Danfoss FC 51 Programming guide

MAKING MODERN LIVING POSSIBLE
Programming Guide
VLT® Micro Drive FC 51
www.danfoss.com/drives
Contents Programming Guide
Contents
1 Introduction
1.2 Abbreviations
1.3 Software Version and Approvals
1.4 Disposal Instruction
2 Safety
2.1 Safety Symbols
2.2 Qualified Personnel
2.3 Safety
3 Programming
3.1 How to Programme
3.2 Status Menu
3.3 Quick Menu
3.4 Main Menu
4 Parameter Descriptions
4.1 Parameter Group 0: Operation/Display
10
11 11
4.2 Parameter Group 1: Load/Motor
4.3 Parameter Group 2: Brakes
4.4 Parameter Group 3: Reference/Ramps
4.5 Parameter Group 4: Limits/Warnings
4.6 Parameter Group 5: Digital In/Out
4.7 Parameter Group 6: Analog In/Out
4.8 Parameter Group 7: Controllers
4.9 Parameter Group 8: Communication
4.10 Parameter Group 13: Smart Logic
4.11 Parameter Group 14: Special Functions
4.12 Parameter Group 15: Drive Information
4.13 Parameter Group 16: Data Readouts
4.14 Parameter Group 18: Extended Motor Data
5 Parameter Lists
5.1 Parameter Overview
5.2 Parameter Lists
5.2.1 Conversion Index 56
14 19 21 25 28 32 36 37 41 46 48 49 51
52 52 56
5.2.2 Change During Operation 56
5.2.3 2-Set-up 56
5.2.4 Type 56
5.2.5 0-** Operation/Display 57
MG02C702 Danfoss A/S © 12/2014 All rights reserved. 1
Contents
VLT® Micro Drive FC 51
5.2.6 1-** Load/Motor 57
5.2.7 2-** Brakes 58
5.2.8 3-** Reference/Ramps 58
5.2.9 4-** Limits/Warnings 59
5.2.10 5-** Digital In/Out 59
5.2.11 6-** Analog In/Out 60
5.2.12 7-** Controllers 60
5.2.13 8-** Comm. and Options 61
5.2.14 13-** Smart Logic 61
5.2.15 14-** Special Functions 61
5.2.16 15-** Drive Information 62
5.2.17 16-** Data Readouts 62
5.2.18 18-** Extended Motor Data 63
6 Troubleshooting
Index
64
70
2 Danfoss A/S © 12/2014 All rights reserved. MG02C702
Introduction Programming Guide
1 Introduction
The nameplate sticker is located on the top of each frequency converter and shows the ratings, serial number, warnings catalog number, and other relevant data for each unit. See Table 1.1 for details, how to read the type code string.
1
1
Illustration 1.1 Nameplate Sticker
MG02C702 Danfoss A/S © 12/2014 All rights reserved. 3
Introduction
VLT® Micro Drive FC 51
1
1.1.1 Type Code
Illustration 1.2 Type Code Definition
Description Pos. Possible choice
Product group 1-3 Frequency converters Series and product type 4-6 Micro Drive Power size 7-10 0.18–22 kW Mains voltage 11-12 S2: Single phase 200–240 V AC
T2: 3-phase, 200–240 V AC
T4: 3-phase, 380–480 V AC Enclosure 13-15 IP20/Chassis RFI filter 16-17 HX: No RFI filter
H1: RFI filter class A1/B
H3:RFI filter A1/B (reduced cable length1)) Brake 18 B: Brake chopper included (from 1.5 kW and up)
X: No brake chopper included Display 19 X: No Local Control Panel
N: Numerical Local Control Panel (LCP)
P: Numerical Local Control Panel (LCP)) with potentiometer Coating PCB 20 C: Coated PCB
X. No coated PCB Mains option 21 X: No mains option Adaptation A 22 X: No adaptation Adaptation B 23 X: No adaptation Software release 24-27 SXXX: Latest release - standard software
Table 1.1 Type Code Description
1) See the VLT® Micro Drive FC 51 Design Guide.
4 Danfoss A/S © 12/2014 All rights reserved. MG02C702
Introduction Programming Guide
1.2 Abbreviations
1.3
Software Version and Approvals
1
1
Abbrevi­ations
a AWG American wire gauge Auto Tune Automatic motor tuning °C I Current A Amp I
LIM
IT mains Mains supply with star point
Joule Energy J=N∙m ft-lb, Btu °F FC Frequency converter f Frequency Hz Hz kHz Kilohertz kHz kHz LCP Local control panel mA Milliampere ms Millisecond min Minute MCT Motion Control Tool M-TYPE Motor type dependent Nm Newton metres in-lbs I
M,N
f
M,N
P
M,N
U
M,N
PELV Protective extra low voltage Watt Power
Pascal Pressure
I
INV
RPM Revolutions per minute s Second SR Size related T Temperature C F t Time s s,hr T
LIM
U Voltage V V
Terms SI units I-P units
Acceleration
Celsius
Current limit
in transformer floating to ground
Fahrenheit
Nominal motor current Nominal motor frequency Nominal motor power Nominal motor voltage
Rated inverter output current
Torque limit
2
m/s
W
Pa =
N/m²
2
ft/s
Btu/hr,
hp
psi, psf,
ft of
water
Software Version
Programming Guide
VLT® Micro Drive
FC 51 Series
This Programming Guide can be used for all VLT
Micro Drive FC 51 frequency converters with
software version 3.1X.
The software version number can be read in
15-43 Software Version.
Table 1.3 Software Version and Approvals
1.4 Disposal Instruction
Equipment containing electrical components must not be disposed of together with domestic waste. It must be separately collected with electrical and electronic waste according to local and currently valid legislation.
®
Table 1.2 Abbreviations
MG02C702 Danfoss A/S © 12/2014 All rights reserved. 5
Safety
VLT® Micro Drive FC 51
2 Safety
22
2.1 Safety Symbols
The following symbols are used in this manual:
WARNING
Indicates a potentially hazardous situation that could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation that could result in minor or moderate injury. It can also be used to alert against unsafe practices.
NOTICE
Indicates important information, including situations that can result in damage to equipment or property.
2.2 Qualified Personnel
WARNING
UNINTENDED START
When the frequency converter is connected to AC mains, DC supply, or load sharing, the motor may start at any time. Unintended start during programming, service, or repair work can result in death, serious injury, or property damage. The motor can start via an external switch, a serial bus command, an input reference signal from the LCP, or after a cleared fault condition. To prevent unintended motor start:
Disconnect the frequency converter from the
mains. Press [Off/Reset] on the LCP before
programming parameters. Fully wire and assembly the frequency
converter, motor, and any driven equipment before connecting the frequency converter to AC mains, DC supply, or load sharing.
Correct and reliable transport, storage, installation, operation, and maintenance are required for the trouble­free and safe operation of the frequency converter. Only qualified personnel are allowed to install or operate this equipment.
Qualified personnel are defined as trained staff, who are authorised to install, commission, and maintain equipment, systems, and circuits in accordance with pertinent laws and regulations. Additionally, the qualified personnel must be familiar with the instructions and safety measures described in these operating instructions.
2.3
Safety
WARNING
HIGH VOLTAGE
Frequency converters contain high voltage when connected to AC mains input, DC supply, or load sharing. Failure to perform installation, start-up, and maintenance by qualified personnel can result in death or serious injury.
Installation, start-up, and maintenance must be
performed by qualified personnel only.
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors, which can remain charged even when the frequency converter is not powered. Failure to wait the specified time after power has been removed before performing service or repair work, could result in death or serious injury.
1. Stop the motor.
2. Disconnect FC 51 from mains (and external DC supply, if present).
3. Wait for 4 minutes (M1, M2 and M3) and 15 min (M4 and M5) for discharge of the DC-link.
4. Disconnect DC bus terminals and brake terminals (if present).
5. Remove motor cable.
WARNING
LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to ground the frequency converter properly can result in death or serious injury.
Ensure the correct grounding of the equipment
by a certified electrical installer.
6 Danfoss A/S © 12/2014 All rights reserved. MG02C702
Safety
Programming Guide
WARNING
EQUIPMENT HAZARD
Contact with rotating shafts and electrical equipment can result in death or serious injury.
Ensure that only trained and qualified
personnel perform installation, start up, and maintenance.
Ensure that electrical work conforms to national
and local electrical codes. Follow the procedures in this document.
CAUTION
INTERNAL FAILURE HAZARD
An internal failure in the frequency converter can result in serious injury, when the frequency converter is not properly closed.
Ensure that all safety covers are in place and
securely fastened before applying power.
2 2
NOTICE
HIGH ALTITUDES
For installation at altitudes above 2000 m, contact Danfoss regarding PELV.
NOTICE
Use on Isolated Mains
For details about the use of the frequency converter on isolated mains, refer to section RFI Switch in the design guide. Follow the recommendations regarding the installation on IT-mains. Use relevant monitoring devices for IT­mains to avoid damage.
MG02C702 Danfoss A/S © 12/2014 All rights reserved. 7
Programming
3 Programming
VLT® Micro Drive FC 51
3.1 How to Programme
33
3.1.1 Programming with MCT 10 Set-up Software
The frequency converter can be programmed from a PC via RS485 com-port by installing the MCT 10 Set-up Software.
This software can either be ordered using code number 130B1000 or downloaded from the Danfoss Web site:
www.danfoss.com/BusinessAreas/DrivesSolutions/software­download
Refer to VLT Operating Instructions.
3.1.2
®
Motion Control Tools MCT 10 Set-up Software,
Programming with the LCP 11 or LCP 12
The LCP is divided into four functional groups:
1. Numeric display.
2. Menu key.
3. Navigation keys.
4. Operation keys and indicator lights (LEDs).
The display
Different information can be read from the display. Set-up number shows the active set-up and the edit set-
up. If the same set-up acts as both active and edit set-up, only that set-up number is shown (factory setting). When active and edit set-up differ, both numbers are shown in the display (Set-up 12). The number flashing, indicates the edit set-up.
Illustration 3.3 Indicating Set-up
The small digits to the left are the selected parameter number.
Illustration 3.4 Indicating Selected Parameter Number
Illustration 3.1 LCP 12 with Potentiometer
Illustration 3.2 LCP 11 without Potentiometer
The large digits in the middle of the display show the value of the selected parameter.
Illustration 3.5 Indicating Value of Selected Parameter
The right side of the display shows the unit of the selected parameter. This can be either Hz, A, V, kW, hp, %, s or RPM.
Illustration 3.6 Indicating Unit of Selected Parameter
8 Danfoss A/S © 12/2014 All rights reserved. MG02C702
130BA466.10
Programming Programming Guide
Motor direction is shown to the bottom left of the display
- indicated by a small arrow pointing either clockwise or
counterclockwise.
Illustration 3.7 Indicating Motor Direction
Press the [Menu] key to select one of the following menus
Status Menu
The Status Menu is either in Readout Mode or Hand on Mode. In Readout Mode the value of the currently selected
readout parameter is shown in the display. In Hand on Mode the local LCP reference is displayed.
Quick Menu
Displays Quick Menu parameters and their settings. Parameters in the Quick Menu can be accessed and edited from here. Most applications can be run by setting the parameters in the Quick Menus.
Main Menu
Displays Main Menu parameters and their settings. All parameters can be accessed and edited here.
LED (indicator lights)
Green LED: The frequency converter is on.
Yellow LED: Indicates a warning. See
chapter 6 Troubleshooting. Flashing red LED: Indicates an alarm. See
chapter 6 Troubleshooting.
Navigation keys [Back]: For moving to the previous step or layer in the
navigation structure. [▲] [▼]: For maneuvering between parameter groups,
parameters and within parameters. [OK]: For selecting a parameter and for accepting changes to parameter settings.
Pressing [OK] for more than 1 s enters Adjust mode. In Adjust mode, it is possible to make fast adjustment by pressing [] [] combined with [OK].
Press [] [] to change value. Press [OK] to shift between digits quickly.
To exit Adjust mode, press [OK] more than 1 s again with changes saving or press [Back] without changes saving.
Operation keys
A yellow light above the operation keys indicates the active key.[Hand On]: Starts the motor and enables control of the frequency converter via the LCP. [Off/Reset]: The motor stops except in alarm mode. In that case the motor will be reset.
[Auto On]:
control terminals or serial communication. [Potentiometer] (LCP 12): The potentiometer works in two ways depending on the mode in which the frequency converter is running. In Auto Mode the potentiometer acts as an extra programmable analog input. In Hand on Mode the potentiometer controls local reference.
The frequency converter is controlled either via
3.2 Status Menu
After power up, the Status Menu is active. Press [Menu] to toggle between Status, Quick Menu and Main Menu.
[▲] and [▼] toggles between the choices in each menu.
The display indicates the status mode with a small arrow above “Status”.
Illustration 3.8 Indicating Status Mode
3.3 Quick Menu
The Quick Menu gives easy access to the most frequently used parameters.
1. To enter the Quick Menu, press [Menu] key until
indicator in display is placed above Quick Menu.
2.
Press [▲] [▼] to select either QM1 or QM2, then press [OK].
3.
Press [▲] [▼] to browse through the parameters in the Quick Menu.
4. Press [OK] to select a parameter.
5.
Press [▲] [▼] to change the value of a parameter setting.
6. Press [OK] to accept the change.
7.
To exit, press either [Back] twice to enter Status, or press [Menu] once to enter Main Menu.
Illustration 3.9 Indicating Quick Menu Mode
3 3
MG02C702 Danfoss A/S © 12/2014 All rights reserved. 9
Programming
VLT® Micro Drive FC 51
3.4 Main Menu
The Main Menu gives access to all parameters.
1. To enter the Main Menu, press [Menu] key until
indicator in display is placed above Main Menu.
33
2.
Press [▲] [▼] to browse through the parameter groups.
3. Press [OK] to select a parameter group.
4.
Press [▲] [▼] to browse through the parameters in the specific group.
5. Press [OK] to select the parameter.
6.
Press [▲] [▼] to set/change the parameter value.
7. Press [OK] to accept the value.
8.
To exit, press either [Back] twice to enter Quick Menu, or press [Menu] once to enter Status.
Illustration 3.10 Indicating Main Menu Mode
10 Danfoss A/S © 12/2014 All rights reserved. MG02C702
Parameter Descriptions Programming Guide
4 Parameter Descriptions
4.1 Parameter Group 0: Operation/Display
0-03 Regional Settings
Option: Function:
In order to meet the needs for different default settings in different parts of the world, 0-03 Regional Settings, is implemented in the frequency converter. The selected setting influences the default setting of the motor nominal frequency.
[0 ] * Interna-
tional
[1] US
Sets default of 1-23 Motor Frequency, to 50 Hz, shows 1-20 Motor Power in kW. Sets default of 1-23 Motor Frequency, to 60 Hz, shows 1-20 Motor Power in HP.
NOTICE
This parameter cannot be changed while motor runs.
0-04 Operating State at Power-up (Hand Mode)
Option: Function:
This parameter controls whether or not the frequency converter start running the motor when powering up after a power down in Hand mode.
NOTICE
If LCP with potentiometer is mounted, reference is set according to actual potentiometer value.
[0] Resume Frequency converter starts in same Hand or
Off State as when powered off. Local reference is stored and used after power-up.
[1] * Forced
Stop, Ref=Old
[2] Forced
Stop, Ref=0
Frequency converter powers up in Off State meaning that motor is stopped after power up. Local reference is stored and used after power-up. Frequency converter powers up in Off State meaning that motor is stopped after power up. Local reference is set to 0. Thus motor will not start running before local reference has been increased.
4.1.1 0-1* Set-up Handling
User-defined parameters and miscellaneous external inputs (eg. bus, LCP, analog/digital inputs, feedback, etc.) controls the functionality of the frequency converter.
A complete set of all parameters controlling the frequency converter is called a set-up. The frequency converter contains 2 set-ups, Set-up 1 and Set-up 2. Furthermore, a fixed set of factory settings can be copied into one or more set-ups.
Some of the advantages of having more than one set-up in the frequency converter are
Run motor in one set-up (Active Set-up) while
updating parameters in another set-up (Edit Set­up)
Connect various motors (one at a time) to
frequency converter. Motor data for various motors can be placed in different set-ups.
Rapidly change settings of frequency converter
and/or motor while motor is running (eg. ramp time or preset references) via bus or digital inputs.
The Active Set-up can be set as Multi Set-up where the active set-up is selected via input on a digital input terminal and/or via the bus control word.
NOTICE
Factory Set-up cannot be used as active set-up.
0-10 Active Set-up
Option: Function:
Active Set-up controls the motor. Shifts between set-ups can only happen when
the motor is coasted
OR
the set-ups between which the shift
happens are linked to each other (see 0-12 Linked Set-ups).
If changing between set-ups that are not linked, the change will not happen before motor is coasted.
NOTICE
The motor is only considered stopped when it is coasted.
4 4
MG02C702 Danfoss A/S © 12/2014 All rights reserved. 11
Parameter Descriptions
VLT® Micro Drive FC 51
0-10 Active Set-up
Option: Function:
[1 ]*Set-up 1
[2] Set-up 2 [9] Multi
Set-up
Set-up 1 is active.
Set-up 2 is active.
Select the active set-up via digital input and/or bus, see 5-1* Digital Inputs choice [23].
0-11 Edit Set-up
44
Option: Function:
The Edit Set-up is for updating parameters in the frequency converter from either LCP or bus. It can be identical or different from the Active Set-up. All set-ups can be edited during operation,
independently of the active set-up. [1 ] * Set-up 1 [2] Set-up 2 [9] Active
Set-up
Update parameters in Set-up 1.
Update parameters in Set-up 2.
Update parameters in set-up selected as Active
Set-up (see 0-10 Active Set-up).
0-12 Link Set-ups
Option: Function:
The link ensures synchronizing of the “not changeable during operation” parameter values enabling shift from one set-up to another during operation. If the set-ups are not linked, a change between them is not possible while the motor is running. Thus the set-up change does not occur until the motor is coasted.
[0] Not
linked
[1 ]*Linked Copy parameters “not changeable during
Leaves parameters unchanged in both set-ups and cannot be changed while motor runs.
operation” parameter values into presently selected Edit Set-up.
NOTICE
This parameter cannot be changed while motor runs.
0-31 Custom Readout Min Scale
0-32 Custom Readout Max Scale
Range: Function:
100.0* [0.00–
9999.00]
It is possible to create a customized readout related to the output frequency of the unit. The value entered in 0-32 Custom Readout Max Scale will be shown at the frequency programmed in 4-14 Motor Speed High Limit. The readout can be shown in the LCP display when in Status Mode or it can be read in 16-09 Custom Readout
4.1.2 0-4* LCP
The frequency converter can operate in the following three modes: Hand, Off and Auto. Hand: The frequency converter is locally operated and does not allow any remote control. By activating Hand a start signal is given. OFF: The frequency converter stops with a normal stop ramp. When Off is chosen the frequency converter can only be started by pressing either Hand or Auto on the LCP. Auto: In Auto-mode the frequency converter can be remote controlled (bus/digital).
0-40 [Hand On] Key on LCP
Option: Function:
[0] Disabled [Hand On] key has no function. [1 ] * Enabled [Hand On] key is functional.
0-41 [Off/Reset] Key on LCP
Option: Function:
[0] Disable Off/Reset [Off/Reset] key has no function. [1 ] * Enable Off/Reset Stop signal and reset of any faults. [2] Enable Reset Only Reset only. Stop (Off) function is
disabled.
0-42 [Auto On] Key on LCP
Option: Function:
[0] Disabled [Auto On] key has no function. [1 ] * Enabled [Auto On] key is functional.
Range: Function:
0.00 * [0.00–
9999.00 ]
It is possible to create a customized readout related to the output frequency of the unit. The value entered in 0-31 Custom Readout Min Scale will be shown at 0 Hz. The readout can be shown in the LCP display when in Status Mode or it can be read in 16-09
Custom Readout
4.1.3 0-5* Copy/Save
0-50 LCP Copy
Option: Function:
The detachable LCP of the frequency converter can be used for storing setups, and thus for transferring data when moving parameter settings from one frequency converter to another.
NOTICE
LCP Copy can only be activated
from the LCP and ONLY when the motor is coasted.
12 Danfoss A/S © 12/2014 All rights reserved. MG02C702
Parameter Descriptions Programming Guide
0-50 LCP Copy
Option: Function:
[0] * No copy [1] All to LCP Copy all setups from the frequency
converter into the LCP.
[2] All from LCP Copy all setups from LCP to frequency
converter.
[3] Size independent
from LCP
Copy non motor size dependent data from LCP to frequency converter.
0-51 Set-up Copy
Option: Function:
Use this function to copy a set-up content into the Edit Set-up. In order to be able to make a set-up copy ensure that
the motor is coasted
0-10 Active Set-up, Active Set-up, is
set to either [1] Set-up 1 or [2] Set-up 2
NOTICE
The keyboard/parameter database are blocked while Set-up Copy is running.
[0 ]*No Copy Copy function is inactive
0-61 Access to Main/Quick Menu w/o Password
Option: Function:
[0] * Full access
[1] LCP: Read Only
[2] LCP: No Access
Select [0] Full Access to disable the password in 0-60 (Main) Menu Password. Select [1] Read Only to block unauthorized editing of Main/Quick menu parameter. Select [2] No Access to block unauthorized editing and viewing of Main/Quick menu parameter.
4 4
[1] Copy from
Set-up 1
[2] Copy from
Set-up 2
[9] Copy from
Factory Set­up
Copy from Set-up 1 to edit set-up chosen in 0-11 Edit Set-up. Copy from Set-up 2 to edit set-up chosen in 0-11 Edit Set-up. Copy from Factory Settings to edit set-up chosen in 0-11 Edit set-up.
4.1.4 0-6* Password
0-60 (Main) Menu Password
Range: Function:
Use password for protection against unintended change of sensitive parameters, eg. motor parameters.
0 * [0-999] Enter the password for access to Main Menu via
the [Main Menu] key. Select the number that should allow for changing other parameter values. 0 means there is no password.
NOTICE
A password has affect on the LCP - not on the bus communication.
NOTICE
Pressing [Menu], [OK] and [▼] will unlock the password. This will automatically enter the parameter editing screen in Quick Menu or Main Menu.
MG02C702 Danfoss A/S © 12/2014 All rights reserved. 13
Parameter Descriptions
VLT® Micro Drive FC 51
4.2 Parameter Group 1: Load/Motor
1-05 Hand Mode Configuration
Option: Function:
1-00 Configuration Mode
Option: Function:
Use this parameter for selecting the application control principle to be used when a Remote Reference is active.
NOTICE
44
Changing this parameter resets 3-00 Reference Range, 3-02 Minimum
[0] Speed
Open Loop
Reference and 3-03 Maximum Reference to their default values.
NOTICE
This parameter cannot be adjusted while motor runs.
[0 ] * Speed
Open Loop
[3] Process Enables process closed loop control. See
For normal speed control (References).
parameter group 7-3* Process PI Control for further information on PI-controller.
1-01 Motor Control Principle
[2]*As
configu­ration in
1-00 Configu­ration Mode.
4.2.1 1-2* Motor Data
This parameter is only relevant when 1-00
Configuration Mode is set to [3] Process Closed Loop. The parameter is used for determining the
reference or setpoint handling when changing from Auto Mode to Hand Mode on the LCP. In Hand Mode the drive always runs in Open Loop configuration regardless of setting in 1-00 Configuration Mode. Local potentiometer (if present) or Arrow up/down determines output frequency limited by Motor Speed High/Low Limit (4-14 Motor Speed High Limit and 4-12 Motor Speed Low Limit). If 1-00 Configuration Mode is set to [1] Open Loop function is as described above. If 1-00 Configuration Mode is set to [3] Process Closed Loop changing from Auto mode to Hand mode results in a setpoint change via local potentiometer or Arrow up/down. The change is limited by Reference Max/Min (3-02 Minimum Reference and 3-03 Maximum Reference).
Option: Function:
[0] U/f Is used for parallel connected motors and/or special
motor applications. The U/f settings are set in 1-55 U/f Characteristic -U and 1-56 U/f Characteristic -F.
NOTICE
When running U/f control slip- and load
Enter the correct motor nameplate data (power, voltage, frequency, current and speed). Run AMT, see 1-29 Automatic Motor Tuning (AMT). Factory settings for advanced motor data, parameter group 1-3* Adv. Motor Data, are automatically calculated.
compensations are not included.
[1] * VVC+ Normal running mode, including slip- and load
compensations.
NOTICE
Parameters in parameter group 1-2* Motor Data cannot be adjusted while motor runs.
1-03 Torque Characteristics
Option: Function:
With more torque characteristics it is possible to run low energy consuming, as well as high torque applications.
[0 ] * Constant
Torque
[2] Automatic
Energy Optimisation
Motor shaft output provides constant torque under variable speed control. This function automatically optimizes energy consumption in centrifugal pump and fan applications. See 14-41 AEO Minimum Magnetisation.
1-20 Motor Power [kW]/[HP] (P
Option: Function:
Enter motor power from nameplate data. Two sizes down, one size up from
nominal VLT rating. [1] 0.09 kW/0.12 HP [2] 0.12 kW/0.16 HP [3] 0.18kW/0.25 HP [4] 0.25 kW/0.33 HP [5] 0.37kW/0.50 HP [6] 0.55 kW/0.75 HP [7] 0.75 kW/1.00 HP [8] 1.10 kW/1.50 HP [9] 1.50 kW/2.00 HP [10] 2.20 kW/3.00 HP [11] 3.00 kW/4.00 HP [12] 3.70 kW/5.00 HP [13] 4.00 kW/5.40 HP
m.n
)
14 Danfoss A/S © 12/2014 All rights reserved. MG02C702
130BA375.11
R
S
P 1-30
R
1s
X
h
P1-35
R
1
X
2
X
1
U
1
I
1
Parameter Descriptions Programming Guide
1-20 Motor Power [kW]/[HP] (P
m.n
)
Option: Function:
[14] 5.50 kW/7.50 HP [15] 7.50 kW/10.0 HP [16] 11.00 kW/15.00 HP [17] 15.00 kW/20.00 HP [18] 18.50 kW/25.00 HP [19] 22.00 kW/29.50 HP [20] 30.00 kW/40.00 HP
NOTICE
Changing this parameter affects parameters 1-22 Motor Voltage to 1-25 Motor Frequency, 1-30 Stator Resistance, 1-33 Stator Leakage Reactance and 1-35 Main Reactance.
1-22 Motor Voltage (U_
Range: Function:
230/400 V [50-999 V] Enter motor voltage from nameplate
1-23 Motor Frequency (f_
Range: Function:
50 Hz* [20-400 Hz] Enter motor frequency from nameplate
data.
1-24 Motor Current (I_
Range: Function:
M-type dependent* [0.01-100.00 A] Enter motor current from
1-25 Motor Nominal Speed (n_
Range: Function:
M-type Dependent* [100–9999
RPM]
data.
m.n
m.n
)
)
)
m.n
nameplate data.
)
m.n
Enter motor nominal speed from nameplate data.
1-29 Automatic Motor Tuning (AMT)
Option: Function:
NOTICE
To gain optimum tuning of the frequency converter, run AMT on a cold motor.
[3] Complete
AMT with Rotating motor
NOTICE
When set to this option, the motor will rotate.
With this option, 1-35 Main Reactance (X2) is also optimized, other than parameters 1-30
Stator Resistance (Rs) and 1-33 Stator Leakage Reactance (X1).
4.2.2 1-3* Adv. Motor Data
Adjust advanced motor data using one of these methods:
1. Run AMT on cold motor. The frequency converter measures value from motor.
2. Enter X1 value manually. Obtain value from motor supplier.
3. Use Rs, X1, and X2 default setting. The frequency converter establishes setting based on motor nameplate data.
NOTICE
These parameters cannot be changed while the motor runs.
4 4
1-29 Automatic Motor Tuning (AMT)
Option: Function:
Use AMT to optimise motor performance. When 1-01 Motor Control Principle is set to [0] U/f, AMT does not work.
NOTICE
This parameter cannot be changed while the motor runs.
1. Stop the frequency converter - make sure that the motor is at standstill
2.
Select [2] Enable AMT
3. Apply start signal
- Via LCP: Press [Hand On]
- Or in Remote On mode: Apply
MG02C702 Danfoss A/S © 12/2014 All rights reserved. 15
[0] * Off AMT function is disabled. [2] Enable AMT AMT function starts running.
start signal on terminal 18
Illustration 4.1 Advanced Motor Data Parameters
1-30 Stator Resistance (Rs)
Range: Function:
Depending on motor data* [Ohm] Set stator resistance value.
1-33 Stator Leakage Reactance (X1)
Range: Function:
Depending on motor data*
[Ohm] Set stator leakage reactance
of motor.
Magn. current
130BD016.10
Hz
Par.1-50
Par.1-51
100%
Par.1-52 RPM
Motor Voltage Par 1-55 [x]
Output Frequency Par 1-56 [x]
1-55[5]
1-55[4]
1-55[3]
1-55[2]
1-55[1] 1-55[0]
1-56 [0]
1-56 [1]
1-56 [2]
1-56 [3]
1-56 [4]
1-56 [5]
130BD017.10
Parameter Descriptions
VLT® Micro Drive FC 51
1-35 Main Reactance (X2)
Range: Function:
Depending on motor data* [Ohm] Set motor main reactance.
4.2.3 1-5* Load Independent Setting
1-56 U/f Characteristic - F
Range: Function:
Simplify U/f characteristics by merging 2 or more points (voltages and frequencies), respectively, are set equal.
This parameter group is for setting the load independent motor settings.
44
1-50 Motor Magnetization at Zero Speed
Range: Function:
This parameter enables different thermal load on motor when running at low speed.
100 %* [ 0–300%] Enter a percentage of rated magnetizing
current. If setting is too low, motor shaft torque may be reduced.
1-52 Min. Speed Normal Magnetizing [Hz]
Range: Function:
0.0 Hz* [0.0–10.0 Hz]
Use this parameter along with 1-50 Motor Magnetizing at Zero Speed. Set frequency required for normal magnetizing current. If frequency is set lower than motor slip frequency, 1-50 Motor Magnetizing at Zero Speed is inactive.
Illustration 4.3 U/f Characteristics
NOTICE
For 1-56 U/f characteristics - F the following applies [0] [1] [2] [3] [4] [5]
Illustration 4.2 Parameters 1-50 and 1-52
1-55 U/f Characteristic - U
Range: Function:
This parameter is an array parameter [0-5] and is only functional when 1-01 Motor Control Principle is set to [0] U/f.
0.0 V* [0.0–
999.9 V]
Enter voltage at each frequency point to manually form a U/f characteristic matching motor. Frequency points are defined in 1-56 U/f characteristics - F.
1-56 U/f Characteristic - F
Range: Function:
This parameter is an array parameter [0-5] and is only functional when 1-01 Motor Control Principle is set to [0] U/f.
0.0
Hz*
[0.0–
1000.0 Hz]
Enter frequency points to manually form a U/f characteristic matching motor. Voltage at each point is defined in 1-55 U/f Characteristic - U. Make a U/f characteristic based on 6 definable voltages and frequencies, see Illustration 4.3.
4.2.4 1-6* Load Dependent Setting
Parameters for adjusting the load-dependent motor settings.
1-60 Low Speed Load Compensation
Range: Function:
Use this parameter to gain optimum U/f characteristic when running at low speed.
100 %* [0–199%]Enter percentage in relation to load when
motor runs at low speed. Change-over point is automatically calculated based on motor size.
16 Danfoss A/S © 12/2014 All rights reserved. MG02C702
130BD018.10
60%
0%
100%
U
m
Changeover
f
out
Par.1-60 Par.1-61
Parameter Descriptions Programming Guide
Illustration 4.4 Load Compensation Characteristics
1-61 High Speed Load Compensation
Range: Function:
Use this parameter to obtain optimum load compensation when running at high speed.
100 %* [0–199%]Enter percentage to compensate in relation
to load when motor runs at high speed. Change-over point is automatically calculated based on motor size.
1-62 Slip Compensation
Range: Function:
100 %* [-400–399%]Compensation for load dependent motor
slip. Slip compensation is calculated automat­ically based on rated motor speed, n
M,N
.
NOTICE
This function is only active when 1-00 Configuration Mode, is set to [0] Speed Open Loop and when 1-01 Motor Control Principle, is set to [1]
+
VVC
1-71 Start Delay
Range: Function:
The start delay defines the time to pass from a start command is given until the motor starts accelerating. Setting start delay to 0.0 s disables 1-72 Start Function, when start command is given.
0.0s* [0.0–
10.0 s]
Enter the time delay required before commencing acceleration.
1-72 Start Function is active during Start delay time.
1-72 Start Function
Option: Function:
[0] DC Hold/Delay
Time
[1] DC Brake/
Delay Time
[2] * Coast/Delay
Time
Motor is energised with DC holding current (2-00 DC Hold Current) during start delay time. Motor is energised with DC braking current (2-01 DC Brake Current) during start delay time. Inverter is coasted during start delay time (inverter off).
1-73 Flying Start
Option: Function:
The Flying Start parameter is used to catch a spinning motor after eg. mains drop-out.
NOTICE
This function is not suitable for hoisting applications.
[0] * Disabled Flying start is not required. [1] Enabled Frequency converter enabled to catch spinning
motor.
NOTICE
When flying start is enabled 1-71 Start Delay, and 1-72 Start Function, have no
function.
4 4
1-63 Slip Compensation Time
Range: Function:
0.10 s [0.05–5.00s]Enter slip compensation reaction speed. A
high value results in slow reaction whereas a low value results in quick reaction. If low-frequency resonance problems arise, use longer time setting.
4.2.5 1-7* Start Adjustments
Considering the need for various start functions in different applications, it is possible to select a number of functions in this parameter group.
MG02C702 Danfoss A/S © 12/2014 All rights reserved. 17
4.2.6 1-8* Stop Adjustments
To meet the need for various stop functions in different application these parameters offer some special stop features for the motor.
1-80 Function at Stop
Option: Function:
The selected function at stop is active in following situations:
Stop command is given and output
speed is ramped down to Min. Speed for Function at Stop.
Start command is removed (standby), and
output speed is ramped down to Min. Speed for Function at Stop.
Parameter Descriptions
VLT® Micro Drive FC 51
1-80 Function at Stop
Option: Function:
DC-brake command is given, and DC-
brake time has passed
While running and calculated output
speed is below Min. Speed for Function at Stop.
[0] * Coast The inverter is coasted.
44
[1] DC
hold
The motor is energised with a DC current. See 2-00 DC Hold Current for more information.
1-82 Min. Speed For Function at Stop [Hz]
NOTICE
When the ETR function has been selected the drive will store the recorded temperature at power down and this temperature will resume at power up regardless of the elapsed time. Changing 1-90 Motor Thermal Protection back to [0] No Protection will reset the recorded temperature.
1-93 Thermistor Resource
Option: Function:
Select the thermistor input terminal.
[0]*None No thermistor is connected.
Range: Function:
0.0 Hz* [0.0–20.0 Hz]
Set the speed at which to activate 1-80 Function at Stop.
[1] Analog
Input 53
Connect thermistor to analog input terminal 53.
NOTICE
Analog input 53 cannot be selected for
4.2.7 1-9* Motor Temperature
other purposes when selected as thermistor resource.
With an estimated motor temperature monitor the frequency converter is able to estimate motor temperature without having a thermistor mounted. It is thus possible to receive a warning or an alarm, if motor temperature exceeds upper operational limit.
1-90 Motor Thermal Protection
Option: Function:
Using ETR (Electronic Terminal Relay) the motor temperature is calculated based on frequency, speed and time. Danfoss recommends using The ETR function, if a thermistor is not present.
NOTICE
ETRElectronic Overload calculation is
[6] Digital
input 29
Connect thermistor to digital input terminal 29. While this input functions as thermistor input, it will not respond to the function chosen in 5-13 Digital Input 29. The value of 5-13 Digital Input 29 remains unchanged in parameter database while function is inactive.
Input Digital/
Analog
Digital 10 V
Analog 10 V
Table 4.1 Threshold Cut-out Values
Supply
Voltage
Threshold Cut-
out
Values <800 Ω 2.9 kΩ <800 Ω 2.9 kΩ
based on motor data from parameter group 1-2* Motor Data.
[0] * No
Protection
[1] Thermistor
Warning
[2] Thermistor
Trip
[3] ETR Warning If calculated upper limit of motor
[4] ETR Trip If 90% of calculated upper limit of motor
Disables temperature monitoring.
A thermistor connected to either digital or analog input gives a warning if upper limit of motor temperature range is exceeded, (see 1-93 Thermistor Resource). A thermistor connected to either digital or analog input gives an alarm and makes the frequency converter trip if upper limit of motor temperature range is exceeded, (see 1-93 Thermistor Resource.
temperature range is exceeded, a warning occurs.
temperature range is exceeded, an alarm occurs and the frequency converter trips.
18 Danfoss A/S © 12/2014 All rights reserved. MG02C702
Parameter Descriptions Programming Guide
4.3 Parameter Group 2: Brakes
4.3.1 2-0* DC-Brake
The purpose of DC-brake function is to brake a rotating motor by applying DC-current to the motor.
2-00 DC Hold Current
Range: Function:
This parameter either holds the motor (holding torque) or pre-heats the motor. The parameter is active if DC Hold has been selected in either 1-72 Start Function or 1-80 Function at Stop.
50%* [0–
150%]
Enter a value for holding current as a percentage of the rated motor current set in 1-24 Motor Current. 100% DC holding current corresponds to I
M,N
.
NOTICE
Avoid 100% current too long as it may overheat the motor.
2-01 DC Brake Current
Range: Function:
50%* [0–
150%]
2-02 DC-Braking Time
Range: Function:
10.0 s* [0.0–60 s]
Set DC-current needed to brake rotating motor. Activate DC-brake in one of the four following ways:
1.
DC-brake command, see 5-1* Digital Inputs choice [5]
2.
DC Cut-in function, see 2-04 DC-Brake
Cut-in Speed
3. DC-brake selected as start function, see
1-72 Start Function
4.
DC-brake in connection with Flying Start, 1-73 Flying Start.
DC-braking time defines the period during which DC-brake current is applied to the motor. Set the time DC-braking current, set in 2-01 DC Brake Current, must be applied.
2-04 DC-Brake Cut-in Speed
Range: Function:
0.0 Hz* [0.0–400.0 Hz]
Set DC-brake cut-in speed to activate DC braking current, set in 2-01 DC Brake Current, when ramping down. When set to 0 the function is off.
4.3.2 2-1* Brake Energy Function
Use the parameters in this group for selecting dynamic braking parameters.
2-10 Brake Function
Option: Function:
NOTICE
Resistor brake is only functional in frequency converters with integrated dynamic brake. An external resistor must be connected.
Resistor brake
The resistor brake limits voltage in the intermediate circuit when the motor acts as generator. Without brake resistor, the frequency converter eventually trips. The resistor brake consumes surplus energy resulting from motor braking. A frequency converter with brake, stops a motor faster than without a brake, which is used in many applications. Requires connection of external brake resistor. An alternative to the resistor brake is the AC brake.
AC brake
The AC brake consumes surplus energy by creating power loss in the motor. It is important to keep in mind that an increase in power loss causes motor temperature to rise.
* Off No brake function.
[0] [1] Resistor
Brake
[2] AC Brake AC brake is active.
2-11 Brake Resistor (Ohm)
Range: Function:
5 Ω* [5–5000 Ω] Set brake resistor value.
Resistor brake is active.
4 4
NOTICE
If DC-brake is activated as start function, DC-brake time is defined by start delay time.
MG02C702 Danfoss A/S © 12/2014 All rights reserved. 19
2-14 Brake Voltage Reduce
Range: Function:
0* [0–
100]
Change this parameter affects the value of 2-11 Brake Resistor (Ohm). Use this parameter to set the voltage reduction for resistor braking. It is only active when 2-10 Brake Function is set to [1] Resistor Brake. This function is valid for 400 v, 5.5–15 kW units.
Parameter Descriptions
VLT® Micro Drive FC 51
2-16 AC Brake, Max Current
Range: Function:
100.0%* [0.0–150.0%] Enter max. permissible current for AC­braking to avoid overheating of motor. 100% equals motor current set in 1-24 Motor Current.
2-17 Over-Voltage Control
Option: Function:
44
[0] * Disabled The OVC is not active/required. [1] Enabled,
not at stop
[2] Enabled OVC is running, also when a stop signal is
Use overvoltage control (OVC) to reduce the risk of the frequency converter tripping due to an over voltage on the DC link caused by generative power from the load. An over-voltage occurs eg. if the ramp down time is set too short compared to the actual load inertia.
OVC is running unless a stop signal is active.
active.
2-22 Activating Mechanical Brake
Range: Function:
If the motor is stopped using ramp, the mechanical brake is activated when motor speed is less than Active Brake Speed. Motor is ramped down to stop in the following situations:
A start command is removed (stand by)
A stop command is activated
Quick-stop is activated (Q-stop ramp is
used)
0
[0–
Select motor speed at which mechanical brake
Hz*
400
activates when ramping down.
Hz]
Mechanical brake automatically activates if frequency converter trips or reports an alarm.
NOTICE
If Resistor Brake has been chosen in 2-10 Brake Function the OVC is not active even though enabled in this parameter.
4.3.3 2-2* Mechanical Brake
For hoisting applications an electro-magnetic brake is required. The brake is controlled by a relay, which releases the brake when activated.
The brake activates if the frequency converter trips or a coast command is given. Furthermore, it activates when motor speed is ramped down below the speed set in 2-22 Active Brake Speed.
2-20 Release Brake Current
Range: Function:
0.00 A* [0.00–100 A] Select motor current at which mechanical
brake releases.
NOTICE
If start delay time has passed, and motor current is below Release brake current, frequency converter trips.
20 Danfoss A/S © 12/2014 All rights reserved. MG02C702
Parameter Descriptions Programming Guide
4.4 Parameter Group 3: Reference/Ramps
Parameters for reference handling, definition of limitations, and configuration of the frequency converter's reaction to changes
4.4.1 3-0* Reference Limits
Parameters for setting the reference unit, limits and ranges.
3-00 Reference Range
Option: Function:
Select the range of reference and feedback signals.
[0] * Min to
Max
[1] -Max to
+Max
3-02 Minimum Reference
Range: Function:
0.00* [-4999-4999] Enter value for minimum reference.
3-03 Maximum Reference
Range: Function:
60.000 Hz if
parameter 0-03 is set to US; 50.000 Hz if parameter 0-03 is set to International *
Reference setpoint ranges can have positive values only. Select this if running in Process Closed Loop. Ranges can have both positive and negative values. If potentiometer is used to adjust motor running in both direction, set reference range to –Max Reference to Max Reference by par.=[1] Choose hand on mode by LCP. Adjust the potentiometer to minimum, the motor can run in anti-clockwise with max speed. Then adjust the potentiometer to maximum, the motor will ramp down to 0 and run clockwise with max speed.
The sum of all internal and external references are clamped (limited) to the minimum reference value, 3-02 Minimum Reference.
Maximum Reference is adjustable in the range
Minimum Reference–4999. [-4999– 4999]
Enter value for Maximum
Reference.
The sum of all internal and
external references are
clamped (limited) to the
maximum reference value,
3-03 Maximum Reference.
4.4.2 3-1* References
Parameters for setting up the reference sources. Select the preset references for the corresponding digital inputs in parameter group, 5-1* Digital Inputs.
3-10 Preset Reference
Option: Function:
Each parameter set-up contains 8 preset references which are selectable via 3 digital inputs or bus.
[18] Bit2
0 0 0 0 0 0 1 1 0 1 0 2 0 1 1 3 1 0 0 4 1 0 1 5 1 1 0 6 1 1 1 7
Table 4.2 Parameter Group 5-1* Digital Inputs Option [16], [17] and [18]
[0.00]*-100.00–
100.00%
Enter the different preset references using array programming. Normally, 100%=value set in 3-03 Maximum Reference. However, there are exceptions if 3-00 Reference Range is set to [0] Min - Max. Example 1:
3-02 Minimum Reference is set to 20 and 3-03 Maximum Reference is set to 50. In this case
0%=0 and 100%=50. Example 2:
3-02 Minimum Reference is set to -70 and 3-03 Maximum Reference is set to 50. In this case
0%=0 and 100%=70.
3-11 Jog Speed [Hz]
Range: Function:
Jog speed is a fixed output speed and overrules the selected reference speed, see parameter group 5-1* Digital Inputs option [14]. If the motor is stopped while in jog mode, the jog signal acts as a start signal. Removing the jog signal makes the motor run according to the selected configuration.
5.0Hz [0.0–
400.0 Hz]
Select speed to function as jog speed.
[17] Bit1
[16] Bit0
[16] Bit0
4 4
MG02C702 Danfoss A/S © 12/2014 All rights reserved. 21
Loading...
+ 51 hidden pages