MID examination cer tificate no.: LT-1621-MI004-028
The INFOCAL 9 is an energy calculator, e.g.
for combination with SONO 3500 CT or
SonoSensor 30.
It is especially designed for heating, cooling or
combined heating/cooling applications in local
and district energy systems.
The INFOCAL 9 has been approved according
to MID in accuracy class 2. The calculators are
designed for remote read-out (AMR).
Features
• For heating and cooling application
• Battery or 230 V AC power supply
• Lithium battery with 12 years lifetime
• Pair of Pt 500 temperature 2-wire sensors
included
• For 2- and 4-wire temperature sensors
• Temperature range: 0 to +160 °C
• Remote reading via M-Bus, radio OMS 868, 2 x
pulse output, 2 x 4-20 mA output
• Two pulse inputs integrated as standard
• Calculator with IP65 protection class as
standard
• For return or supply pipe flow sensor or flow
meter installation
• Individual tariff functions
• History memory for 32 months
• Suitable for Danfoss ECL Comfort controller
• Special option with 2 flow sensors, 2
pressure sensors and 3 temperature sensors
measurement
Flow
direction
Flow meter/sensor in return pipe
Flow direction
Flow meter/sensor in supply pipe
© Danfoss | 2020.04 AI215286474517en-000301 | 1
Data sheet Infocal 9 - Energy calculator
Ordering Infocal 9
Ordering accessories
Primarily for flow
meter/sensor
SONO 3500 CT
(DN10 0-DN150)
SONO 3500 CT
(DN200- DN350)
SONO 3500 CT
(DN400-DN500)
SONO 3500 CT
(DN600-DN1200)
SONO 3500 CT
(DN10 0-DN150)
SONO 3500 CT
(DN200- DN350)
SONO 3500 CT
(DN400-DN500)
SONO 3500 CT
(DN600-DN1200)
SonoSensor 30
(DN15 - DN25)
SonoSensor 30
(DN40 - DN100)
1)
Cable length of P t 500, Ø 5.2 mm, 2-wire temp erature sensor.
Pulse value
Installation
2,5 liter / pulse Return Battery 0,01 MWh M-Bus 3m 187F9 007
10 liter / pulse Return Battery 0,01 MWh M-Bus 5m 187F9 008
50 liter / pulse Return Battery 0,01 MWh M-Bus 5m 187F 9009
100 liter / pulse Return Batter y 0,01 MWh M-Bus 5m 187F9010
2,5 liter / pulse Return 230V AC 0,01 MW h M-Bus 3m 187 F90 11
10 liter / pulse Return 230V AC 0,01 MW h M-Bus 5m 187F9 012
50 liter / pulse Return 230V AC 0,01 MWh M-Bus 5m 187F9013
100 liter / pulse Return 230V AC 0,01 MWh M-Bus 5m 187F9 014
1 liter / pulse Return Battery
10 liter / pulse Return Battery 0,01 MWh M-Bus 3m 187F9001
Power
supply
Energy
units
0,0 01
MWh
Communication
Cable
length
1)
M-Bus 2m 187F9000
Code
number
Product Designation Quantity Code no.
Power supply Batter y 3.6 V DC (D-cell) 1 pc. 187F3380
Power supply Mains unit 230 V AC 1 pc. 187F3381
Communication module M-Bus module 1 pc. 187F3382
Communication module Radio OMS 868.95 MHz 1 pc. 187F3383
Communication module RS-232 M-Bus 1 pc. 187F3385
Communication module RS-485 M-Bus
Communication module M-Bus, RS232 and two pulses outputs
Communication module M-Bus, RS232 and two 4 -20mA outputs
1)
1)
1)
1 pc. 187F3386
1 pc. 187F3387
1 pc. 187F3388
Temperature sensor Pt 500 / f 5.2 mm / 1.5 m cable, MID 1 pair 187F3125
Temperature sensor Pt 500 / f 5.2 mm / 2 m cable, MID 1 pair 187F3126
Temperature sensor Pt 500 / f 5.2 mm / 3 m cable, MID 1 pair 187F3127
Temperature sensor Pt 500 / f 5.2 mm / 5 m cable, MID 1 pair 187F3390
Temperature sensor Pt 500 / f 5.2 mm / 10 m cable, MID 1 pair 187F3391
Sensor pockets Ø 5.2 mm, brass, 35 mm length 1 pair 087G6053
Sensor pockets Ø 5.2 mm, brass, 52 mm length 1 pair 087G6054
Sensor pockets Ø 5.2 mm, brass, 85 mm length 1 pair 087G6055
Sensor pockets Ø 5.2 mm, brass,120 mm length 1 pair 087G6056
Sensor pockets Ø 5.2 mm, stainless steel, 85 mm length 1 pair 087G6057
Sensor pockets Ø 5.2 mm, stainless steel, 120 mm length 1 pair 087G6058
Sensor pockets Ø 5.2 mm, stainless steel, 155 mm length 1 pair 087G6059
Sensor pockets Ø 5.2 mm, stainless steel, 210 mm length 1 pair 087G6060
1)
Only with mains su pply 230 V AC
2 | AI215286474517en-000301 © Danfoss | 2020.04
Data sheet Infocal 9 - Energy calculator
Technical data
Design and function
Basic data Accuracy Class 2, EN1434
Ambient Class E2 +M1
Environmental Class C EN1434
Protection class IP 65
Max. ambient humidity 93% rel. humidity
Display
indication
Temperature Ambient operating temperature C° +5 ... +55
Input
Supply voltage 3.6 V DC Lithium-battery (D-cell) or Mains supply 230 V AC
Batter y
life time
Weight
Calculator
The calculator contains all necessary circuits for
recording flow rates and temperatures, and for
calculating, logging and displaying the data.
The calculator housing can be mounted on the
wall or standard DIN rail.
The calculator can be conveniently read from
an 8-digit display with units and symbols. Two
push-buttons provides user-friendly control of
the various display loops.
All failures and faults are recorded automatically
and shown on LCD display.
To protect the reading data, all relevant data
are saved in a non-volatile memory (EEPROM).
This memory saves the measured values,
device parameters and types of error at regular
intervals.
Temperature sensors
Pairs of Pt 500 Ø5.2 mm (or Ø6.0 mm)
temperature sensors with 2-wire (or 4-wire)
leads can be used. Cable lengths of 3 m, 5 m and
10 m are available.
Optical interface
Optical interface is integrated into the front
panel of the calculator. It is designed for data
reading via M-bus protocol.
The optical interface is activated by pressing the
control button, and it automatically shuts off
5 minutes after the button has been activated
Display LCD, 8-digit
Units MWh - GJ - Gcal - °C - m³ - m³/ h
Values displayed
Temperature sensors Typ e
Measuring cycle T(s)
Max. temperature difference ∆θmax (K) 160
Min. temperature difference ∆θmin (K) 3
Starting temp. difference ∆θ (K) 0.15 K
Temperature, measuring range θ (°C) 0 ... 160
min. 12 years (including AMR communication)
0.5 kg
Energy , volume, power, flow rate ,
temperatures
Pt 500 with 2 or 4-wire leads;
Ø 5.2 or Ø 6.0 mm
Temperature: 10s
(for both bat tery and 230 V supply)
Wired M-Bus interface
The energy meter has one slot for an additional
communication module. The internal M-Bus
module provides data reading possibility via
M-Bus protocol:
• M-Bus protocol according to EN13757-3
standard
• 2-wire with polarity reversal protection
• Electrical isolation
• Maximum voltage 50 V DC
• Current drawn: one M-Bus load (1.5 mA)
• Primary or secondary addressing
• Baud rate 300/1200/2400/4800/9600 (default:
2400 baud rate)
• Battery lifetime min. 12 years ( D cell)
• Fastest reading interval at battery supply: one
meter on the bus every 280 seconds (2400
baud rate)
• Fastest reading interval at mains supply: no
limits
Radio OMS 868.95 MHz interface
The module can provide data reading via radio
module:
• Wireless M-Bus protocol according to
EN13757- 4
• OMS (open metering system) compatible
• 868.95 MHz, T1 mode (unidirectional)
• Sending interval every 90 seconds (suitable for
‘walk by’ readings)
or after data transmission via interface is
completed.
AI215286474517en-000301 | 3© Danfoss | 2020.04