, Minute, Second, Millisecond
The time fields are not supported by the VLT LonWorks option. The VLT will respond to parameter access requests as soon as they are received. Any values in the time fields of the Parameter access command will be ignored. All time fields will be set to 0 in the Parameter access response.
Function SNVT type Variable Name Parameter access command SNVT_preset nviParamCmd
Network Variable Output from VL T
Network Variable Input to VLT
Function SNVT type Variable Name Parameter access response SNVT_preset nvoParamResp
35
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
Parameter Access Error Codes
Exception Code Interpretation
1 Illegal function for the addressed node 2 Illegal data address (i.e., illegal parameter number) 3 Illegal data value 6 Busy
Example 1:
The examples below demonstrate use of the
parameter access command and parameter access response functions of the controller
node. In the examples, the controller node has a parameter access command SNVT_preset called nvoParamCmd and a parameter access response SNVT_preset called nviParamResp. In writing to the drive correctly, the access response simply repeats the entered data. In the event of an error, an error code is displayed in value [3]. See Parameter Access Error Codes above.
Parameter Access Error Codes
In the event of an error message in response to a Parameter access command (see VLT Parameter Access), the VLT sends 0xff in value
bit [0] and an error code in value [3]. Error code definitions are presented in the table below.
Parameter Access Command and Response Examples
Parameter 971 must be set to STORE ACTIVE SETUP for entering data values through LonWorks
parameter access
command
in order to save changes in drive. See parameter 971 in
Parameter Descriptions
section of this manual.
NOTE
Consult conversion index in the
VL T Instruction Manual
parameter table for correct conversion factor for reading and writing to and from drive.
CAUTION
!
The controller node writes 30 seconds to parameter 206 (205), Ramp time up of the VLT. Conversion index is 0, so the conversion factor is 1.0 (VLT 5000 conversion factor -2)).
The controller node access command sends the following parameter write request to the VLT.
nvoParamCmd.learn= LN_LEARN_CURRENT nvoParamCmd.selector = 206 nvoParamCmd.value[0] = 0 nvoParamCmd.value[1] = 0 nvoParamCmd.value[2] = 0 nvoParamCmd.value[3] = 1E hex (30 decimal)
The controller node receives the following parameter access response from the VLT.
nviParamResp.learn = LN_LEARN_CURRENT nviParamResp.selector = 206 nviParamResp.value[0] = 0 nviParamResp.value[1] = 0 nviParamResp.value[2] = 0 nviParamResp.value[3] = 1E hex nviParamResp.day = 0 nviParamResp.hour = 0 nviParamResp.minute = 0 nviParamResp.second = 0 nviParamResp.millisecond = 0
VLT 5000 parameters are shown in parenthesis, where applicable.
36
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
A controller node writes [2] (REFERENCE [UNIT]) to parameter 007 (009), Large Display Readout, of the VLT.
The controller node sends the following parameter write request to the VLT.
nvoParamCmd.learn = LN_LEARN_CURRENT nvoParamCmd.selector = 7 nvoParamCmd.value[0] = 0 nvoParamCmd.value[1] = 0 nvoParamCmd.value[2] = 0 nvoParamCmd.value[3] = 2
Example 2:
Time 1 - The controller node receives the following parameter access response from the VLT.
nviParamResp.learn = LN_LEARN_CURRENT nviParamResp.selector = 7 nviParamResp.value[0] = 0 nviParamResp.value[1] = 0 nviParamResp.value[2] = 0 nviParamResp.value[3] = 2 nviParamResp.day = 0 nviParamResp.hour = 0 nviParamResp.minute = 0 nviParamResp.second = 0 nviParamResp.millisecond = 0
Example 3:
Example 4:
A controller node writes 18.0 Hz to VLT parameter 201, Output Frequency Low Limit. The conversion index is -1, so the conversion factor is 0.1.
The controller node sends the following parameter write request to the VLT.
nvoParamCmd.learn = LN_LEARN_CURRENT nvoParamCmd.selector = 201 nvoParamCmd.value[0] = 0 nvoParamCmd.value[1] = 0 nvoParamCmd.value[2] = 0 nvoParamCmd.value[3] = B4 hex (180 decimal)
The controller node receives the following parameter access response from the VLT.
nviParamResp.learn = LN_LEARN_CURRENT nviParamResp.selector = 201 nviParamResp.value[0] = 0 nviParamResp.value[1] = 0 nviParamResp.value[2] = 0 nviParamResp.value[3] = B4 hex nviParamResp.day = 0 nviParamResp.hour = 0 nviParamResp.minute = 0 nviParamResp.second = 0 nviParamResp.millisecond = 0
A controller node reads the value of parameter 407 (411), Switching Frequency, in the VLT. The value stored in parameter 407 is 10 kHz. The conversion index is 2, so the conversion factor is 100.
The controller node sends the following parameter read request to the VLT.
nvoParamCmd.learn = LN_RECALL nvoParamCmd.selector = 407 nvoParamCmd.value[0] = 0 nvoParamCmd.value[1] = 0 nvoParamCmd.value[2] = 0 nvoParamCmd.value[3] = 0
The controller node receives the following parameter access response from the VLT.
nviParamResp.learn = LN_RECALL nviParamResp.selector = 407 nviParamResp.value[0] = 0 nviParamResp.value[1] = 0 nviParamResp.value[2] = 0 nviParamResp.value[3] = 64 hex (100 decimal) nviParamResp.day = 0 nviParamResp.hour = 0 nviParamResp.minute = 0 nviParamResp.second = 0 nviParamResp.millisecond = 0
VLT 5000 parameters are shown in parenthesis, where applicable.
37
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
Standard Object Support
The VLT LonWorks option supports two standard objects and three SNVTs, per the LonMark standard object philosophy. The standard objects are the Node Object (containing the Object request, Object status, and Object alarm) and the Controller object, (containing the network variables described in the preceding sections). The Object request is a LonMark device used to obtain status and alarm information from a node.
It is not necessary for a controller to support the Node Object network variables. The
Object request, Object status and Object alarm provide status and alarm information
for controllers that only support this type of functionality. The status and alarm functions described in the preceding sections contain more drive specific information than Object status and Object alarm.
1. The VLT sends an Object status containing drive status information and an Object alarm containing fault informationin response to the following Object requests:
RQ_NORMAL, RQ_UPDATE_STATUS, and RQ_UPDATE_ALARM.
Network Variables for Node Object Support
Function SNVT type Variable Name Input/Output Object request SNVT_obj_request nviRequest Input Object status SNVT_obj_status nvoStatus Output Object alarm SNVT_alarm nvoAlarm Output
A controller node error is written to VLT parameter 201, Output Frequency Low Limit, with 80.0 Hz when the high limit is 60 Hz. The conversion index is -1, with conversion factor 0.1.
The controller node sends the following parameter write request to the VLT.
nvoParamCmd.learn = LN_LEARN_CURRENT nvoParamCmd.selector = 201 nvoParamCmd.value[0] = 0 nvoParamCmd.value[1] = 0 nvoParamCmd.value[2] = 3 hex nvoParamCmd.value[3] = 20 hex (800 decimal)
The controller node receives the following parameter access response from the VLT.
nviParamResp.learn = LN_NULL nviParamResp.selector = 201 nviParamResp.value[0] = 0 nviParamResp.value[1] = 0 nviParamResp.value[2] = 0 nviParamResp.value[3] = 3 (illegal data value) nviParamResp.day = 0 nviParamResp.hour = 0 nviParamResp.minute = 0 nviParamResp.second = 0 nviParamResp.millisecond = 0
The nviRequest.object_id should be set to “1” (controller node). The network uses nviRequest, nvoStatus and nvoAlarm variables for these functions.
2. The VLT sends an Object status containing a bit map of supported status fields in response to all other Object requests, including undefined requests.
3. The VLT Object status supports the following status fields: invalid_id, invalid_request,open_circuit, out_of_service, electrical_fault, comm_failure, manual_control, and in_alarm. All other fields are always set to 0.
4. The VLT sends an Object alarm following any set or reset of a drive fault condition.
5. The Object alarm supports the AL_ALM_CONDITION and AL_NO_CONDITION alarm types.
Example 5:
38
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
222AMA failed 318HPFB timeout 4 17 Serial communication timeout 5 16 Short circuit 6 15 Switch mode fault 714Ground fault 813Overcurrent
9 12 Current limit 10 11 Motor thermistor 11 10 Motor overtem
p
erature 12 9 Inverter overload 13 *8 Undervolta
g
e
14 **7 Overvolta
g
e
15 4 Mains failure
Bit
number
Alarm
number
Alarm Description
023Brake test failed 1
X
Trip
locked
222
A
MA tuning not OK
321
A
MA tuning OK 4 20 Power up fault 519
A
SIC fault 618HPFB timeout 7 17 Standard bus timeout 8 16 Short circuit 9 15 Switch mode fault
10 14 Ground fault 11 13 Overcurrent 12 12
T
orque limit 13 11 Motor thermistor 14 10 Motor overload 15 9 Inverter overload
Bit
number
Alarm
number
Alarm Description
Factory setting
VLT 6000/
8000 Alarm
Descriptions
Alarm numbers and descriptions that correspond to nvoAlarmWord bit numbers are
shown in the table below. See the VLT 6000/
8000 Instruction Manual for more details.
**
**
* also bit 10 of nvoWarning 1 ****
****
** also bit 11 of nvoWarning 1
VLT 5000 parameters are shown in parenthesis, where applicable.
VLT 5000 Alarm Descriptions
Alarm numbers and descriptions that correspond to nvoAlarmWord bit numbers are shown in the table below.
See the VLT 5000 Instruction Manual for more details.
39
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
Parameter Descriptions
803803
803803
803 Bus time outBus time out
Bus time outBus time out
Bus time out
Selection:
1 - 99 sec 1 sec
Function: Sets the duration for the bus time out function. If the set time passes without the drive receiving a LonWorks message addressed to
Factory setting
it, the drive will take the action specified in parameter 804, Bus Time Out Function.
NOTE After time out counter is reset it must be triggered by v alid control word before ne w time out can be activated.
VLT 5000 parameters are shown in parenthesis, where applicable.
Parameter List
In addition to the parameters listed above, the drive's control terminals issue digital inputs that control functions similar to those provided by nviStartStop, nviResetFault, and nviControlWord. Parameters (502) 503 through 508 determine how the drive
responds to commands for (quick stop, VLT 5000 only), coasting stop, DC brake, start, reverse, setup select and preset reference select. See Network Drive Control
Input in this manual and the VLT Instruction Manual for more information.
Conversion Data PNU Parameter Description Default V alue Range Index T ype 803 Bus time out 1 sec 1 - 99 sec. 0 3 804 Bus time out function no function 0 3 805 Bit 10 function Bit 10 = > CTW ACT 0 6 927 Parameter edit Enable 0 6 928 Process control Enable 0 6 970 Edit setup Activ e Setup 0 5 971 Store data v alues no action 0 5
40
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
804804
804804
804 TT
TT
T
ime out functionime out function
ime out functionime out function
ime out function
Selection: Off
(NO FUNCTION) [0]
Freeze output frequency
(FREEZE OUTPUT FREQ.) [1]
Stop with auto restart
(STOP) [2]
Output frequency = JOG freq.
(JOGGING) [3]
Output frequency = Max. freq.
(MAX SPEED) [4]
Stop with trip
(STOP AND TRIP) [5]
Control without DeviceNet
(NO COM OPT CONTROL) [6]
Select set-up 4
(SELECT SET UP 4) [7]
Function: The time out timer is triggered at the first reception of a valid control word, i.e., bit 10 = ok.
The time out function can be activated in two different ways:
1. The drive does not receive a LonWorks command addressed to it within the specified time.
2. Parameter 805 is set to bit 10 = 0 time out and a control word with “bit 10 = 0 is sent to the drive.
The VLT remains in the time out state until one of the following four conditions is true:
1. A valid control word (Bit 10 = ok) is received
and the drive is reset through the bus, the digital input terminals or the local control panel. (Reset is only necessary when the time out function Stop w/trip is selected.) Control via LonWorks is resumed using the received control word.
2. Local control via the local control panel is enabled.
3. Parameter 928, Access to process control, is set to Disabled. Normal control via the digital input terminals and the RS-485 interface is now enabled.
Factory setting
4. Parameter 804, Bus time out function, is set to Off. Control via LonWorks is resumed and the most recent control word is used.
Description of Selections:
Freeze output frequency. Maintain present output frequency until communication is resumed.
Stop with auto restart. Stop and automatically restart when communication is resumed.
Output frequency = JOG freq. Drive will produce JOG frequency set in parameter 209 (213), Jog frequency, until communication is resumed.
Output frequency = Max. freq. Drive will produce maximum output frequency (set in parameter 202, Output frequency) until communication is resumed.
Stop with trip. Drive stops and requires a reset command before it will restart.
Control without LonWorks. Control via LonWorks is disabled. Control is possible via digital input terminals and/or standard RS-485 interface until LonWorks communication is resumed.
Select setup 4. Setup 4 is selected in parameter 002 (004), Active setup, and settings of setup 4 are used. Parameter 002 (004) is not reset to the original value when communication is resumed.
VLT 5000 parameters are shown in parenthesis, where applicable.
41
MG.60.N1.22 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000 HVAC / VLT® 8000 AQUA
Data Value:
Preprogrammed (FACTORY SETUP) [0] Setup 1 (SETUP 1) [1] Setup 2 (SETUP 2) [2] Setup 3 (SETUP 3) [3] Setup 4 (SETUP 4) [4]
Active Setup (ACTIVE SETUP) [5]
Factory Setting
805805
805805
805 ContrContr
ContrContr
Contr
ol Wol W
ol Wol W
ol W
oror
oror
or
dd
dd
d
Bit 10 FunctionBit 10 Function
Bit 10 FunctionBit 10 Function
Bit 10 Function
Selection:
No function
(NO FUNCTION) [0]
Bit 10 = 1: control word active
(BIT 10 = 1 >CTW ACTIVE) [1]
Bit 10 = 0: control word active
(BIT 10 = 0 >CTW ACTIVE) [2]
Bit 10 = 0: bus time out
(BIT 10 = 0 >TIME OUT) [3]
Function: According to the drive's standard communications profile, control word and speed reference will be ignored if bit 10 of the control word is 0. Parameter 805 lets the user change the function of bit 10. This is some times necessary, as some masters set all bits to 0 in various fault situations. In these cases, it makes sense to change the function of bit 10 so that the VLT is commanded to stop (coast) when all bits are 0.
Description of Selections:
No function. Bit 10 is ignored, i.e., control word and speed reference are always valid.
Bit 10 = 1 >CTW active. The control word and speed reference are ignored if bit 10 = 0.
Bit 10 = 0 >CTW active. The control word and speed reference are ignored if bit 10 = 1. If all bits of the control word are 0, the VLT reaction will be coasting.
Bit 10 = 0 >time out. The time out function selected in parameter 804 is activated when bit 10 is 0.
Data Value:
Disable (DISABLE) [0]
Enable (ENABLE) [1]
This parameter determines LonWorks control of the drive. When Enable is selected, drive parameters 503 through 508 determine the interaction between various LonWorks and digital drive input commands. See the VLT Instruction Manual for details.
When this parameter is set to Store active setup, LonWorks downloaded parameters are written to EEPROM and stored. Store edit setup stores the setup selected in parameter
970. Store all setups stores all setups in parameter 970. When finished (appx. 15 sec.), it automatically returns to No action. Any parameters values written via the serial bus with No action selected are lost when power is removed from the drive. The function is only activated with the VLT in stop mode.
Data Value:
Disable (DISABLE) [0]
Enable (ENABLE) [1]
This parameter determines if LonWorks can be used to access and edit drive parameters.
927927
927927
927 Parameter editParameter edit
Parameter editParameter edit
Parameter edit
928928
928928
928 PrPr
PrPr
Pr
ocess controcess contr
ocess controcess contr
ocess contr
olol
olol
ol
970970
970970
970 Edit setup selectEdit setup select
Edit setup selectEdit setup select
Edit setup select
971971
971971
971 StorStor
StorStor
Stor
e data valuee data value
e data valuee data value
e data value
Data Value: No action (NO ACTION) [0]
Store all setups
(STORE ALL SETUPS [1]
Store edit setup
(STORE EDIT SETUP) [2]
Store active setup
(STORE ACTIVE SETUP) [3]
With
Bit 10
= 0
>CTW active
selected, nviStartStop and nviResetFault commands will not function.
CAUTION
!
This parameter selects the setup being edited, through either the drive control panel or LonWorks. The drive may operate in one setup while editing another. Active setup selects the parameter being edited as the setup controling drive operation.
Loading...