Danfoss HRB 3, HRB 4 Data sheet

Data sheet
Rotary valves HRB 3, HRB 4
Description
Danfoss HRB rotary valves are primarily designed for regulation of flow temperature in heating systems where a certain leakage can be accepted and where a defined control characteristic is not required.
HRB rotary valves can be used in combination with electric actuators AMB 162 and AMB 182.
Features:
• Lowest leakage in class
• Unique position indicator (visible also when actuator in mounted)
• Ergonomic handle
• Easy installation
• For mixing and diverting applications
• Internal thread connection
Main data:
• DN 15–50
• k
0.4-40 m3/h
VS
• PN 10
• T
=110 ° C
max
• 3-way or 4-way
• S characteristic
Ordering
Typ e
HRB 3 HRB 4
DN k
(mm) (m
15
20
25
32 16 Rp 1 ⁄" 065Z0408 065Z0415
40 25 Rp 1 ⁄" 065Z0409 065Z0416
50 40 Rp 2" 065Z0410 065Z0417
VS
3
/h)
0.4
0.63 065Z0400
1.0 065Z0401
1.63 065Z0402
2.5 065Z0403 065Z0411
4.0 065Z0398 -
2.5
4.0 065Z0404 065Z0412
6.3 065Z0405 065Z0413
6.3
10 065Z0 407 065Z0414
PN Connection
Rp ⁄”
10
Rp ⁄"
Rp 1"
Code No.
HRB 3 HRB 4
065Z0399
-
065Z0397 -
065Z0406 -
© Danfoss | 2017.07
VD.LH.B5.02 | 1
Data sheet Rotary valves HRB 3, HRB 4
Ordering (continued)
Technical data
Spare parts for old generation AMB actuators
Picture Typ e Code No.
Retrofit linkages for:
HRB 3 (Gen. 2009)
065B2220 ---> 065B2230
HRB 4 (Gen. 2009)
065B2240 - --> 065B2246
Nominal diameter DN 15 20 25 32 40 50
Control characteristic S characteristic
Leakage
Nominal pressure PN 10
Max. closing pressure bar Diverting: 2 / Mixing: 1
Torque at PN Nm 5
Medium Circulation water / glycolic mixture up to 50 %
Medium pH Min. 7, max. 10
Medium temperature °C 2 … 110
Connections Internal thread. ISO 7/1
Materials
Valve body and slide shoe CuZn36Pb2As (Brass DZR, CW 602N)
Stuffing box CuZn36Pb2As (Brass DZR, CW 602N)
Stuffing box sealing EPDM
082G4235
HRB 3 Diverting: max. 0.3 % of flow / Mixing: max. 1 % of flow
HRB 4 max. 1.0 % of k
Spare parts and accessories for HRB valves
Typ e DN Code No.
15-2 0 065Z0444
25 065Z0445
Transparent cover, scale and pointer
HRB 3/4 15-2 0 065Z0449
HRB 3/4 25 065Z0450
HRB 3/4 32 065Z0451
Stuffing box
Replacement handle 065Z0442
Linkage kit for AMB (G en. 2 014) 082H 0255
HRB 3 40 065Z0452
HRB 4 40 065Z0460
HRB 3 50 065Z0453
HRB 4 50 065Z0461
VS
32 065Z0446
40 065Z0447
50 065Z0448
Pressure temperature diagram
PN 10
CuZn36Pb2As
2 | VD.LH.B5.02
© Danfoss | 2017.07
Data sheet Rotary valves HRB 3, HRB 4
Valve characteristics
B
A
Installation
HRB 3
Mixing
Diverting
Valve mounting
Before valve mounting pipes have to be cleaned and free from abrasion. Mechanical loads on valve body caused by the pipes are not allowed. It is recommended to install a strainer into application to avoid damaging controlling components.
HRB 4
Flow
From boiler
Back to boiler
Return
Connection
HRB 3 can be used as a mixing valve, diverting valve and in connection with heat exchangers where a certain leakage can be accepted.
HRB 4 operates according to the double shunt principle i.e. the water from the boiler is mixed with a certain portion of the water in the return. In this way the water which goes to the boiler reaches a higher return temperature than by using 3-way valves. This means that the risk of corrosion in oil and solid fuel boilers is reduced.
Disposal
© Danfoss | 2017.07
Note: Insta ll a strainer up stream of the va lve (e.g. Dan foss FVR/FV F)
The valve must be dismantled and the elements sorted into various material groups before disposal.
AMB
FVR/FVF
VD.LH.B5.02 | 3
Loading...
+ 5 hidden pages