Danfoss FC 361 Design guide

ENGINEERING TOMORROW
Design Guide
VLT® AutomationDrive FC 361
90–315 kW, Enclosure Sizes J8–J9
vlt-drives.danfoss.com
Contents Design Guide
Contents
1 Introduction
1.2 Additional Resources
1.3 Document and Software Version
1.4 Approvals and Certications
1.5 Conventions
2 Safety
2.1 Safety Symbols
2.2 Qualied Personnel
2.3 Safety Precautions
3 Product Overview and Features
3.1 Power Ratings, Weights, and Dimensions
3.2 Automated Operational Features
3.3 Custom Application Features
3.4 Dynamic Braking Overview
3.5 Back-channel Cooling Overview
4
4
4
4
4
5
6
6
6
6
7
7
8
10
13
14
4 Options and Accessories Overview
4.1 Fieldbus Devices
4.2 Functional Extensions
5 Specications
5.1 Electrical Data, 380-480 V
5.2 Mains Supply
5.3 Motor Output and Motor Data
5.4 Ambient Conditions
5.5 Cable Specications
5.6 Control Input/Output and Control Data
5.7 Enclosure Weights
5.8 Exterior and Terminal Dimensions
6 Mechanical Installation Considerations
6.1 Storage
6.2 Lifting the Unit
6.3 Operating Environment
15
15
15
16
16
18
18
18
19
19
22
23
33
33
33
34
6.4 Mounting Congurations
6.5 Cooling
6.6 Derating
MG06K102 Danfoss A/S © 03/2019 All rights reserved. 1
34
35
35
Contents VLT® AutomationDrive FC 361
7 Electrical Installation Considerations
7.1 Safety Instructions
7.2 Wiring Schematic
7.3 Connections
7.4 Control Wiring and Terminals
7.5 Fuses and Circuit Breakers
7.6 Motor
7.7 Residual Current Devices (RCD) and Insulation Resistance Monitor (IRM)
7.8 Leakage Current
7.9 IT Mains
7.10 Eciency
7.11 Acoustic Noise
7.12 dU/dt Conditions
7.13 Electromagnetic Compatibility (EMC) Overview
7.14 EMC-compliant Installation
7.15 Harmonics Overview
8 Basic Operating Principles of a Drive
38
38
39
40
41
44
45
47
47
49
49
49
50
51
54
57
60
8.1 Description of Operation
8.2 Drive Controls
9 Application Examples
9.1 Programming a Closed-loop Drive System
9.2 Wiring for Open-loop Speed Control
9.3 Wiring for Start/Stop
9.4 Wiring for External Alarm Reset
9.5 Wiring for a Motor Thermistor
9.6 Wiring Conguration for the Encoder
10 How to Order a Drive
10.1 Drive Congurator
10.2 Ordering Numbers for Options and Accessories
10.3 Spare Parts
11 Appendix
11.1 Abbreviations and Symbols
60
60
68
68
68
69
70
71
71
72
72
74
74
75
75
11.2 Denitions
11.3 RS485 Installation and Set-up
11.4 RS485: FC Protocol Overview
11.5 RS485: FC Protocol Telegram Structure
11.6 RS485: FC Protocol Parameter Examples
2 Danfoss A/S © 03/2019 All rights reserved. MG06K102
76
77
78
79
83
Contents Design Guide
11.7 RS485: Modbus RTU Overview
11.8 RS485: Modbus RTU Telegram Structure
11.9 RS485: Modbus RTU Message Function Codes
11.10 RS485: Modbus RTU Parameters
11.11 RS485: FC Control Prole
Index
83
84
87
88
88
95
MG06K102 Danfoss A/S © 03/2019 All rights reserved. 3
Introduction VLT® AutomationDrive FC 361
11
1 Introduction
1.1 Purpose of the Design Guide
This design guide is intended for:
Project and systems engineers.
Design consultants.
Application and product specialists.
The design guide provides technical information to understand the capabilities of the drive for integration into motor control and monitoring systems.
VLT® is a registered trademark.
1.2 Additional Resources
Other resources are available to understand advanced drive functions and programming.
The operating guide provides detailed information
for the installation and start-up of the drive.
The programming guide provides greater detail on
working with parameters and many application examples.
Instructions for operation with optional
equipment.
Supplementary publications and manuals are available from Danfoss. See %3Adocumentation%2Csegment%3Adds for listings.
Document and Software Version
1.3
This manual is regularly reviewed and updated. All suggestions for improvement are welcome. Table 1.1 shows the version of the manual and the corresponding software version.
Manual version Remarks Software version
MG06K1xx First edition. 1.0x
Table 1.1 Manual and Software Version
www.danfoss.com/en/search/?lter=type
Approvals and Certications
1.4
Drives are designed in compliance with the directives described in this section.
1.4.1 CE Mark
The CE mark (Conformité Européenne) indicates that the product manufacturer conforms to all applicable EU directives.
The EU directives applicable to the design and manufacture of drives are:
The Low Voltage Directive.
The EMC Directive.
The Machinery Directive (for units with an
integrated safety function).
The CE mark is intended to eliminate technical barriers to free trade between the EC and EFTA states inside the ECU. The CE mark does not regulate the quality of the product. Technical specications cannot be deduced from the CE mark.
1.4.2 Low Voltage Directive
Drives are classied as electronic components and must be CE-labeled in accordance with the Low Voltage Directive. The directive applies to all electrical equipment in the 50– 1000 V AC and the 75–1500 V DC voltage ranges.
The directive mandates that the equipment design must ensure the safety and health of people and livestock, and the preservation of material by ensuring the equipment is properly installed, maintained, and used as intended. Danfoss CE labels comply with the Low Voltage Directive, and Danfoss provides a declaration of conformity upon request.
4 Danfoss A/S © 03/2019 All rights reserved. MG06K102
Introduction Design Guide
1.4.3 EMC Directive
Electromagnetic compatibility (EMC) means that electro­magnetic interference between pieces of equipment does not hinder their performance. The basic protection requirement of the EMC Directive 2014/30/EU states that devices that generate electromagnetic interference (EMI) or whose operation could be aected by EMI must be designed to limit the generation of electromagnetic interference and shall have a suitable degree of immunity to EMI when properly installed, maintained, and used as intended.
A drive can be used as stand-alone device or as part of a more complex installation. Devices in either of these cases must bear the CE mark. Systems must not be CE-marked but must comply with the basic protection requirements of the EMC directive.
1.5 Conventions
Numbered lists indicate procedures.
Bullet lists indicate other information and
description of illustrations.
Italicized text indicates:
- Cross-reference.
- Link.
- Footnote.
- Parameter name, parameter group
name, parameter option.
All dimensions in drawings are in mm (in).
An asterisk (*) indicates a default setting of a
parameter.
1 1
MG06K102 Danfoss A/S © 03/2019 All rights reserved. 5
Safety VLT® AutomationDrive FC 361
2 Safety
22
2.1 Safety Symbols
The following symbols are used in this guide:
WARNING
Indicates a potentially hazardous situation that could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation that could result in minor or moderate injury. It can also be used to alert against unsafe practices.
NOTICE
Indicates important information, including situations that can result in damage to equipment or property.
2.2 Qualied Personnel
Only qualied personnel are allowed to install or operate this equipment.
WARNING
DISCHARGE TIME
The drive contains DC-link capacitors, which can remain charged even when the drive is not powered. High voltage can be present even when the warning LED indicator lights are o. Failure to wait the specied time after power has been removed before performing service or repair work can result in death or serious injury.
Stop the motor.
Disconnect AC mains and remote DC-link power
supplies, including battery back-ups, UPS, and DC-link connections to other drives.
Disconnect or lock PM motor.
Wait for the capacitors to discharge fully. The
minimum waiting time is 20 minutes.
Before performing any service or repair work,
use an appropriate voltage measuring device to make sure that the capacitors are fully discharged.
Qualied personnel are dened as trained sta, who are authorized to install, commission, and maintain equipment, systems, and circuits in accordance with pertinent laws and regulations. Also, the personnel must be familiar with the instructions and safety measures described in this manual.
Safety Precautions
2.3
WARNING
HIGH VOLTAGE
Drives contain high voltage when connected to AC mains input, DC supply, load sharing, or permanent motors. Failure to use qualied personnel to install, start up, and maintain the drive can result in death or serious injury.
Only qualied personnel must install, start up,
and maintain the drive.
WARNING
LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to ground the drive properly can result in death or serious injury.
Ensure the correct grounding of the equipment
by a certied electrical installer.
6 Danfoss A/S © 03/2019 All rights reserved. MG06K102
Product Overview and Featur... Design Guide
3 Product Overview and Features
3.1 Power Ratings, Weights, and Dimensions
For enclosure sizes and power ratings of the drives, refer to Table 3.1. For more dimensions, see chapter 5.8 Exterior and Terminal Dimensions.
Enclosure size J8 J9
IP
NEMA
Shipping dimensions [mm (in)] Height 587 (23) 587 (23)
Width 997 (39) 1170 (46)
Depth 460 (18) 535 (21)
Height 909 (36) 1122 (44)
Drive dimensions [mm (in)]
Maximum weight [kg (lb)] 98 (216) 164 (362)
Table 3.1 Power Ratings, Weight, and Dimensions, Enclosure Sizes J8–J9, 380–480 V
Width 250 (10) 350 (14)
Depth 375 (15) 375 (15)
20
Chassis
20
Chassis
3 3
MG06K102 Danfoss A/S © 03/2019 All rights reserved. 7
Product Overview and Featur... VLT® AutomationDrive FC 361
3.2 Automated Operational Features
Automated operational features are active when the drive is operating. Most of them require no programming or set­up. The drive has a range of built-in protection functions to protect itself and the motor when it runs.
33
For details of any set-up required, in particular motor parameters, refer to the programming guide.
3.2.1 Short-circuit Protection
The overvoltage can be handled either using a brake function (parameter 2-10 Brake Function) and/or using overvoltage control (parameter 2-17 Over-voltage Control).
Brake functions
AC brake is an alternative to improving braking without using a brake resistor. This function controls an over­magnetization of the motor when the motor is acting as a generator. Increasing the electrical losses in the motor allows the OVC function to increase the braking torque without exceeding the overvoltage limit.
NOTICE
Motor (phase-to-phase)
The drive is protected against short circuits on the motor side by current measurement in each of the 3 motor phases. A short circuit between 2 output phases causes an overcurrent in the inverter. The inverter is turned o when the short circuit current exceeds the allowed value (Alarm 16, Trip Lock).
Mains side
A drive that works correctly limits the current it can draw from the supply. Still, it is recommended to use fuses and/or circuit breakers on the supply side as protection if there is component break-down inside the drive (1st fault).
NOTICE
To ensure compliance with IEC 60364 for CE, it is mandatory to use fuses and/or circuit breakers.
AC brake is not as eective as dynamic braking with a resistor.
Overvoltage control (OVC)
By automatically extending the ramp-down time, OVC reduces the risk of the drive tripping due to an overvoltage on the DC link.
NOTICE
OVC can be activated for a PM motor.
NOTICE
Do not enable OVC in hoisting applications.
3.2.3 Missing Motor Phase Detection
3.2.2 Overvoltage Protection
Motor-generated overvoltage
The voltage in the DC link is increased when the motor acts as a generator. This situation occurs in the following cases:
The load rotates the motor at constant output
frequency from the drive, that is, the load generates energy.
During deceleration (ramp-down) if the inertia
moment is high, the friction is low, and the ramp­down time is too short for the energy to be dissipated as a loss throughout the drive system.
Incorrect slip compensation setting causing
higher DC-link voltage.
Back EMF from PM motor operation. If coasted at
high RPM, the PM motor back EMF can potentially exceed the maximum voltage tolerance of the drive and cause damage. To help prevent this situation, the value of parameter 4-19 Max Output Frequency is automat­ically limited based on an internal calculation based on the value of parameter 1-40 Back EMF at 1000 RPM, parameter 1-25 Motor Nominal Speed, and parameter 1-39 Motor Poles.
The missing motor phase function (parameter 4-58 Missing Motor Phase Function) is enabled by default to avoid motor damage if a motor phase is missing. The default setting is 1000 ms, but it can be adjusted for faster detection.
3.2.4 Supply Voltage Imbalance Detection
Operation under severe supply voltage imbalance reduces the lifetime of the motor and drive. If the motor is operated continuously near nominal load, conditions are considered severe. The default setting trips the drive if there is supply voltage imbalance (parameter 14-12 Response to Mains Imbalance).
3.2.5 Switching on the Output
Adding a switch to the output between the motor and the drive is allowed, however fault messages can appear.
8 Danfoss A/S © 03/2019 All rights reserved. MG06K102
Product Overview and Featur... Design Guide
3.2.6 Overload Protection
Torque limit
The torque limit feature protects the motor against overload, independent of the speed. Torque limit is controlled in parameter 4-16 Torque Limit Motor Mode and parameter 4-17 Torque Limit Generator Mode. The time before the torque limit warning trips is controlled in parameter 14-25 Trip Delay at Torque Limit.
Current limit
The current limit is controlled in parameter 4-18 Current Limit, and the time before the drive trips is controlled in parameter 14-24 Trip Delay at Current Limit.
Speed limit
Minimum speed limit: Parameter 4-11 Motor Speed Low Limit [RPM] or parameter 4-12 Motor Speed Low Limit [Hz]
limit the minimum operating speed range of the drive. Maximum speed limit: Parameter 4-13 Motor Speed High Limit [RPM] or parameter 4-19 Max Output Frequency limits the maximum output speed that the drive can provide.
Electronic thermal relay (ETR)
ETR is an electronic feature that simulates a bimetal relay based on internal measurements. The characteristic is shown in Illustration 3.1.
Voltage limit
The inverter turns link capacitors when a certain hard-coded voltage level is reached.
Overtemperature
The drive has built-in temperature sensors and reacts immediately to critical values via hard-coded limits.
o to protect the transistors and the DC
3.2.7 Locked Rotor Protection
There can be situations when the rotor is locked due to excessive load or other factors. The locked rotor cannot produce enough cooling, which in turn can overheat the motor winding. The drive is able to detect the locked rotor situation with PM VVC+ control (parameter 30-22 Locked Rotor Protection).
3.2.8 Automatic Derating
The drive constantly checks for the following critical levels:
High temperature on the control card or heat
sink.
High motor load.
High DC-link voltage.
Low motor speed.
As a response to a critical level, the drive adjusts the switching frequency. For high internal temperatures and low motor speed, the drive can also force the PWM pattern to SFAVM.
NOTICE
The automatic derating is dierent when
parameter 14-55 Output Filter is set to [2] Sine-Wave Filter Fixed.
3.2.9 Automatic Energy Optimization
Automatic energy optimization (AEO) directs the drive to monitor the load on the motor continuously and adjust the output voltage to maximize eciency. Under light load, the voltage is reduced and the motor current is minimized. The motor benets from:
Increased eciency.
Reduced heating.
Quieter operation.
There is no need to select a V/Hz curve because the drive automatically adjusts motor voltage.
3.2.10 Automatic Switching Frequency Modulation
The drive generates short electrical pulses to form an AC wave pattern. The switching frequency is the rate of these pulses. A low switching frequency (slow pulsing rate) causes audible noise in the motor, making a higher switching frequency preferable. A high switching frequency, however, generates heat in the drive that can limit the amount of current available to the motor.
Automatic switching frequency modulation regulates these conditions automatically to provide the highest switching frequency without overheating the drive. By providing a regulated high switching frequency, it quiets motor operating noise at slow speeds, when audible noise control is critical, and produces full output power to the motor when required.
3.2.11 Automatic Derating for High Switching Frequency
The drive is designed for continuous, full-load operation at switching frequencies between 1.5–2 kHz for 380–480 V. The frequency range depends on power size and voltage rating. A switching frequency exceeding the maximum allowed range generates increased heat in the drive and requires the output current to be derated.
An automatic feature of the drive is load-dependent switching frequency control. This feature allows the motor to benet from as high a switching frequency as the load allows.
3 3
MG06K102 Danfoss A/S © 03/2019 All rights reserved. 9
Product Overview and Featur... VLT® AutomationDrive FC 361
3.2.12 Power Fluctuation Performance
The drive withstands mains uctuations such as:
Transients.
Momentary drop-outs.
33
The drive automatically compensates for input voltages ±10% from the nominal to provide full rated motor voltage and torque. With auto restart selected, the drive automat­ically powers up after a voltage trip. With ying start, the drive synchronizes to motor rotation before start.
Short voltage drops.
Surges.
3.2.13 Resonance Damping
Resonance damping eliminates the high-frequency motor resonance noise. Automatic or manually selected frequency damping is available.
3.2.14 Temperature-controlled Fans
Sensors in the drive regulate the operation of the internal cooling fans. Often, the cooling fans do not run during low load operation, or when in sleep mode or standby. These sensors reduce noise, increase eciency, and extend the operating life of the fan.
3.2.15 EMC Compliance
Electromagnetic interference (EMI) and radio frequency interference (RFI) are disturbances that can aect an electrical circuit due to electromagnetic induction or radiation from an external source. The drive is designed to comply with the EMC product standard for drives IEC 61800-3 and the European standard EN 55011. Motor cables must be shielded and properly terminated to comply with the emission levels in EN 55011. For more information regarding EMC performance, see chapter 7.13.1 EMC Test Results.
The components that make up the galvanic isolation are:
Supply, including signal isolation.
Gatedrive for the IGBTs, trigger transformers, and
optocouplers.
The output current Hall eect transducers.
3.3 Custom Application Features
Custom application functions are the most common features programmed in the drive for enhanced system performance. They require minimum programming or set­up. See the programming guide for instructions on activating these functions.
3.3.1 Automatic Motor Adaptation
Automatic motor adaptation (AMA) is an automated test procedure used to measure the electrical characteristics of the motor. AMA provides an accurate electronic model of the motor, allowing the drive to calculate optimal performance and eciency. Running the AMA procedure also maximizes the automatic energy optimization feature of the drive. AMA is performed without the motor rotating and without uncoupling the load from the motor.
3.3.2 Built-in PID Controller
The built-in proportional, integral, derivative (PID) controller eliminates the need for auxiliary control devices. The PID controller maintains constant control of closed­loop systems where regulated pressure, ow, temperature, or other system requirements must be maintained.
The drive can use 2 feedback signals from 2 dierent devices, allowing the system to be regulated with dierent feedback requirements. The drive makes control decisions by comparing the 2 signals to optimize system performance.
3.3.3 Motor Thermal Protection
3.2.16 Galvanic Isolation of Control Terminals
All control terminals and output relay terminals are galvan­ically isolated from mains power, which completely protects the controller circuitry from the input current. The output relay terminals require their own grounding. This isolation meets the stringent protective extra-low voltage (PELV) requirements for isolation.
10 Danfoss A/S © 03/2019 All rights reserved. MG06K102
To protect the application from serious damage, the drive oers several dedicated features.
Torque limit
The torque limit protects the motor from being overloaded independent of the speed. Torque limit is controlled in
parameter 4-16 Torque Limit Motor Mode and parameter 4-17 Torque Limit Generator Mode. Parameter 14-25 Trip Delay at Torque Limit controls the time
before the torque limit warning trips.
Current limit
Parameter 4-18 Current Limit controls the current limit, and parameter 14-24 Trip Delay at Current Limit controls the
time before the current limit warning trips.
1.21.0 1.4
30
10
20
100
60
40
50
1.81.6 2.0
2000
500
200
400 300
1000
600
t [s]
175ZA052.12
f
OUT
= 2 x f
M,N
f
OUT
= 0.2 x f
M,N
f
OUT
= 1 x f
M,N
(par. 1-23)
IMN(par. 1-24)
I
M
Product Overview and Featur... Design Guide
Minimum speed limit
Parameter 4-12 Motor Speed Low Limit [Hz] sets the minimum output speed that the drive can provide.
Maximum speed limit
Parameter 4-14 Motor Speed High Limit [Hz] or parameter 4-19 Max Output Frequency sets the maximum
output speed that the drive can provide.
ETR (electronic thermal relay)
The drive ETR function measures the actual current, speed, and time to calculate motor temperature. The function also protects the motor from being overheated (warning or trip). An external thermistor input is also available. ETR is an electronic feature that simulates a bimetal relay based on internal measurements. The characteristic is shown in Illustration 3.1.
The drive can be congured (parameter 14-10 Mains Failure) to dierent types of behavior during mains drop-out:
Trip lock once the DC-link is exhausted.
Coast with ying start whenever mains return
(parameter 1-73 Flying Start).
Kinetic back-up.
Controlled ramp down.
Flying start
This selection makes it possible to catch a motor that is spinning freely due to a mains drop-out. This option is relevant for centrifuges and fans.
Kinetic back-up
This selection ensures that the drive runs as long as there is energy in the system. For short mains drop-out, the operation is restored after mains return, without bringing the application to a stop or losing control at any time. Several variants of kinetic back-up can be selected.
Congure the behavior of the drive at mains drop-out in
parameter 14-10 Mains Failure and parameter 1-73 Flying Start.
3.3.5 Automatic Restart
3 3
The drive can be programmed to restart the motor automatically after a minor trip, such as momentary power loss or uctuation. This feature eliminates the need for manual resetting and enhances automated operation for remotely controlled systems. The number of restart
Illustration 3.1 ETR
The X-axis shows the ratio between I
motor
and I
motor
attempts and the duration between attempts can be limited.
3.3.6 Full Torque at Reduced Speed
nominal. The Y-axis shows the time in seconds before the ETR cuts o and trips the drive. The curves show the characteristic nominal speed at twice the nominal speed and at 0.2 x the nominal speed. At lower speed, the ETR cuts o at lower heat due to less cooling of the motor. In that way, the motor is protected from being overheated even at low speed. The ETR feature calculates the motor temperature based on actual current and speed. The calculated temperature is visible as a
The drive follows a variable V/Hz curve to provide full motor torque even at reduced speeds. Full output torque can coincide with the maximum designed operating speed of the motor. This drive diers from variable torque drives and constant torque drives. Variable torque drives provide reduced motor torque at low speed. Constant torque drives provide excess voltage, heat, and motor noise at less than full speed.
readout parameter in parameter 16-18 Motor Thermal.
3.3.7 Frequency Bypass
3.3.4 Mains Drop-out
During a mains drop-out, the drive keeps running until the DC-link voltage drops below the minimum stop level. The minimum stop level is typically 15% below the lowest rated supply voltage. The mains voltage before the drop­out and the motor load determine how long it takes for the drive to coast.
MG06K102 Danfoss A/S © 03/2019 All rights reserved. 11
In some applications, the system can have operational speeds that create a mechanical resonance. This mechanical resonance can generate excessive noise and possibly damage mechanical components in the system. The drive has 4 programmable bypass-frequency bandwidths. The bandwidths allow the motor to step over speeds that induce system resonance.
. . . . . .
Par. 13-11 Comparator Operator
Par. 13-43 Logic Rule Operator 2
Par. 13-51 SL Controller Event
Par. 13-52 SL Controller Action
130BB671.13
Coast Start timer Set Do X low Select set-up 2 . . .
Running Warning Torque limit Digital input X 30/2 . . .
= TRUE longer than..
. . . . . .
Product Overview and Featur... VLT® AutomationDrive FC 361
3.3.8 Motor Preheat
To preheat a motor in a cold or damp environment, a small amount of DC current can be trickled continuously into the motor to protect it from condensation and cold starts. This function can eliminate the need for a space heater.
33
3.3.9 Programmable Set-ups
The drive has 4 set-ups that can be independently programmed. Using multi-setup, it is possible to switch between independently programmed functions activated by digital inputs or a serial command. Independent set-ups are used, for example, to change references, or for day/ night or summer/winter operation, or to control multiple motors. The LCP shows the active set-up.
Set-up data can be copied from drive to drive by downloading the information from the removable LCP.
3.3.10 Smart Logic Control (SLC)
Smart logic control (SLC) is a sequence of user-dened actions (see parameter 13-52 SL Controller Action [x]) executed by the SLC when the associated user-dened event (see parameter 13-51 SL Controller Event [x]) is evaluated as TRUE by the SLC. The condition for an event can be a particular status, or that the output from a logic rule or a comparator operand becomes TRUE. The condition leads to an associated action as shown in Illustration 3.2.
Illustration 3.2 SLC Event and Action
Events and actions are each numbered and linked in pairs (states), which means that when event [0] is fullled (attains the value TRUE), action [0] is executed. After the 1 action is executed, the conditions of the next event are evaluated. If this event is evaluated as true, then the corresponding action is executed. Only 1 event is evaluated at any time. If an event is evaluated as false, nothing happens in the SLC during the current scan interval and no other events are evaluated. When the SLC starts, it only evaluates event [0] during each scan interval. Only when event [0] is evaluated as true, the SLC executes action [0] and starts evaluating the next event. It is possible to program 1–20 events and actions. When the last event/action has been executed, the sequence starts over again from event [0]/action [0]. Illustration 3.3 shows an example with 4 event/actions:
st
12 Danfoss A/S © 03/2019 All rights reserved. MG06K102
130BA062.14
State 1 13-51.0 13-52.0
State 2 13-51.1 13-52.1
Start event P13-01
State 3 13-51.2 13-52.2
State 4 13-51.3 13-52.3
Stop event P13-02
Stop event P13-02
Stop event P13-02
Par. 13-11 Comparator Operator
=
TRUE longer than.
. . .
. . .
Par. 13-10 Comparator Operand
Par. 13-12 Comparator Value
130BB672.10
. . . . . .
. . . . . .
Par. 13-43 Logic Rule Operator 2
Par. 13-41 Logic Rule Operator 1
Par. 13-40 Logic Rule Boolean 1
Par. 13-42 Logic Rule Boolean 2
Par. 13-44 Logic Rule Boolean 3
130BB673.10
Product Overview and Featur... Design Guide
Illustration 3.3 Order of Execution when 4 Events/Actions are
Programmed
Comparators
Comparators are used for comparing continuous variables (output frequency, output current, analog input, and so on) to xed preset values.
3.4 Dynamic Braking Overview
Dynamic braking slows the motor using 1 of the following methods:
AC brake
The brake energy is distributed in the motor by changing the loss conditions in the motor (parameter 2-10 Brake Function = [2]). The AC brake function cannot be used in applications with high cycling frequency since this situation overheats the motor.
DC brake
An overmodulated DC current added to the AC current works as an eddy current brake (parameter 2-02 DC Braking Time 0 s).
3 3
Illustration 3.4 Comparators
Logic rules
Combine up to 3 boolean inputs (TRUE/FALSE inputs) from timers, comparators, digital inputs, status bits, and events using the logical operators AND, OR, and NOT.
Illustration 3.5 Logic Rules
MG06K102 Danfoss A/S © 03/2019 All rights reserved. 13
130BG823.10
225 mm (8.9 in)
225 mm (8.9 in)
Product Overview and Featur... VLT® AutomationDrive FC 361
3.5 Back-channel Cooling Overview
A unique back-channel duct passes cooling air over the heat sinks with minimal air passing through the electronics area.
There is an IP54/Type 12 seal between the back-channel cooling duct and the electronics area of the VLT® drive. This back­channel cooling allows 90% of the heat losses to be exhausted directly outside the enclosure. This design improves reliability and prolongs component life by dramatically reducing interior temperatures and contamination of the electronic
33
components. Dierent back-channel cooling kits are available to redirect the airow based on individual needs.
3.5.1 Airow for J8 & J9 Enclosures
Illustration 3.6 Standard Airow Conguration for Enclosures J8 and J9
14 Danfoss A/S © 03/2019 All rights reserved. MG06K102
Options and Accessories Ove... Design Guide
4 Options and Accessories Overview
4.1 Fieldbus Devices
This section describes the eldbus devices that are
available with the VLT® AutomationDrive FC 361 series. Using a eldbus device reduces system cost, delivers faster and more ecient communication, and provides an easier user interface. For ordering numbers, refer to chapter 10.2 Ordering Numbers for Options and Accessories.
4.1.1
VLT® PROFIBUS DP-V1 MCA 101
The VLT® PROFIBUS DP-V1 MCA 101 provides:
Wide compatibility, a high level of availability,
support for all major PLC vendors, and compati­bility with future versions.
Fast, ecient communication, transparent instal-
lation, advanced diagnosis, and parameterization and auto-conguration of process data via a GSD
le.
Acyclic parameterization using PROFIBUS DP-V1,
PROFIdrive, or Danfoss FC prole state machines.
4.1.2
VLT® PROFINET MCA 120
The VLT® PROFINET MCA 120 combines the highest performance with the highest degree of openness. The option is designed so that many of the features from the
VLT® PROFIBUS MCA 101 can be reused, minimizing user eort to migrate PROFINET and securing the investment in a PLC program.
Same PPO types as the VLT® PROFIBUS DP V1
MCA 101 for easy migration to PROFINET.
Built-in web server for remote diagnosis and
reading out of basic drive parameters.
Supports MRP.
Supports DP-V1. Diagnostic allows easy, fast, and
standardized handling of warning and fault information into the PLC, improving bandwidth in the system.
Implementation in accordance with Conformance
Class B.
Functional Extensions
4.2
This section describes the functional extension options that
are available with the VLT® AutomationDrive FC 361 series. For ordering numbers, refer to chapter 10.2 Ordering Numbers for Options and Accessories.
4.2.1
VLT® General Purpose I/O Module MCB 101
The VLT® General Purpose I/O Module MCB 101 oers an extended number of control inputs and outputs:
3 digital inputs 0–24 V: Logic 0 < 5 V; Logic 1 >
10 V.
2 analog inputs 0–10 V: Resolution 10 bits plus
sign.
2 digital outputs NPN/PNP push-pull.
1 analog output 0/4–20 mA.
Spring-loaded connection.
4.2.2
VLT® Encoder Input MCB 102
The MCB 102 option oers the possibility to connect various types of incremental and absolute encoders. The connected encoder can be used for closed-loop speed control and closed-loop ux motor control.
The following encoder types are supported:
5 V TTL (RS 422).
1VPP SinCos.
4.2.3
VLT® Resolver Option MCB 103
The MCB 103 option enables connection of a resolver to provide speed feedback from the motor.
Primary voltage: 2–8 V
Primary frequency: 2.0–15 kHz.
Primary maximum current: 50 mA rms.
Secondary input voltage: 4 V
Spring-loaded connection.
rms
.
.
rms
4 4
MG06K102 Danfoss A/S © 03/2019 All rights reserved. 15
Specications VLT® AutomationDrive FC 361
5 Specications
5.1 Electrical Data, 380-480 V
VLT® AutomationDrive FC 361
High/normal overload NO HO NO HO NO HO NO
(High overload=150% current during 60 s, normal
overload=110% current during 60 s)
Typical shaft output at 400 V [kW] 90 90 110 110 132 132 160
Typical shaft output at 460 V [hp] 125 125 150 150 200 200 250
55
Enclosure size J8
Output current (3-phase)
Continuous (at 400 V) [A] 177 177 212 212 260 260 315
Intermittent (60 s overload) (at 400 V) [A] 195 266 233 318 286 390 347
Continuous (at 460 V) [A] 160 160 190 190 240 240 302
Intermittent (60 s overload) (at 460 V) [kVA] 176 240 209 285 264 360 332
Continuous kVA (at 400 V) [kVA] 123 123 147 147 180 180 218
Continuous kVA (at 460 V) [kVA] 127 127 151 151 191 191 241
Maximum input current
Continuous (at 400 V) [A] 171 171 204 204 251 251 304
Continuous (at 460 V) [A] 154 154 183 183 231 231 291
Maximum number and size of cables per phase
Mains and motor [mm2 (AWG)]
Maximum external mains fuses [A]
Estimated power loss at 400 V [W]
Estimated power loss at 460 V [W]
Eciency
Output frequency [Hz] 0–590
Heat sink overtemperature trip [°C (°F)]
Weight, enclosure protection rating IP20 kg (lbs) 98 (216)
Eciency
Output frequency [Hz] 0–590
Heat sink overtemperature trip [°C (°F)]
Control card overtemperature trip [°C (°F)]
3)
3)
1)
2), 3)
2), 3)
N90K N110 N132 N160
2x95 (2x3/0)
315 315 350 400
2031 2031 2559 2289 2954 2923 3770
1828 1828 2261 2051 2724 2089 3628
0.98
110 (230)
0.98
110 (230)
75 (167)
Table 5.1 Electrical Data for Enclosures J8, Mains Supply 3x380–480 V AC
1) For fuse ratings, see chapter 7.5 Fuses and Circuit Breakers.
2) Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions). These
values are based on a typical motor eciency (IE/IE3 border line). Lower eciency motors add to the power loss in the drive. Applies to
dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control
card power consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-
eciency-directive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for
slots A and B each add only 4 W.
3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Eciency measured at nominal current. For energy
eciency class, see chapter 5.4 Ambient Conditions. For part load losses, see drives.danfoss.com/knowledge-center/energy-eciency-directive/#/.
16 Danfoss A/S © 03/2019 All rights reserved. MG06K102
Specications Design Guide
VLT® AutomationDrive FC 361
High/normal overload HO NO HO NO HO NO
(High overload=150% current during 60 s, normal
overload=110% current during 60 s)
Typical shaft output at 400 V [kW] 160 200 200 250 250 315
Typical shaft output at 460 V [hp] 250 300 300 350 350 450
Enclosure size J9
Output current (3-phase)
Continuous (at 400 V) [A] 315 395 395 480 480 588
Intermittent (60 s overload) (at 400 V) [A]
Continuous (at 460 V) [A] 302 361 361 443 443 535
Intermittent (60 s overload) (at 460 V) [kVA] 453 397 542 487 665 589
Continuous kVA (at 400 V) [kVA] 218 274 274 333 333 407
Continuous kVA (at 460 V) [kVA] 241 288 288 353 353 426
Maximum input current
Continuous (at 400 V) [A] 304 381 381 463 463 567
Continuous (at 460 V) [A] 291 348 348 427 427 516
Maximum number and size of cables per phase
Mains and motor [mm2 (AWG)]
Maximum external mains fuses [A]
Estimated power loss at 400 V [W]
Estimated power loss at 460 V [W]
Eciency
Output frequency [Hz] 0–590
Heat sink overtemperature trip [°C (°F)]
Weight, enclosure protection rating IP20 kg (lbs) 164 (362)
Eciency
Output frequency [Hz] 0–590
Heat sink overtemperature trip [°C (°F)]
Control card overtemperature trip [°C (°F)]
3)
3)
1)
2), 3)
2), 3)
N200 N250 N315
473 435 593 528 720 647
2x185 (2x350 mcm)
550 630 800
3093 4116 4039 5137 5004 6674
2872 3569 3575 4566 4458 5714
0.98
110 (230)
0.98
110 (230)
80 (176)
5 5
Table 5.2 Electrical Data for Enclosures J9, Mains Supply 3x380–480 V AC
1) For fuse ratings, see chapter 7.5 Fuses and Circuit Breakers.
±
2) Typical power loss is at normal conditions and expected to be within
values are based on a typical motor eciency (IE/IE3 border line). Lower eciency motors add to the power loss in the drive. Applies to
dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control
card power consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-
eciency-directive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for
slots A and B each add only 4 W.
3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Eciency measured at nominal current. For energy
eciency class, see chapter 5.4 Ambient Conditions. For part load losses, see drives.danfoss.com/knowledge-center/energy-eciency-directive/#/.
15% (tolerance relates to variety in voltage and cable conditions). These
MG06K102 Danfoss A/S © 03/2019 All rights reserved. 17
Specications VLT® AutomationDrive FC 361
5.2 Mains Supply
Mains supply (L1, L2, L3) Supply voltage 380–480 V ±10%
Mains voltage low/mains voltage drop-out: During low mains voltage or a mains drop-out, the drive continues until the DC-link voltage drops below the minimum stop level, which corresponds typically to 15% below the lowest rated supply voltage of the drive. Power-up and full torque cannot be expected at mains voltage lower than 10% below the lowest rated supply voltage of the drive.
Supply frequency 50/60 Hz ±5%
Maximum imbalance temporary between mains phases 3.0% of rated supply voltage True power factor (λ) ≥0.9 nominal at rated load
55
Displacement power factor (cos Φ) near unity (>0.98) Switching on input supply L1, L2, L3 (power-ups) Maximum 1 time/2 minute Environment according to EN60664-1 Overvoltage category III/pollution degree 2
The drive is suitable for use on a circuit capable of delivering up to 100 kA short circuit current rating (SCCR) at 480/600 V.
1) Calculations based on IEC61800-3.
1)
5.3 Motor Output and Motor Data
Motor output (U, V, W) Output voltage 0–100% of supply voltage
Output frequency 0–590 Hz Output frequency in ux mode 0–300 Hz Switching on output Unlimited Ramp times 0.01–3600 s
1) Dependent on voltage and power.
1)
Torque characteristics
Starting torque (constant torque) Maximum 150% for 60 s
Overload torque (constant torque) Maximum 150% for 60 s
1) Percentage relates to the nominal current of the drive.
2) Once every 10 minutes.
1), 2)
1), 2)
5.4 Ambient Conditions
Environment J8/J9 enclosure IP20/Chassis Vibration test (standard/ruggedized) 0.7 g/1.0 g Relative humidity 5%–95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation) Aggressive environment (IEC 60068-2-43) H2S test Class Kd Aggressive gases (IEC 60721-3-3) Class 3C3 Test method according to IEC 60068-2-43 H2S (10 days) Ambient temperature (at SFAVM switching mode)
- with derating Maximum 55 °C (131 °F)
- with full output power of typical EFF2 motors (up to 90% output current) Maximum 50 °C (122 °F)
- at full continuous FC output current Maximum 45 °C (113 °F)
Minimum ambient temperature during full-scale operation 0 °C (32 °F) Minimum ambient temperature at reduced performance -10 °C (14 °F) Temperature during storage/transport -25 to +65/70 °C (13 to 149/158 °F) Maximum altitude above sea level without derating 1000 m (3281 ft) Maximum altitude above sea level with derating 3000 m (9842 ft)
1) For more information on derating, see chapter 6.6 Derating.
EMC standards, Emission EN 61800-3
1)
1)
1)
18 Danfoss A/S © 03/2019 All rights reserved. MG06K102
Specications Design Guide
EMC standards, Immunity EN 61800-3
Energy eciency class
1) Determined according to EN 50598-2 at:
Rated load.
90% rated frequency.
Switching frequency factory setting.
Switching pattern factory setting.
1)
IE2
5.5 Cable Specications
Cable lengths and cross-sections for control cables Maximum motor cable length, shielded 150 m (492 ft) Maximum motor cable length, unshielded 300 m (984 ft)
Maximum cross-section to motor and mains See chapter 5.1 Electrical Data, 380-480 V
Maximum cross-section to control terminals, rigid wire 1.5 mm2/16 AWG (2x0.75 mm2)
Maximum cross-section to control terminals, exible cable 1 mm2/18 AWG
Maximum cross-section to control terminals, cable with enclosed core 0.5 mm2/20 AWG
Minimum cross-section to control terminals 0.25 mm2/23 AWG
1) For power cables, see electrical data in chapter 5.1 Electrical Data, 380-480 V.
5.6 Control Input/Output and Control Data
Digital inputs Programmable digital inputs 4 (6)
Terminal number 18, 19, 271), 291), 32, 33 Logic PNP or NPN Voltage level 0–24 V DC Voltage level, logic 0 PNP <5 V DC Voltage level, logic 1 PNP >10 V DC Voltage level, logic 0 NPN >19 V DC Voltage level, logic 1 NPN <14 V DC Maximum voltage on input 28 V DC Input resistance, R
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminals 27 and 29 can also be programmed as outputs.
i
Approximately 4 kΩ
5 5
1)
Analog inputs Number of analog inputs 2 Terminal number 53, 54 Modes Voltage or current Mode select Switches A53 and A54 Voltage mode Switch A53/A54=(U) Voltage level 0 V to +10 V (scaleable) Input resistance, R Maximum voltage ±20 V Current mode Switch A53/A54=(I) Current level 0/4 to 20 mA (scaleable) Input resistance, R Maximum current 30 mA Resolution for analog inputs 10 bit (+ sign) Accuracy of analog inputs Maximum error 0.5% of full scale Bandwidth 100 Hz
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
MG06K102 Danfoss A/S © 03/2019 All rights reserved. 19
i
i
Approximately 10 kΩ
Approximately 200 Ω
Mains
Functional isolation
PELV isolation
Motor
DC-bus
High voltage
Control
+24 V
RS485
18
37
130BA117.10
Specications VLT® AutomationDrive FC 361
Illustration 5.1 PELV Isolation
55
Pulse inputs Programmable pulse inputs 2 Terminal number pulse 29, 33 Maximum frequency at terminal 29, 33 (push-pull driven) 110 kHz Maximum frequency at terminal 29, 33 (open collector) 5 kHz Minimum frequency at terminal 29, 33 4 Hz Voltage level See Digital Inputs in chapter 5.6 Control Input/Output and Control Data Maximum voltage on input 28 V DC Input resistance, R
i
Pulse input accuracy (0.1–1 kHz) Maximum error: 0.1% of full scale
Analog output Number of programmable analog outputs 1 Terminal number 42 Current range at analog output 0/4–20 mA Maximum resistor load to common at analog output 500 Accuracy on analog output Maximum error: 0.8% of full scale Resolution on analog output 8 bit
The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control card, RS485 serial communication Terminal number 68 (P, TX+, RX+), 69 (N, TX-, RX-) Terminal number 61 Common for terminals 68 and 69
The RS485 serial communication circuit is functionally separated from other central circuits and galvanically isolated from the supply voltage (PELV).
Approximately 4 k
Digital output Programmable digital/pulse outputs 2
Terminal number 27, 29 Voltage level at digital/frequency output 0–24 V Maximum output current (sink or source) 40 mA Maximum load at frequency output 1 k Maximum capacitive load at frequency output 10 nF Minimum output frequency at frequency output 0 Hz Maximum output frequency at frequency output 32 kHz Accuracy of frequency output Maximum error: 0.1% of full scale Resolution of frequency outputs 12 bit
1) Terminals 27 and 29 can also be programmed as inputs.
The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
20 Danfoss A/S © 03/2019 All rights reserved. MG06K102
1)
Specications Design Guide
Control card, 24 V DC output Terminal number 12, 13 Maximum load 200 mA
The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital inputs and outputs.
Relay outputs Programmable relay outputs 2
Maximum cross-section to relay terminals 2.5 mm2 (12 AWG)
Minimum cross-section to relay terminals 0.2 mm2 (30 AWG) Length of stripped wire 8 mm (0.3 in) Relay 01 terminal number 1–3 (break), 1–2 (make)
Maximum terminal load (AC-1)1) on 1–2 (NO) (Resistive load)
Maximum terminal load (AC-15)1) on 1–2 (NO) (Inductive load @ cosφ 0.4) 240 V AC, 0.2 A
Maximum terminal load (DC-1)1) on 1–2 (NO) (Resistive load) 80 V DC, 2 A
Maximum terminal load (DC-13)1) on 1–2 (NO) (Inductive load) 24 V DC, 0.1 A
Maximum terminal load (AC-1)1) on 1–3 (NC) (Resistive load) 240 V AC, 2 A
Maximum terminal load (AC-15)1) on 1–3 (NC) (Inductive load @ cosφ 0.4) 240 V AC, 0.2 A
Maximum terminal load (DC-1)1) on 1–3 (NC) (Resistive load) 50 V DC, 2 A
Maximum terminal load (DC-13)1) on 1–3 (NC) (Inductive load) 24 V DC, 0.1 A Minimum terminal load on 1–3 (NC), 1–2 (NO) 24 V DC 10 mA, 24 V AC 2 mA Environment according to EN 60664-1 Overvoltage category III/pollution degree 2 Relay 02 terminal number 4–6 (break), 4–5 (make)
Maximum terminal load (AC-1)1) on 4–5 (NO) (Resistive load)
Maximum terminal load (AC-15)1) on 4–5 (NO) (Inductive load @ cosφ 0.4) 240 V AC, 0.2 A
Maximum terminal load (DC-1)1) on 4–5 (NO) (Resistive load) 80 V DC, 2 A
Maximum terminal load (DC-13)1) on 4–5 (NO) (Inductive load) 24 V DC, 0.1 A
Maximum terminal load (AC-1)1) on 4–6 (NC) (Resistive load) 240 V AC, 2 A
Maximum terminal load (AC-15)1) on 4–6 (NC) (Inductive load @ cosφ 0.4) 240 V AC, 0.2 A
Maximum terminal load (DC-1)1) on 4–6 (NC) (Resistive load) 50 V DC, 2 A
Maximum terminal load (DC-13)1) on 4–6 (NC) (Inductive load) 24 V DC, 0.1 A Minimum terminal load on 4–6 (NC), 4–5 (NO) 24 V DC 10 mA, 24 V AC 2 mA Environment according to EN 60664-1 Overvoltage category III/pollution degree 2
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
1) IEC 60947 part 4 and 5.
2) Overvoltage Category II.
2), 3)
2), 3)
400 V AC, 2 A
400 V AC, 2 A
5 5
Control card, +10 V DC output Terminal number 50 Output voltage 10.5 V ±0.5 V Maximum load 25 mA
The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control characteristics Resolution of output frequency at 0–1000 Hz ±0.003 Hz System response time (terminals 18, 19, 27, 29, 32, 33) 2 m/s Speed control range (open loop) 1:100 of synchronous speed Speed accuracy (open loop) 30–4000 RPM: Maximum error of ±8 RPM
All control characteristics are based on a 4-pole asynchronous motor.
Control card performance Scan interval 5 M/S
MG06K102 Danfoss A/S © 03/2019 All rights reserved. 21
Specications VLT® AutomationDrive FC 361
Control card, USB serial communication USB standard 1.1 (full speed) USB plug USB type B device plug
NOTICE
Connection to PC is carried out via a standard host/device USB cable. The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. The USB connection is not galvanically isolated from ground. Use only isolated laptop/PC as connection to the USB connector on the drive or an isolated USB cable/converter.
5.7 Enclosure Weights
55
Enclosure 380–480 V
J8 98 (216)
J9 164 (362)
Table 5.3 Enclosure J8–J9 Weights, kg (lb)
22 Danfoss A/S © 03/2019 All rights reserved. MG06K102
130BF322.10
61 (2.4)
128 (5.0)
495 (19.5)
660 (26.0)
Specications Design Guide
5.8 Exterior and Terminal Dimensions
5.8.1 J8 Exterior Dimensions
5 5
Illustration 5.2 Front View of J8
MG06K102 Danfoss A/S © 03/2019 All rights reserved. 23
148 (5.8)
20 (0.8)
130BF801.10
844 (33.2)
39 (1.5)
375 (14.8)
82 (3.2)
18 (0.7)
Specications VLT® AutomationDrive FC 361
55
Illustration 5.3 Side View of J8
24 Danfoss A/S © 03/2019 All rights reserved. MG06K102
656 (25.8)
200 (7.9)
200 (7.9)
130 (5.1)
889 (35.0)
909 (35.8)
844 (33.2)
78 (3.1)
123 (4.8)
250 (9.8)
180 (7.1)
A
B
A
B
33 (1.3)
11 (0.4)
25 (1.0)
11 (0.4)
20 (0.8)
9 (0.3)
24 (0.9)
25 (1.0)
M10
M10
130BF802.10
Specications Design Guide
5 5
Illustration 5.4 Back View of J8
MG06K102 Danfoss A/S © 03/2019 All rights reserved. 25
e30bg615.10
83 (3.3)
0.0
188 (7.4)
22 (0.9)
62 (2.4)
101 (4.0)
145 (5.7)
184 (7.2)
223 (8.8)
0.0
1
2
3
Specications VLT® AutomationDrive FC 361
5.8.2 J8 Terminal Dimensions
55
1 Mains terminals 3 Ground terminals
2 Motor terminals
Illustration 5.5 J8 Terminal Dimensions (Front View)
26 Danfoss A/S © 03/2019 All rights reserved. MG06K102
M10
13 (0.5)
32 (1.3)
59 (2.3)
10 (0.4)
244 (9.6)
272 (10.7)
0.0
0.0
1
2
4
3
5
M10
13 (0.5)
32 (1.3)
145 (5.7)
182 (7.2)
3X M8x18
0
0
e30bg573.10
Specications Design Guide
5 5
1 and 4 Mains terminals 2 and 5 Motor terminals
3 Ground terminals
Illustration 5.6 J8 Terminal Dimensions (Side Views)
MG06K102 Danfoss A/S © 03/2019 All rights reserved. 27
130BF323.10
176 (6.9)
611 (24.1)
59 (2.3)
868 (34.2)
55
Specications VLT® AutomationDrive FC 361
5.8.3 J9 Exterior Dimensions
Illustration 5.7 Front View of J9
28 Danfoss A/S © 03/2019 All rights reserved. MG06K102
Loading...
+ 72 hidden pages