Rotary valves HRB 3, HRB 4

Description

 

 

 

 

HRB rotary valves can be used in combination

 

 

 

 

 

with electric actuators AMB 162 and AMB 182.

 

 

 

 

 

Features:

 

 

 

 

 

 

 

• Lowest leakage in class

 

 

 

 

 

 

Unique position indicator

 

 

 

 

 

 

 

(visible also when actuator in mounted)

 

 

 

 

 

Ergonomic handle

 

 

 

 

 

 

 

Easy installation

 

 

 

 

 

 

 

• For mixing and diverting applications

 

 

 

 

 

Internal thread connection

 

 

 

 

 

 

Main data:

 

 

 

 

 

 

 

DN 15–50

 

 

 

 

 

 

 

kVS 0.4-40 m3/h

 

 

 

 

 

 

 

PN 10

 

 

 

 

 

 

 

Tmax=110 °C

 

 

 

 

 

 

 

3-way or 4-way

 

 

 

 

 

 

 

S characteristic

 

 

 

Danfoss HRB rotary valves are primarily designed

 

 

 

 

 

 

 

 

 

for regulation of flow temperature in heating

 

 

 

 

 

 

systems where a certain leakage can be accepted

 

 

 

 

 

 

and where a defined control characteristic is not

 

 

 

 

 

 

required.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ordering

 

 

 

 

 

 

 

 

 

Type

DN

kVS

 

PN

 

Connection

Code No.

 

 

 

 

(mm)

(m3/h)

 

 

HRB 3

HRB 4

 

 

 

 

 

 

 

 

 

0.4

 

 

 

 

065Z0399

 

 

 

 

0.63

 

 

 

 

065Z0400

-

 

 

15

1.0

 

 

 

Rp 1/2”

065Z0401

 

 

 

 

 

 

 

 

1.63

 

 

 

065Z0402

 

 

 

 

 

 

 

 

 

 

 

 

2.5

 

 

 

 

065Z0403

065Z0411

 

 

 

4.0

 

 

 

 

065Z0398

-

 

HRB 3

 

2.5

 

10

 

 

065Z0397

-

 

HRB 4

20

4.0

 

 

Rp 3/4"

065Z0404

065Z0412

 

 

 

 

 

 

 

6.3

 

 

 

 

065Z0405

065Z0413

 

 

25

6.3

 

 

 

Rp 1"

065Z0406

-

 

 

10

 

 

 

065Z0407

065Z0414

 

 

 

 

 

 

 

 

 

32

16

 

 

 

Rp 1 1/4"

065Z0408

065Z0415

 

 

40

25

 

 

 

Rp 1 1/2"

065Z0409

065Z0416

 

 

50

40

 

 

 

Rp 2"

065Z0410

065Z0417

© Danfoss | 2017.07

VD.LH.B5.02 | 1

Data sheet

Rotary valves HRB 3, HRB 4

Ordering (continued)

Spare parts for old generation AMB actuators Spare parts and accessories for HRB valves

Picture

Type

Code No.

 

Retrofit linkages for:

 

 

HRB 3 (Gen. 2009)

 

 

065B2220 ---> 065B2230

082G4235

 

HRB 4 (Gen. 2009)

 

 

065B2240 ---> 065B2246

 

Type

 

 

DN

Code No.

 

 

 

15-20

065Z0444

 

 

 

25

065Z0445

Transparent cover, scale and pointer

 

32

065Z0446

 

 

 

40

065Z0447

 

 

 

50

065Z0448

 

HRB 3/4

 

15-20

065Z0449

 

HRB 3/4

 

25

065Z0450

 

HRB 3/4

 

32

065Z0451

Stuffing box

HRB 3

 

40

065Z0452

 

HRB 4

 

40

065Z0460

 

HRB 3

 

50

065Z0453

 

HRB 4

 

50

065Z0461

Replacement handle

 

065Z0442

Linkage kit for AMB (Gen. 2014)

 

082H0255

Technical data

Nominal diameter

DN

15

 

20

 

25

 

32

 

40

 

50

Control characteristic

 

 

 

 

 

S characteristic

 

 

 

Leakage

HRB 3

 

Diverting: max. 0.3 % of flow / Mixing: max. 1 % of flow

 

HRB 4

 

 

 

 

max. 1.0 % of kVS

 

 

 

 

 

 

 

 

 

 

 

Nominal pressure

PN

 

 

 

 

 

10

 

 

 

 

Max. closing pressure

bar

 

 

 

 

Diverting: 2 / Mixing: 1

 

 

 

Torque at PN

Nm

 

 

 

 

 

5

 

 

 

 

Medium

 

 

 

Circulation water / glycolic mixture up to 50 %

 

Medium pH

 

 

 

 

 

Min. 7, max. 10

 

 

 

Medium temperature

°C

 

 

 

 

 

2 … 110

 

 

 

Connections

 

 

 

 

 

Internal thread. ISO 7/1

 

 

 

Materials

 

 

 

 

 

 

 

 

 

 

 

 

Valve body and slide shoe

 

 

 

 

CuZn36Pb2As (Brass DZR, CW 602N)

 

 

 

Stuffing box

 

 

 

 

CuZn36Pb2As (Brass DZR, CW 602N)

 

 

 

Stuffing box sealing

 

 

 

 

 

 

EPDM

 

 

 

Pressure temperature diagram

PN 10

CuZn36Pb2As

2 | VD.LH.B5.02

© Danfoss | 2017.07

Danfoss HRB 3, HRB 4 Data sheet

Data sheet

Rotary valves HRB 3, HRB 4

Valve characteristics

B

A

HRB 3

HRB 4

Installation

Mixing

Diverting

 

Flow

<![if ! IE]>

<![endif]>From boiler

<![if ! IE]>

<![endif]>Return

 

Back to boiler

Valve mounting

Before valve mounting pipes have to be cleaned and free from abrasion. Mechanical loads on valve body caused by the pipes are not allowed. It is recommended to install a strainer into application to avoid damaging controlling components.

Note:

Install a strainer upstream of the valve (e.g. Danfoss FVR/FVF)

Connection

HRB 3 can be used as a mixing valve, diverting valve and in connection with heat exchangers where a certain leakage can be accepted.

HRB 4 operates according to the double shunt principle i.e. the water from the boiler is mixed with a certain portion of the water in the return. In this way the water which goes to the boiler reaches a higher return temperature than by using 3-way valves. This means that the risk of corrosion in oil and solid fuel boilers is reduced.

AMB

FVR/FVF

Disposal

The valve must be dismantled and the elements

 

sorted into various material groups before

 

disposal.

© Danfoss | 2017.07