Hard-Wired Floor Heating Controls
FH-WC Connection Box - 230 VAC output
Application
Ordering
Technical specications
FH-WC is a wiring center for connecting thermal actuators to the room thermostats. It is provided with two potential-free relays for controlling a circulation pump and a boiler. The relays are activated when one or more thermostats require heat. FH-WC has 8 available outputs.
FH-WC is connected to 230 VAC/50 Hz.
Mounting is made easy due to the symbols
FH-WC is a connection box for use in hydronic oor heating systems supplied from a manifold.
Product Typ e
Connection box with power cord and plug
Power supply 230 VAC ± 10%
Number of outputs 8
Output voltage 230 VAC
Max. load per output 3 W (max. 2 actuators per output)
Pump and boiler relay Max. load 230 VAC (2A)
Ambient temperature 0 - 50° C
Transport temperature -20 - 60° C
IP class 20
FH-WC 230 VAC 230 VAC NC/16 088H0016
printed on the screw terminals.
voltage
Output
voltage
Actuator,
type/no.
Code no.
VDSPD402
ErP class
Mains cable length 2 m
Weight 1.5 kg
Internal fuse F 4.0 A
(1%)
© Danfoss | FHH | 2015.09 | 1
Data Sheet FH-WC Connection Box - 230 VAC output
TWA
TWA
F
TWA
F
Connection Diagrams
NO or NC
}
L
N
NC
NO
2
BasicPlus
WT-T
Connection of FH-WC with BasicPlus2 WT-T 230 V room thermostats
~ 230V
L N
L
230V ~ 230V ~
N
L
N
FH-CWF
loor sensor
NO or NC
}
L
N
S2
S1
NC
NO
2
BasicPlus
WT-D / WT-P
Connection of FH-WC with BasicPlus2 WT-D and WT-P 230 V room thermostats
FH-CWF
loor sensor
NO or NC
}
Auxiliary relay
L
N
S2
S1
A1
A2
NC
NO
2
BasicPlus
WT-DR / WT-PR
~ 230V
L N
L
230V ~ 230V ~
N
~ 230V
L N
L
230V ~ 230V ~
N
L
N
L
N
2 | © Danfoss | FHH | 2015.09
Connection of FH-WC with BasicPlus2 WT-DR and WT-PR 230 V room thermostats
Please note!
If the Normally Open (NO) output from BasicPlus2 is used for pump or boiler relay, the function of the relay will be inverted.
For further information on the BasicPlus2 range of room thermostats, see the appropriate data sheet.