Danfoss Link HP-kit Installation Instructions Manual

MAKING MODERN LIVING POSSIBLE
Danfoss Heat Pumps
Danfoss Link™ HP-kit
Installation instructions
Installation manual Danfoss Link™ HP kit
Introduction
units in your heating system. An
HP-kit for DHP-H
e
r
w
t
y
u
q
Key to symbols
q Heat Pump (HP)
w GateWay y Room Sensor (RS)
e DCM03 u Hydronic Controller (HC)
r Link Central Controller (CC)
* The heat pump kit can also be used with Danfoss Online 2, with the exception of product numbers
086L2381 and 086L2382.
** Please note that all buildings may have obstructions which can impact on communication and the
maximum transmission distance. If you encounter problems with wireless communication, the wireless signal can be amplied by means of Danfoss Link CF-RU repeater units.
t living connect®
en
VIIFR102 © Danfoss 03/2014
2
Installation manual Danfoss Link™ HP kit
Note the following when installing the Danfoss Link HP kit:
• Installation and positioning must be done in accordance with applicable laws and regulations.
• The Danfoss Link HP kit only works in conjunction with heat pumps DHP-H/L/A 2009 or later, using soft-
ware version 1.34 or later, and DHP-AQ with software version 2.2 or later. The Danfoss Link
HP kit is not
suitable for heat pumps with a cooling function (DHP-C and heat pumps with a cooling module).
Quick Installation Guide
21
Install all mains powered units rst and add them to the network
Install the components of the Danfoss Link™ HP kit
3
Create rooms and add battery-powered units one at a time
^
^
^
^
+-+
-
4
Perform the network test with the Dan­foss Link ™ CC is in its nal location
“OK”
Tip!
• The ? key on the Danfoss Link™ CC panel can be used at any time during installation.
• Always check for the latest software version at www.link.danfoss.com be fore installation. See the section on software upgrades in the Danfoss Link™ CC Installation Manual.
3
VIIFR102 © Danfoss 03/2014
Installation manual Danfoss Link™ HP kit
1
Safety precautions
C Installation must be carried out in accordance with applicable laws and regulations, as well as
these instructions.
C The terminal blocks are live and can be highly dangerous due to the risk of electric shock. The
power supply must be disconnected before commencing electrical installation.
Installation, HP kit for Danfoss DHP-H/L/A
The HP kit ’s main components comprise a GateWay card, tted inside the heat pump, and a DCM03, which communicates wirelessly with the other parts of the heating system. Danfoss Link installed to avoid problems when installing the HP kit.
1. Check the software version on the control unit display. Press the left arrow
2. Press “minus” until the cursor reaches the “Version” menu.
3. Press the “right arrow”. This will bring up the software version in the display.
Contents
Verify the contents of the HP kit. The delivery must contain the following:
Description Quantity
DCM03 DCM03 cable GateWay (incl. power cable)
GateWay cable
Mounting clips This manual
Location
Mount the GateWay card inside the heat pump on the prepared holes in the electrical panel. The DCM03 unit must be positioned outside the heat pump in order to be able to communicate wirelessly with Danfoss Link suppress the wireless signals. A network test will show if the location provides the necessary signal conditions.
Fitting the GateWay card
1. Open the cover by turning the open/close mechanism, after which the
CC is used to control the system. Ensure that this control unit has the latest software
on the heating pump control until the display changes to “Service menu”.
Danfoss Link
to
DHP-H/L/A requires software version 1.34 or later.
1 1 1 1 4 1
CC. The DCM03 unit must not be installed on the heat pump as the metal cabinet may
cover can be lifted off. Be careful with the display cable behind the cover.
Service menu
- Installation
- Version
< >
2
≥1.34
≥ 2.2
or later
+
_
!
VIIFR102 © Danfoss 03/2014
3
4
Installation manual Danfoss Link™ HP kit
x4
q
qq
COM
q
en
COM
q
w
2. Fit 4 x “plastic clips” q in the prepared holes in
the electrical panel.
3. Press the GateWay card into the clip until the
card q locks into place.
4. Attach the GateWay cable to the card in the
socket marked COM w.
Connecting the GateWay cable
5. Depending on the configuration, i.e. which other cards are already in the heat pump, connect the
other end of the GateWay cable as follows (A, B or C):
COM
COM
EXT
A. Heat pump without electronic
expansion card (Standard):
Connect the GateWay cable directly to the terminal marked EXT on the relay card.
B. Heat pump with electronic
Connect the GateWay cable to the contact marked EXT on the expansion card.
expansion card:
COM
COM
EXT
COM
EXT
EXT
C. Air/water heat pump with
expansion card.
If the expansion card and defrost card are already installed in the heat pump, connect the GateWay cable to the contact marked EXT on the defrost card.
EXT
5
VIIFR102 © Danfoss 03/2014
Installation manual Danfoss Link™ HP kit
w
Electrical Installation
C Read the safety precautions before beginning the
electrical installation.
1. Connect the enclosed wires to the GateWay card con-
tact marked 230VAC q.
2. Connect the other end of the cable to the terminal
block on the electrical panel.
3. Connect the blue cable to connection point N1b and
the black cable to connection point 217 in the terminal bank.
4. To connect the cables:
• Insert a flat screwdriver in the hole below the hole in which the cable is to be installed. Next, press the screwdriver downwards to release locking mecha­nism q.
• Insert the stripped section of the cable into the upper hole while pulling the screwdriver out at the same time. Make sure that the cable is securely in place in the terminal.
Fitting DCM03
1. Attach the DCM03 cable to the GateWay card q. Route the DCM03 cable w up through the inside of the heat pump and out again through the cable bushing on the top.
q
COM
N1
215
216
N1b
217
217
N1b
2
2. Remove the rear panel of the DCM03 unit by pressing in the spring-loaded plates on the sides q and pull the rear panel downwards w so that it can be removed.
VIIFR102 © Danfoss 03/2014
COM
1
q
6
Installation manual Danfoss Link™ HP kit
3. Using the rear panel as a template, mark perpendicular drill holes at a suitable height on the wall close to the heat pump.
4. Drill holes with a diameter suitable for the rawlplugs and screws to be used. The size and type of screw will depend on the wall material. Screws and rawlplugs are not included in the installation kit.
5. Insert the rawlplugs into the drilled holes and screw the rear panel securely into position.
6. Re-fit the front.
7. Connect the DCM03 cable to the outlet marked RS 485 on the DCM03 unit.
8. Secure the cable to the wall using cable clamps.
RS 485
Start-up
C Before connecting power to the GateWay card, make sure that the electrical installation has been
carried out correctly and that there is no risk of injury or damage.
1. Start the heat pump as specified in the heat pump installation guide.
2. Connect to Danfoss Link™ CC (see Chapter “Connection to Danfoss Link™ CC”)
en
7
VIIFR102 © Danfoss 03/2014
Installation manual Danfoss Link™ HP kit
Danfoss HP kit for DHP-AQ
The installation kit q for the DHP-AQ series consists of a power supply, where a DIN rail is connected to the DHP-AQ control (MAXI +60, MIDI or MINI). The DCM03 unit w is wall-mounted outside the control unit so that it can communicate wirelessly with the Danfoss Link TM CC 3 panel. The Danfoss Link communicates with the other Danfoss Link An example of a heating system with wireless units is shown in the gure below. The Danfoss Link components are indicated with a dotted line.
Danfoss HP kit for DHP-AQ
components in the heating system.
2
CC e panel
3
1
Legend
q Heat pump
w DCM03 t Room sensor (RS)
e Link Central Controller (CC) y Hydronic controller (HC)
r living connect
4 5 6
®
Delivery check
Check the delivery contents of 086L2382:
Description Qty. Pos.
AC/DC transformer (power supply DCM03) Cable 230VAC - ACDC switching supply DCM03 Connection cable DHP-AQ-DCM03 DIN rail (for ACDC transformer assembly) Membrane nipple Screws Installation manual
1
1 1 1 1 1 4 1
VIIFR102 © Danfoss 03/2014
D
F
E
A
B C D E F G
-
G
II
B
C
A
8
Installation manual Danfoss Link™ HP kit
Safety instructions
C Installation must be carried out in accordance with applicable laws and regulations, as well as
these instructions.
C The cables are live and may cause fatal electrical shock. The heat pump power supply must be
switched off before commencing electrical installation.
Software version
1. Check the software version on the DHP-AQ control display. Press the left arrow on the heating pump control until the display changes to “Service menu”.
2. Press “minus” until the cursor reaches the “Version” menu.
3. Press the “right arrow”. This will bring up the software version in the display. Link requires a softwareversion of 2.2 or newer.
for DHP-AQ
Service menu
- Installation
- Version
≥ 2.2
+
< >
_
Location
The power supply must be mounted inside the heat pump control in the prepared holes in the electrical panel. The DCM03 device is designed to be mounted on a wall as close as possible to the heat pump. The distance is limited by the length of the DCM03 connection cable.
Installing the power supply
1. Switch off the power to the heat pump.
C Read the safety instructions before connect-
ing any wiring.
9
VIIFR102 © Danfoss 03/2014
Installation manual Danfoss Link™ HP kit
1. The cover is opened by turning the open/close mechanism, after which the cover can be lifted off. Be careful with the display cable behind the cover.
1
2
!
3
2. Mount the DIN rail in the prepared holes in the electrical panel. Fasten the rail using screws and a
suitable tool. Self-tapping screws may also be used.
2. Attach the converter by first placing it on the upper part of the fitting and then snapping it into position.
VIIFR102 © Danfoss 03/2014
10
Installation manual Danfoss Link™ HP kit
Červený Rød Rot Red Rojo Rouge Rosso Rood Rød Czerwony Красный Punainen Röd
Wiring
1. Connect the grey wire to the L terminal and the blue wire to the N terminal.
2. Route the cables through the electrical cabinet
and connect the grey wire to L 1:1 and the blue wire to N on the connector bank.
1
N
L
II
2
II
3. Connect the DCM03 cable, red to + (positive)
and white to - (negative).
11
2
+
VIIFR102 © Danfoss 03/2014
L1:1L1:1
L1:1
N
N
III
1
Installation manual Danfoss Link™ HP kit
RJ45
III
RS 485
8. Connect the DCM03 cable to the free RJ45 connection on the relay
card. Pass the cable up through the cable lead-in and through the membrane nipple. Adjust the length and press the membrane nipple back.
Fitting DCM03
1. Remove the DCM03 unit rear panel by pressing in the spring-loaded plates on the side of the unit and pulling the rear panel downwards until it can be removed.
2. Using the rear panel as a template, mark perpendicular boreholes at a suitable height on the wall next to the heat pump.
q
w
3. Drill a hole with a diameter that can accommodate the rawlplugs and screws to be used. Screws and rawlplugs are not included in the installation kit.
4. Insert the plugs in the holes and fasten the rear panel.
5. Re-fit the front.
6. Connect the DCM03 cable to the outlet marked RS 485 on the DCM03 unit.
7. Secure the cable with cable clamps at a suitable distance on the wall.
VIIFR102 © Danfoss 03/2014
12
Installation manual Danfoss Link™ HP kit
Connection to Danfoss Link™ CC
C Before connecting to a power outlet, make sure that the electrical installation has been carried out
correctly and that there is no risk of injury or damage.
• Start the heat pump
• Remove the front panel from the Danfoss Link™ CC by carefully pulling it o. Pull near the edges of the panel.
• Press the Setup button for three seconds to open the service
.
area
Note!
The heat pump must be added to the network as a service unit. For more information about connecting to
networks see the accompanying Danfoss Link™ CC Installation Manual.
Add any dedicated repeaters (CF-RU) BEFORE adding the heat pump to the wireless network.
Service functions
1
Rooms and units
?
Click here to add the DCM03 module to Danfoss Link ™CC.
Note!
During installation, the distance between Danfoss Link™ CC and DCM03 must not exceed 1.5 metres.
Rooms and units
2
Add service unit
?
Add service unit
3
Start registration
?
Connecting other units to Danfoss Link™ CC, wireless connection
Connect other service and room units, e.g. HC oor heating and living connect radiator thermostats. Start with the service units. For more information about connecting other units, see the accompanying Danfoss Link ™ CC installation instructions.
13
VIIFR102 © Danfoss 03/2014
Installation manual Danfoss Link™ HP kit
Conducting a network test after adding a new unit
Once the installation is complete, a network test must be carried out to ensure that communication between all added units and Danfoss Link CC™ is stable.
Note! Do not carr y out the network test until Danfoss Link™ CC has been tting in its nal position.
Service functions
1
Status and troubleshooting
When the network test completes, Danfoss Link™ CC waits for the battery-powered units to be activated and registered. Follow the on-screen instructions. If the network test completes without problems, no further interaction will be required. If the network test runs slowly, Danfoss Link™ CC will guide you through the troubleshooting procedures and provide useful tips as to how to speed up the process.
Entering basic settings in Danfoss Link™ CC
The heat pump has now been added to the wireless system and is ready to be integrated with other units in the system (e.g. Danfoss HC oor heating and/or living connect ® radiator thermostats). This is done via the Service menu using the following settings:
Service functions
1
Rooms and units
Status and troubleshooting
2
Network
?
Rooms and units
2
Unit management
?
Status of wireless network
3
Start network test
?
Unit management
3
Congure Unit
Select Unit
4
Heat pump
?
?
?
System integration System integration
5 6
System integration System integration
? ?
VIIFR102 © Danfoss 03/2014
?
14
Installation manual Danfoss Link™ HP kit
Troubleshooting
If an error occurs in communication with the GateWay card, the heat pump and DCM03, this may be indicated in a number of dierent ways. If the heating system is in operation when the error occurs, a yellow warning icon will be shown in the Danfoss Link Refer to the instructions in chapter 7.1 in the installation manual for Danfoss Link about the error and suggestions for suitable remedial measures.
If the wireless communication between Danfoss Link ing:
1. Cable connections
2. Check that the units are connected to the mains and that they are switched on (LEDs illuminating
correctly).
3. Check that DCM is set to Danfoss Link integration and not to Danfoss Online. By pressing the DCM
button quickly three times, you will switch between showing status for Danfoss Online and Dan­foss Link changes from Danfoss Online to Danfoss Link integration to Danfoss Online, the lights flash twice and more slowly.
4. Check LED on the GateWay card:
• Start-up: Flashing, on 90% off 10%.
• Approval DCM-HP: on 50% off 50% (rapid).
• Approval failed: on 75% off 25% (flashes twice (slowly) with a long pause in between).
• Send settings to DCM: on 50% off 50% (slow).
• Everything OK: 100% (constant light).
5. Check whether DCM03 has been registered correctly in the Danfoss Link CC panel in accordance
with the Danfoss Link
6. Has a network test been performed to check whether all units in the heating system are working? See
the Danfoss Link
7. There may be too much distance between DCM03 and Danfoss Link CC, or wireless communica-
tion may be obstructed because of physical objects or other obstructions. Try a new location for the DCM03 until a good signal strength is obtained. If this is not possible due to physical components of the building, use a repeater (CF-RU). Install this repeater between the Danfoss Link DCM03 unit.
8. In rare cases, it may be necessary to delete the heat pump as a service unit and then re-install it.
Follow the instructions in Chapter 5.3 in the Danfoss Link remove a service unit.
CC display.
CC for more information
CC and DCM03 does not work, check the follow-
integration. The LEDs on DCM03 (both red and green) flash rapidly 3 times when status
integration. When switching from Danfoss Link
CC Installation Manual, Chapter 4, ”Adding service units”.
CC Installation Manual, Chapter 4.9 “Performing a network test”.
CC and the
CC Installation Manual about how to
NOTE! If you restore the factory settings, you must also re-install all the units.
9. The faulty component in the HP kit may need to be replaced. First, delete the service unit as
described in the Danfoss Link
15
CC Installation Manual. Next, add a replacement unit.
VIIFR102 © Danfoss 03/2014
Installation manual Danfoss Link™ HP kit
Using Danfoss Link™ CC with Online 2
* The following does not apply to HP kits with product numbers: 086L2381 and 086L2382, as these are not compatible with Online 2.
When DanfossLink™ CC are used in conjunction with Online 2*, they can be integrated in the following two ways:
• System integration
• No system integration
“No system integration” is the default method during installation. When system integration is selected, Danfoss
CC manages most functions in the heat pump. In this case, the functions controlled by Danfoss Link CC are
Link locked in relation to Online. The table below shows the relationship between disabled and enabled functions from an Online perspective.
Tab Section Function System integr. No system
Status Indoor temperature (value: ROOM
Details Heat curve Curve No Yes
Danfoss DHP-AQ Calendar
control
Danfoss DHP-H, L Calendar
control
No = Function cannot be changed via Online when the system is in ”system integration” Yes = Function can be changed Online regardless of whether system integration has been enabled or not
(+/-)
Min No Yes
Max No Yes
+5 ºC No Yes
0 ºC No Ye s
-5 ºC No Yes
Heat stop Yes Ye s
Room factor No Yes
Temperature decrease No Yes
Hot water block Yes Ye s
Quiet mode Ye s Yes
EVU mode Yes Ye s
Temperature decrease No Yes
No Yes
Yes Ye s
integr.
Using the Online application, you can change the integration options and go from “System integration” to “No system integration” and take control of the function settings and vice versa.
VIIFR102 © Danfoss 03/2014
16
Installation manual Danfoss Link™ HP kit
Recycling instructions
When the crossed-out wastepaper basket symbol is shown on the product, it means that the product is subject to European Parliament and Council Directive 2002/96/EC. Locate your nearest recycling centre for electrical and electronic products. Adhere to local regulations and do not put old products (e.g. batteries) in your general household waste. By properly disposing of your old products you can help to reduce negative impacts on the environment and public health.
en
17
VIIFR102 © Danfoss 03/2014
VIIFR102
© Danfoss 08/2013
18
19
VIIFR102
© Danfoss 08/2013
VIIFR102
© Danfoss 08/2013
Danfoss Heat Pumps
Box 950
671 29 ARVIKA
Phone +46 570 81300
E-mail: dhpinfo@danfoss.com
Internet: www.heating.danfoss.com
Danfoss assumes no responsibility whatsoever for any errors occurring in catalogues, brochures or other printed material. Danfoss reserves the right to
make changes to (the design of) its products with no prior warning.
The same applies to products already on order provided that the previously agreed specications remain unchanged.
All trademarks in this material are the property of the respective company. Danfoss and the Danfoss logotype are trademarks which belong to Danfoss
A/S. All rights reserved.
83
Loading...