Instructions: Control Panel LCP 501
Instructions: MCD Control Panel LCP 501
Order Code: 175G0096
1. Description
The MCD 500 LCP can be mounted up to 3 metres away from the soft starter, allowing remote control and monitoring. The LCP is rated IP65 when mounted correctly in accordance with these instructions.
2. |
Packing List |
|
|
|
1 x LCP |
|
4 x M3 x 16 Screw |
|
1 x Cable, DB9, 3 metres |
4 x M3 Flat washer |
|
|
1 x Gasket, foam |
|
4 x M3 Spring washer |
|
1 x Instruction sheet |
|
4 x M3 Nut |
|
|
|
2 x Jack screw |
3. |
Specifications |
|
|
Maximum cable length |
3 metres |
|
|
Protection |
IP65 and NEMA12 |
MI.17.G1.02 - VLT is a registered Danfoss trademark
Instructions: Control Panel LCP 501
4. Mounting the LCP
Models MCD5-0021 to MCD5-0105: The LCP can be removed or replaced while the starter is running. It is not necessary to remove mains or control voltage.
Models MCD5-0131 to MCD5-1600: The bus bar and/or heatsink are live whenever mains voltage is connected. Remove mains and control voltage from the soft starter before removing the cover.
1.Use the template to drill four mounting holes and two holes for the DB9 connector.
2.Apply the foam gasket to the back of the LCP.
3.Align the LCP over the holes and screw in place.
<![if ! IE]><![endif]>177HA614.10
4. Plug the cable into the LCP and the soft starter.
177HA615.10
|
177HA616.10 |
MCD5-0021 to MCD5-0105 |
MCD5-0131 to MCD5-1600 |