Danfoss FED-IF, FED-FF Data sheet [cs]

Data sheet FED sensors
Sequence control of cooling and heating circuit
Products
FED-IF: with integrated sensor FED-FF: with remote sensor
The FED sensors are used in applications in which a cooling and a heating circuit are to be controlled by one controller. Both FED-IF and FED-FF sensors can be applied to chilled ceilings, fancoils and induc­tion units.
For control of cooling and heating circuits in fancoil and induction units use the FED-FF with remote sensor. By placing the sensor in the air inlet a quicker reaction time of the air temperature changes is achieved. Using the remote sensor, the remote temperature adjuster can be placed directly on the cabinet.
Ordering and specifications
Type Code no. Sensor Capillary tube Setting range FED-IF 013G5463 Integrated sensor 4 + 11 m FED-FF 013G5462 Remote sensor 2 + 2 + 2 m
Application
Sequence control of chilled ceiling and radiator Sequence control of fancoils and induction units
Cooling circuit
17-27 °C
Cooling circuit
RA-C
FED-IF
Heating circuit/radiator
RA-N
CD-ST VD.33.T1.02 © Danfoss 06/99 1
FED-FF
RA-C
Heating circuit
RA-C RA-N
Data sheet Climate controls: FED sensors
FED sensor design
Cooling adapter
Actuator
Remote temperature adjuster
Remote sensor (only FED-FF)
Capillary reel (only FED-IF)
Heating adapter
Temperature setting
The FED sensors are applied with the RA-N and the RA-C valves. The FED sensors are equipped with a reverse device for the control of cooling circuits. With the reverse device the valve in the cooling
Comfort temperature ~ 22 °C at Xp = 0 K
The FED sensors have been developed for room temperature control via water-based cooling and heating systems.
The FED sensors are based on the self-acting principle. The liquid-filled sensors control the
circuit will open when the temperature rises above the setpoint temperature. The valve in the heating circuit will open when the temperature falls below the setpoint tem­perature.
valves via capillaries and adapters.
The scale shows the approximate set-point offset from the comfort temperature which is approximately 22° C at X
= 0 K.
p
2 VD.33.T1.02 © Danfoss 06/99 CD-ST
Data sheet Climate controls: FED sensors
Sequence control The control is done by the sensor, in which a
neutral zone is built-in. In the neutral zone neither an activation of the valve in the heat­ing circuit nor of the valve in the cooling circuit takes place. In that way it is secured that cool­ing and heating do not take place simultane­ously.
The neutral zone is in the area from
0.5 - 2.5 °C dependending on the system design. If the differential pressure is high on both circuits (~0.6 bar), the neutral zone is at a minimum. On the other hand if the differen­tial pressure is low on both circuits (~0.1 bar), the neutral zone is at a maximum. An adjustment of the neutral zone can be made by turning the knob of the cooling adap­ter with a pair of pointed pliers. Turning clock­wise the neutral zone is increased, turning counter-clockwise the neutral zone is de­creased. The factory setting of the neutral zone is marked in the knob recess.
Irrespective of the temperature setting of the FED-sensor the necessary neutral zone will always be kept. See also figures below.
Sequence control of cooling and heating circuit
Neutral zone
Water flow through heating circuit
Water flow through cooling circuit
Adjustment of the neutral zone
Factory setting mark
Setting of comfort temperature
- example: hotter t
t
1
2
Setting of comfort temperature example: colder t
t
1
0
CD-ST VD.33.T1.02 © Danfoss 06/99 3
Data sheet Climate controls: FED sensors
Temperature control through sequence control with FED sensor
a) Control of heating circuit - FED with RA-N valve
Xp = 0 K
Xp = 2 K
Note! Example at neutral zone = 2 °C. Setpoint = 22 °C
b) Control of cooling circuit - FED with RA-C valve
Xp = 0 K
Xp = 3 K
The FED sensor controls in sequence via two temperature scales: one for the heating circuit (a) and one for the cooling circuit (b).
When the setting knob is turned a parallel control of both temperature scales is taking place. The neutral zone ensures that cooling and heating do not take place simultaneously.
Sequenzing with FED thermostat
Waterflow,
Waterflow, heating
cooling
Example
A setting in the red temperature area means that the set point of both cooling and heating circuit is raised. A setting in the blue temperature area lowers the set point of both cooling and heating cir­cuits.
The setting knob is turned to rise the room temperature with 2 °C from 22 °C to approxi­mately 24 °C at X Due to the neutral zone the set point of the cooling valve at X
0.5-2.5 K higher depending on the system
= 0 K on the heating valve.
p
= 0 K will be between
p
design.
The valve in the heating circuit will open at a sensor temperature below 24 °C. If an RA-N valve is mounted in the heating circuit and dimensioned at the presetting N, the RA-N valve will provide full water quantity at a P­band of 2 K, i.e. a sensor temperature of 22°C.
If the neutral zone e.g. is 2 K the valve in the cooling circuit will start opening at a sensor temperature above 26 °C (setpoint: 24 °C + neutral zone: 2 K). With a RA-C valve in the cooling circuit (di­mensioned at presetting N) the valve will pro­vide full water quantity with a P-band of 3 K, i.e. at a sensor temperature of 29 °C (setpoint: 24 °C + neutral zone: 2 K + P-band: 3 K).
Setpoint on knob (N = neutral zone)
Sequence control when rising the setpoint temperature with 2 °C.
Neutral
zone
Waterflow, heating
Waterflow, cooling
4 VD.33.T1.02 © Danfoss 06/99 CD-ST
Data sheet Climate controls: FED sensors
Limiting the set tempera­ture of FED sensors
Serial coupling
The set temperature of the remote tempera­ture adjuster depends on the sensor type and the valves, which are used with the sensors.
It is easy to limit or lock the set temperature by means of the built-in locking/limiting de­vice.
Maximum limitation of temperature areaMinimum limitation of temperature area
Several possibilities of placing the FED remote temperature adjuster
Via the soft but strong ø 0.8 mm capillary and the patented serial coupling of capillary and adapters it is possible to control two valves in sequence.
The FED sensors are delivered with the cool­ing adapter closest to the remote temperature adjuster and the heating adapter furthest
It is easy to change the order of the valves: Just loosen the actuators from the adapters and exchange the adapters. The FED sensor still controls in the right sequence.
The interchange of valve adapters provide numerous possibilities of placing the FED remote temperature adjuster.
away from the remote temperature adjuster.
CD-ST VD.33.T1.02 © Danfoss 06/99 5
Data sheet Climate controls: FED sensors
Design
1. Heating adapter
2. Actuator
3. Adjustment bellow
4. Capillary reel (only FED-IF)
5. Cooling adapter
6. Neutral zone adjustment knob
7. Reverse device
8. Adjustment bellow
9. Actuator
10. Capillary reel
11. Remote temperature adjuster
12. Bellow
13. Remote temperature sensor (only FED-FF)
Dimensions
FED-IF
FED-FF
VD.33.T1.02 © Danfoss 06/99 CD-ST
Loading...