Danfoss LLG, LLG S Installation guide [da]

Installation Guide
Sight glass LLG
148R9536
1 2
3
Segment with 20 screws
148R9536
Segment with 12 screws
and
A
B
LLG 44 32
Note!
A
Bolts for anges are not tightened from factory. The bolts must be tightened on site.
4
© Danfoss A/S (MWA), 2015-02 DKRCI.PI.GG0.A2.ML / 520H8306 1
Nm LB-feet
DANSK
Installation
Installér LLG 185-1550 på en plade vha. de 4 skruer, der leveres med væskestands­glasset. Brug gevindhullerne på bagsiden til at montere væskestandsglasset på konsollen (leveres ikke af Danfoss).
Tilslut altid rørene efter at LLG er monteret på konsollen. Det er vigtigt, at der efter tilslutning af rør er et minimum af indre spænding i væskestandsglasset.
Sørg for, at der er plads til at isolere bag LLG samt plads til serviceeftersyn osv.
Max. arbejdstryk
25 bar g.
Arbejdstemperatur
LLG, LLG S:
Min. –10°C Max. +100°C
LLG SF (med synsadapter):
Min. –50°C Max. +30°C
Der tages forbehold for fejl og mangler. Danfoss forbeholder sig ret til uden forudgående varsel at foretage ændringer af produkter og specikationer.
Vedligeholdelse
Udskiftning af pakning
Løsn alle LLG skruer ¼ omgang i modsat rækkefølge af tilspænd-ingssekvensen. I samme rækkefølge løsnes alle skruer helt.
Fjern alle rester fra gammelt paknings­materiale og rengør alle overader. Over­aden skal være fri for grater og ridser.
Pakningen pakkes ud. Pakningen må ikke beskadiges (bukkes, ridses). Den skal holdes ren.
Placer pakningen på bagstykkets pakade og monter glasset ovenpå (se g. 1). Beskyttelsespladen placeres på glasset og forstykket monteres ovenpå. (Ved LLG SF fungerer synsadapteren også som beskyttelsesplade).
Tilspænd skruerne. Tilspændingssekvensen (se g. 2 og 3) skal overholdes. Skruerne spændes med følgende tilspændings­momenter:
Punkt 1
Med hånden til skruen har kontakt med forstykket.
Punkt 2
Med momentnøgle til 15 Nm.
Punkt 3
12 skruer: Skruerne nr. 1-8 til 30 Nm og 9-12 til 15 Nm.
20 skruer: Skruerne nr. 1-16 til 30 Nm og 17-20 til 15 Nm.
Punkt 3 gentages til ingen af skruerne drejes ved de angivne momenter.
ENGLISH
Installation
Install LLG 185-1550 on a bracket using the 4 screws delivered together with the glass. Use the threaded holes on the back of the frame to mount the glass on the bracket (no Danfoss delivery).
Always connect the piping after mounting on the bracket. Note the importance of a minimum of stress in the liquid level glasses from the connected pipes.
Make sure that there is sucient space behind the LLG to secure proper insulation and service inspection etc.
Max. operating pressure
25 bar g (362 psi g).
Working temperature
LLG, LLG S:
Min. –10°C (+14°F) Max. + 100°C (+212°F)
LLG SF (with sight adapter):
Min. –50°C (–58°F) Max. + 30°C (+86°F)
Errors and omissions excepted. The data are subject to change without notice.
Maintenance
Replacement of packing
Loosen all the screws of the LLG by ¼ of a turn in reverse order of the tightening sequence. Loosen all the screws completely, in the same order.
Remove all remains of old packing material and clean all surfaces. There must be no burrs, marks or scratches on the surface.
Unpack the packing. Do not damage (bend or scratch) the packing. Keep it clean.
Place the packing on the packing surface of the back piece and mount the glass hereon (see g. 1). Place the protection plate on the glass and mount the front piece on top. (As far as the LLG SF is concerned the sight adapter also serves as protection plate).
Tighten the screws. The sequence of tightening (see g. 2 and 3) must be observed. Tighten the screws according to the following torque moments:
Point 1
Tighten the screws by hand till they touch the front piece.
Point 2
Use a torque wrench to tighten the screws to 15 Nm (11 ft lb).
Point 3
12 screws; Tighten the screws number 1-8 to 30 Nm (22 ft lb) and number 9-12 to 15 Nm (11 ft lb).
20 screws; Tighten the screws number 1-16 to 30 Nm (22 ft lb) and number 17-20 to 15 Nm (11 ft lb).
Repeat point 3 till none of the screws can be turned at the moments stated.
2 DKRCI.PI.GG0.A2.ML / 520H8306 © Danfoss A/S (MWA), 2015-02