Installation guide
Shut-off ball valve, 49bar for A2L refrigerants
Type GBC E
Refrigerants:
GBC 6s E-28s E: R290, R32, R452B, R454A, R454B, R454C, R455A, R516A, R1234yf
GBC 35s E-79s E: R32, R452B, R454A, R454B, R454C, R455A, R516A, R1234yf
009R9515
For a complete list of approved refrigerants, visit http://store.danfoss.com/ and search for individual
code numbers, where refrigerants are listed as part of product details.
This product is approved for R290, R32, R452B, R454A, R454B, R454C, R455A, R516A, R1234yf by ignition
source assessment in accordance to standard EN ISO80079-36.
Temperature range:
-40 °C - 100°C /-40 °F - 212°F
Note: The product can be only used in liquid line and suction line.
Max. working pressure: PS/MWP = 49 bar / 710 psig
Remove cap and access cap (if present)
Danfoss
49 bar
710 psig
009R9515
Opening valve
Danf
9G8075
Valve size
6s - 22s 7 5.2
25s - 28s 17 12.6
32s - 35s 20 14.8
38s - 54s 34 25.2
67s - 79s RP 34 25.2
67s - 79s 60 44.2
OPEN Position CLOSED Position
Danfoss
9G8078
© Danfoss | DCS (nb) | 2020.04
Danfoss
90 bar
psig
Max. Torque
Nm ft-lbs
Danfoss
Danfoss
90 bar
psig
AN305142159617en-000201 | 1
9G8079
Brazing (Copper and Copper alloy)
9G156.14
Min. 5% Ag
Max. 100 °C / 212 °F
Wet cloth must cover the label !
Install valve core (if present) and cap
Install valve core
with approx. torque
0.3 Nm / 0.2 ft-lbs
49 bar
710 psig
Tighten cap Tighten the cap with approx. torque
Valve size
Max. Torque
Nm ft-lbs
6s - 12s 10 7.4
16s - 22s 15 11.0
25s - 35s 20 14.8
42s - 79s 32 23.6
Danfoss
© Danfoss | DCS (nb) | 2020.04
Fully openFully closed
Danfoss
AN305142159617en-000201 | 2