Danfoss Horizontal Distribution Unit Data sheet

Data Sheet
Horizontal Distribution Unit - HDU Single-port
Application
Technical Data
Danfoss pre-fabricated HDU distribution units are made for distribution and measuring of water­based heating in 2-pipe horizontal systems.
A HDU is easily mounted on the apartment wall and connected to the riser. The radiators in the apartment are connected through the manifold.
The unit design provides a good overview of the installation, which makes after-service easy.
All Danfoss distribution units are equipped with:
heat meter, for individual measuring of en-
ergy consumption. dP controller, to ensure hydraulic stability in
the heating system.
The HDU single-port unit is wall-mounted and created for serial radiator distribution. HDU sin­gle-port units come in two versions, with left or right connection.
Max. temperature 90 °C Max. working pressure in heating system piping before the unit 2 bar Normal required differential pressure over unit (HDU-SF) 0.26 bar* Max. differential pressure in a control loop 0.22 bar Max. static pressure 10 bar (PN10) Connection to riser (in and out) R ¾" Connection to manifold (out) ¾" Power supply (Heat Meter) A-cell battery, 3.6 VDC
HDU Single-port
- with left connection
*At differential pressure in control loop 10 kPa at 100% AB-PM setting.
Danfoss Heating Solutions VDIGA102 © Danfoss 08/2012 1
Data Sheet Horizontal Distribution Unit - HDU Single-port
Installation Example
HDU single-port system
Ordering
HDU-SF Connection Code no.
Horizontal Distribution Unit Single Flat - HDU-SF single-port right 003L1241 Horizontal Distribution Unit Single Flat - HDU-SF single-port left 003L1242
Accessories and Spare Parts Code no.
Manifold port plug (10 pcs.) 003L1246 Capillary tube for AB-PM 003L8152 Filter for strainer 065B8248
Modules for Heat Meter Code no.
M-Bus module 087G6027
Communication
Function
Compression Fittings Data Size Code no.
For PEX tubing (in accordance with ISO 15875)
For ALUPEX tubing
For steel and copper tubing
Note! Max. flow temperature given by the tube manufacturer must not be exceeded.
L-Bus module (use for external radio) 087G6035 RS232 module 087G6029 RS485 module 087G6032 Analogue output module (4 - 20 mA) 087G6034 Combined module (2 pulse inputs / 1 pulse output) 087G6041 Pulse input module (2 inputs) 087G6037 Pulse output module (2 outputs) 087G6039
16 x 2 mm 013G4156
PN6 G ¾” internal thread
PN10 G ¾” internal thread
PN10 G ¾” internal thread
20 x 2 mm 013G4160
20 x 2.25 mm 013G4093
20 x 2.5 mm 013G4161
16 x 2 mm 013G4186 20 x 2 mm 013G4190
20 x 2.25 mm 013G4093
20 x 2.5 mm 013G4191
16 mm 013G4126 18 mm 013G4128
2 VDIGA102 © Danfoss 08/2012 Danfoss Heating Solutions
1
2
3
4
6
7
Data Sheet Horizontal Distribution Unit - HDU Single-port
Design
Materials in Contact with Water
1. Ball valve for in- and outlet connection to the riser.
2. Strainer to trap dirt, sand etc. from pipe water (re-
placement filter available as accessory).
3. AB-PM automatic balancing valve, combines three functions: differential pressure controller, control valve with linear characteristic and flow limiter.
4. Manifold for radiator connection, flow.
5. Manifold for radiator connection, return.
6. Automatic air vent and drainage (both inlet and
outlet has drainage and air vent possibilities).
7. Heat Meter for energy measuring, with 8-digit LCD.
8. Cabinet (with lockable door).
Shut- off valves Body, tailpiece, ball Brass
Seals PTFE O-ring EPDM
Strainer Body Brass
Filter Stainless steel O-ring EPDM
AB-PM valve Body, cone (CV), seat (CV) Brass
Membrane, O-ring, seat (PC) EPDM Spring, cone (PC), screw Stainless steel Flat gasket NBR Sealing agent Dimethacrylate Ester Capillary tube Copper
& 5 Manifold Inlet adapter, shutter, manifold
pipe, Euro cone connector O-rings EPDM
Air vent & drainage Body Brass
Seals EPDM
Heat Meter Body of flow meter Brass
Temperature sensors, reflectors Stainless steel Measuring tube qp 0.6 - 2.5 --> PES
Other parts Assembly nipples Brass
Flat gaskets Aramide fibres, NBR
Brass
qp 3.5 - 60 --> PEEK-GF or PPS-GF
Danfoss Heating Solutions VDIGA102 © Danfoss 08/2012 3
ΔP_a
ΔP_v
Q [l/h]
ΔP_loopΔP_a ≥ ΔP_v + ΔP_loop
100%
90%
80%
70% 60%
50%
40%
30%
20%
5 6 7
8 9 10
11 12 13 14 15 16 17 18
450
400
350
300
250
200
150
100
50
0
Data Sheet Horizontal Distribution Unit - HDU Single-port
Settings
Q = Needed design flow for the loop. Δ P_loop = Needed design Δ P for the loop. Δ P_a = available Δ P. Δ P_V = min needed Δ P for AB-PM (starting Δ PV) = 16 kPa
Flow l/h
Δ P_loop [kPa]
Flow [l/h] - average
Δ P_loop
[kPa]
5 139 192 253 289 327 351 376 395 410 6 134 185 244 278 315 337 360 381 399 7 130 177 235 267 303 323 344 366 387 8 125 170 226 256 290 309 329 351 374
9 120 162 216 244 277 294 313 335 360 10 115 155 207 233 264 280 297 319 345 11 110 147 197 221 251 265 281 302 328 12 104 140 187 209 237 250 264 285 311 13 99 132 177 197 223 235 248 268 292 14 93 124 166 185 209 220 232 250 273 15 87 116 156 173 195 204 215 232 252 16 81 108 145 160 180 188 198 213 230 17 75 100 134 148 165 173 182 194 207 18 68 92 123 135 150 157 165 174 183 19 62 84 112 122 134 141 148 154 158 20 55 76 101 109 119 124 131 133 132
20% 30% 40% 50% 60% 70% 80% 90% 100%
4 VDIGA102 © Danfoss 08/2012 Danfoss Heating Solutions
   
    
Data Sheet Horizontal Distribution Unit - HDU Single-port
Example Given:
Design flow trough radiatorsloop: 300 l/h Pressure drop trough the loop at design flow: 10 kPa
Solution:
Set to 70 %, AB-PM will control differential pressure of 10 kPa when design flow is ach­ieved. It will at any loads including keep it under 22 kPa at zero load, while limiting the flow to radiator system to 300 l/h.
AB-PM Automatic Balanc­ing Valve
AB-PM is a combined automatic balancing valve. It features three functions in a compact valve body:
1. Differential pressure controller.
2. Control valve with linear characteristic.
3. Flow limiter.
Benefits:
Reliable heating system resulting in proper
heat distribution even at partial loads and noise free operation based on stable low Δp over thermostatic radiator valves even in in­stallation where higher pump head is needed.
Lower heating cost.
Better indoor temperature control • Faster in
simpler installation with less installation space needed.
Technical data
Nominal diameter DN20 Control valves characteristic Linear Shut-off leakage rate Acc. to ISO 5208 class A - no visible leakage CV stroke 2.25 mm
Connection
Ext. thread ISO 228/1 G 1 A Actuator M 30 x 1.5
Design
1. Spindle.
2. Stuffing box.
3. Pointer.
4. Control valve’s cone.
5. Membrane.
6. Main spring.
7. Hollow cone (pressure controller).
8. Vulcanized seat (pressure controller).
9. Impulse tube.
AB-PM is a combined automatic balancing valve. It is working as Δp controller, flow limiter and zone controller. Higher pressure acts on the upper side of the control diaphragm (5) while via an impulse tube (9) lower pressure in the return pipe acts on the lower side of the diaphragm. When available pressure increases at partial loads, the membrane closes and thus keeps stable Δp inside the control­led loop. Δp controller keeps constant differential pressure on the controlled loop including the con­trol part of AB-PM (similar as if ASV-I would be integrated into ASV-P).
Danfoss Heating Solutions VDIGA102 © Danfoss 08/2012 5
The control part of AB-PM is working as a flow limiter. This enables to set both the design flow as well as needed Δp. The flow rate is defined by presetting AB-PM, based on pressure demand of the loop. With actuator mounted on the valve, AB-PM can be used as zone valve. When connected to the room controller with time programs, functions such as night setback, holiday mode, etc become available.
SONOMETER™1100
Heat meter
Made in Germany
3030716 087G6103 Installation: high temp.
S/N: 41598383
qs: 5m3/h qp: 2.5m3/h qi: 0.025m3/h PS/PN: 16 DN20 IP54 Θq: 5...130°C
Θ: 1....180°C
ΔΘ: 3...177K Pt 500 class 2 E1 / M1 P.-Year 2012
GPM
V
ΔT ΔT
-V
Data Sheet Horizontal Distribution Unit - HDU Single-port
Sonometer 1100 Heat Me­ter
The SONOMETER™1100 is an ultrasonic static compact energy meter especially designed for heating, cooling or combined heating/cooling application in local and district energy systems. The SONOMETER™1100 as a compact energy me­ter consists of the following components:
Ultrasonic flow sensor.
Calculator with integral hardware and soft-
ware for measuring flow rate, temperature and energy consumption.
Pair of temperature sensors.
Features
Complete dynamic range: ≥ 1 : 1500.
Lithium battery, 230 V AC or 24 V AC mains unit.
Battery lifetime 11 years (16 years optional).
Unique free- beam principle.
Swirl-free flow around reflector.
Lower pressure loss.
Robust stainless steel reflector.
Insensitive to dirt.
Measuring accuracy meets the requirements of EN 1434 ( MID) class 2.
Special features
Remote reading via M-Bus, L-Bus, RS 232, RS 485, Radio or optical interface.
Individual remote reading (Automatic Meter Reading) with add on modules Plug & Play.
2 communication ports (e.g. M-Bus + M-Bus).
Insensitive to presence of magnetite parts in heating water.
Straight parts before and after HDU-SF are not required.
History memory for 24 months.
Extensive diagnostic displays.
IZAR@SET parameterization software on Windows basis guarantees optimum adaptation to the
user’s specific needs.
Software
The IZAR@SET parameterization software on windows basis is a convenient tool for handling the en­ergy meter. The IZAR@SET software is available on web site www.hydrometer.de. It is used for:
commissioning
reading out measured values
printing out energy meter logs
energy meter configuration
application analysis
print the meter protocol
6 VDIGA102 © Danfoss 08/2012 Danfoss Heating Solutions
Data Sheet Horizontal Distribution Unit - HDU Single-port
Technical Data
Temperature sensors Type Pt 500 with 2-wire leads Sensor current mA Pt 500 peak < 2; rms < 0.012 Measuring cycle T s Mains unit supply: 2 (A-cell battery: 16; D-cell battery: 4)
Input
Supply voltage
Basic features
Display indication
Max. temperature dif­ference
Min. temperature dif­ference
Starting temperature difference
Absolute temperature measuring range
Operating voltage
Ambient class EN 1434 class E1 + M1 Protection class IP 54 Type Static energy meter to EN 1434 (MID) Measuring process Ultrasonic volume measurement Display LCD, 8-digit Units MWh - kWh - GJ - Gcal - MBtu - gal - GMP - °C - °F - m³ - m³/h Total values 99 999 999 - 9999 999.9 - 999 999.99 - 99 999.999 Values displayed Power - energy - flow rate - temperature - volume
Δθmax K 177
Δθmax K 3
Δθmax K 0.125
θ °C 1...180
U
N
3.6 V DC (Lithium-battery) / 230 V AC / 24 V AC
Measuring accuracy to EN 1434 Class 2
Design and Function
The SONOMETER™1100 as a compact energy meter consists of the following components:
Ultrasonic flow sensor.
Calculator with integral hardware and software for measuring flow rate, temperature and ener-
gy consumption. Optimized pair of temperature sensors.
The calculator contains all the necessary circuits for recording the flow rate and temperature and for calculating, logging and displaying the data. The energy meter can be conveniently read from a sin­gle-line 8-digit display with units and symbols. A push-button provides user-friendly control of the various display loops. All failures and faults are recorded automatically and shown on the LC display. To protect the read­ing data, all the relevant data are saved in a non-volatile memory (EEPROM). This memory saves the measured values, device parameters and types of error at regular intervals.
Danfoss Heating Solutions VDIGA102 © Danfoss 08/2012 7
Data Sheet Horizontal Distribution Unit - HDU Single-port
Ultrasonic flow sensor
The ultrasonic technology of the flow sensor permits very high measuring accuracy and can be used in the supply or return line. The flow sensor meets the requirements of EN 1434 / class 2. Supply voltage: Lithium battery 3.6 V DC A-cell (11 years typical lifetime).
Temperature Sensors
Pairs of Pt 500 temperature sensors with 2-wire leads are used.
8 VDIGA102 © Danfoss 08/2012 Danfoss Heating Solutions
Data Sheet Horizontal Distribution Unit - HDU Single-port
Interfaces
Optical: ZVEI interface as standard, for communication and testing, M-Bus protocol.
M-Bus: The M-Bus communication module is a serial interface for communication with external
M-Bus control centre. The module contains a 2-pole terminal strip with terminals marked 24, 25, which are connected to M-Bus control centre. M-Bus protocol to EN 1434-3 standard. L-Bus: Adapter for external radio module; configurable telegram, according to EN1434-3. Data reading and parametrization are via two wires with polarity reversal protection. M-Bus protocol.
RS232:The RS232 communication module is a serial interface for communication with external
devices, e.g. PC. The module contains a 3-pole terminal strip with terminals marked 62(Dat), 63(Req) and 64(GND). A special adapter cable is required for connection. (order no. 087H0121).
RS485: The RS485 communication module is a serial interface for communication with external
devices, e.g. PC. The module contains a 4-pole terminal strip with terminals marked "D+", "D-", "+12V", "-12V". The module needs an external power supply of 12 V DC ±5 V.
Pulse output: The module contains connections for 2 pulse outputs, , proportional to the flow or
heat consumption. The module contains a 4-pole terminal strip with pulse input 1 marked as “O1 - |_” and input 2 as “O2 - |_”. External supply: Vcc = 3-30 V DC. Output current < 20 mA with a residual voltage of < 0.5 V Open collector (drain) Electrically isolated Output 1: f < 4 Hz. Pulse duration: 125 ms ±10 %. Pulse break: > 125 ms –10 %
Output 1:
Output frequency: f < 4 Hz
Pulse duration: 125 ms ±10 %
Pulse break: > 125 ms –10 %
Output 2:
Output frequency: f < 100 Hz
Pulse duration
Pulse break ~1:1
Volume pulse value is configurablevia IZAR@SET software
Pulse input: Module for two additional pulse counters. The module contains a 4-pole terminal
strip with pulse input 1 marked as “I1 - |_” and input 2 as “I2 - |_”. Pulse inputs 1 and 2 are programmable for a value of: 1, 2.5, 10, 25, 100, 250, 1000, 2500 litres
per pulse. Possible units are all the energy units available in the meter, the volume unit m³ or no unit
Input frequency is in the range < 8 Hz. Min. pulse duration 10 ms.
Input resistance 2.2 MΩ.
Terminal voltage 3 V DC.
Data is accumulated separately in registers
Data is readable as IN1 and IN2 in the display and can be transmitted over the communication
modules Cable length up to 10 m
The combined module is equipped with 2 inputs and 1 output. Combined pulse input / out-
put:The pulse input specification is the same as that of the pulse input module above. The pulse output specification is the same as pulse output module above, but not electrically isolated. pulse duration /pulse break ~ 1:1. Configurable via IZAR@SET software.
Analogue output:
The module contains connections for 2 passive analogue outputs, which can be programmed as desired using the IZAR@SET software. The outputs are marked on the terminal strip as “1” and “2” with the respective polarity “+” and “–”.
Passive; external power supply: 10…30 V DC
Current loop 4 … 20 mA, where 4 mA = 0 value; 20 mA = programmed max. value
Overload up to 20.5 mA, then fault current
Errors are generated at 3.5 mA or 22.6 mA (programmable)
Output values: power, flow rate, Configurable via IZAR@SET software.
Danfoss Heating Solutions VDIGA102 © Danfoss 08/2012 9
Data Sheet Horizontal Distribution Unit - HDU Single-port
Slot 1
Analogue output module (4-20 mA).
Combined module (2 pulse inputs / 1 pulse output).
Pulse input module (2 inputs).
M-Bus module.
L-Bus module (use for external radio).
RS232 module.
RS485 module.
Slot 2
Pulse output module.
Combined module (2 pulse inputs / 1 pulse output).
Pulse input module (2 inputs).
M-Bus module.
L-Bus module (use for external radio).
RS232 module.
RS485 module.
Event Memory
Events such as changes and faults are stored in a nonvolatile memory with a capacity of up to 127 entries. The following events are recorded:
Checksum error.
Temperature measurement error.
Ultrasonic operating time measurement errors.
Start and end of test mode.
Changing of the main configuration.
10 VDIGA102 © Danfoss 08/2012 Danfoss Heating Solutions
Data Sheet Horizontal Distribution Unit - HDU Single-port
Monthly Memory
The SONOMETER™1100 has a history memory of 24 months. The following values are stored in the EEPROM on the programmable interval (daily, weekly, monthly):
Date/ Time.
Cumulated energy.
Tariff energy 1.
Tariff energy 2.
Tariff definition 1.
Tariff definition 2.
Cumulated volume.
Error hour counter.
Value of max. flow.
Time max. flow.
Date max. flow.
Value of max. power.
Time max. power.
Date max. power.
Pulse input counter 1.
Pulse input counter 2.
Pulse 1 definition.
Pulse 2 definition.
Operating days.
Max. forward temperature.
Time max. forward temperature.
Date max. forward temperature.
Max. return temperature.
Time max. return temperature.
Date max. return temperature.
Log Memory
The large two log memory blocks are used to store consumption values. The storage frequency can be selected from various storage intervals (1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30, 60 minutes or the default setting of 24 hours, Day in the month, Day of the week, (1024 seconds), 15th or end of month). The data saved in the log memory can be used for the following analyses:
Reading the calculator on a certain day. Example: If the day for reading is 01.10, the calculator
reading is displayed for the period from 01.10 of the previous year to 30.09 of the current year. Comparison of the last consumption period with the preceding period.
Extract of possible log memory settings
Memory
block area 1 1 hour Error status, overload time temperature, overload area 2 24 hours 16 byte 299 299 days area 1 1 hour 8 byte 1113 46 days area 2 24 hours 8 byte 599 599 days
Storage
interval
Values Date block size
example
16 byte 556 23 days time flow rate, supply temperature, return tempera­ture, date and time, energy, tariff energy 1, tariff ener­gy 2, tariff definition 1, tariff definition 2, volume, er­ror day counter
Number of
data records
Recording
period
Max. Actual Values Memories
The calculator creates maximum values for power, flow rate and temperatures based on consump­tion time, which are stored in the EEPROM. The integration intervals are adjustable to 6, 15, 30 or 60 minutes, 24 hours (and 1024 seconds). Default setting is 60 minutes.
Danfoss Heating Solutions VDIGA102 © Danfoss 08/2012 11
Data Sheet Horizontal Distribution Unit - HDU Single-port
Tariff Function
The calculator offers four optional tariff memories for monitoring plant load states for limit tariffs. Extensive tariff conditions make it possible to adapt the energy meter individually to the required customer-specific applications.
The following limit types are possible (this example applies to the display with 3 decimal places):
Type LIMIT LIMIT resolution
∆T 1 ... 255 °C 1 °C
TR T
F
P 1 ... 255 °C 1 kW Q 100 ... 25 500 l/h 100 l/h Z 15 minutes
Display Control
The readings are displayed on the calculator by a 8-digit LCD with units and symbols.
Loop Structure
The SONOMETER™1100 display has six loops. Some display windows consist of two (to maximum seven) displays that are shown alternately at 4-second intervals. Some pictures in loops or a com­plete loop can be deactivated separately. For quick visual guidance, the loops in the display are numbered from 1 to 6. The main loop with the current data, e.g. for energy, volume and flow rate is programmed as default setting.
1 ... 255 °C 1 °C
Overview of Loops
12 VDIGA102 © Danfoss 08/2012 Danfoss Heating Solutions
Data Sheet Horizontal Distribution Unit - HDU Single-port
Informative Displays
Loop Sequence Window 1 Window 2
"1"
Main loop
Loop Sequence Window 1 Window 2 Window 3
"2"
Accounting date loop
1.1 Accumulated energy
1.2 Volume
1.3 Flow
1.4 Power
1.5 Forward temperature Return temperature
1.6 Difference temperature
1.7 Operating days
1.9 Error status
1.10 Display test
2.1 Accounting date 1 (date 1) Accounting date 1 energy 'Accd 1A'
2.2 Next accounting date 1 (date 1) Next accounting date 1 energy 'Accd 1L'
2.3 Previous accounting date 1 (date 1) Previous accounting date 1 energy 'Accd 1'
2.4 'Accd 1' Date of next accounting date 1
2.5 Accounting date 2 (date 2) Accounting date 2 energy 'Accd 2A'
2.6 Next accounting date 2 (date 2) Next accounting date 2 energy 'Accd 2L'
2.7 Previous accounting date 2 (date 2) Previous accounting date 2 energy 'Accd 2'
2.8 'Accd 2' Date of next accounting date 2
Loop Sequence Window 1 Window 2
"3"
Info loop
Loop Se-
"4"
Pulse input loop
Loop Se-
"5"
Tariff loop
Loop Se-
"6"
Monthly value loop
3.1 Current date
3.2 'SEC_Adr' Secondary address
3.3 'Pri_Adr 1' Primary address 1
3.4 'Pri_Adr 2' Primary address 2
3.5 Installation position
3.6 'Port 1' No. of the mounted module at port 1
3.7 'Port 2' No. of the mounted module at port 2
3.8 Status integrated radio (Sequence will be shown only in meters with
3.9 No. of error hours
3.10 'F01-001' (software version) Checksum
quence
4.1 'In1' Accumulated values pulse input 1 'PPI' pulse value 1
4.2 'In2' Accumulated values pulse input 2 'PPI' pulse value 2
Window 1 Window 2 Window 3 Window 4 Window 5 Window 6 Window 7
quen
ce
Window 1 Window 2 Window 3 Window 4 Window 5 Window 6
quen
ce
6.1 'Date last month'
6.2 'Date month -1'date month -1Energy Tariff 1 Tariff 2 Volume
Window 1 Window 2 Window 3
The tariff loop is switched off as a standard at the heat meter or meter for cooling.
Accumulated
energy
Energy Tariff 1 Tariff 2 Volume
integrated radio)
6.3 'Date month -2'date month -2Energy Tariff 1 Tariff 2 Volume
...
... ...
6.24 'Date month -
date month -23Energy Tariff 1 Tariff 2 Volume
23'
Danfoss Heating Solutions VDIGA102 © Danfoss 08/2012 13
260
380
51
49
2389
72
25
95
125
450
665
120
Data Sheet Horizontal Distribution Unit - HDU Single-port
Loop review
A push-button mounted on the front of the calculator is used to switch to the various displays. The button can be pressed for a short or long time. A short press of the button ( < 3 seconds) switches to the next display within a loop and a long press ( > 3 seconds) switches to the next display loop. The “Energy” window (sequence 1.1) in the main loop is the basic display.
The calculator switches automatically to power save mode if the button is not pressed for approx. 4 minutes and returns to the basic display when the button is pressed again. The loop settings can be programmed to suit the customer’s individual requirements using the IZAR@SET software.
Dimensions
14 VDIGA102 © Danfoss 08/2012 Danfoss Heating Solutions
Data Sheet Horizontal Distribution Unit - HDU Single-port
Danfoss Heating Solutions VDIGA102 © Danfoss 08/2012 15
Data Sheet Horizontal Distribution Unit - HDU Single-port
Danfoss A/S Heating Solutions Haarupvaenget 11 8600 Silkeborg Denmark Phone:+45 7488 8000 Fax: +45 7488 8100 Email: heating.solutions@danfoss.com www.heating.danfoss.com
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss Heating Solutions and the Danfoss Heating Solutions logotype are trademarks of Danfoss A/S. All rights reserved.
16 VDIGA102 © Danfoss 08/2012 Danfoss Heating Solutions
Loading...