Danfoss INFOCAL 8 Instruction

Danfoss District Energy VI.SH.L1.02 DEN-SMT/PL
1
Instruction
1.0 Table of contents
INFOCAL 8 Energy calculator
1.0 Table of contents ......................................................................................................................................................................................................................................................................... 1
2.0 Safety notes and product information ........................................................................................................................................................................................................................1
3.0 Installation of energy calculator .......................................................................................................................................................................................................................................2
4.0 Installation of temperature sensors ...............................................................................................................................................................................................................................3
5.0 Pulse input volume pulses ....................................................................................................................................................................................................................................................4
6.0 Power supply ..................................................................................................................................................................................................................................................................................5
7.0 Start-up operation ...................................................................................................................................................................................................................................................................... 6
8.0 Expansion modules ................................................................................................................................................................................................................................................................... 6
9.0 Communication ...........................................................................................................................................................................................................................................................................7
10.0 Display .................................................................................................................................................................................................................................................................................................9
11.0 Simple operation ......................................................................................................................................................................................................................................................................10
12.0 Error codes ....................................................................................................................................................................................................................................................................................10
Following instructions refer to the energy calculator.
The regulations on the use of energy meters must be observed! The meter installation is only to be performed by an installation and/ or electrical contractor using personnel trained in the installation and use of electrical equipment and familiar with the Low Voltage Directive.
- The specied absolute temp. measuring range is 0 ... 90°C/105°C/180°C
- The temperature range depends on calculator variant
- The exact temperature range is shown on the type plate
- The specied operating/ambient conditions are: 5…55 °C; max. 93% rel. humidity
- Protection class: IP54;
- Ambient temperatures below 35 °C ensures typical battery lifetime
This installation guide is intended for trained personnel and does not contain any basic working steps.
If the ow sensor is insulated with the pipeline, the calculator must be accessible.
Safety Note
The seal on the energy calculator must not be damaged! A damaged seal will result in immediate invalidation of the factory warranty and verication. The cables supplied with the calculator must not be shortened, extended or changed in any other way.
Instruction INFOCAL 8
DEN-SMT/PL VI.SH.L1.02 Danfoss District Enrgy
2
Make sure the energy calculatorv is installed suciently far away from possible sources of electromagnetic interference (switches, electric motors, uorescent lamps, etc...)
.
The energy calculator should be installed in an accessible position for service and operating personnel. Initial operation is to be carried out and recorded after installation.
For medium temperatures of more than 90°C or if T
water
< T
ambient
(for application as cooling meter or heat meter with cooling tari), the calculator must be removed from the ow sensor and installed asucient distance away from heat sources. A wall holder (supplied with meter) or a space holder (optional) is available for this purpose.
3.0 Installation of energy calculator
T: 5 ... 90°C T
water
> T
ambient
T: 5 ... 130 / 150°C T
water
< T
ambient
space holderwall mounting
Instruction INFOCAL 8
Handle the temperature sensors carefully! The sensor cables are tted with coloured type labels:
Red (TH): sensor in hot line, Blue (TC): sensor in cold line
Make sure the sensors are mounted symmetrically (both directly immersed, or both installed in a pocket). The maximum cable length is 10 m. The connecting cables must not be shortened or extended. The free temperature sensor can be installed in a ball valve /adapter or in a conformity tested pocket for this type of sensor. Ensure that the temperature sensors are permanently connected during operation.
For installation in a ball valve (same for adapter), a 4-piece coupling set is enclosed in a separate bag. See procedure under item 1…5 on the right. Insert an O-ring in the sensor hole using the mounting pin supplied. If the sensor is installed in a pocket, it must be inserted as far as the bottom of the pocket and then secured. The pockets are best installed in T-pieces with a 45° or 90° angle. The tip of the pocket must point in the opposite direction to the direction of ow and must be located in the middle of the pipe. The temperature sensors must be sealed after installation in the pockets.
Connect the sensor cables to terminals as shown below.
- For 2-wire connection to terminal 5-6 and 7-8
- For 4-wire connection to terminal 1/5 - 6/2 and 3/7 - 8/4
Calculator type
Sensor
marking
Wiring 2-wire sensor
Wiring 4-wire sensor
Installation
position
Heating
Red T
Hot
(5-6) T
Hot
(1/5-6/2) Inlet
Blue T
Cold
(7-8) T
Cold
(3/7-8/4) Outlet
Heating / Cooling
Red T
Hot
(5-6) T
Hot
(1/5-6/2) Inlet
Blue T
Cold
(7-8) T
Cold
(3/7-8/4) Outlet
Cooling
Red T
Hot
(5-6) T
Hot
(1/5-6/2) Outlet
Blue T
Cold
(7-8) T
Cold
(3/7-8/4) Inlet
Cable entries: 1: Cable entry for connecting T
Hot
2: Cable entry for connecting T
Cold
Terminals for temperature sensors:
4.0 Installation of temperature sensors
The operation of any violation of this guidance will result in immediate invalidation of the factory warranty and verication.
Tighten the plug screw with a torque of approx. 12 Nm
Installation in a ball valve:
Installation in a pocket:
Danfoss District Energy VI.SH.L1.02 DEN-SMT/PL
3
Instruction INFOCAL 8
DEN-SMT/PL VI.SH.L1.02 Danfoss District Enrgy
4
Installation of temperature sensors, continued
District heating/
boiler application
Installation of temperature sensors in 3 types of applications:
Combined heating/
cooling application
Chilled water application
THT
C
TCT
H
Flow meter connection with pulse input and, if required, with power supply at the terminals 9 (+Vcc), 10 (ow pulse), 11 (- Gnd) of the calculator.
- Pulse frequency < 200 Hz
- Pulse duration > 3 msec
- Pulse rate in display “Loop 3 - INFO” (In0)
Flow sensor connection Sensor marking
External Vcc 3.6 V 9 (+)
Open collector 10
Ground 11 (-)
5.0 Pulse input volume pulses
Calculator heating
Calculator heating / cooling
Calculator cooling
Instruction INFOCAL 8
6.0 Power supply
INFOCAL 8 can be powered from lithium battery (11 or 16 years life­time) or 230V AC / 24V AC mains unit supply.
Battery
3.6 V DC lithium battery is tted in the standard version. The battery is not to be charged, replaced or short-circuited. Ambient temperatures below 35°C ensure the typical life of the battery.
Mains unit
24 VAC or 230 VAC power supply units can be changed to or retro­tted at any time. The cable is to be fuse at max. 6 A and protected against manipulation. Connect the cable according the labelling of the terminal. The power supply unit noties the meter if mains voltage is present.
If the power supply fails, the backup battery (CR2032) provides the power supply for up to 1 year. The LCD readings (on pressing button) and the date and time are still updated, but none of the measuring functions work, incl. the ow rate measurement. Communication still functions over the optional M-Bus, RS485 and RS232 modules or the optical interface, but reduces the life of the backup battery. The radio function is switched o in the event of power supply failure.
Caution
Used batteries must be disposed of at suitable waste collection points. Risk of explosion if battery is replaced by an incorrect type.
Caution
It is strictly necessary to have protective safety cover installed at all times. Under no circumstances connect between the two phases otherwise the power supply unit will be destroyed.
SONO 1500 CT Calculator terminal
Vcc (brown)* 9 (+)
Pulse (white) 10
GND (blue) 11 (-)
SONO 3500 CT Calculator terminal
56 10 57 11 (-)
white blue yellow brown
Wiring ow sensor SONO 1500 CT:
* Connect only if SONO 1500 CT with external supply
Wiring ow meter SONO 3500 CT: (Typically connected to pulse output A)
Danfoss District Energy VI.SH.L1.02 DEN-SMT/PL
5
Instruction INFOCAL 8
DEN-SMT/PL VI.SH.L1.02 Danfoss District Enrgy
6
Once the calculator has been installed, the components (calculator, volume measuring component and both temperature sensors) must be sealed and the meter taken into operation.
Bleed the system until the ow rate display is steady. Check the display for a plausible indication of ow rate and temperatures.
7.0 Start-up operation
The energy calculator has two slots for expansion modules. The mod­ules can be used and combined as shown in the table. The analogue module needs both slots. Integrated radio is always possible. The analog module occupies both positions.
8.1 Installation of modules
1. Open the calculator by releasing the side fasteners
2. Lock the module into the appropriate slot and carefully connect the pre-formed ribbon cable at both ends.
3. Close the lid and check the calculator for correct operation by pressing the push button (loop 3). Renew the seal of the housing lid if the calculator functions correctly.
The relevant ESD regulations (electrostatic discharge) must be observed. No liability is accepted for damage (especially to electronic circuits) resulting from failure to comply with the ESD regulations.
These modules have no eect on consumption recording and can be tted retrospectively without damaging the verication mark.
interface / slot 2
no module
M-Bus
RS232
RS485
pulse input
L-Bu s
(for external
radio)
interface / slot 1
no module
M-Bus
RS232 RS485
pulsse input
pulse output
pulse in-/
output
analogue
output
4...20mA
L-Bu s
(for external
radio)
• combination is possible  combination is not possible * integrated radio is always possible
2
1
3
3
8.0 Expansion modules
1 Slot 1 2 Slot 2 3 Fixing clips
Instruction INFOCAL 8
9.0 Communication
The calculator supports three communication channels. Additional to the radio communication two wired communication modules can be used, e.g. two M-Bus modules. The protocol of the two channels can be dierent but is preset at factory, whereby the radio telegram will have the same content than the module 2. Customer specic requirements can be dened by using the IZAR@SET Software. Each port has its own primary address. Both ports have a common second­ary address, which is set to the serial number ex works.
9.1 Communication via radio
The integrated radio module is an interface for communication with OMS radio receivers. Unidirectional communication has the following specication:
• The module sends every 12 s (send period 0.1 % of duty cycle (min. 8 s); variable, depending on protocol length and programming)
• The radio communicates the actual data register
• Transmission frequency: 868 MHz or 434 MHz
• Various Diehl Metering receivers are available for receiving the protocol (e.g. Bluetooth, GPRS, LAN, …)
• The protocol corresponds to the”Open Metering” or “DM Standard” and is encrypted
• Reading modes: Walk-By, Drive-By, Fixed-Network
• For problematic radio installations (shield) the external radio module set can also be used
9.2 M-Bus communication module
The M-Bus communication module is a serial interface for communi­cation with external devices (M-Bus control centres), e.g. IZAR CENT­ER. A number of meters can be connected to a control centre. The module contains a 2-pole terminal strip with terminals marked 24, 25.
• The connection is not polarity-conscious and is electrically isolated
• M-Bus protocol to EN 1434 standard;
• 300 or 2400 baud (auto baud detect)
• Connection for 2 x 2.5 mm² wires
• Current drawn: one M-Bus load
9.3 RS232 Communication module
The RS232 communication module is a serial interface for communi­cating with external devices, e.g. PC; 300 or 2400 bauds. The module contains a 3-pole terminal strip with terminals marked 62 (Dat), 63 (Req) and 64 (GND). The used communication protocol is M-Bus. The coloured wires are to be connected as shown:
9.4 RS485 Communication module
The RS485 communication module is a serial interface for commu­nication with external devices, e.g. PC; 2400 bauds only. The used communication protocol is M-Bus. The module contains a 4-pole terminal strip with terminals marked D+, D-, +12 V and GND. The module needs an external power supply of 12 VDC ±5 V.
62 = brown 63 = white 64 = green
Danfoss District Energy VI.SH.L1.02 DEN-SMT/PL
7
Instruction INFOCAL 8
DEN-SMT/PL VI.SH.L1.02 Danfoss District Enrgy
8
9.5 Pulse input function module
Module for two additional meters. Pulse input 1 is marked as “I1- ”,
input 2 with “I2 - “. Pulse inputs can be programmed (IZAR@SET ) with a value: 1, 2.5, 10, 25, 100, 250, 1000, 2500 litre per pulse.
• Pulse transmitter must be electrically isolated, e.g. Reed contact
• Possible units are all the energy units available in the meter, the volume unit m³ or no unit.
Data is accumulated separately in registers; can be read in the dis­play as IN1 and IN2 and can be transferred via the communication modules.
9.6 Pulse output function module
The module is equipped with 2 pulse outputs, which can be freely programmed using the IZAR@SET software. The outputs are marked as “O1 - “ and “O2 - “ on the terminal strip and as Out1 and Out2 on the display.
• External supply: Vcc = 3-30 VDC
• Output current ≤ 20 mA with a residual voltage of ≤ 0.5 V
• Open Collector (Drain)
• Electrically isolated
• Output 1: f ≤ 4 Hz Pulse duration: 125 ms ±10 % Pulse pause: ≥ 125 ms –10 %
• Output 2: f ≤ 100 Hz Pulse duration pulse/pause ~1:1
• The volume pulse rate can be freely programmed
• Standard: last digit in the display
9.7 Combined function module (IN/OUT)
The combined module has 2 inputs and 1 output. See chapter 8.5 for the specic characteristics on the pulse input. A 3 VDC voltage is connected to the “+” terminal and can be used as the supply for a ow sensor. The pulse output has the same characteristics as pulse output 1 speci­ed under 8.6. It is not, however, electrically isolated.
9.8 Analogue output function module
The module has 2 passive analogue output connections which are freely programmable using the IZAR@SET software. On the terminal strip, the electrically isolated outputs “1” and “2” are marked and the polarity is indicated (“+” and “–”).
• Passive, external power supply: 10…30 VDC
• Current loop 4 … 20 mA whereat 4 mA = 0 value; 20 mA = programmable maximum value
• Overload up to 20.5 mA, then residual current
• The module displays errors with 3.5 mA or 22.6 mA (programmable)
• Output values: power, ow, temperatures
9.9 Test output
The internally located test output is intended for testing laboratories. The manufacturer supplies two special cables:
1. Volume testing pulse
2. Energy testing pulse
Please refer to the inspection and testing manual for further specications (pulse rate, pulse duration/pause, pulse frequency).
Input frequency ≤ 8 Hz Min. pulse duration 10 ms Input resistance 2.2 M Terminal voltage 3 VDC Cable length up to 10 m
The module is connected with the meter electronics by means of a ribbon cable. The separate plug connector on module slot 2 is necessary for the perfect functioning of the analogue outputs.
Ensure that the temperature sensors (measurement resistances) remain in contact without interruption during energy verication.
T
T
T T
Instruction INFOCAL 8
10.0 Display
To show the data generated by the calculator in the display, various windows are provided as loop functions that can be called up in succession to display the system information associated with each window (e.g. energy amounts, water volume, running days, water amounts, current temperatures). The energy calculator has 6 dier­ent display loops.
The various display windows comprise up to several displays that change at intervals of 2 – 4 s. The loops in the display are numbered 1, 2, ... and 6 to help the user nd his way around quickly. The main loop is programmed with the current data as default setting, e.g. for energy, volume and ow rate.
Informative Displays (Standard)
Loop Sequence Window 1 Window 2 Window 3
“1”
Main loop
1.1 Accumulated energy
1.2 Volume
1.3 Accumulated energy (cooling)
(Sequence will be shown only
in a heat meter with cooling tariff)
1.4 Flow
1.5 Power
1.6 Forward ⁄  return temperature
1.7 Temperature dierence
1.8 Operating days Error hours
1.9 Error status
1.1 Display test
Loop Sequence Window 1 Window 2 Window 3
“2”
Accounting
date loop
2.1 Accounting date 1 Accounting date 1 energy ‚ Accd 1A’
2.2 ‚Accd 1’ Future accounting date 1
2.3 Accounting date 1 previous year
Accounting date 1
previous year energy
‚ Accd 1L’
2.4 Accounting date 2 Accounting date 2 energy ‚A ccd 2A’
2.5 ‚Accd 2’ Future accounting date 2
2.6 Accounting date 2 previous year
Accounting date 2
previous year energy
‚Accd 2L’
...
2.14 Accounting date 2 previous year Pulse input 2 Pulse input volume 2
Loop Sequence Window 1 Window 2 Window 3
“3“
Info loop
3.1 Current date Current time
3.2 ,SEC_Adr' Secondary address
3.3 ,Pri_ Adr 1' Primary address 1
3.4 ,Pri_Adr 2' Primary address 2
3.5 Installation position
3.6 Pulse input  Volume
3.7 ,Port 1’ No. of the mounted module at port 1
3.8 ,Port 2’ No. of the mounted module at port 2
3.9 Status integrated radio
(Sequence will be shown only in
meters with integrated radio)
3.1 software version Checksum
Loop Sequence Window 1 Window 2 Window 3
“4”
Pulse input
loop
4.1 ,I n1' Accumulated value pulse input 1 ,PPI' pulse value 1
4.2 ,In2' Accumulated value pulse input 2 ,PPI' pulse value 2
Loop Sequence Window 1 Window 2 Window 3 Window 4 Window 5 Window 6
“5”
Tari loop
Only in a heat meter with cooling tariff.
Loop Sequence Window 1 Window 2 Window 3 Window 4 Window 5 Window 6
“6”
Monthly value
loop
6.1 ,LOG’ date last month energy volume max. flow rate max. power
6.2 ,LOG’ date month  1 energy volume max. flow rate max. power
6.3 ,LOG’ date month  2 energy volume max. flow rate max. power
... ...
6.24 ,LOG’ date month  23 energy volume max. flow rate max. power
Danfoss District Energy VI.SH.L1.02 DEN-SMT/PL
9
Instruction INFOCAL 8
DEN-SMT/PL VI.SH.L1.02 Danfoss District Enrgy
10
The push-button is used to switch through the various displays. The button can be pressed for a short or long time. A short press of the button (< 3 seconds) switches to the next display within a loop and a long press (> 3 seconds) switches to the next display loop. The “Energy” window (sequence 1.1) in the main loop is the basic display. The meter automatically switches o the display to save power if the button is not pressed for approx. 4 minutes (except in the event of fault) and returns to the basic display when the button is pressed again.
11.0 Simple operation
The error code is displayed in the main loop if an error occurs. All the other windows can still be selected by pressing the button. The error code display appears again automatically if the button is not pressed for approx. 4 minutes.
The error display disappears automatically as soon as the cause of the error has been cleared. All errors present longer than 6 minutes are saved in the error log.
Error code
Description
C – 1 Basic parameters saved in ash or RAM have been lost E 1 Temperature range outside [-19.9 °C ... 199.9 °C] e.g.
sensor short-circuit, sensor break
E 3** Flow and return sensors interchanged E 4 Hardware error US measurement, e.g. transducer
or control defective or short circuit
E 6** Flow direction of ow meter incorrect E 8
No primary power supply (only with power supply unit); supply via backup battery
E 9 Battery nearly discharged, end of lifetime reached E A*
Leak: Pipe break detection
E b*
Leak: Energy meter leak detection
E C*
Leak: Leak pulse input 1
E d*
Leak: Leak pulse input 2
* optional ** application dependent
12.0 Error codes
Instruction INFOCAL 8
Danfoss District Energy VI.SH.L1.02 DEN-SMT/PL
11
Instruction INFOCAL 8
VI.SH.L1.02
Produced b y Danfoss A/S © 12/2014
Loading...