Danfoss Infocal 9 Data sheet

Danfoss Infocal 9 Data sheet

Data sheet

Infocal 9

Energy calculator

Description/Application

MID examination certificate no.: LT-1621-MI004-028

The INFOCAL 9 is an energy calculator, e.g. for combination with SONO 3500 CT or SonoSensor 30.

It is especially designed for heating, cooling or combined heating/cooling applications in local and district energy systems.

The INFOCAL 9 has been approved according to MID in accuracy class 2. The calculators are designed for remote read-out (AMR).

Features

For heating and cooling application

Battery or 230 V AC power supply

Lithium battery with 12 years lifetime

Pair of Pt 500 temperature 2-wire sensors included

For 2- and 4-wire temperature sensors

Temperature range: 0 to +160 °C

Remote reading via M-Bus, radio OMS 868, 2 x pulse output, 2 x 4-20 mA output

Two pulse inputs integrated as standard

Calculator with IP65 protection class as standard

For return or supply pipe flow sensor or flow meter installation

Individual tariff functions

History memory for 32 months

Suitable for Danfoss ECL Comfort controller

Special option with 2 flow sensors, 2

pressure sensors and 3 temperature sensors measurement

Application drawings

Flow direction

Flow meter/sensor in return pipe

Flow direction

Flow meter/sensor in supply pipe

© Danfoss | 2020.04

AI215286474517en-000301 | 1

Data sheet

Infocal 9 - Energy calculator

Ordering Infocal 9

Primarily for flow

Pulse value

Installation

 

Power

Energy

Communication

Cable

Code

meter/sensor

 

supply

units

length1)

number

SONO 3500 CT

2,5 liter / pulse

Return

 

Battery

0,01 MWh

M-Bus

3m

187F9007

(DN100-DN150)

 

 

 

 

 

 

 

 

 

SONO 3500 CT

10 liter / pulse

Return

 

Battery

0,01 MWh

M-Bus

5m

187F9008

(DN200-DN350)

 

 

 

 

 

 

 

 

 

SONO 3500 CT

50 liter / pulse

Return

 

Battery

0,01 MWh

M-Bus

5m

187F9009

(DN400-DN500)

 

 

 

 

 

 

 

 

 

SONO 3500 CT

100 liter / pulse

Return

 

Battery

0,01 MWh

M-Bus

5m

187F9010

(DN600-DN1200)

 

 

 

 

 

 

 

 

 

SONO 3500 CT

2,5 liter / pulse

Return

 

230V AC

0,01 MWh

M-Bus

3m

187F9011

(DN100-DN150)

 

 

 

 

 

 

 

 

 

SONO 3500 CT

10 liter / pulse

Return

 

230V AC

0,01 MWh

M-Bus

5m

187F9012

(DN200-DN350)

 

 

 

 

 

 

 

 

 

SONO 3500 CT

50 liter / pulse

Return

 

230V AC

0,01 MWh

M-Bus

5m

187F9013

(DN400-DN500)

 

 

 

 

 

 

 

 

 

SONO 3500 CT

100 liter / pulse

Return

 

230V AC

0,01 MWh

M-Bus

5m

187F9014

(DN600-DN1200)

 

 

 

 

 

 

 

 

 

SonoSensor 30

1 liter / pulse

Return

 

Battery

0,001

M-Bus

2m

187F9000

(DN15 - DN25)

 

MWh

 

 

 

 

 

 

 

SonoSensor 30

10 liter / pulse

Return

 

Battery

0,01 MWh

M-Bus

3m

187F9001

(DN40 - DN100)

 

 

 

 

 

 

 

 

 

1) Cable length of Pt 500, Ø 5.2 mm, 2-wire temperature sensor.

 

 

 

 

 

Ordering accessories

Product

Designation

Quantity

Code no.

 

 

 

 

Power supply

Battery 3.6 V DC (D-cell)

1 pc.

187F3380

 

 

 

 

Power supply

Mains unit 230 V AC

1 pc.

187F3381

 

 

 

 

Communication module

M-Bus module

1 pc.

187F3382

 

 

 

 

Communication module

Radio OMS 868.95 MHz

1 pc.

187F3383

 

 

 

 

Communication module

RS-232 M-Bus

1 pc.

187F3385

 

 

 

 

Communication module

RS-485 M-Bus1)

1 pc.

187F3386

Communication module

M-Bus, RS232 and two pulses outputs1)

1 pc.

187F3387

Communication module

M-Bus, RS232 and two 4-20mA outputs1)

1 pc.

187F3388

Temperature sensor

Pt 500 / f 5.2 mm / 1.5 m cable, MID

1 pair

187F3125

 

 

 

 

Temperature sensor

Pt 500 / f 5.2 mm / 2 m cable, MID

1 pair

187F3126

 

 

 

 

Temperature sensor

Pt 500 / f 5.2 mm / 3 m cable, MID

1 pair

187F3127

 

 

 

 

Temperature sensor

Pt 500 / f 5.2 mm / 5 m cable, MID

1 pair

187F3390

 

 

 

 

Temperature sensor

Pt 500 / f 5.2 mm / 10 m cable, MID

1 pair

187F3391

 

 

 

 

Sensor pockets

Ø 5.2 mm, brass, 35 mm length

1 pair

087G6053

 

 

 

 

Sensor pockets

Ø 5.2 mm, brass, 52 mm length

1 pair

087G6054

 

 

 

 

Sensor pockets

Ø 5.2 mm, brass, 85 mm length

1 pair

087G6055

 

 

 

 

Sensor pockets

Ø 5.2 mm, brass,120 mm length

1 pair

087G6056

 

 

 

 

Sensor pockets

Ø 5.2 mm, stainless steel, 85 mm length

1 pair

087G6057

 

 

 

 

Sensor pockets

Ø 5.2 mm, stainless steel, 120 mm length

1 pair

087G6058

 

 

 

 

Sensor pockets

Ø 5.2 mm, stainless steel, 155 mm length

1 pair

087G6059

 

 

 

 

Sensor pockets

Ø 5.2 mm, stainless steel, 210 mm length

1 pair

087G6060

 

 

 

 

1) Only with mains supply 230 V AC

2 | AI215286474517en-000301

© Danfoss | 2020.04

Data sheet

Infocal 9 - Energy calculator

Technical data

Basic data

Accuracy

 

Class 2, EN1434

 

Ambient

 

Class E2 +M1

 

Environmental

 

Class C EN1434

 

Protection class

 

IP 65

 

Max. ambient humidity

 

93% rel. humidity

Display

Display

 

LCD, 8-digit

indication

Units

 

MWh - GJ - Gcal - °C - m³ - m³/ h

 

 

 

Values displayed

 

Energy , volume, power, flow rate ,

 

 

temperatures

 

 

 

 

Temperature

Ambient operating temperature

 

+5 ... +55

Input

Temperature sensors

 

Type

Pt 500 with 2 or 4-wire leads;

 

 

Ø 5.2 or Ø 6.0 mm

 

 

 

 

 

Measuring cycle

 

T(s)

Temperature: 10s

 

 

(for both battery and 230 V supply)

 

 

 

 

 

Max. temperature difference

 

∆θmax (K)

160

 

Min. temperature difference

 

∆θmin (K)

3

 

Starting temp. difference

 

∆θ (K)

0.15 K

 

Temperature, measuring range

 

θ (°C)

0 ... 160

Supply voltage

3.6 V DC Lithium-battery (D-cell) or Mains supply 230 V AC

 

Battery

min. 12 years (including AMR communication)

 

 

life time

 

 

 

 

 

 

Weight

0.5 kg

 

 

 

 

 

 

 

Design and function

Calculator

 

The calculator contains all necessary circuits for

 

recording flow rates and temperatures, and for

 

calculating, logging and displaying the data.

 

The calculator housing can be mounted on the

 

wall or standard DIN rail.

 

The calculator can be conveniently read from

 

an 8-digit display with units and symbols. Two

 

push-buttons provides user-friendly control of

 

the various display loops.

 

All failures and faults are recorded automatically

 

and shown on LCD display.

 

To protect the reading data, all relevant data

 

are saved in a non-volatile memory (EEPROM).

 

This memory saves the measured values,

 

device parameters and types of error at regular

 

intervals.

Temperature sensors

Pairs of Pt 500 Ø5.2 mm (or Ø6.0 mm) temperature sensors with 2-wire (or 4-wire) leads can be used. Cable lengths of 3 m, 5 m and 10 m are available.

Optical interface

Optical interface is integrated into the front panel of the calculator. It is designed for data reading via M-bus protocol.

The optical interface is activated by pressing the control button, and it automatically shuts off

5 minutes after the button has been activated or after data transmission via interface is completed.

Wired M-Bus interface

The energy meter has one slot for an additional communication module. The internal M-Bus module provides data reading possibility via M-Bus protocol:

M-Bus protocol according to EN13757-3 standard

2-wire with polarity reversal protection

Electrical isolation

Maximum voltage 50 V DC

Current drawn: one M-Bus load (1.5 mA)

Primary or secondary addressing

Baud rate 300/1200/2400/4800/9600 (default: 2400 baud rate)

Battery lifetime min. 12 years ( D cell)

Fastest reading interval at battery supply: one meter on the bus every 280 seconds (2400 baud rate)

Fastest reading interval at mains supply: no limits

Radio OMS 868.95 MHz interface

The module can provide data reading via radio module:

Wireless M-Bus protocol according to EN13757-4

OMS (open metering system) compatible

868.95 MHz, T1 mode (unidirectional)

Sending interval every 90 seconds (suitable for ‘walk by’ readings)