Danfoss FH Data sheet

Data Sheet
FH Composite Pipes
Application
Ordering
The grey Danfoss FH composite pipe is 100% impervious to air, temperature resistant and highly exible. It consists of an aluminium pipe which is covered inside and out with a Polyethyl­ene layer. All layers are permanently bonded with each other through a layer of adhesive.
Unlinked Polyethylene with its raised tempera­ture resistance (PE-RT) is used, in accordance with EN ISO 22391. The octen side chains of the molecular structure of the PE-RT (Polyethylene Raised Temperature resistance) give a similar eect to that of the linked PE.
The Danfoss FH composite pipes are manufac­tured in such a way that the aluminium layer prevents the pipe from going back to its original form. This make the pipes easy to install.
Product Typ e Size Length Code no.
FH composite pipe FH-CPA 16 x 2 mm 200 m 088X0001
FH composite pipe FH-CPC 16 x 2 mm 500 m 088X0003
Accessories
Technical Specications
VDDXA702
Product Size Code no.
Compression tting for FH pipes 16 x 2 mm 013G4186
Compression tting for FH pipes 20 x 2.25 mm 013G 4093
Materials PE-RT / Aluminium / PE-HD
Max. working pressure 10 bar
Test pressure 16 bar
Max. ow temperature (short term) 110 °C
Max. working temperature 95° C (not for continous operation)
Recommended max. working temperature 65° C
Minimum bending radius with bending springs
Pipe dimension
[mm]
16 80 (5 x Od) 64 ( 4 x Od) 64 (4 x Od)
20 100 (5 x Od) 80 ( 4 x Od) 80 ( 4 x Od)
Od = outside diameter
Manual pipe bender
radius [mm]
Internal pipe bending
spring radius [mm]
External bending
spring radius [mm]
© Danfoss | FHH | 2015.10 | 1
Pressure Loss
1 2 3 4 5 6 7 8 9101 2 3 4 5 6 7 8 9 102 2 3 4 5 6 7 8 9 10
3
Volume flow - water quantity m [kg/h]
1000
800
600
400
200
100
80
60
40
20
10
Water temperature: 40° C
Ø 20 / 16 mm
Ø 18 / 14 mm
Ø 17 / 13 mm
Ø 16 / 12 mm
Ø 14 / 10 mm
Ø 11.6 / 8.6 mm
Pressure loss [Pa/m]
(1 mbar = 100 Pa)
Danfoss A/S
Floor Heating Hydronics • Ulvehavevej 61 • DK-7100 Vejle • Denmark • Phone: +45 7488 8500 • Fax: +45 7488 8501 heating@danfoss.com • www.oorheating.danfoss.com
Danfoss ca n accept no respons ibility for pos sible errors in ca talogues, bro chures and other pr inted material. Da nfoss reserves t he right to alter its p roducts with out notice. This als o applies to produ cts already o n order provided t hat such alteratio ns can be made with out subsequenti al changes being n ecessary in spe cications alr eady agreed. All trade marks in this mate rial are proper ty of the respec tive companies . Danfoss and the Dan foss logotyp e are trademark s of Danfoss A/S. Al l rights reserv ed.
2 | © Danfoss | Danfoss | FHH | 2015.10