The Manifold FHF is used for controlling water flow
in under floor heating systems. Each tube of the
floor heating system is connected to the manifold,
thus making it possible to control water flow or heat
supply to each room in the building individually.
The manifold consists of a supply and return manifold. The supply manifold includes possibility for
individual shut-off of each circuit and as an option
also flowmeter. The return manifold is equipped
with integrated Danfoss pre-setting valves securing
optimal hydraulic balance in the system.
Manifold without flowmeter
The valves can be controlled electronically by
thermal actuators or act as self-acting units by
means of remote temperature adjusters.
The manifold is supplied in modules of up to 12
outlets. In addition extension pieces are available
for connecting the manifolds in series. Ball valves
are available as an option for positive shut-off
between manifold and system.
The end pieces FHF-EM and FHF-EA are supplied
with manual airvent or alternatively with automatic
airvent, purge valve. The end pieces are placed at
the end of the manifold.
Manifold set 2+2FHF-2088U0502
Manifold set 3+3FHF-3088U0503
Manifold set 4+4FHF-4088U0504
Manifold set 5+5FHF-5088U0505
Manifold set 6+6FHF-6088U0506
Manifold set 7+7FHF-7088U0507
Manifold set 8+8FHF-8088U0508
Manifold set 9+9FHF-9088U0509
Manifold set 10+10FHF-10088U0510
Manifold set 11+11FHF-11088U0511
Manifold set 12+12FHF-12088U0512
Manifold set 2+2, with flowmeterFHF-2F088U0522
Manifold set 3+3, with flowmeterFHF-3F088U0523
Manifold set 4+4, with flowmeterFHF-4F088U0524
Manifold set 5+5, with flowmeterFHF-5F088U0525
Manifold set 6+6, with flowmeterFHF-6F088U0526
Manifold set 7+7, with flowmeterFHF-7F088U0527
Manifold set 8+8, with flowmeterFHF-8F088U0528
Manifold set 9+9, with flowmeterFHF-9F088U0529
Manifold set 10+10, with flowmeterFHF-10F088U0530
Manifold set 11+11, with flowmeterFHF-11F088U0531
Manifold set 12+12, with flowmeterFHF-12F088U0532
Manifold set 2+2, basicFHF-2B088U0542
Manifold set 3+3, basicFHF-3B088U0543
Manifold set 4+4, basicFHF-4B088U0544
Manifold set 5+5, basicFHF-5B088U0545
Manifold set 6+6, basicFHF-6B088U0546
Manifold set 7+7, basicFHF-7B088U0547
Manifold set 8+8, basicFHF-8B088U0548
Manifold set 9+9, basicFHF-9B088U0549
Manifold set 10+10, basicFHF-10B088U0550
Manifold set 11+11, basicFHF-11B088U0551
Manifold set 12+12, basicFHF-12B088U0552
The pre-setting of the manifold valves determines
the flow in the floor heating tubes and is therefore an important factor for obtaining optimal hydraulic balance in the system. A correct hydraulic
balance is important if optimal comfort shall be
achieved with a minimum of energy consumption
and is easily carried out following the example
shown below.
Example
Room 1 1. Determine longest tube/largest room 25 m
2. Desired cooling (ΔT)5 °C (typical)
3. Determine heat requirement for the room50 W/m
4. Conversion factor 1,16
5. Calculation of flow for the room
Room 2 6. Determine area for the next room15 m2
7. Calculation of flow for the room
(ΔT and heat requirement is assumed
identical for the rooms in this case)
The diagrams shows the capacities for each heating circuit at different pre-settings of the manifold
valves. Please note that the capacities are slightly
different depending on whether a manifold with
flowmeter or a manifold without flowmeter has
Item
DescriptionMaterial
1SightglassHeat resistant plastic
2Flowmeter nutBrass, CuZn39Pb3
been chosen. Based on the above calculations and
capacity diagrams each manifold valve is pre-set
by rotating the red ring until the correct value on
the ring is in-line with the sight mark on the valve.
Max. differential pressure: 0,6 bar.
Max. working pressure:Manifold without flowmeter 10 bar / Manifold with flowmeter 6 bar.
Max. test pressure:Manifold without flowmeter 16 bar / Manifold with flowmeter 10 bar.
Max. flow temperature:90 °C.