Danfoss KP 98 Installation guide

Danfoss
60-1416.10
Danfoss
60-1416.10
Danfoss
60-1416.10
Installation guide
Thermostat Type KP 98 (cross ambient)
060R9749
Oil temp. High temp. (OIL) bulb (HT) bulb
KP 98 man. (OIL)/man.(HT) rese t
Note:
Code no. stamped on top of control.
Ambient temperatures Max. bulb temperatures
min. -40 °F (-40 °C) max. 150 °F ( 65 °C)
(175 °F (80 °C) for max. 2 hours)
max. 300 °F (150 °C)
060R9749
max. 480 °F (250 °C)
Enclosure Cable entry
~ NEMA 1
60-786.12
CAUTION:
The mounting panel must be plane to avoid damage of control.
Mounting
Mount OIL temperature bulb in compressor crankcase and the HT bulb on/in discharge line as shown.
Small pipe size Large pipe size OD > 3.5 in.
Danfoss
60-1419.10
O.D.
© Danfoss A/S (RC-MDP / jmn), 2014-08 DKRCC.PI.CA0.A6.22 / 520H8513 1
Wiring
CAUTION: disconnect power supply
before wiring connections are made to avoid possible electrical shock or damage to equipment.
All wiring should conform to the National Electrical Code and local regulations.
Contact load ratings
120 V a.c. 16 FLA, 96 LRA
240 V a.c. 8 FLA, 48 LRA
240 V d.c. 12 W pilot duty
See label inside cover.
Manual tripping
(Electrical contacts/wiring test)
OIL side HT side
B
SPST
Terminal block
CAUTION: Use terminal screws furnished in the contact block. Use tightening torque 20 lb. in. (2.3 Nm). Use copper wire only.
B-C open on oil temperature rise B-C open on discharge temperature rise A is not used
See label for current wiring inside cover.
C
Contact positionContact position
TRIP use FINGERS ONLY! (Do NOT use screwdriver)
Manual reset
To resume control operation after safety cut-out, push man. reset knob as indicated
Note:
OIL/HT man. reset is possible only after oil or discharge temperature is equal to or has dropped below cut-in value.
Adjustment spindle(s) location
Contact position
Danfoss
60-801.13
Contact position
C
B
OIL reset
HT man. reset
KP 98 A. MAN./MAN. RESET
2 DKRCC.PI.CA0.A6.22 / 520H8513 © Danfoss A/S (RC-MDP / jmn), 2014-08
Danfoss
60-1417.10
Danfoss
60-1418.10
Setting
Oil temp. (OIL) side setting High temp. (HT) side setting
1. Adjust range spindle to desired CUT-OUT value (max. allowable oil temp.)
2. Dierential (DIFF.) is xed 25 °F (14 °C) Value printed on scale plate
CUT OUT minus DIFFERENTIAL equals CUT OUT minus DIFFERENTIAL equals CUT-IN CUT-IN
Example: Example: CUT-OUT – DIFF. = CUT-IN CUT-OUT - DIFF. = CUT-IN 200 °F 25 °F = 175 °F 325 °F - 45 °F = 280 °F (93 °C) (14 °C) (79 °C) (163 °C) (25 °C) (138 °C)
OIL temp. scale
Cut out
Di.
1. Adjust range spindle to desired CUT-OUT value (max. allowable discharge temp.)
2. Dierential (DIFF.) is xed 45 °F (25 °C) Value printed on scale plate
HT scale
Cut out
Di.
Note:
CUT-OUT = compressor cut-out CUT-IN = compressor cut-in
Adjustment
Danfoss
60-802.12
Note:
Remove lockplate before adjustment. Replace lockplate after adjustment (if desired).
3 DKRCC.PI.CA0.A6.22 / 520H8513 © Danfoss A/S (RC-MDP / jmn), 2014-08
Loading...