Introduction
The instructions provide information about the replacement of memory module (ordering number: 134B0791).
A memory module is a component that stores motor and pump data, as well as rmware and parameter settings of a frequency converter. If a frequency converter malfunctions, the motor and pump data, rmware, and parameter settings on this frequency converter can be copied to new frequency converters of the same power sizes. Doing this saves the time for setting up the frequency converters for the same applications.
A memory module is pre-installed on the frequency converter. The data and parameter settings on a memory module are encoded les that are protected from direct viewing.
To access les in a memory module, or transfer les between a memory module and a PC, a memory module programmer is required. It is not included in this package and needs to be ordered separately (ordering number: 134B0792).
1 Memory module
2 Status indicator light
3 Socket for memory module
4 Memory module programmer
5 USB Type-B receptacle
Items Supplied
Ordering number Items supplied
134B0791 Memory module
Safety Instructions
Only qualied personnel is allowed to install or operate this equipment. Qualied personnel is dened as trained sta, who are authorised to install, commission, and maintain equipment, systems and circuits in accordance with pertinent laws and regulations. Additionally, the personnel must be familiar with the instructions and safety measures described in the operating instructions.
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors, which can remain charged even when the frequency converter is not powered. High voltage can be present even when the warning LED indicator lights are specied time after power has been removed before performing service or repair work can result in death or serious injury.
Stop the motor.
Disconnect AC mains and remote DC-link power
supplies, including battery back-ups, UPS, and DC­link connections to other frequency converters.
Disconnect or lock PM motor.
Wait for the capacitors to discharge fully. The
minimum duration of waiting time is specied in Table 1 . 1 .
Before performing any service or repair work, use
an appropriate voltage measuring device to make sure that the capacitors are fully discharged.
Volt age [V]
380–480 0.55–7.5 (0.75–10) 4
Power range
[kW (hp)]
Failure to wait the
o.
Minimum waiting time
(minutes)
Illustration 1.1 Memory Module and Memory Module Programmer
Danfoss A/S © 9/2015 All rights reserved. MI03Q202
Tab le 1 . 1 D i s char ge T ime
Memory Module Replacement
Tools r e q u ire d
Tor x 2 0 screwd r i ver
Complete the following steps to replace the memory module:
1. Stop the motor and the frequency converter, and wait for the capacitors to discharge completely. The discharge time is
specied
2. Remove the front cover. Refer to the operating instructions for instructions of removing the front cover.
3. Remove the memory module from the frequency converter, as shown in Illustration 1.2.
4. If applicable, transfer les to the new memory module. Refer to the Memory Module Programmer Installation Instructions for details.
5. Install the new memory module.
6. Mount the front cover. Refer to the operating instructions for instructions of mounting the front cover.
7. When the frequency converter powers up, the data on the memory module is downloaded to the frequency converter and takes eect.
in Ta b l e 1. 1 .
Illustration 1.2 Remove the Memory Module from the Frequency
Converter
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.