Hearby, Danfoss A/S declares that the radio equipment type Danfoss Link DBR is in compliance
with directive 2014/53/EU.
The full text of the EU declaration of conformity is available at the following internet address, http://
heating.danfoss.co.uk
Danfoss can accept no responsibility for possible errors in catalogues, brochures, and other printed
material. All trademarks in this material are property of the respective companies. Danfoss and the
Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
For safety reasons the heating system must have a bypass
function. This is either built into the boiler or it must be
installed in the system.
Demount other heating control timers in the installation or
they will interfere with the Danfoss Link™ heating control
algorithm. If weather compensation is present it should be set
to constant comfort.
The Danfoss Link™ Dynamic Boiler Relay (DBR) is an electronic
FR
device for turning gas and oil boilers ON/OFF depending on
heat demand.
The Danfoss Link™ DBR must in applications with bypass valve
such as AVDO, be installed in combination with the ESM-11
temperature sensor (included inside the box) for turning the
boiler ON/OFF based on heating demand and water temperature in return pipe for running the system at optimal energy
efficiency.
This pack includes:
1 x Danfoss Link™ Dynamic Boiler Relay
1 x ESM-11 Temperature Sensor
Installation
The Danfoss Link™ wireless system’s transmission range is sucient for most applications; however each building has dierent
obstacles aecting communication and maximum transmission
distance. If communication problems occur Danfoss suggests
that accessories would be required to support the system, such
as repeaters.
In exceptional cases the wireless system may not be suitable for
your installation.
Be aware that installation and placement must be
according to local building regulations.
Installation in application with bypass valve
using AVDO
In installations with bypass using AVDO, remember to mount
and wire the ESM-11 Temperature Sensor included in the pack.
Note:
· The ESM-11 Temperature Sensor needs to b e mounted on the
return pipe.
·Mount t he ESM-11 Tempe rature Sensor in the bypass circuit
(gure 1) and not outside of the circuit (gure 2). Pay at tention
that the ESM -11 must be o utside the circuit of an e ventual storage tank
Note: Refer to boiler manufacturer’s manual for wiring connections
to the boiler.
jumper
if tted
T
T
Boiler ON/OFF
terminals
Adding the device
The process of adding the D anfoss Link™ DBR
to a system is performed on the Danfoss Lin k™ CC.
Note that the Danfoss Link™ DBR
must be added as a Service Device.
When adding, press and
release the install button,
and observe that the LED
gives a fast green ash.
If adding is successful the LED turns green permanently.
For further information, see the D anfoss Link™ CC instruction
manual.
NL
FR
Note: If adding the D anfoss Link™ DBR to the Danfoss Link™ CC is
unsuccessful, make sure th e right Danfoss Link™ CC software
version is applied. Correct ver sion: 4.1.0 or higher.
When Dynamic Control is selected, the on/o cycles are determined by the heat demand in the rooms and the temperature
of the return pipe into the boiler to optimize energy savings.
Recommended in systems with bypass in heating circuit, such
as AVDO valve. It is possible to adjust the Setpoint Limits in
this mode. Dynamic Control only possible to select with ESM11 sensor mounted on return pipe
On when Heat Demand
The boiler is only ON when there is heat demand from a
reference room in the system. Recommended for modulating boilers and non-condensing boilers.
TPI (Time Proportional Interval)
A duty cycle is calculated and used to control the boiler.
Select ‘Cycle Time’ in Settings.
The recommended Maximum Temperature is below 54 degrees to
ensure maximum eciency with condensing boilers.
If Maximum Temperature is set too low, there is a risk of not reaching
the desired temperature.
Congure the Minimum
Temperature and Maximum
temperature for Return Line
setpoint temperatures for
Danfoss Link™ DBR here.
(Note: You can only set these
setpoint limits within the
Dynamic mode.)
Congure settings of the Danfoss LinkTM DBR
Relay Output Conguration
NO (Normally Open) and NC (Normally Closed)
Cycle time
• 6 cycles/hour is recommended for condensing non-modulating gas boilers.
• 3 cycles/hour is recommended for condensing non-modulating oil boilers.
Once the Danfoss Link™ DBR and all other devices in the system
have been registered and the Danfoss Link™ CC is placed in
its nal position, perform a network test (see
separate Danfoss Link™ CC manual).
Note: If the connection to the Danfoss Link™ CC is
lost for more than 1½ hour, the Danfoss Link™
DBR will go into safety mode. In this mode the
boiler will be turned ON continuously.
Factory reset
Turn o the power to the device, then press and hold the install
button in front of the device for approx. 5 sec. while the power
is switched on again. The button must be held until LED gives a
red ash.