Installation guide
Pressure switch
Type KPI 34, KPI 35, KPI 36 and KPI 38
060R9308
060R9308
© Danfoss A/S (AC-MCI/jmn), 2013-11 IC.PI.P10.D5.02 / 520B5862 1
KPI 34, KPI 35, KPI 36, KPI 38
Type Range Di.
KPI 34 -0.2 − 3 bar 0.5 − 1.25 bar
KPI 35 -0.2 − 8 bar 0.4 − 2 bar
KPI 36 4 − 12 bar 0.5 − 1.6 bar
KPI 38 8 − 28 bar 1.8 − 6 bar
t1 min. -40 °C
t1 max. 65 °C
t2 min. -40 °C
t2 max. 100 °C
P
max.
test
KPI 34: 18 bar
KPI 35: 18 bar
KPI 36: 18 bar
KPI 38: 30 bar
Please note: No maintenance is required for the
switches after nal installation.
Please note: scale in KP units is indicative only.
For accurate setting or when using according to FM
aproval use additional pressure gauge to set the unit.
Listed refrigeration
controller 61B5
Standard contact
Alternating current
AC-1 : 10A, 440V
AC-3 : 6A, 440V
AC-15: 4A, 440V
Blocked rotor: 112A
Direct current:
DC-13, 12W, 220V
Voltage FL LR
AC DC A A
240 — 6 36 8A
120 — 8 48 10A
— 240 — — — 12W
Use copper wire only
Tightening torque 20 lb. in.
Resist.
load
Pilot
duty
3A
CAUTION:
Disconnect power supply before wiring connections
are made or service to avoid possible electrical shock
or damage to equipment. Do never touch live parts
with your ngers or with any tool.
2 IC.PI.P10.D5.02 / 520B5862 . © Danfoss A/S (AC-MCI/jmn), 2013-11