Speci cation
Power supply: 24 volt powered models - 20-30 Vac, 50/60Hz 230 volt powered models - 210-250 Vac, 50/60Hz Temperature range: Heating stage - O -5-30°C Cooling stage - 16-37°C-O Temperature accuracy: ± 0.5°C Deadzone adjustment: 1, 2, 3 or 4°C Voltage rating of contacts: 20-250 Vac, 50/60Hz Current rating of contacts: 10mA - 3A resistive, 1A inductive Switching action: Voltage free SPDT contacts, Type 1B Time accuracy: ± 1 minute Memory retention: 24V & 230V models: 15 days Battery model: 1 minute for battery change IP rating: IP30 Dimensions (mm): 130 x 100 x 38 (W x H x D) Control pollution situation: Degree 2 Rated impulse voltage: 2.5 KV Ball pressure test: 75°C
Applications
HCS & HCST Models
Ordering Details
Features 24 volt 230 volt
Type Co de Type Co de
Heat or cool operation, selectable at time of installation
3-speed fan output HCS6101-3 087N722500
Heat & cool systems (with auto changeover), for use in 4-pipe systems
3-speed fan output HCT6113-3 087N759326
HC & HCT Models
Wiring
HCS & HCST Models with 3 speed fan (Heat or Cool)
HC & HCT Models with 3 speed fan (4 pipe auto change-over)
1
Installation
1. Thermostat Location
3. Separating the Wallplate
2. Unpacking the Thermostat
4. Fitting the Thermostat to the Wall 5. Wiring Access - Incorrect
6. Wiring Access - Correct 7. Cable Size
Max cable size