Installation guide
Shut-off ball valve
Type GBCH 6s to GBCH 42s
<![endif]>009R8516
Refrigerant: |
Max. working pressure: |
|
|
R744 (CO2) |
|
||
|
GBCH 6s - 28s: PS/MWP = |
90 bar / 1305 psig |
|
Temperature range: |
|||
GBCH 35s - 42s: PS/MWP = |
75 bar / 1085 psig |
||
-40 °C – 100 °C / -40 °F – 212 °F |
|
|
Warning: Applicable to all common non-flammable refrigerants, excluding R717 and to noncorrosive gases/liquids dependent on sealing material compatibility.
The design pressure shall not be less than the value outlined in Section 9.2 of ANSI/ ASHRAE 15 for the refrigerant used in the system. Only authorized persons are allowed to operate this valve, as closing can cause build-up of excessive pressure in the system. For the application use with R744 as part of a secondary loop or cascade system should refer to the datasheet for more attentions.
Remove cap and access cap (if present)
<![if ! IE]><![endif]>Danfoss 9G8043
90 bar
1305 psig
Opening valve
<![if ! IE]> <![endif]>Danfoss 9G8045 |
Valve size |
Max. Torque |
|
|
|||
|
Nm |
ft-lbs |
|
|
|
|
6s - 22s |
7 |
5.2 |
|
28s |
26 |
19.2 |
90 bar |
35s |
27 |
19.9 |
|
42s |
48 |
35.4 |
OPEN Position |
CLOSED Position |
|
|
|
|
|
<![if ! IE]> <![endif]>Danfoss 9G8047 |
|
<![if ! IE]> <![endif]>Danfoss 9G8046 |
|
|
© Danfoss | DCS (jmn) | 2018.03 |
|
DKRCC.PI.FB0.I1.02 | 520H12717 | 1 |