In this installation manual, the word “element”
refers to both heating cables and heating mats.
If the words “heating cable” or “heating mat” are
used, the instruction in question applies only to
this type of element.
All dimensioning, product selection, installation
and commissioning of any given application are
the responsibility of an authorized installer.
Any application using heating elements or thermostats purchased by end user must be approved by
an authorized electrician prior to commissioning.
• Including type, size, installation and connection of the heating element.
• Including type, size, connection and settings
of the thermostat controlling the heating
element.
• Children shall not play with the heating
element.
• This heating element can be used by
children aged from 8 years and above and
1�1 Safety Instructions
persons with reduced physical, sensory or
mental capabilities or lack of experience and
knowledge if they have been given supervision or instruction concerning use of the
appliance in a safe way and understand the
hazards involved.
• Cleaning and user maintenance shall not be
made by children without supervision.
The intended use of the heating elements covered
by this installation manual is oor heating, only.
• According to IEC 60335 the mats may not be
installed in a metallic oor or storage heating
application.
• Mats shall be fully embedded in at least 5
mm concrete, screed, tile adhesive or similar.
incl. tiles
Never cut or shorten the heating element
• Cutting the heating element will void the
warranty.
• Cold leads can be shortened to suit requirements.
If ohmic resistance and insulation resistance are
not as labelled, the element must be replaced.
• The ohmic resistance must be within -5 to
+10 % of the value labelled.
• The insulation resistance should read >20
M after one minute at min. 500V DC.
3�1 Installing heating elements
Observe all instructions and guidelines in section
1.1 and 1.2.
Heating elements
• Position the heating element so that it is at
least half the C-C distance from obstacles.
• Elements must always be in good contact
with the heat distributor (e.g. concrete), see
section 4 for details.
Heating mats
• Always roll out heating mats with the heating cables facing up.
• When the heating mat reaches the area
boundary, cut the liner/net and turn the mat
before rolling it back.
Extending cold leads
• Avoid extending cold leads if possible. Wire
cold leads to e.g. junction boxes or cable
wells.
• Be aware of power loss in the cable according to local regulations.
3�2 Sensor Installation
• Mandatory under wooden oors and on
wooden sub oors.
• The oor sensor should be mounted in an insulating conduit, sealed at the oor end, for
easy replacement of the sensor if required.
• The oor sensor must be considered a LIVE
cable; therefore any extension made to the
sensor wiring should be treated in the same
way as normal mains voltage cabling.
8
8
Danfoss VIEXD202
Danfoss VIEGC502
• The sensor can be extended up to a total of
50 m using 1.5 mm installation cable.
• The minimum bending radius for the pipe is
50 mm (1).
• The sensor cable must be placed between
two loops of the heating cable (2).
• To avoid cracks in the concrete oor do not
switch on the heat until the oor has completely hardened.
Cut out a wall groove and x
cable ducts and connection
box. Chisel o a groove for the
sensor conduit and cold cable.
Fix the sensor conduit e.g. with
a glue gun.
4�2 Floor heating in joist oor constructions
Wooden oor on joist constructions
The sub oor construction must be well
insulated
• Insulate thermal bridges and close vents, e.g.
between the oor construction and walls/
roofs.
Roll out the element. Attach it to
the sub oor. Cut and turn the
mat mesh when meeting walls
or obstacles. Do NOT cut the
heating elements.
Apply exible self-levelling
compound, vapour barrier, and
tile adhesive, depending on the
oor nish.
1. Wooden oor covering.
2. Floor joists.
3. Heating Cable.
4. Mesh (reinforced or ne) or aluminium foil.
5. Insulation.
6. Vapour barrier.
7. Sub oor construction.
• The optimal distance between the heating
cables and the underside of the oor covering is 3-5 cm.
• The heating cable must be fastened to the
mesh or foil at ma. 25 cm intervals.
The heating cables may not touch the insulation or woodwork
• Fine mesh or foil can be laid directly onto the
insulation, reinforced mesh should be raised
10 mm from the insulation (e.g. use llets).
• The distance between the heating cable and
the joists should be at least 30 mm.
Danfoss VIEXD202
Danfoss VIEGC502
Heating cables may cross a joist
• Through a 30 mm x 60 mm (h x w) recess
lined with aluminium tape.
• Make sure the cable is never in contact with
bare wood.
• Must be separated from cables by at least 5
mm of pressure distribution board.
Installation summary
Cut out a hole for the connection and the oor
sensor conduit and remove any sharp edges.
Fix the conduit to the sub oor e.g. with glue.
See the installation manual for the Danfoss Reect
product for further information.
4�4 Floor heating in concrete oors (> 3 cm)
Wooden oors (example with concrete slab)
• Observe the total insulation value above the
pressure distribution board.
• R < 0.10 mK/W corresponding 1 Tog or a
thin carpet.
Install the heating cable. Make sure that the
cable, end termination, and connection are in
contact with the aluminium plate or surrounded by aluminium.
Other combinations of oor covering and existing
oor construction are also possible.
Danfoss VIEXD202
Danfoss VIEGC502
1. Top ooring.
2. Noise absorption mat/rag felt, tile adhesive
depending on top ooring.
3. Vapour barrier.
4. Concrete.
5. Heating cable.
6. Concrete slab or reinforced mesh.
7. Insulation.
8. Capillary-breaking layer, concrete, etc..
The heating cables may not touch the
insulation
• The heating cable must be separated by
reinfored mesh or concrete slab.
Cables wrapped around pipes
are attached as shown for
every 20-30 cm of pipe with
aluminium tape. Straight cables
Apply aluminium tape below
(mandatory for plastic pipes)
and on top of pipe for the whole
length of cable.
must be tted as shown at 5
or 7 o’clock. In-pipe cables are
tted directly in the pipe with
compression gland.
16
16
Danfoss VIEXD202
Danfoss VIEGC502
Extend cold leads/terminate
cables, and place connections
in a dry place. Mount connection box on or close to pipe, and
install thermostat next to pipe.
If the element is connected to a thermostat such
as a ECtemp, congure basic settings according to
the table below and as described in the thermostat installation manual.
If applicable, adjust the temperature limit in accordance with the manufacturer’s recommendations in order to prevent damage to e.g. the oor
or the pipe.
ThermostatMax� loadFloor heating in generalFrost protection of pipe systems
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed or electronically published material. Danfoss reserves the right to alter its products without notice. This also
applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specications already agreed. All trademarks in this material are property of
the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.