Danfoss Gas detection in refrigeration systems Application guide

0 (0)
Danfoss Gas detection in refrigeration systems Application guide

Application Guide

Gas detection in refrigeration systems

GDIR.danfoss.com

Application Guide | Gas detection in refrigeration systems

Contents

 

 

 

 

 

Page

 

Commonly used abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

 

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

 

Sensor technology . . . . . . . . . . . . . . . . .

.

. . . . . . . . . . . . . . . . . . . . .

.

.4

 

 

EC - Electrochemical sensor . . . . . . . . . .

.

. . . . . . . . . . . . . . . . . . . . . .

.

4

 

 

SC - Semiconductor sensor (solid state) . . . . .

.

. . . . . . . . . . . . . . . . . . . . .

.

.5

 

 

P- Pellistor sensor . . . . . . . . . . . . . . .

.

. . . . . . . . . . . . . . . . . . . . . .

.

6

 

 

IR - Infrared . . . . . . . . . . . . . . . . . .

.

. . . . . . . . . . . . . . . . . . . . . .

.

6

 

 

Which sensor is suitable to a given refrigerant? .

.

. . . . . . . . . . . . . . . . . . . . . .

.

6

 

Sensor response time . . . . . . . . . . . . . . .

.

. . . . . . . . . . . . . . . . . . . . . .

.

7

 

The need for gas detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8

 

Legislation and standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

 

 

Requirements for gas detection according to EN 378:2016 and ISO 5149:2014 . . . . . . . . . . 9

 

 

F-Gas legislation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

 

 

Requirements for gas detection according to ASHRAE 15-2016 (USA) . . . . . . . . . . . . .

10

 

 

Requirements for gas detection according to ANSI/IIAR-2 (USA) . . . . . . . . . . . . . . .

. 10

 

Installation guideline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

 

Location of gas detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

 

Number of gas detectors in a facility . . . . . . . .

.

. . . . . . . . . . . . . . . . . . . . . .

13

 

Calibration / test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

 

Calibration methods . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . 14

 

 

Method I Calibration by means of replacing sensor heads . . . . . . . . . . . . . . . . . .

. 14

 

 

Method II Calibration of gas detectors by means of calibration gas . . . . . . . . . . . . . .

. 14

 

 

Bump test . . . . . . . . . . . . . . . . . . .

.

. . . . . . . . . . . . . . . . . . . . .

. 15

 

 

Alarm / sensitivity range gas detectors . . . . .

.

. . . . . . . . . . . . . . . . . . . . . .

16

 

 

Danfoss recommendations for alarm levels . . . . . . . . . . . . . . . . . . . . . . . . . . 16

 

Actions

triggered by gas detection . . . . . . . .

.

. . . . . . . . . . . . . . . . . . . . . .

18

 

References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

 

Annex I - Common refrigerant data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

 

Annex II - EN 378:2016 and ISO 5149:2014 . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . 20

 

Annex III - ASHRAE 15-2016 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

 

 

 

 

 

 

 

 

Commonly used

LFL

= Lower Flammability Level

GWP = Global Warming Potential

 

 

abbreviations

OEL

= Occupational Exposure Limits

TRK

= Technische Richtkonzentrationen

 

 

 

ATEL = Acute-Toxicity Exposure Limit

MAK = Maximale Arbeitsplatzkonzentrationen

 

 

ODL = Oxygen Deprivation Limit

TLV

= Threshold Limit Value

 

 

 

OSH = Occupational Safety Limit

STEL = Short Term Exposure Limit

 

 

 

ODP = Ozone Depletion Potential

PEL

= Permissible Exposure Limits

 

 

 

 

 

 

 

 

 

 

 

© Danfoss | DCS (mwa) | 2018.08

DKRCI.PA.S00.A2.02 | 520H12772 | 3

Application Guide | Gas detection in refrigeration systems

Introduction

Gas detection and leak detection are two distinct

 

activities that covers the same topic, but the

 

methods are very different.

 

Gas detection covers the analysis of air samples

 

to determine whether they contain refrigerant

 

gas. Leak detection is a systematic inspection

 

of a refrigeration system to determine whether

 

it is leaking. The terms gas detection and leak

 

detection are not interchangeable, and must not

 

be mixed.

 

Leak detection equipment is normally hand-

 

held equipment carried by people, and used for

 

detection of leaks in refrigeration systems. There

 

are several types of leak detectors available,

 

ranging from simple techniques like soapy water

 

to sophisticated electrical instruments.

 

Gas detection equipment is usually used in

 

a fixed installation with a number of sensors

 

located in areas where refrigerant might be

 

expected to accumulate in the event of a plant

 

leak.

These locations depend upon the layout of the machinery room and adjacent spaces, on the configuration of the plant and also on the refrigerant in question.

Before selecting the appropriate gas detection equipment, a number of questions have to be answered:

Which gases have to be measured and in what quantities?

––Which sensor principle is the most suitable?

––How many sensors are needed?

––Where and how should they be positioned and calibrated?

Which alarm limits are appropriate?

––How many are required?

––How is the alarm information processed?

This application guide will address these questions.

Sensor technology

The choice of sensor technology for refrigerant

 

gas detection will depend on the specific target

 

refrigerant gas and ppm range required. Danfoss

 

offers a range of different sensor technologies

to match most commonly used refrigerants, appropriate ppm ranges, and safety requirements for refrigeration systems.

EC - Electrochemical sensor

Electrochemical sensors are mainly used for toxic

An oxidation / reduction reaction generates an

 

gases and are suitable for ammonia.

electric current that is proportional to the gas

 

 

concentration.

They consist of two electrodes immersed in an electrolyte medium.

max.

Tolerance range min.

<![if ! IE]>

<![endif]>Sensitivity

“High” gas concentration

“Low” gas concentration

 

Time

Max. operating time before calibration

Fig. 1: Sensitivity of electrochemical sensors

They are very accurate (+/- 2%) and tend to be used mainly for toxic gases, which cannot be detected otherwise, or where high levels of accuracy are needed (fig. 1).

Danfoss offers specific EC sensors for ammonia in ranges up to 0-5.000 ppm with an expected lifetime of 2 years, depending on exposure to target gas.

Exposure to large ammonia leaks or constant background ammonia will shorten the sensor life (fig. 2). EC sensors can be re-calibrated as long as the sensitivity of the sensor is above 30%.

They are very selective and rarely subject to cross-interference. They may react to sudden large humidity changes but settle quickly.

4 | DKRCI.PA.S00.A2.02 | 520H12772

© Danfoss | DCS (mwa) | 2018.08

Application Guide | Gas detection in refrigeration systems

EC - Electrochemical sensor (continued)

<![if ! IE]>

<![endif]>Sensitivity

“Substantial” gas leak

Important!

Sensor must be calibrated or new sensor must be installed.

If the sensitivity of the sensor falls below 30%; install new sensor

Max. operating time before calibration

max.

Tolerance range min.

30% sensitivity

Time

Fig. 2: Large ammonia exposure shortens the lifetime of electrochemical sensors.

SC - Semiconductor sensor

The semi-conductor sensor functions by

(solid state)

measuring the resistance change (proportional to

 

the concentration), as gas is absorbed on to the

 

surface of a semi-conductor, which is normally

 

made from metal oxides.

 

These can be used for a wide range of gases

 

including combustible, toxic and refrigerant

 

gases.

 

It is claimed that they perform better than the

 

catalytic type in the detection of combustible

 

gases at low concentrations, up to 1.000 ppm.

 

These are low-cost, long life, sensitive and can be

 

used to detect a large range of gases including

 

all the HCFC, HFC refrigerants, ammonia and

 

hydrocarbons.

However, they are not selective, and are not suitable for detecting a single gas in a mixture, or for use where high concentrations of interfering gases are likely to be present (fig. 3).

Interference from short term sources (e.g. exhaust gas from a truck), creating false alarms, can be overcome by enabling a delay of the alarm.

Semi-conductors for halocarbons can be used to detect more than one gas or a mixture simultaneously. This is particularly useful in monitoring a plant room with several different refrigerants.

<![if ! IE]>

<![endif]>Sensitivity

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<![if ! IE]>

<![endif]>Gas 1

 

<![if ! IE]>

<![endif]>Gas 2

 

<![if ! IE]>

<![endif]>Gas 3

 

<![if ! IE]>

<![endif]>Target Gas

 

<![if ! IE]>

<![endif]>Gas 4

 

<![if ! IE]>

<![endif]>Gas 5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

“Broad” sensitivity spectrum

Semiconductor

Pellistor

“Narrow” sensitivity spectrum

Electrochemical

Infrared

Gas specification

Fig. 3: Sensitivity spectrum of various sensor technologies

© Danfoss | DCS (mwa) | 2018.08

DKRCI.PA.S00.A2.02 | 520H12772 | 5

Application Guide | Gas detection in refrigeration systems

P- Pellistor sensor

Pellistors (sometimes called a bead or catalytic)

 

are mainly used for combustible gases including

 

ammonia, and are the most popular sensors for

 

this application at high detection levels.

 

The sensor functions by burning the gas at

 

the surface of the bead and measuring the

 

resultant resistance change in the bead (which is

 

proportional to concentration).

 

These are relatively low-cost, well established

 

and understood, and they have a good life span

 

(expected life time 3 to 5 years). The response

 

time is usually below 10 seconds.

 

They can be subject to poisoning in certain

 

applications.

Poisoning is the reduction of the reaction of the sensor to the target gas due to the presence (contamination) of another substance on the surface of the catalyst, that either reacts with it or forms a layer on top of it reducing its capacity to react to the target gas. Most common poisoning substances are silicon compounds.

Pellistors are used mainly with combustible gases and are therefore suited for ammonia and the hydrocarbon refrigerants at high concentrations.

They do sense all combustible gases, but they respond at different rates to each, and so they can be calibrated for particular gases.

There are ammonia specific versions.

IR - Infrared

Infrared technology utilises the fact that most

 

gases have a characteristic absorption band in

 

the infrared region of the spectrum, and this

 

can be used to detect them. Comparison with a

 

reference beam allows the concentration to be

 

determined.

 

Even though they are relatively expensive in

 

comparison to other sensor, they have long life

 

time of up to 15 years, high accuracy, and low

 

cross sensitivity

Due to its measuring principle infrared sensors can be subject to issues in dusty environments, where the presence of too many particles in the air may disturb the reading.

They are recommended and commonly used for Carbon dioxide detection. Although technology exists for other gases also, it is not common to find it in commercial solutions.

Which sensor is suitable to a given refrigerant?

Based on the target refrigerant gas and the actual ppm range the below table provides an overview of the suitability of the various sensor technologies offered by Danfoss.

Suitability of different sensor technologies:

 

 

 

 

Semi-conducter

Electro-chemical

 

 

Pellistor

Infrared

 

 

 

 

 

 

(Catalytic)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ammonia “low” concentration

 

4

 

 

 

(< 100 ppm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ammonia “medium” concentration

(4)

4

 

 

 

(< 1000 ppm) 1)

 

 

 

Ammonia “high” concentration

4

(4)2

 

(4)

(<10000 ppm)

 

 

 

 

 

 

 

 

Ammonia“very high” concentration

 

4

(> 10000 ppm)

 

 

 

 

 

 

 

 

 

Carbon Dioxide

 

 

 

4

CO2

 

 

 

 

 

 

 

 

 

 

 

HC

 

4

Hydrocarbons

 

 

 

 

 

 

 

 

 

HCFC - HFC

4

 

 

Halocarbons

 

 

 

 

 

 

 

 

 

 

 

 

Best solution

 

 

Suitable - but less attractive

 

 

 

Not suitable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1) Measuring range 0-1000 ppm. Can be adjusted in the whole range. 2) Up to 5000 ppm. For specific applications.

6 | DKRCI.PA.S00.A2.02 | 520H12772

© Danfoss | DCS (mwa) | 2018.08

Application Guide | Gas detection in refrigeration systems

Sensor response time

The response time is the elapsed time for a sensor

 

to read a given percentage of the actual value for

 

a step change in the target gas concentrations.

 

Response time for most sensors is given as t90,

 

meaning the time that it takes the sensor to read

 

90% of the actual concentration. Fig. 4 shows an

 

example of a sensor with a reponse time t90 of 90

 

seconds.

As shown in the graphic, the sensor reaction above 90% becomes slower and takes longer to read the 100%.

<![if ! IE]>

<![endif]>Change

1

 

 

 

 

 

0.9

 

 

 

 

 

0.8

 

 

 

 

 

 

 

 

 

 

 

<![if ! IE]>

<![endif]>Concentration

0.7

 

 

 

 

 

0.6

 

 

 

 

 

0.5

 

 

 

 

 

0.4

 

 

 

 

 

<![if ! IE]>

<![endif]>of

0.3

 

 

 

 

 

<![if ! IE]>

<![endif]>Fraction

 

 

 

 

 

0.2

 

 

 

 

 

0.1

 

 

 

 

 

 

0

 

 

 

 

 

 

0

50

100

150

200

250

Time, s

Fig. 4: Sensor with a response time t90 of 90 seconds

GAS

Sensor technology

Response time t90, seconds

 

 

 

 

Electrochemical 0-100/ 0-300 ppm

<40s

 

 

 

 

Electrochemical 0-1000ppm

<40s

 

 

 

Ammonia

Electrochemical 0-5000ppm

<40s

 

 

 

 

Semiconductor

>120s

 

 

 

 

Pellistor

<20s

 

 

 

Infrared

Infrared

<90s

 

 

 

Halocarbons

Semiconductor

>120s

 

 

 

Hydrocarbons

Pellistor

<15s

 

 

 

© Danfoss | DCS (mwa) | 2018.08

DKRCI.PA.S00.A2.02 | 520H12772 | 7

Application Guide | Gas detection in refrigeration systems

The need for gas detection

There are several reasons why gas detection

Hydrocarbons are classified as flammable. Thus,

 

is required. Two obvious reasons are to protect

it’s critical to verify that the concentration around

 

people, production and equipment from the

the refrigeration system does not exceed the

 

impact of potential gas leakages and to comply

flammability limit.

 

with regulations. Other good reasons include:

Fluorinated refrigerants all have a certain

 

• Reduced service cost (cost of replacement gas

 

and the service call).

negative impact on the environment, for which

 

• Reduced energy consumption cost due to lack

reason it’s very important to avoid any leaks.

 

 

 

of refrigerant.

CO2 (Carbon Dioxide) is directly involved in

 

• Risk for damaging stock products due to a

 

the respiration process and should be treated

 

substantial leak.

 

accordingly. Approximately 0.04% CO2 is

 

• Possibility to reduce insurance costs.

 

present in the air. With higher concentration,

 

• Taxes or quota on non-environmentally

 

some adverse reactions are reported starting

 

friendly refrigerants

 

with increase in breath rate (~100% at 3%

 

 

 

The various refrigeration applications require gas

CO2 concentration) and leading to loss of

 

consciousness and death at CO2 concentrations

 

detection for different reasons.

 

above 10%.

 

 

 

 

 

 

Ammonia is classified as a toxic substance with

 

 

a very unique smell, as such it is “self alarming”.

 

 

However, gas detectors are required to guarantee

 

 

early warnings, and to monitor areas where

 

 

people are not always present, such as machinery

 

 

rooms. It is important to be aware that ammonia

 

 

is the only common refrigerant lighter than air.

 

 

In many cases, this will lead to ammonia rising

 

 

above the breathing zone making it impossible

 

 

for people to early detect ammonia leakages. The

 

 

use of gas detectors in the right zones ensures

 

 

early warnings in case of ammonia leakages.

 

Legislation and standards The requirements for gas detection are different across countries worldwide. An overview of the most common rules and regulation can be found on the following pages.

Europe:

The present safety standard for refrigeration systems in Europe is EN 378:2016.

The specified alarm levels in EN 378:2016 are set at levels to allow evacuation of an area. The levels do not reflect the effects of long term exposure to leaked refrigerants. In other words, in EN 378 a gas detector is to warn when a sudden large release occurs, while machine room ventilation and system quality measures are to ensure that small leaks are too small to cause adverse health effects.

Note!

Requirements for gas detection equipment in Europe are covered by national legislation in the different countries, and consequently may differ from the requirements specified in EN 378.

8 | DKRCI.PA.S00.A2.02 | 520H12772

© Danfoss | DCS (mwa) | 2018.08

Loading...
+ 16 hidden pages