Danfoss Link Dynamic Boiler Relay Installation guide [fr]

Danfoss Link™ Dynamic Boiler Relay
Installation Guide
Danfoss Heating
Installation Guide Danfoss Link™ DBR
UK
UK
NL
Hearby, Danfoss A/S declares that the radio equipment type Danfoss Link DBR is in compliance with directive 2014/53/EU. The full text of the EU declaration of conformity is available at the following internet address, http:// heating.danfoss.co.uk
Danfoss can accept no responsibility for possible errors in catalogues, brochures, and other printed material. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
2
VIIOS202 © Danfoss 07/2017
Table of Contents
Introduction.................................................. 4
Installation ................................................... 4
Installation in application with bypass valve using AVDO....... 5
Mounting .................................................... 6
Wiring ....................................................... 7
Adding the device ............................................ 7
Congure Danfoss Link™ DBR ................................. 8
Congure the DBR Operation Mode........................... 9
Congure the DBR Settings .................................. 10
Perform network test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Factory reset ................................................ 11
Status indicator.............................................. 11
Technical specications...................................... 12
Disposal instructions ........................................ 12
Important information
For safety reasons the heating system must have a bypass function. This is either built into the boiler or it must be installed in the system.
Demount other heating control timers in the installation or they will interfere with the Danfoss Link™ heating control algorithm. If weather compensation is present it should be set to constant comfort.
Electric heating devices are not supported.
VIIOS202 © Danfoss 07/2017
3
Installation Guide Danfoss Link™ DBR
UK
NL
Introduction
The Danfoss Link™ Dynamic Boiler Relay (DBR) is an electronic
device for turning gas and oil boilers ON/OFF depending on heat demand.
The Danfoss Link™ DBR must in applications with bypass valve such as AVDO, be installed in combination with the ESM-11 temperature sensor (included inside the box) for turning the boiler ON/OFF based on heating demand and water tempera­ture in return pipe for running the system at optimal energy efficiency.
This pack includes:
1 x Danfoss Link™ Dynamic Boiler Relay 1 x ESM-11 Temperature Sensor
Installation
The Danfoss Link™ wireless system’s transmission range is su­cient for most applications; however each building has dierent obstacles aecting communication and maximum transmission distance. If communication problems occur Danfoss suggests that accessories would be required to support the system, such as repeaters.
In exceptional cases the wireless system may not be suitable for your installation.
Be aware that installation and placement must be according to local building regulations.
4
VIIOS202 © Danfoss 07/2017
UK
Condensing
Boiler
Bypass
Valve
(AVDO)
Dynamic Boiler
Relay (DBR)
ESM-11
Temperature
Sensor
70C
70C
50C
50C
Condensing
Boiler
Bypass
Valve
(AVDO)
Dynamic Boiler
Relay (DBR)
ESM-11
Temperature
Sensor
70C
70C
50C
50C
Condensing
Boiler
Dynamic Boiler
Relay (DBR)
70C
70C
50C
50C
Bypass Valve (AVDO)
ESM-11
Temperature
Sensor
Installation in application with bypass valve using AVDO
In installations with bypass using AVDO, remember to mount and wire the ESM-11 Temperature Sensor included in the pack.
Note:
· The ESM-11 Temperature Sensor needs to b e mounted on the return pipe.
·Mount t he ESM-11 Tempe rature Sensor in the bypass circuit (gure 1) and not outside of the circuit (gure 2). Pay at tention that the ESM -11 must be o utside the circuit of an e ventual stor­age tank
Figure 1
Figure 2
VIIOS202 © Danfoss 07/2017
NL
5
Installation Guide Danfoss Link™ DBR
UK
NL
The Danfoss Link™ DBR is not recommended in application
without bypass valve. Install Danfoss Link™ DBR together with e.g. AVDO bypass valve.
If boiler has internal bypass valve and installed with weather compensation, the Danfoss Link™ DBR can be installed without
the Return Sensor, in operation mode “On when Heat Demand”
Mounting
Note: The Danfoss Link™ DBR must be mounted on a at surface.
For mounting the temperature sensor correctly on the pipe please see enclosed installation guide for ESM-11 Temperature
Sensor.
6
VIIOS202 © Danfoss 07/2017
UK
UK
Wiring
Danfoss Link™ DBR
Electronics
Remove
1NL 234
230 V AC
ESM-11
Note: Refer to boiler manufacturer’s manual for wiring connections
to the boiler.
jumper if tted
T
T
Boiler ON/OFF
terminals
Adding the device
The process of adding the D anfoss Link™ DBR to a system is performed on the Danfoss Lin k™ CC. Note that the Danfoss Link™ DBR must be added as a Service Device.
When adding, press and release the install button, and observe that the LED gives a fast green ash. If adding is successful the LED turns green permanently. For further information, see the D anfoss Link™ CC instruction manual.
NL
Note: If adding the D anfoss Link™ DBR to the Danfoss Link™ CC is
unsuccessful, make sure th e right Danfoss Link™ CC software version is applied. Correct ver sion: 4.1.0 or higher.
VIIOS202 © Danfoss 07/2017
7
Installation Guide Danfoss Link™ DBR
UK
NL
Congure Danfoss LinkTM DBR
Select “Manage Devices” in “Rooms and Devices”.
Select Device to congure Select operation mode
8
VIIOS202 © Danfoss 07/2017
Select “Congure Device”.
according to the application
UK
Congure the Danfoss LinkTM DBR Operation Mode
Dynamic Control (Recommended)
When Dynamic Control is selected, the on/o cycles are deter­mined by the heat demand in the rooms and the temperature of the return pipe into the boiler to optimize energy savings. Recommended in systems with bypass in heating circuit, such as AVDO valve. It is possible to adjust the Setpoint Limits in this mode. Dynamic Control only possible to select with ESM­11 sensor mounted on return pipe
On when Heat Demand
The boiler is only ON when there is heat demand from a reference room in the system. Recommended for modu­lating boilers and non-condensing boilers.
TPI (Time Proportional Interval)
A duty cycle is calculated and used to control the boiler. Select ‘Cycle Time’ in Settings.
NL
VIIOS202 © Danfoss 07/2017
9
UK
Installation Guide Danfoss Link™ DBR
NL
Setpoint Limits
The recommended Maximum Temperature is below 54 degrees to ensure maximum eciency with condensing boilers. If Maximum Temperature is set too low, there is a risk of not reaching the desired temperature.
Congure the Minimum Temperature and Maximum temperature for Return Line setpoint temperatures for
Danfoss Link™ DBR here. (Note: You can only set these setpoint limits within the Dynamic mode.)
Congure settings of the Danfoss LinkTM DBR
Relay Output Conguration
NO (Normally Open) and NC (Normally Closed)
Cycle time
• 6 cycles/hour is recommended for condensing non-modulat­ing gas boilers.
• 3 cycles/hour is recommended for condensing non-modulat­ing oil boilers.
10
VIIOS202 © Danfoss 07/2017
UK
Perform network test
Once the Danfoss Link™ DBR and all other devices in the system have been registered and the Danfoss Link™ CC is placed in its nal position, perform a network test (see separate Danfoss Link™ CC manual).
Note: If the connection to the Danfoss Link™ CC is
lost for more than 1½ hour, the Danfoss Link™ DBR will go into safety mode. In this mode the boiler will be turned ON continuously.
Factory reset
Turn o the power to the device, then press and hold the install button in front of the device for approx. 5 sec. while the power is switched on again. The button must be held until LED gives a red ash.
Status indicator
Green LED OFF Relay OFF/Standby
Green LED ON Relay ON/Heating
Green LED fast ash Adding or link test
Green LED short ash Ready for adding
Red LED slow ash Adding not OK
Link test not OK Safe State Active
NL
VIIOS202 © Danfoss 07/2017
11
Loading...
+ 25 hidden pages