Danfoss LonWorks 78 kbps, LonWorks 1.25 Mbps Operating guide

LonWorks® 78 kbps and 1.25 Mbps Option Card
Instruction Manual
DANGER
!
Rotating shafts and electrical equipment can be hazardous. Therefore, it is strongly recommended that all electrical work conform to the National Electrical Code (NEC) and all local regulations. Installation, start-up and maintenance should be performed only by qualified personnel.
VLT® 5000 / VLT® 6000
does not disconnect the equipment from the AC line and is not to be used as a safety switch.
3. Correct protective grounding of the equipment must be established. The user must be protected against supply voltage and the motor must be protected against overload in accordance with applicable national and local regulations.
4. Ground currents are higher than 3 mA.
Factory recommended procedures, included in this manual, should be followed. Always disconnect electrical power before working on the unit.
Although shaft couplings or belt drives are generally not furnished by the manufacturer, rotating shafts, couplings and belts must be protected with securely mounted metal guards that are of sufficient thickness to provide protection against flying particles such as keys, bolts and coupling parts. Even when the motor is stopped, it should be considered “alive” as long as its controller is energized. Automatic circuits may start the motor at any time. Keep hands away from the output shaft until the motor has completely stopped and power is disconnected from the controller.
Motor control equipment and electronic controls are connected to hazardous line voltages. When servicing drives and electronic controls, there will be exposed components at or above line potential. Extreme care should be taken to protect against shock. Stand on an insulating pad and make it a habit to use only one hand when checking components. Always work with another person in case of an emergency. Disconnect power whenever possible to check controls or to perform maintenance. Be sure equipment is properly grounded. Wear safety glasses whenever working on electric control or rotating equipment.
Safety Guidelines
1. The drive must be disconnected from the AC line before any service work is done.
2. The “Stop/Off” key on the local control panel of the drive
W arnings Against Unintended Start
1. While the drive is connected to the AC line, the motor can be brought to a stop by means of external switch closures, serial bus commands or references. If personal safety considerations make it necessary to ensure that no unintended start occurs, these stops are not sufficient.
2. During programming of parameters, the motor may start. Be certain that no one is in the area of the motor or driven equipment when changing parameters.
3. A motor that has been stopped may start unexpectedly if faults occur in the electronics of the drive, or if an overload, a fault in the supply AC line or a fault in the motor connection or other fault clears.
4. If the “Local/Hand” key is activated, the motor can only be brought to a stop by means of the “Stop/Off” key or an external safety interlock.
NOTE: It is responsibility of user or person installing drive to provide proper gr ounding and branch circuit protection for incoming power and motor overload according to National Electrical Code (NEC) and local codes.
The Electronic Thermal Relay (ETR) is UL listed. VLTs provide Class 20 motor overload protection in accordance with the NEC in single motor applications, when VLT 6000 parameter 117 (VLT 5000 parameter 128) is set for ETR Trip 1 and parameter 105 is set for rated motor (nameplate) current.
DANGER
!
Touching electrical parts may be fatal – even after equipment has been disconnected from AC line. To be sure that capacitors have fully dis­charged, wait 14 minutes after power has been removed before touching any internal component.
2
MG.60.E4.02 - VLT is a registered Danfoss trademark
Overview
Introduction............................................................................................. 5
About This Manual .................................................................................. 5
Assumptions ........................................................................................... 5
What You Should Already Know ............................................................ 5
References .............................................................................................. 5
LonWorks Overview................................................................................ 6
LON Concept........................................................................................... 6
Applications ............................................................................................ 6
VLT LonWorks Option Card.................................................................... 7
Node Arrangements................................................................................ 7
Message Passing .................................................................................... 7
Collision Detection ................................................................................. 8
Network Management............................................................................. 8
Routers and Bridges............................................................................... 9
Installation
Wiring Installation................................................................................... 10
Card Installation...................................................................................... 10
T ools Required ........................................................................................ 10
VL T LonW orks Option Card.......................................................................11
Installation Instructions ......................................................................... 12
Network Initialization of LonW orks Option Car d .................................. 19
LonMark XIF Files ................................................................................... 19
VLT® 5000 / VLT® 6000
Table of Contents
T wisted Pair Netw ork Configuration
78 kbps and 1.25 Mbps T ransf ormer Coupled Twisted Pair Model ....... 20
Double Terminated Bus Topology........................................................... 20
T erminator Switch ................................................................................... 20
Performance Specification...................................................................... 2 1
Communication on TP/XF-78 and TP/XF-1250 Channels ...................... 21
Diagnostic LEDs
LonWorks Car d Diagnostic LEDs ........................................................... 22
Status LED ............................................................................................... 22
Service LED ............................................................................................. 22
Service LED Patterns and Descriptions ................................................. 23
MG.60.E4.02 - VLT is a registered Danfoss trademark
3
Interface/Network Variables
VL T Adjustable Frequency Drive
and LonWorks Netw ork Configuration ................................................... 24
Network Drive Control Input ................................................................... 24
Drive Feedback to Network ..................................................................... 27
Drive Status Bit Definitions..................................................................... 28
Network Timer Functions....................................................................... 30
VL T P arameter Access ............................................................................ 31
Parameter Access Error Codes............................................................... 32
Parameter Access Command and Response Examples........................ 32
Standard Object Support ........................................................................ 3 4
Alarm Descriptions.................................................................................. 35
Parameters
Parameter List ......................................................................................... 36
Parameter Description............................................................................. 3 6
Decommissioning VLT Adjustable Frequency Drive
Decommissioning VL T Drive from LonW orks Network ......................... 39
VLT® 5000 / VLT® 6000
4
MG.60.E4.02 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000
Introduction
About This Manual
This manual provides comprehensive instructions on the installation and set up of the LonWorks Option Card for the VLT 5000 and the VLT 6000 Adjustable Frequency Drive to communicate over a LonWorks network.
For specific information on installation and operation of the adjustable frequency drive, refer to the VLT 5000 Installation, Operation
and Instruction Manual or VLT 6000 Installation, Operation and Instruction Manual.
This manual is intended to be used for both instruction and reference. It only briefly touches on the basics of the LonWorks protocol whenever it is necessary for gaining an understanding of the LonWorks profile for drives and the LonWorks Option Card for the Adjustable frequency drive.
This manual is also intended to serve as a guideline when you specify and optimize your
Portions of this manual are printed with the permission of the Echelon Corporation and the National Electrical Contractors Association of the USA (NECA).
Echelon®, LonTalk®, Neuron® and LonWorks are registered trademarks of the Echelon Corporation. VLT® is a registered trademark of Danfoss Inc.
communication system. Even if you are an experienced LonWorks programmer, we suggest that you read this manual in its entirety before you start programming, since important information can be found in all sections.
®
Assumptions
What Y ou Should Already Know
References
This manual assumes that you have a controller node that supports the interfaces in this document and that all the requirements stipulated in the controller node, as well as
The Danfoss LonWorks Option Card is designed to communicate with any controller node that supports the interfaces defined in
LonMaker™ for Windows® User's Guide.
VLT® 5000 Installation, Operation and Instruction Manual
(Referred to as the VLT Instruction Manual in this document.)
VLT ®6000 Installation, Operation and Instruction Manual
(Referred to as the VLT Instruction Manual in this document.)
the Adjustable Frequency Drive, are strictly observed along with all limitations therein.
this document. It is assumed that you have full knowledge of the capabilities and limitations of the controller node.
MG.60.E4.02 - VLT is a registered Danfoss trademark
5
VLT® 5000 / VLT® 6000
LonWorks Overview
LON Concept
LonWorks is both an existing standard and hardware developed by Echelon Corporation. Echelon's stated goal is to establish a com­modity solution to the presently daunting problems of designing and building control networks.
The result is LonMark Interoperability which makes it possible for independent network devices to operate together over a LonWorks network. The LonMark program was developed to address interoperability issues. As a result, the LonMark Interoperability Association Task Groups (LonUsers Groups) were developed. The task groups determine that each device on the network has an object definition, create
The LonWorks communications structure is similar to that of a local area network (LAN) in that messages are continually exchanged between a number of processors. A LonWorks system is a determined local operating network (LON). LON technology offers a means for integrating various distributed systems that perform sensing, monitoring, control, and other automated functions. A LON allows these intelligent devices to communicate with one another through an assortment of communications media using a standard protocol.
LON technology supports distributed, peer­to-peer communications. That is, individual
standards and models to be used by particular applications and create a common platform for presenting data. A standard network variable type (SNVT) facilitates interoperability by providing a well defined interface for communication between devices made by different manufacturers. The VLT Adjustable Frequency Drive supports the node object and controller standard object definitions of LonMark Interoperability.
Customers are currently using LonWorks for process control, building automation, motor control, elevator operation, life safety systems, power and HVAC distribution and similar intelligent building applications.
network devices can communicate directly with one another without need for a central control system. A LON is designed to move sense and control messages which are typically very short and which contain commands and status information that trigger actions. LON performance is viewed in terms of transactions completed per second and response time. Control systems do not need vast amounts of data, but they do demand that the messages they send and receive are absolutely correct. The critical factor in LON technology is the assurance of correct signal transmission and verification.
Applications
6
An important LonWorks benefit is the network’s ability to communicate across different types of transmission media. The NEURON chip is the heart of the LonWorks system. The NEURON chip's commu­nication port allows for the use of transceivers for other media (such as coax and fiber optic) to meet special needs.
LonWorks control devices are called nodes. Physically, each node consists of a NEURON chip and a transceiver. With proper design, the nodes become building blocks that can
be applied to control a variety of tasks, such as lighting or ventilating, integrating a variety of communications media.
The tasks which the nodes perform are determined by how they have been connected and configured. Because hardware design, software design, and network design may be independent in a LonWorks-based system, a node’s function can be programmed to accommodate the networks in which it will be used.
MG.60.E4.02 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000
VLT LonWorks Option Card
The Danfoss VLT LonWorks option card is comprised of a control card with a NEURON chip and a memory card. When installed into the VLT adjustable frequency drive, the unit enables the drive to communicate with other devices on the LON. The VLT drive is designed to provide precision control of standard induction electrical motors. The drive receives three reference signals along with start/stop and reset commands from the network. The drive also receives a 16-bit control word that provides full operational control of the drive. (See Network Drive Control Input for additional details.)
In response, the drive provides 16 output network variables containing important drive and motor data. (See Drive Feedback to Network.) Output to the network includes drive status, current, voltage, motor and inverter thermal status, and alarms and warnings.
LonWorks supports many different types of transmission media. A LonWorks network physical layer option can be transformer coupled twisted pair (78 kbps and 1.25 Mbps), free topology, link power, power line, RF, RS-485, fiber optic, coaxial, or infrared.
The VLT LonWorks option supports four transmission media with three versions of the VLT LonWorks option card. The VLT LonWorks option card versions are:
1. Free topology, which also operates on a link power network.
2. 78 kbps transformer coupled twisted pair.
3. 1.25 Mbps transformer coupled twisted pair.
A router is required to interface to a LonWorks network when not supported by one of the three option card versions.
Node Arrangements
Message Passing
LonWorks nodes can be addressed either individually or in groups. A group can contain up to 64 nodes, and one LonWorks network can support 255 groups. Furthermore, any node can be part of 15 different groups. A subnet, very similar to a group, can contain 127 nodes. A domain is the largest arrangement of nodes with a single domain able to handle 255 subnets. Thus a domain can handle 32,385 separate nodes. A single node may be connected to no more than two domains.
The group structure has the advantage of allowing a number of nodes to be reached at only one address. This method reduces the
There are a number of trade-offs between network efficiency, response time, security, and reliability. Generally, LonWorks defaults to the greatest degree of safety and verification for all communications over the LON network. The LonTalk protocol, built into the chips, is the operating system that coordinates the LonWorks system. It offers four basic types of message service.
record keeping inside each chip to a minimum, allowing faster operation. However, high efficiency individual addressing can be done at all levels of a LonWorks system. The address table of a node contains entries for the group type and size and tells the node how many acknowledgments to expect when it sends a message. It also tells the NEURON chip which domain to use and the node group member number, which identifies an acknowledgment as coming from the node. The address also contains a transmit timer, a repeat timer, a retry counter, a receive timer, and the group ID.
The most reliable service is acknowledged (or end-to-end acknowledged service), where a message is sent to a node or group of nodes and individual acknowledgments are ex­pected from each receiver. If an acknowledgment is not received from all des­tinations, the sender times out and re-tries the transaction. The number of retries and time-out duration are both selectable. Ac-
MG.60.E4.02 - VLT is a registered Danfoss trademark
7
VLT® 5000 / VLT® 6000
Message Passing (continued)
Collision Detection
knowledgments are generated by the network host processor without intervention of the ap­plication. Transaction IDs are used to keep track of messages and acknowledgments so that the application does not receive dupli­cate messages.
An equally reliable service is request/response, where a message is sent to a node or group of nodes and individual responses are ex­pected from each receiver. Incoming messages are processed by the application on the receiving side before a response is generated. The same retry and time-out op­tions are available as with acknowledged service. Responses may include data, so that this service is particularly suitable for remote procedure call or client/server applications.
The LonTalk protocol uses a unique collision avoidance algorithm which allows an overloaded channel to carry near to its maximum capacity, rather than reducing its throughput due to excessive collisions between messages. When using a communications medium that supports collision detection, such as twisted pair, the LonTalk protocol can optionally cancel transmission of a packet as soon as a collision is detected by the transceiver. This option
Next in reliability is unacknowledged repeated. Messages are sent multiple times to a node or a group of nodes with no response expected. This service is typically used when broadcasting to large groups of nodes when traffic generated by all the responses would overload the network.
The final method in reliability is unac- knowledged, where a message is sent once to a node or group of nodes and no response is expected. This option is typically used when the highest performance is required, network bandwidth is limited, and the application is not sensitive to the loss of a message.
allows the node to immediately retransmit any packet that has been damaged by a collision. Without collision detection, the node would wait the duration of the retry time to notice that no acknowledgment was received. At that time it would retransmit the packet, assuming acknowledge or request/response service. For unacknowledged service, an undetected collision means that the packet is not received and no retry is attempted.
Network Management
8
Depending on the level of a given application, a LonWorks network may or may not require the use of a network management node. A network management node performs management functions, such as:
• Find unconfigured nodes and download their network addresses.
• Stop, start, and reset node applications.
• Access node communication statistics.
• Configure routers and bridges.
• Download new applications programs.
• Extract the topology of a running network.
MG.60.E4.02 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000
Routers and Bridges
A router (or bridge) is a special node that consists of two connected NEURON chips, each connected to a separate channel (see figure below). Routers and bridges pass packets back and forth between these channels. There are four types of routers. A repeater is the simplest form of router, simply forwarding all packets between the two channels. A bridge simply forwards all packets which match its domains between the two channels. Using a bridge or repeater, a subnet can exist across multiple channels. A learning router monitors the network traffic and learns the network topology at the domain/subnet level. The learning router then uses its knowledge to selectively route packets between channels. Like a learning router, a configured router selectively routes packets between channels by consulting internal routing tables. Unlike a learning router, the contents of the internal routing tables are specified using network management commands.
Initially, each router sets its internal routing tables to indicate that all subnets could lie on either side of the router. Suppose that node 6, in the figure below, generates a message bound for node 2. Learning router 1 initially picks up the message. It examines the source subnet field of the message and notes in its internal routing tables
that subnet 2 lies below it. The router then compares the source and destination subnet IDs and, since they are different, the message is passed on. Meanwhile, learning router 2 also passes the message on, making an appropriate notation in its internal routing tables regarding the location of subnet 2.
Suppose now that node 2 generates an acknowledgment. This acknowledgment is picked up by learning router 1, which now notes the location of subnet 1. Learning router 1 examines its internal routing tables, and, noting that subnet 2 lies below, passes the message on. When the message appears on subnet 2, it is noted by both node 6 (the destination) and learning router 2. Learning router 2 does not pass it on but merely notes that subnet 1, like subnet 2, lies somewhere above. Learning router 2 will not learn of the existence or location of subnet 3 until a message is originated from there. Subnets cannot cross routers. While bridges and repeaters allow subnets to span multiple channels, the two sides of a router must belong to separate subnets. Since routers are selective about the packets they forward to each channel, the total capacity of a system can be increased in terms of nodes and connections.
Channel
1 2 3 4
Subnet 1
Channel
9 10 11 12
Subnet 3
MG.60.E4.02 - VLT is a registered Danfoss trademark
Learning
R
Router 1
Learning Router 2
Learning Routers
Source: Echelon Corp.
R
Channel
5 6 7 8
Subnet 2
9
Wiring
CAUTION
!
CAUTION
!
Installation
WW
iringiring
W
iring
WW
iringiring The adjustable frequency drive generates a carrier frequency with a pulse frequency between 3 kHz and 14 kHz. This results in radiated frequency noise from the motor cables. It is very important that the LonWorks cable be isolated as much as possible from the drive output cabling to the motor. Use shielded wire rather than twisted-pair. Do not run LonWorks cabling and motor cables in parallel or in close proximity to one another. Ensure that the drive is properly grounded.
VLT® 5000 / VLT® 6000
Card Installation
The following section describes the installation procedures for the LonWorks option card (see following illustration). For additional information on installation and operation of the VLT adjustable frequency drive, refer to the VLT Instruction Manual.
DANGER
!
VLT adjustable frequency drive contains dangerous voltages when connected to line power. After disconnecting from line, wait at least 14 minutes before touching any electrical com­ponents.
WARNING
!
Only a competent electrician should carry out electrical installation. Impr oper installation of motor or VLT can cause equipment failure, serious injury or death. Follow this manual, National Electrical Code (USA) and local safety codes.
Electronic components of VLT adjustable frequency drives are sensitive to electrostatic dis­charge (ESD). ESD can reduce performance or destro y sensitive electronic components. Follow proper ESD procedures during installation or servicing to prevent damage.
It is responsibility of user or installer of VLT adjustable frequency drive to provide pr oper grounding and motor overload and branch protection according to National Electrical Code (USA) and local codes.
Tools Required
10
Flat-head screw driver Torx T-10 screw driver Torx T-20 screw driver
MG.60.E4.02 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000
Terminator Switch
Ribbon Cable Socket (to Memory Board)
LEDs
Terminal Connector
Service Pin Switch SW1
Mounting Hole
LEDs
Terminal Connector
Service Pin Switch SW3
Ribbon Cable Socket (to Control Board)
Ribbon Cable Socket (to drive control board)
Host Chip
LonWorks Control Board
Drive Memory
VLT LonWorks Option Card
(Free T opology Model)
MG.60.E4.02 - VLT is a registered Danfoss trademark
Memory Board
11
Installation Instructions
VLT® 5000 / VLT® 6000
1. Access to Control Card Cassette
2. Disconnect Control Card Cassette
IP20/NEMA 1 and Bookstyle
• Remove Local Control Panel (LCP) by pulling out from top of display (A) by hand. LCP connector on panel back will disconnect.
• Remove protective cover by gently prying with a screw driver at notch (B) and lift cover out of guide pin fittings.
IP54/NEMA 12
• Open front panel of drive by loosening captive screws and swing open.
• Disconnect Local Control Panel (LCP) cable from drive control card.
• Remove control wiring by unplugging connector terminals (A).
• Remove grounding clamps (B) by removing two screws holding each in place. Save screws for reassembly.
• Loosen two captive screws (C) securing cassette to chassis.
(A)
(B)
(A)
(B)
12
(C)
MG.60.E4.02 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000
3. Remove Cassette and Ribbon Cables
• Lift control card cassette from bottom.
• Unplug two ribbon cables (A) and (B) from control board.
• Unhinge cassette at top to remove.
NOTE Ribbon cables will need to be reconnected to same connec­tions from which removed.
(A)
(B)
4. Chassis Ground Connections
NOTE Ground strips are used on 208 V drives of 22 kW (30 HP) or less and on 460 V drives of 45 kW (60 HP) or less. For all other drives, go to step 6.
• Location of holes to mount grounding strips can vary with drive configuration. When applicable, remove mounting screws and washers located in chassis using Torx T-20 screw driver and save for reassembly. Otherwise, grounding strips attach with screws and washers provided, as shown in step 5.
MG.60.E4.02 - VLT is a registered Danfoss trademark
13
VLT® 5000 / VLT® 6000
5. Install Chassis Ground Connections
• Align ground strips over screw holes. Strip with fewest contact points mounts on cable side of chassis. Tabs on grounding strips point toward outside of chassis.
• Replace screws removed in step 4 and add additional screws and washers provided, as necessary. Tighten to
0.9 Nm (8 in-lbs) using Torx T-20 screw driver.
Ground Strips
6. Install Ribbon Cables between Option Cards
• Attach ribbon cables between LonWorks control card and memory card.
• Be sure exposed wire portion of ribbon cable (A) is facing front of socket (B). Do not remove blue insulation covering end of ribbon cable.
• Pull up collar (C) of ribbon cable socket, insert cable and push collar closed.
• Repeat procedure for all ribbon cables.
IP20/NEMA 1 and IP54/NEMA 12
• Remove terminal connector from terminal block (D) and connect to terminal block (E) at this time for ease of access.
(D)
(E)
14
MG.60.E4.02 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000
7. Remove LCP Cradle
8. Ribbon Cable Routing
IP20/NEMA 1 and Bookstyle
• Carefully push in tabs at corners of LCP cradle to release clips. Pull out to disengage clips and lift cradle free.
• Route ribbon cables from LonWorks memory card through slot at side of control board cassette.
9. Insert LonWorks Card
MG.60.E4.02 - VLT is a registered Danfoss trademark
• Insert edge of LonWorks cards into slot in side of cassette and align screw holes.
15
VLT® 5000 / VLT® 6000
10. Secure LonW orks Card
11. Install Ribbon Cable on VLT Control Board
• Secure LonWorks card with 3 self-tapping screws and washers provided using Torx T-10 screw driver. Tighten to 8 in-lbs (0.9 Nm).
• Be sure not to twist or crimp ribbon cables.
• Insert cables into corresponding sockets and fasten in accordance with directions in step 5.
12. Install LCP Cradle
16
IP20/NEMA 1 and Bookstyle
• Insert cradle clips into holes in cassette.
• Push down on cradle to snap it into place.
MG.60.E4.02 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000
13. Install Spring T ension Clip
IP20/NEMA 1 and IP54/NEMA 12
• Spring tension clip (A) is used as a cable strain relief and ground point for shielded cable.
• Insert clip through inner wall of chassis at slot provided.
• Compress spring into clip at outer wall of chassis.
(A)
14. Install Ribbon Cables
• Connect ribbon cables.
• Connect control card cassette to hinge at top of drive and fit into chassis.
NOTE Ribbon cables must be recon­nected to same connections from which removed.
MG.60.E4.02 - VLT is a registered Danfoss trademark
17
VLT® 5000 / VLT® 6000
15. Install Control Card Cassette
16. Plug in T erminal Connector
• Fasten control card cassette by alternately tightening two captive screws (A). Tighten to 0.9 Nm (8 in-lbs).
• Route control wires through clamp fasteners (B) and secure clamps with two screws.
• Connect control terminals (C) by firmly pressing them into connector receptacles.
• Connect signal wire NET A to terminal 79 and NET B to 80 of terminal connector. (In free topology model, connections can be reversed.)
(C)
(A)
(B)
61 80 79
IP20/NEMA 1 and IP54/NEMA 12
• Plug network connector into terminal block at side of control card cassette.
• Insert LonWorks cable between inner wall of chassis and spring tension clip.
NOTE Shielded cable is recommended. Ground shielded cable at spring tension clip location or ground at cable clamp by removing cable insulation at contact point. Do not use connector terminal 61.
Bookstyle
• Remove knockout from top of drive (A).
• Route control wires through clamp fasteners (B) on cable plate and secure clamps with screws. Tighten to 0.9 Nm (8 in-lbs).
• Secure cable plate to drive with screws and screw holes provided. Tighten to
0.9 Nm (8 in-lbs).
• Plug network connector (C) into terminal block at top of control card cassette.
(A)
Shield 61
NET B 80
NET A 79
(B)
(C)
18
MG.60.E4.02 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000
Network Initialization of LonW orks Option Card
LonMark XIF Files
The LonWorks option card contains a NEURON chip with a unique address. After hardware installation, initialize the LonWorks option card. Addressing nodes on the LonWorks network is performed at installation time by an installation tool or network management tool. Addressing requires the retrieval of a node’s NEURON ID. The NEURON ID is a 48 bit number that identifies every manufactured NEURON chip. There are several methods by which the network software will initialize the drive automatically. The network can recognize the drive without action beyond proper installation. The card is then ready to be programmed for network operation. The VLT LonWorks option supports three additional methods of addressing a node:
1. Service Pin - There are two momentary-contact service switches that send the NEURON ID over the network. If the network software prompts the action, press
A LonMark interface file (.XIF extension) provides the host processor with device information. With this, it is possible to design a LonWorks network without the adjustable frequency drive being physically present. The VLTLON.XIF can be downloaded from the Internet site www.danfoss.com/drives. The LonWorks option card does not contain an internal interface file.
either service pin (SW1 or SW3) to transmit the NEURON ID over the network. The service pin locations are shown in the illustration in Terminator and Service Switch Locations in this manual.
2. Query and Wink - The LonWorks option card is shipped with a domain of “0” and subnet of “1.” Upon receiving the wink command, the on-board green status LED flashes so that the installer can locate the node. The chip sends out its Neuron ID over the network in response to the query command.
3. NEURON ID Label - The VLT LonWorks option card has a NEURON ID label that displays the NEURON ID as a 12 digit hexadecimal number. The installer can manually enter the NEURON ID during installation.
The VLT LonWorks network interface consists only of SNVTs. The SNVTs support the LonMark Controller Profile along with VLT configuration, control and monitoring capabilities. Any combination of SNVTs can be used to operate the VLT.
Echelon Corporation has also developed a set of free plug-ins available through their web site at www.echelon.com/plugin/default.htm. Also intended for network design, these plug-ins provide easy access to screens which simplify the process of manually setting up the drive, testing, and monitoring operation.
The drive may also be added to the network upon initialization.
MG.60.E4.02 - VLT is a registered Danfoss trademark
19
VLT® 5000 / VLT® 6000
78 kbps and
1.25 Mbps Transformer Coupled Twisted Pair Model
Doubly Terminated Bus Topology
T erminator and Service Switch Locations
The 78 kbps and 1.25 Mbps Transformer Coupled Twisted Pair model system is designed to support doubly terminated bus topology.
TRANSCEIVER
TERMINATION
The terminator switch location for the 78 kbps or 1.25 Mbps Transformer Coupled Twisted Pair model is shown below.
TT
erminator Switcherminator Switch
T
erminator Switch
TT
erminator Switcherminator Switch
TERMINATION
Service Pin SwitchesService Pin Switches
Service Pin Switches
Service Pin SwitchesService Pin Switches
Switch 1:Switch 1:
Switch 1:
Switch 1:Switch 1:
Network TNetwork T
Network T
Network TNetwork T The VLT LonWorks node is terminated.
Network TNetwork T
Network T
Network TNetwork T The VLT LonWorks node is not
terminated. Factory setting.
ermination ONermination ON
ermination ON
ermination ONermination ON
ermination OFFermination OFF
ermination OFF
ermination OFFermination OFF
78 kbps and 1.25 Mbps LonWorks
Control Card
20
MG.60.E4.02 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000
CAUTION
!
Performance Specification
Communica­tion on TP/ XF-78 and TP/XF-1250 Channels
The table below provides a summary of the performance specifications for the 78 kbps and
PerformancePerformance
Performance
PerformancePerformance SpecificationsSpecifications
Specifications
SpecificationsSpecifications
TP/XF-78TP/XF-78
TP/XF-78
TP/XF-78TP/XF-78
1.25 Mbps transformer-coupled twisted pair channels.
TP/XF-1250TP/XF-1250
TP/XF-1250
TP/XF-1250TP/XF-1250
Transmission Speed 78kbps 1.25Mbps Nodes per Channel 64 64 Network Bus Wiring UL Level IV, 0.65 mm (22 AWG) shielded Network Stub Wiring UL Level IV, 0.5 mm (22 or 24 AWG) shielded Network Bus Length
Typical Worst case
Maximum Stub Length
1
2
2000m (6,560 ft) 500m (1,640 ft) 1330m (4,360 ft) 125m (410 ft)
3
3m (10 ft) 0.3m (0 to 70°C)
1 ft (32°F to 158°F) Network Terminators Required at both ends of the network Temperature
Operating 0 to 70°C (64 nodes) 0 to +70°C (64 nodes)
(32°F to 158°F) (32°F to 158°F)
Non-operating –40 to +85°C (44 nodes) –20 to +85°C (32 nodes)
(–40°F to +185°F) (–4°F to +185°F)
–40 to +70°C (20 nodes)
(–40°F to +158°F) Electrostatic Discharge
to Network Connectors
No Errors to 15,000 V to 15,000 V No Hard Failures to 20,000 V to 20,000 V
Isolation between Network and I/O Connectors
0 - 60Hz (60 seconds) 1,000 VRMS 1,000 VRMS 0 - 60Hz (continuous) 277 VRMS 277 VRMS
MG.60.E4.02 - VLT is a registered Danfoss trademark
1
Typical conditions are 20°C (68°F), +5 VDC
supply voltage, normal wire temperature, and 64 evenly distributed nodes.
2
Worst case conditions are the combined
effect of worst case conditions of all the above performance parameters — nodes per channel, network bus length, stub length, temperature, etc.
3
The stub length in the table assumes a mutual
capacitance of 56 pF/m (17 pF/ft) for the twisted pair stub cable. Actual lengths may be shorter or longer depending on the actual, measured value.
It is necessary to terminate theIt is necessary to terminate the
It is necessary to terminate the
It is necessary to terminate theIt is necessary to terminate the ends of a TP/XF-78 or TP/XF-1250ends of a TP/XF-78 or TP/XF-1250
ends of a TP/XF-78 or TP/XF-1250
ends of a TP/XF-78 or TP/XF-1250ends of a TP/XF-78 or TP/XF-1250 twisted pair bus to minimizetwisted pair bus to minimize
twisted pair bus to minimize
twisted pair bus to minimizetwisted pair bus to minimize rr
eflections. Failureflections. Failur
r
eflections. Failur
rr
eflections. Failureflections. Failur
bus will degrade networkbus will degrade network
bus will degrade network
bus will degrade networkbus will degrade network performance.performance.
performance.
performance.performance.
e to terminate thee to terminate the
e to terminate the
e to terminate thee to terminate the
21
VLT® 5000 / VLT® 6000
LonW orks Card Diagnostic LEDs
Status LED
The LonWorks board includes two LEDs to display the communication status of the board, display the state of the NEURON chip, and respond to the network management
The Status LED patterThe Status LED patter
The Status LED patter
The Status LED patterThe Status LED patter
ONON
ON
ONON
There is power on the board but there has not been any communication to an input network variable in the last 2 seconds.
Flashing 10 times per secondFlashing 10 times per second
Flashing 10 times per second
Flashing 10 times per secondFlashing 10 times per second
There is regular network communication to the VLT's input network variables.
Flashing intermittentlyFlashing intermittently
Flashing intermittently
Flashing intermittentlyFlashing intermittently
There is network communication to the VLT's input network variables but input network variables are received at a period greater than 2 seconds.
ns arns ar
ns ar
ns arns ar
e:e:
e:
e:e:
“wink” command. The onboard LEDs are the Service LED (LED 1, red) and the Status LED (LED 2, green).
LEDsLEDs
LEDs
LEDsLEDs
Service LED
Flashing 5 times per secondFlashing 5 times per second
Flashing 5 times per second
Flashing 5 times per secondFlashing 5 times per second
The response to the network management “Wink” command. The VLT LonWorks node must be reset to leave the wink state.
OFFOFF
OFF
OFFOFF
No power on board or hardware fault.
The Service LED displays the state of the NEURON chip. The following table shows the Service LED patterns for various states and defines their meaning.
22
MG.60.E4.02 - VLT is a registered Danfoss trademark
Service LED Patterns and Descriptions
LED Pattern Operation Description
Continuously ON Power-up of Neuron 3120xx
chip-based node or Neuron 3150 chip-based node with any PROM
VLT® 5000 / VLT® 6000
Use EEBLANK and follow reinitialization procedure.
Continuously OFF Power-up of Neuron 3120xx
chip-based node or Neuron 3150 chip-based node with any PROM
ON for one second at power-up followed by approximately 2 seconds OFF, then stays ON
Short flash every 3 seconds Anytime
Flashing at 1 second intervals Anytime Indicates node is unconfigured
Power-up/Reset May be caused by Neuron chip
Indicates bad node hardware.
firmware when mismatch occurs in application checksum.
Indicates watchdog timer resets occurring.
Possible corrupt EEPROM.
For Neuron 3150 chip-based node, use EEBLANK and follow reinitialization procedure.
but has an application. Proceed with loading node.
Brief flash at power-up. OFF duration approximately 10 seconds after which stays ON
Brief flash at power-up. OFF duration approximately 1 to 15 seconds, depending on application size and system clock. LED then begins flashing at 1 second intervals.
Brief flash at power-up followed by OFF
MG.60.E4.02 - VLT is a registered Danfoss trademark
Using EEBLANK or Neuron 3150 chip-based node
First power-up with new PROM on Neuron 3150 chip­based custom node. Unconfigured firmware state exported.
Indicate completion of blanking process.
Indicates unconfigured state.
Node is configuring and running normally.
Service LED Pattern Descriptions
23
VLT® 5000 / VLT® 6000
VLT adjustable frequency drive and LonWorks Network
Configuration Network
Drive Control
Input
The VLT LonWorks option card supports LonMark network design to improve interoperability. The Controller Object contains the VLT Adjustable Frequency Drive profile. The configuration parameters are network
The most common functions for controlling the VLT Adjustable Frequency Drive from the LonWorks network are made readily available. Those functions and their descriptions are presented in the table below. The control word function accesses additional drive capabilities for network control.
The choice of open loop or closed loop operation of the drive is selected in parameter 100, Configuration.
Using nviRefPcnt, the drive's reference is expressed as a percentage of the reference range. The range is set using parameters 204, Min. Reference and 205, Max. Reference. In open loop operation, reference represents the drive's desired output speed. In this case, set Min. Reference to 0 Hz and Max. Reference equal to Max. Frequency in parameter 202.
In closed loop operation, reference represents the desired setpoint. It is recommended that parameters 204 and 205 be set equal to parameters 201, Min. Frequency and 202, Max. Frequency.
variable inputs to the VLT. Configuration of parameters needs setting only one time, usually at installation.
analog input terminals should not be used for reference signals. The default setting (0%) should be maintained for preset references in parameters 211 (215) through 214 (218). Also, in closed loop operation, the default setting (0.0) should be maintained for drive setpoints in parameters 418 (215) and 419 (218).
Start/Stop and Reset fault SNVT_lev_disc. ST_OFF and ST_NUL are interpreted as low or “0.” ST_LOW, ST_MED, ST_HIGH, and ST_ON are interpreted as high or “1.”
NOTE T o optimize network performance and for proper drive operation, use only one of following input reference commands.
Reference 1
Network variable nviRefPcnt is a signed value. It represents the desired percentage of the VLT drive's reference range.
24
All references provided to the drive are added to the total reference value. If reference is to be controlled by the LonWorks bus only, ensure that all other reference inputs are zero. This means that digital input terminals and
Function SNVT type Variable Name Units Max Min Start/Stop SNVT_lev_disc nviStartStop Boolean Start Stop
*Reset fault SNVT_lev_disc nviResetFault Boolean Reset Enable
Reference 1 SNVT_lev_percent nviRefPcnt 0.005% 163.835 –163.840
Reference 2 SNVT_angle_vel nviRefRads 0.1 rad/sec 3276.7 –3276.8 Reference 3 SNVT_freq_hz nviRefHz 0.1 Hz 6553.5 0 Control word SNVT_state nviControlword 16 Boolean NA NA
* Reset on a transition from 0 to 1. A 0 must be sent after reset to enable the next reset.
Network Variable Inputs to VLT
VLT 5000 parameters are shown in parenthesis, where applicable.
MG.60.E4.02 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000
p
p
p
p
p
q
q
p
p
g
g
g
g
)
)
)
p
)
)
)
)
g
g
g
g
g
g
e
e
Network Drive Control Input
(continued)
Reference 2
Network variable nviRefRads is a signed value. A negative value is interpreted as zero. It represents the desired output frequency of the drive in radians/second in open loop. It is rarely used in closed loop.
Reference 3
Network variable nviRefHz is an unsigned value. It represents the output frequency of the drive in Hz in open loop. It is rarely used in closed loop mode.
Control Word
The input network variable nviControlWord is a 16-bit word that provides additional operational control of the drive, as listed in the table below. The settings shown represent the Coast Stop command
Bit
Bit Setting
Setting 00001
BitBit
SettingSetting
00
00 0000Preset Ref. LSB
0000 01
01 0000Preset Ref. MSB
0101 02
02 1111DC Brake
0202 03
03 0000 Coast Stop
0303 04
04 1111Quick Stop
0404 05
05 1111 Freeze Freq.
0505 06
06 0000Ramp Stop
0606 07
07 0000 no Reset
0707 08
08 0000no Jog
0808 09
09 0000 no function
0909 10
10 1111 see Parm. 805
1010 11
11 0000 Relay 1 OFF
1111 12
12 0000 Relay 2 OFF
1212 13
13 0000 Setup LSB
1313 14
14 0000 Setup MSB
1414 15
15 0000no Reversing
1515
Preset Ref. LSB
Preset Ref. LSBPreset Ref. LSB
Preset Ref. MSB
Preset Ref. MSBPreset Ref. MSB
DC Brake no DC Brake
DC BrakeDC Brake
Coast Stop no Coast Stop
Coast StopCoast Stop
Quick Stop no Quick Stop
Quick StopQuick Stop
Freeze Freq. no Freeze Freq.
Freeze Freq.Freeze Freq.
Ramp Stop Start
Ramp StopRamp Stop
no Reset Reset
no Resetno Reset
no Jog Jog
no Jogno Jog
no function 02
no functionno function
see Parm. 805 03
see Parm. 805see Parm. 805
Relay 1 OFF Relay 1 ON
Relay 1 OFFRelay 1 OFF Relay 2 OFF Relay 2 ON
Relay 2 OFFRelay 2 OFF
no Reversing Reversing
no Reversingno Reversing
Setup LSB 06
Setup LSBSetup LSB Setup MSB 07
Setup MSBSetup MSB
1
11
no DC Brake
no DC Brakeno DC Brake
no Coast Stop
no Coast Stopno Coast Stop no Quick Stop
no Quick Stopno Quick Stop
no Freeze Freq. nviStartStop
no Freeze Freq.no Freeze Freq.
Start Bit
StartStart
Reset 00
ResetReset
Jog 01
JogJog
Relay 1 ON 04
Relay 1 ONRelay 1 ON Relay 2 ON 05
Relay 2 ONRelay 2 ON
Reversing 08
ReversingReversing
Control Word Bit Descriptions
for Coast Stop
The VLT 5000 allows the choice between two control word profiles, selected in parameter 512, Telegram Profile. The table below defines the Profidrive control word used for transmitting commands to the drive using the Profibus protocol.
Bit
Bit 1111
BitBit 00
00 ON 1
0000 01
01 ON 2
0101 02
02 ON 3
0202 03
03 Enable
0303 04
04 Ramp
0404 05
05 Ramp Enable
0505 06
06 Start
0606 07
07 Reset
0707 08
08 ON
0808 09
09 ON
0909 10
10 Valid
1010 11
11 Slow down
1111 12
12 Catch up
1212 13
13
1313 14
14
1414 15
15 Reversing
1515
Valu
Value
ValueValu
32768
32768
3276832768
16384
16384
1638416384
8192
8192
81928192 4096
4096
40964096 2048
2048
20482048 1024
1024
10241024
512
512
512512 256
256
256256 128
128
128128
64
64
6464 32
32
3232 16
16
1616
8888 4444 2222 1111
0000
OFF 1
OFF 1
OFF 1OFF 1 OFF 2
OFF 2
OFF 2OFF 2 OFF 3
OFF 3
OFF 3OFF 3
Motor coastin
Motor coastin
Motor coastin
Motor coastin
Quick stop
Quick stop
Quick sto
Quick sto
Freeze out freq.
Freeze out fre
Freeze out fre
sto
Ramp sto
Ram
Ramp sto
Ramp sto
No function
No function
No functionNo function
Jo
1 OFF
1 OFF
Jo
Jo
1 OFFJog 1 OFF 2 OFF
2 OFF
Jo
Jo
Jo
2 OFFJog 2 OFF
Data not valid
Data not valid
Data not validData not valid
No function
No function
No functionNo function
No function
No function
No functionNo function
No function
No function
No functionNo function
Setup 1 (LSB)
Setup 1 (LSB
Setup 1 (LSB
Setup 1 (LSB
Setup 2 (MSB
Setu
Setup 2 (MSB
Setup 2 (MSB
.
.Freeze out freq.
2 (MSB
ON 1
ON 1ON 1 ON 2
ON 2ON 2 ON 3
ON 3ON 3
Enable
EnableEnable
Ramp
RampRamp
Ramp Enable
Ramp EnableRamp Enable
Start
StartStart
Reset
ResetReset
ON
ONON ON
ONON
Valid
ValidValid
Slow down
Slow downSlow down
Catch up
Catch upCatch up
Reversing
ReversingReversing
Profidrive Control W ord Bit
Descriptions
The equivalent control word bit settings to start and stop the drive (nviStartStop) and to reset after a fault (nviResetFault) are described in the table below.
nviStartStop nviResetFault
nviStartStopnviStartStop
Bit 00001
BitBit 00 00000
0000 01 00000
0101 02 11111
0202 03 11111
0303 04 11111
0404 05 11111
0505 06 00001
0606 07 00000
0707 08 00000
0808 09
09 00000
0909 10
10 11111
1010 11
11 00000
1111 12
12 00000
1212 13
13 00000
1313 14
14 00000
1414 15
15 00000
1515
nviResetFault
nviResetFaultnviResetFault
10
01
11
00
00
00 00
00 11
11 11
11 11
11 11
11 10
11 01
00 00
00 00
00 11
11 00
00 00
00 00
00 00
00 00
00
1 Description
Description
11
DescriptionDescription
0Preset Ref LSB
Preset Ref LSB
00
Preset Ref LSBPreset Ref LSB
0Preset Ref MSB
Preset Ref MSB
00
Preset Ref MSBPreset Ref MSB
1No DC Brake
No DC Brake
11
No DC BrakeNo DC Brake
1 No Coast Stop
No Coast Stop
11
No Coast StopNo Coast Stop
1 No Quick Stop
No Quick Stop
11
No Quick StopNo Quick Stop
1 No Freeze Freq.
No Freeze Freq.
11
No Freeze Freq.No Freeze Freq.
0Start
Start
00
StartStart
1 Reset
Reset
11
ResetReset
0Jog
Jog
00
JogJog
0 No function
No function
00
No functionNo function
1Bit 10
Bit 10
11
Bit 10Bit 10
0 Relay 1 On
Relay 1 On
00
Relay 1 OnRelay 1 On
0 Relay 2 On
Relay 2 On
00
Relay 2 OnRelay 2 On
0 Setup LSB
Setup LSB
00
Setup LSBSetup LSB
0Setup MSB
Setup MSB
00
No value is written to the control word
No value is written to the control word
No value is written to the control word
No value is written to the control word
Setup MSBSetup MSB
0 Reversing
Reversing
00
ReversingReversing
Start/Stop and Fault Reset Control W ord
Bit Descriptions
NOTE Drive always stops and ignores serial bus commands to run when OFF/STOP or STOP/RESET function is activated from drive keypad.
VLT 5000 parameters are shown in parenthesis, where applicable.
MG.60.E4.02 - VLT is a registered Danfoss trademark
25
Precedence of the stop commands is:
1. Coast stop
2. Quick stop
3. DC brake stop
4. Ramp stop
Coast stop
The drive output stops immediately and the motor coasts to a stop.
• Drive display show UN.READY (unit ready) when coast stop is active.
• Drive cannot run in any mode.
• Parameter 503 (502), Coasting stop, determines interaction with input 27.
Quick stop
The drive output frequency ramps down to 0 Hz according to time set in parameter 207 (212), Ramp Down Time.
• Drive display shows STOP.
• Drive cannot run in AUTO mode but can run in HAND mode.
VLT® 5000 / VLT® 6000
Ramp stop
The drive output frequency ramps down to 0 Hz according to time set in parameter 207, Ramp Down Time.
• Factory setting is 60 sec for fan applications and 10 sec for most pump applications.
• Drive display shows STAND BY.
• Drive can run in HAND mode or AUTO through a digital input command.
• Parameter 505, Start, determines interaction with input 18.
DC brake stop
The drive brakes the motor to a stop using DC injection braking.
• Parameters 114 (125) and 115 (126) determine amount and time of DC current applied for braking.
• Drive display shows DC STOP.
• Drive cannot run in AUTO mode but can run in HAND mode.
• Parameter 504, DC Brake, determines interaction with input
27.
26
MG.60.E4.02 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000
Drive Feedback to Network
The VLT LonWorks option provides 16 output variables to the network containing important drive and motor feedback data. Feedback data is sent when there is a change in value. The VLT LonWorks option will only transmit bound network variables. Since some data changes continuously, the transmission rate of those variables is limited. Min send time specifies the minimum time between transmissions of
The Drive Outputs (1, 2, or 3) will have a maximum time between transmission set by the Max send time. This function acts as a transmit heartbeat and allows a controller node to determine the health of the controller/VLT connection. The Max send time function is disabled when the configuration network variable nciMaxsendT is not configured or is set to “0.”
variables.
Function SNVT type Variable Name Units Max Min Drive status SNVT_state nvoDrvStatus 16 Boolean NA NA Drive output 1 SNVT_lev_percent nvoOutputPcnt 0.005% 163.835 – Current SNVT_amp nvoDrvCurnt 0.1 amps 3276.7 0 Energy SNVT_elec_kwh nvoDrvEnrg 1 kWh 65,535 0 Power SNVT_power_kilo nvoDrvPwr 0.1 kW 6553.5 0 Statusword SNVT_state nvoStatusWord 16 Boolean NA NA Drive output 2 SNVT_angle_vel nvoOutputRads 0.1 rad/sec 3276.7 –3276.8 Drive output 3 SNVT_freq_hz nvoOutputHz 0.1 Hz 6553.5 0 Output voltage SNVT_volt nvoVoltage 0.1 V 3276.7 –3276.8 Digital input SNVT_state nvoDigitlInput 16 Boolean NA NA Alarm SNVT_state nvoAlarmWord 16 Boolean NA NA Warning 1 SNVT_state nvoWarning1 16 Boolean NA NA Warning 2 SNVT_state nvoWarning2 16 Boolean NA NA DC voltage SNVT_volt nvoDCVolt 0.1 V 3276.7 0 Motor temp SNVT_lev_cont nvoTempMtr 0.5 % 100 0 Inverter temp SNVT_lev_cont nvoTempInvrtr 0.5 % 100 0
163.840
Drive status
NvoDrvStatus, nvoStatusWord, nvo­DigitalInput, nvoAlarmWord, nvoWarning1 and nvoWarning2 are all 16 bit Boolean values using the SNVT_state variable type. Individual bits represent specific drive status states. The tables provided in Drive Status Bit Definitions define each bit.
Drive output 1
Network variable nvoOutputPcnt provides an analog indication of drive operation. In open loop, this is the drive output frequency in percentage within the reference range. To avoid negative numbers, or numbers above 100%, set parameter 204, Min. Reference to 0 Hz, and parameter 205, Max. Reference equal to parameter 202, Max. Frequency.
VLT 5000 parameters are shown in parenthesis, where applicable.
MG.60.E4.02 - VLT is a registered Danfoss trademark
Network Variable Outputs from VLT
In closed loop, this is the drive's feedback signal within the reference range. For best operation, set Min. Reference to equal parameter 413 (414), Min. Feedback, and
Max. Reference to equal parameter 414 (415), Max. Feedback.
Drive output 2 and Drive Output 3
Output 2 is useful in open loop to report the drive's output frequency in rad/sec. Output 3 in open loop reports the drive's output in Hz. Note that in closed loop nvoOutputHz will report the actual Feedback and not the output frequency. For best results, set Min. Reference to 0 Hz and Max. Reference equal to Max. Frequency. These variable are rarely used in closed loop.
27
VLT 6000 Drive Status Bit Definitions
Bit Value 0 1 Bit Value 0 1 00 32768 33 OFF 33 ON 00 32768
01 16384 32 OFF 32 ON 01 16384 02 8192 29 OFF 29 ON 02 8192 03 4096 27 OFF 27 ON 03 4096 04 2048 19 OFF 19 ON 04 2048 05 1024 18 OFF 18 ON 05 1024 06 512 17 OFF 17 ON 06 512 07 256 16 OFF 16 ON 07 256 08 128 no function 08 128 09 64 no function 09 64 10 32 no function 10 32 11 16 no function 11 16 12 8 no function 12 8 13 4 no function 13 4 Stopped Running 14 2 no function 14 2 No Warning Warning 15 1 no function 15 1 no Alarm Alarm
Bit Value 0 1 Bit Value 0 1 00 32768 Alarm Ctrl. Ready 00 32768 normal Unknown Fault
01 16384 Alarm Drive Ready 01 16384 normal Trip Lock 02 8192 Safety Open Safety Closed 02 8192 normal AMA Fault 03 4096 No Alarm Alarm 03 4096 normal HPFB Timeout 04 2048 04 2048 normal RS-485 Timeout 05 1024 05 1024 normal ASIC Fault 06 512 06 512 normal Short circuit 07 256 no Warning Warning 07 256 normal SMPS Fault 08 128 Not at Ref. at Ref. 08 128 normal Ground Fault 09 64 Hand Mode Auto Mode 09 64 normal Overcurrent 10 32 Fr. Range Warn Freq. in Range 10 32 normal Current limit 11 16 Stopped Running 11 16 normal Mtr. Thermistor 12 8 no used 12 8 normal Motor thermal 13 4 normal Voltage Warn. 13 4 normal Undervoltage 14 2 normal Current lim. 14 2 normal Overvoltage 15 1 normal Therm. Warning 15 1 normal In. Phase loss
no function no function no function no function no function no function no function no function no function no function no function no function no function
nvoDigitalInput
not used not used not used
nvoDrvStatus
nvoStatusWord nvoAlarmWord
VLT® 5000 / VLT® 6000
Bit Value 0 1 Bit Value 0 1 00 32768 normal Ref. High 00 32768 normal Autoramping
01 16384 normal Ctrl. Crd. Fault 01 16384 normal Start Delay 02 8192 normal Pwr. Crd. Fault 02 8192 normal Sleep Boost 03 4096 normal HPFB Timeout 03 4096 normal Sleep 04 2048 normal RS-485 Timeout 04 2048 normal AMA Done 05 1024 normal Overcurrent 05 1024 normal AMA Running 06 512 normal Current limit 06 512 normal Rev. Start 07 256 normal Thermistor O.T. 07 256 no Ramp Ramping 08 128 normal Motor O.T. 08 128 Forward Reverse 09 64 normal Inverter O.T. 09 64 not at Ref. at Reference 10 32 normal U.V. Alarm 10 32 Stopped Running 11 16 normal O.V. Alarm 11 16 Remote Ref. Local Ref. 12 8 normal U.V. Warning 12 8 normal OFF (HOA) 13 4 normal O.V. Warning 13 4 Auto Start/stop Hand 14 2 normal Input Phase Loss 14 2 normal Run Request 15 1 normal Live Zero 15 1 Run Permission no Run Perm.
nvoWarning1 nvoWarning2
28
MG.60.E4.02 - VLT is a registered Danfoss trademark
VLT 5000 Drive Status Bit Definitions
Bit Value 0 1 Bit Value 0 1 00 32768 33 OFF 33 ON 00 32768
01 16384 32 OFF 32 ON 01 16384 02 8192 29 OFF 29 ON 02 8192 03 4096 27 OFF 27 ON 03 4096 04 2048 19 OFF 19 ON 04 2048 05 1024 18 OFF 18 ON 05 1024 06 512 17 OFF 17 ON 06 512 07 256 16 OFF 16 ON 07 256 08 128 no function 08 128 09 64 no function 09 64 10 32 no function 10 32 11 16 no function 11 16 12 8 no function 12 8 Remote Local 13 4 no function 13 4 Stopped Running 14 2 no function 14 2 No Warning Warning 15 1 no function 15 1 no Alarm Alarm
Bit Value 0 1 Bit Value 0 1 00 32768 Alarm Ctrl. Ready 00 32768 normal Brake Test fail
01 16384 Alarm Drive Ready 01 16384 normal Trip Lock 02 8192 Safety Open Safety Closed 02 8192 normal AMA Fault 03 4096 No Alarm Alarm 03 4096 normal AMA OK 04 2048 04 2048 normal Power Up Fault 05 1024 05 1024 normal ASIC Fault 06 512 06 512 normal HPFB Timeout 07 256 no Warning Warning 07 256 normal RS-485 Timeout 08 128 Not at Ref. at Ref. 08 128 normal Short circuit 09 64 Local Bus Control 09 64 normal Power Fault 10 32 Fr. Range Warn Freq. in Range 10 32 normal Ground Fault 11 16 Stopped Running 11 16 normal Over current 12 8 no used Stall, Autostart 12 8 normal Torque limit 13 4 normal Voltage Warn. 13 4 normal Motor Thermal 14 2 normal Current lim. 14 2 normal Motor Overload 15 1 normal Therm. Warning 15 1 normal Inverter Overload
nvoDigitalInput
nvoStatusWord
VLT® 5000 / VLT® 6000
no function no function no function no function no function no function no function no function no function no function no function no function
nvoDrvStatus
not used not used not used
nvoAlarmWord
Bit Value 0 1 Bit Value 0 1 00 32768 normal Brake Test Fault 00 32768 normal Ramping
01 16384 normal Ctrl. Crd. Fault 01 16384 normal AMT 02 8192 normal Pwr. Crd. Fault 02 8192 normal Start Fwd/Rev 03 4096 normal HPFB Timeout 03 4096 normal Slow down 04 2048 normal RS-485 Timeout 04 2048 normal Catch up 05 1024 normal Overcurrent 05 1024 normal FB High 06 512 normal Torque limit 06 512 normal FB Low 07 256 normal Thermistor O.T. 07 256 normal Current High 08 128 normal Motor O.T. 08 128 normal Current Low 09 64 normal Inverter O.T. 09 64 normal Freq. High 10 32 normal U.V. Alarm 10 32 normal Freg. Low 11 16 normal O.V. Alarm 11 16 normal Brake Test OK 12 8 normal U.V. Warning 12 8 normal Braking Max. 13 4 normal O.V. Warning 13 4 normal Braking 14 2 normal Input Phase Loss 14 2 normal Discharge OK 15 1 normal No motor 15 1 normal Out Freq. Range
nvoWarning1
MG.60.E4.02 - VLT is a registered Danfoss trademark
nvoWarning2
29
VLT® 5000 / VLT® 6000
Network Timer Functions
Function SNVT Variable Units Max Min Default
type Name
Min send SNVT nciMin- time 0 days 0 days 0 days time _elapsed SendT 0 hours 0 hours 0 hours
_tm 1 min 0 min 0 min
5 sec 0 sec 0 sec 535 msec 100 msec
30 msec
Max SNVT nciMax- time 0 days 0 days 0 days receive _elapsed ReceiveT 18 hours 0 hours 0 hours time _tm 12 min 0 min 0 min
15 sec 1 sec 0 sec 0 msec 0 msec 0 msec
Max SNVT nciMax- time 0 days 0 days 0 days send _elapsed SendT 0 hours 0 hours 0 hours time _tm 1 min 0 min 0 min
5 sec 0 sec 0 sec 535 msec 100 msec
30 msec
1
78 kbps transformer coupled twisted pair and 78 Kbps free topology transceiver models.
2
1.25 Mbps transformer coupled twisted pair transceiver model.
2
2
1
1
500 msec
(Off)
0 msec (Off)
Network Timer Functions
Min send time
Sets the minimum period between transmissions for all output network variables, using the network variable nciMinSendT. This function is used to keep the transmission of variables that change continuously from dominating the network communication.
Max receive time
This drive function is replaced by the value set in parameter 803, Bus Time Out. The LonWorks option will initiate bus time out activities when the time set in parameter 803 expires without receiving an input network variable directed to the drive. This acts like a LonWorks receive heartbeat. The action taken by the drive is determined by the setting selected in parameter 804, Bus time out function. See the parameter description section of this manual. The value of nciMaxReceiveT has no effect on the operation of the drive.
Max send time
This function sets the maximum time between transmissions for the network variables Drive Output 1, 2, and 3 using the configuration network variable nciMaxSendT. It can be used by the controller to monitor the health of the VLT and controller connection. It acts like a LonWorks send heartbeat.
The Max send time function is disabled when nciMaxSendT is not configured or set to “0.”
30
MG.60.E4.02 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000
VL T Parameter Access
A controller node can monitor or modify any VLT parameter by supporting the Parameter
access command and the Parameter access response functions. These functions allow a
controller complete access to the features of the VLT and the ability to configure drives with predefined settings, using the network variables nviParamCmd and nvoParamResp.
The following definitions describe how the fields of SNVT_preset are used by the VLT LonWorks option:
Learn
This field contains the function code for the VLT. The values for this field are:
LN_RECALL (0), LN_LEARN_CURRENT (1), LN_LEARN_VALUE (2), and LN_REPORT_VALUE (3).
LN_RECALL (0) and LN_REPORT_VALUE (3) are interpreted as read commands.
LN_LEARN_CURRENT (1) and LN_LEARN_VALUE (2) are interpreted as write commands.
Any other value in this field will result in an error message in the Parameter access
response.
Selector
This field contains the VLT parameter number, written in decimal notation, that is to be written or read. Requests for undefined parameters will result in an error message in the Parameter access esponse.
The controlling device should compare the parameter number of the response message to the requested parameter number to determine that the information received is the requested information and not a response to another controller or from another VLT.
Value
This array contains the parameter information to and from the VLT. All VLT parameters use 16 bit signed or unsigned values. The most significant 2 hex bytes of data will be stored in value [0] and the least significant 2 hex bytes of data will be stored in value [3]. In the event of an error message, the VLT will send 0xff in value [0] and an error code in value [3]. The error codes are defined in the section Parameter Access Error Codes in this manual.
NOTE
Consult
Conversion Inde x
in
the VLT Instruction Manual
parameter table for correct conversion factor f or reading and writing to and from drive.
Day, Hour, Minute, Second, Millisecond
The time fields are not supported by the VLT LonWorks option. The VLT will respond to parameter access requests as soon as they are received. Any values in the time fields of the Parameter access command will be ignored. All time fields will be set to “0” in the Parameter access response.
Function SNVT type Variable Name Parameter access command SNVT_preset nviParamCmd
Function SNVT type Variable Name Parameter access response SNVT_preset nvoParamResp
MG.60.E4.02 - VLT is a registered Danfoss trademark
Network Variable Input to VLT
Network Variable Output from VLT
31
VLT® 5000 / VLT® 6000
CAUTION
!
Parameter Access Error Codes
Parameter Access Command and Response Examples
In the event of an error message in response to a Parameter access command (see VLT Parameter Access), the VLT sends 0xff in value
Parameter Access Error Codes
Exception Code Interpretation
1 Illegal function for the addressed node 2 Illegal data address (i.e., illegal parameter number) 3 Illegal data value 6 Busy
The examples below demonstrate use of the
parameter access command and parameter access response functions of the controller
node. In the examples, the controller node has a parameter access command SNVT_preset called nvoParamCmd and a parameter access response SNVT_preset called nviParamResp. In writing to the drive correctly, the access response simply repeats the entered data. In the event of an error, an error code is displayed in value [3]. See Parameter Access Error Codes above.
bit [0] and an error code in value [3]. Error code definitions are presented in the table below.
Parameter 971 must be set to STORE ACTIVE SETUP for entering data values through LonWorks
command
changes in drive. See parameter 971 in section of this manual.
Consult conversion index in the
VL T Instruction Manual
table for correct conversion factor for reading and writing to and from drive.
parameter access
in order to save
Parameter Descriptions
NOTE
parameter
Example 1:
32
The controller node writes 30 seconds to parameter 206 (205), Ramp time up of the VLT. Conversion index is 0, so the conversion factor is 1.0 (VLT 5000 conversion factor -2)).
The controller node access command sends the following parameter write request to the VLT.
nvoParamCmd.learn= LN_LEARN_CURRENT nvoParamCmd.selector = 206 nvoParamCmd.value[0] = 0 nvoParamCmd.value[1] = 0 nvoParamCmd.value[2] = 0 nvoParamCmd.value[3] = 1E hex (30 decimal)
VLT 5000 parameters are shown in parenthesis, where applicable.
The controller node receives the following parameter access response from the VLT.
nviParamResp.learn = LN_LEARN_CURRENT nviParamResp.selector = 206 nviParamResp.value[0] = 0 nviParamResp.value[1] = 0 nviParamResp.value[2] = 0 nviParamResp.value[3] = 1E hex nviParamResp.day = 0 nviParamResp.hour = 0 nviParamResp.minute = 0 nviParamResp.second = 0 nviParamResp.millisecond = 0
MG.60.E4.02 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000
Example 2:
Example 3:
A controller node writes 18.0 Hz to VLT parameter 201, Output Frequency Low Limit. The conversion index is -1, so the conversion factor is 0.1.
The controller node sends the following parameter write request to the VLT.
nvoParamCmd.learn = LN_LEARN_CURRENT nvoParamCmd.selector = 201 nvoParamCmd.value[0] = 0 nvoParamCmd.value[1] = 0 nvoParamCmd.value[2] = 0 nvoParamCmd.value[3] = B4 hex (180 decimal)
A controller node writes [2] (REFERENCE [UNIT]) to parameter 007 (009), Large Display Readout, of the VLT.
The controller node sends the following parameter write request to the VLT.
nvoParamCmd.learn = LN_LEARN_CURRENT nvoParamCmd.selector = 7 nvoParamCmd.value[0] = 0 nvoParamCmd.value[1] = 0 nvoParamCmd.value[2] = 0 nvoParamCmd.value[3] = 2
The controller node receives the following parameter access response from the VLT.
nviParamResp.learn = LN_LEARN_CURRENT nviParamResp.selector = 201 nviParamResp.value[0] = 0 nviParamResp.value[1] = 0 nviParamResp.value[2] = 0 nviParamResp.value[3] = B4 hex nviParamResp.day = 0 nviParamResp.hour = 0 nviParamResp.minute = 0 nviParamResp.second = 0 nviParamResp.millisecond = 0
Time 1 - The controller node receives the following parameter access response from the VLT.
nviParamResp.learn = LN_LEARN_CURRENT nviParamResp.selector = 7 nviParamResp.value[0] = 0 nviParamResp.value[1] = 0 nviParamResp.value[2] = 0 nviParamResp.value[3] = 2 nviParamResp.day = 0 nviParamResp.hour = 0 nviParamResp.minute = 0 nviParamResp.second = 0 nviParamResp.millisecond = 0
Example 4:
MG.60.E4.02 - VLT is a registered Danfoss trademark
A controller node reads the value of parameter 407 (411), Switching Frequency, in the VLT. The value stored in parameter 407 is 10 kHz. The conversion index is 2, so the conversion factor is 100.
The controller node sends the following parameter read request to the VLT.
nvoParamCmd.learn = LN_RECALL nvoParamCmd.selector = 407 nvoParamCmd.value[0] = 0 nvoParamCmd.value[1] = 0 nvoParamCmd.value[2] = 0 nvoParamCmd.value[3] = 0
VLT 5000 parameters are shown in parenthesis, where applicable.
The controller node receives the following parameter access response from the VLT.
nviParamResp.learn = LN_RECALL nviParamResp.selector = 407 nviParamResp.value[0] = 0 nviParamResp.value[1] = 0 nviParamResp.value[2] = 0 nviParamResp.value[3] = 64 hex (100 decimal) nviParamResp.day = 0 nviParamResp.hour = 0 nviParamResp.minute = 0 nviParamResp.second = 0 nviParamResp.millisecond = 0
33
VLT® 5000 / VLT® 6000
Example 5:
Standard Object Support
A controller node error is written to VLT parameter 201, Output Frequency Low Limit, with 80.0 Hz when the high limit is 60 Hz. The conversion index is -1, with conversion factor 0.1.
The controller node sends the following parameter write request to the VLT.
nvoParamCmd.learn = LN_LEARN_CURRENT nvoParamCmd.selector = 201 nvoParamCmd.value[0] = 0 nvoParamCmd.value[1] = 0 nvoParamCmd.value[2] = 3 hex nvoParamCmd.value[3] = 20 hex (800 decimal)
The VLT LonWorks option supports two standard objects and three SNVTs, per the LonMark standard object philosophy. The standard objects are the Node Object (containing the Object request, Object status, and Object alarm) and the Controller object, (containing the network variables described in the preceding sections). The Object request is a LonMark device used to obtain status and alarm information from a node.
The controller node receives the following parameter access response from the VLT.
nviParamResp.learn = LN_NULL nviParamResp.selector = 201 nviParamResp.value[0] = 0 nviParamResp.value[1] = 0 nviParamResp.value[2] = 0 nviParamResp.value[3] = 3 (illegal data value) nviParamResp.day = 0 nviParamResp.hour = 0 nviParamResp.minute = 0 nviParamResp.second = 0 nviParamResp.millisecond = 0
The nviRequest.object_id should be set to “1” (controller node). The network uses nviRequest, nvoStatus and nvoAlarm variables for these functions.
2. The VLT sends an Object status containing a bit map of supported status fields in response to all other Object requests, including undefined requests.
It is not necessary for a controller to support the Node Object network variables. The
Object request, Object status and Object alarm provide status and alarm information
for controllers that only support this type of functionality. The status and alarm functions described in the preceding sections contain more drive specific information than Object status and Object alarm.
1. The VLT sends an Object status containing drive status information and an Object alarm containing fault informationin response to the following Object requests:
RQ_NORMAL, RQ_UPDATE_STATUS, and RQ_UPDATE_ALARM.
Function SNVT type Variable Name Input/Output Object request SNVT_obj_request nviRequest Input Object status SNVT_obj_status nvoStatus Output Object alarm SNVT_alarm nvoAlarm Output
3. The VLT Object status supports the following status fields: invalid_id, invalid_request,open_circuit, out_of_service, electrical_fault, comm_failure, manual_control, and in_alarm. All other fields are always set to “0.”
4. The VLT sends an Object alarm following any set or reset of a drive fault condition.
5. The Object alarm supports the AL_ALM_CONDITION and AL_NO_CONDITION alarm types.
34
Network Variables for Node Object Support
MG.60.E4.02 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000
p
g
g
p
A
A
p
A
q
VLT 6000 Alarm Descriptions
Alarm numbers and descriptions that correspond to nvoAlarmWord bit numbers are
Bit
number
222AMA failed 3 18 HPFB timeout 4 17 Serial communication timeout 5 16 Short circuit 615Switch mode fault 714Ground fault 8 13 Overcurrent
9 12 Current limit 10 11 Motor thermistor 11 10 Motor overtem 12 9 Inverter overload 13 *8 Undervolta 14 **7 Overvolta 15 4 Mains failure
**
* also bit 10 of nvoWarning 1
** ****
** also bit 11 of nvoWarning 1
****
Alarm
number
e
e
shown in the table below. See the VLT 6000 Instruction Manual for more details.
Alarm Description
erature
VLT 5000 Alarm Descriptions
Alarm numbers and descriptions that correspond to nvoAlarmWord bit numbers are shown in the table below.
Bit
number
023Brake test failed
1XTri
222
321
420Power u
519
6 18 HPFB timeout
7 17 Standard bus timeout
8 16 Short circuit
915Switch mode fault 10 14 Ground fault 11 13 Overcurrent 12 12 Tor 13 11 Motor thermistor 14 10 Motor overload 15 9 Inverter overload
Alarm
number
locked MA tuning not OK MA tuning OK
SIC fault
ue limit
See the VLT 5000 Instruction Manual for more details.
Alarm Description
fault
VLT 5000 parameters are shown in parenthesis, where applicable.
Factory setting
MG.60.E4.02 - VLT is a registered Danfoss trademark
35
VLT® 5000 / VLT® 6000
Parameter List
Parameter Descriptions
Conversion Data PNU Parameter Description Default V alue Range Index T ype 803 Bus time out 1 sec 1 - 99 sec. 0 3 804 Bus time out function no function 0 3 805 Bit 10 function Bit 10 = > CTW ACT 0 6 927 Parameter edit Enable 0 6 928 Process control Enable 0 6 970 Edit setup Active Setup 0 5 971 Store data values no action 0 5
In addition to the parameters listed above, the drive's control terminals issue digital inputs that control functions similar to those provided by nviStartStop, nviResetFault, and nviControlWord. Parameters (502) 503 through 508 determine how the drive
responds to commands for (quick stop, VLT 5000 only), coasting stop, DC brake, start, reverse, setup select and preset reference select. See Network Drive Control
Input in this manual and the VLT Instruction Manual for more information.
803803
803
803803 Bus time outBus time out
Bus time out
Bus time outBus time out
Selection:
1 - 99 sec 1 sec
Function: Sets the duration for the bus time out function. If the set time passes without the drive receiving a LonWorks message addressed to
it, the drive will take the action specified in parameter 804, Bus Time Out Function.
NOTE After time out counter is reset it must be triggered by valid contr ol word before new time out can be activated.
36
VLT 5000 parameters are shown in parenthesis, where applicable.
Factory setting
MG.60.E4.02 - VLT is a registered Danfoss trademark
804804
804
804804 TT
ime out functionime out function
T
ime out function
TT
ime out functionime out function
Selection: Off
(NO FUNCTION) [0]
Freeze output frequency
(FREEZE OUTPUT FREQ.) [1]
Stop with auto restart
(STOP) [2]
Output frequency = JOG freq.
(JOGGING) [3]
Output frequency = Max. freq.
(MAX SPEED) [4]
Stop with trip
(STOP AND TRIP) [5]
Control without DeviceNet
(NO COM OPT CONTROL) [6]
Select set-up 4
(SELECT SET UP 4) [7]
Function: The time out timer is triggered at the first reception of a valid control word, i.e., bit 10 = ok.
The time out function can be activated in two different ways:
1. The drive does not receive a LonWorks command addressed to it within the specified time.
2. Parameter 805 is set to “bit 10 = 0 time out” and a control word with “bit 10 = 0” is sent to the drive.
The VLT remains in the time out state until one of the following four conditions is true:
1. A valid control word (Bit 10 = ok) is received and the drive is reset through the bus, the digital input terminals or the local control panel. (Reset is only necessary when the time out function Stop w/trip is selected.) Control via LonWorks is resumed using the received control word.
2. Local control via the local control panel is enabled.
3. Parameter 928, Access to process control, is set to Disabled. Normal control via the digital input terminals and the RS-485 interface is now enabled.
VLT® 5000 / VLT® 6000
4. Parameter 804, Bus time out function, is set to Off. Control via LonWorks is resumed and the most recent control word is used.
Description of Selections:
Freeze output frequency. Maintain present output frequency until communication is resumed.
Stop with auto restart. Stop and automatically restart when communication is resumed.
Output frequency = JOG freq. Drive will produce JOG frequency set in parameter 209 (213), Jog frequency, until communication is resumed.
Output frequency = Max. freq. Drive will produce maximum output frequency (set in parameter 202, Output frequency) until communication is resumed.
Stop with trip. Drive stops and requires a reset command before it will restart.
Control without LonWorks. Control via LonWorks is disabled. Control is possible via digital input terminals and/or standard RS-485 interface until LonWorks communication is resumed.
Select setup 4. Setup 4 is selected in parameter 002 (004), Active setup, and settings of setup 4 are used. Parameter 002 (004) is not reset to the original value when communication is resumed.
VLT 5000 parameters are shown in parenthesis, where applicable.
Factory setting
MG.60.E4.02 - VLT is a registered Danfoss trademark
37
805805
CAUTION
!
805
805805 ContrContr
ol Wol W
oror
ol W
ol Wol W
or
oror
dd
d
dd
Contr
ContrContr Bit 10 FunctionBit 10 Function
Bit 10 Function
Bit 10 FunctionBit 10 Function
Selection:
No function
(NO FUNCTION) [0]
Bit 10 = 1: control word active
(BIT 10 = 1 >CTW ACTIVE) [1]
Bit 10 = 0: control word active
(BIT 10 = 0 >CTW ACTIVE) [2]
Bit 10 = 0: bus time out
(BIT 10 = 0 >TIME OUT) [3]
Function: According to the drive's standard communications profile, control word and speed reference will be ignored if bit 10 of the control word is 0. Parameter 805 lets the user change the function of bit 10. This is some times necessary, as some masters set all bits to 0 in various fault situations. In these cases, it makes sense to change the function of bit 10 so that the VLT is commanded to stop (coast) when all bits are 0.
VLT® 5000 / VLT® 6000
Description of Selections:
No function. Bit 10 is ignored, i.e., control word and speed reference are always valid.
Bit 10 = 1 >CTW active. The control word and speed reference are ignored if bit 10 = 0.
With
Bit 10
selected, nviStartStop and nviResetFault commands will not function.
Bit 10 = 0 >CTW active. The control word and speed reference are ignored if bit 10 = 1. If all bits of the control word are 0, the VLT reaction will be coasting.
Bit 10 = 0 >time out. The time out function selected in parameter 804 is activated when bit 10 is 0.
= 0
>CTW active
927927
927
927927 Parameter editParameter edit
Parameter edit
Parameter editParameter edit
928928
928
928928 PrPr
ocess controcess contr
Pr
ocess contr
PrPr
ocess controcess contr
970970
970
970970 Edit setup selectEdit setup select
Edit setup select
Edit setup selectEdit setup select
971971
971
971971 StorStor
e data valuee data value
Stor
e data value
StorStor
e data valuee data value
olol
ol
olol
Data Value:
Disable (DISABLE) [0]
Enable (ENABLE) [1]
Data Value:
Disable (DISABLE) [0]
Enable (ENABLE) [1]
Data Value:
Preprogrammed (FACTORY SETUP) [0] Setup 1 (SETUP 1) [1] Setup 2 (SETUP 2) [2] Setup 3 (SETUP 3) [3] Setup 4 (SETUP 4) [4]
Active Setup (ACTIVE SETUP) [5]
Data Value: No action (NO ACTION) [0]
Store all setups
(STORE ALL SETUPS [1]
Store edit setup
(STORE EDIT SETUP) [2]
Store active setup
(STORE ACTIVE SETUP) [3]
Factory Setting
This parameter determines if LonWorks can be used to access and edit drive parameters.
This parameter determines LonWorks control of the drive. When Enable is selected, drive parameters 503 through 508 determine the interaction between various LonWorks and digital drive input commands. See the VLT Instruction Manual for details.
This parameter selects the setup being edited, through either the drive control panel or LonWorks. The drive may operate in one setup while editing another. Active setup selects the parameter being edited as the setup controling drive operation.
When this parameter is set to Store active setup, LonWorks downloaded parameters are written to EEPROM and stored. Store edit setup stores the setup selected in parameter
970. Store all setups stores all setups in parameter 970. When finished (appx. 15 sec.), it automatically returns to No action. Any parameters values written via the serial bus with No action selected are lost when power is removed from the drive. The function is only activated with the VLT in stop mode.
38
MG.60.E4.02 - VLT is a registered Danfoss trademark
VLT® 5000 / VLT® 6000
Decommissioning VLT Drive from LonWorks Network
CAUTION
!
Specific procedures must be followed when removing VLT drive from LonWorks network. Failure to adhere to steps described can result in drive entering inoperable state.
The VLT drive cabling connector must be disconnected prior to removing the drive from the LonWorks network configuration to prevent corruption of the drive EEPROM processor. Decommission the drive from the network in accordance with the following procedure.
1. Use LonWorks software configuration tool to remove bindings from drive function blocks.
2. Use LonWorks software configuration tool to remove drive function blocks from all drive variables.
3. Disconnect LonWorks cabling from drive input terminal.
4. Use LonWorks software configuration tool to remove drive device from network.
Improper decommissioning of the drive may result in locking up the drive with the display reading as follows.
Failed
OPTION ERROR:
1: NO OPT. RESPONSE
Try to reinitialize drive by removing power until display does blank. Reapply power. If drive functions are not restored, order the Danfoss EEBLANK Kit (P/N 175L4167) to restore the EEPROM functionality.
MG.60.E4.02 - VLT is a registered Danfoss trademark
39
Loading...