The design guide provides technical information to
understand the capabilities of the drive for integration into
motor control and monitoring systems.
VLT® is a registered trademark.
1.2 Additional Resources
Other resources are available to understand advanced
drive functions and programming.
The operating guide provides detailed information
•
for the installation and start-up of the drive.
The programming guide provides greater detail on
•
working with parameters and many application
examples.
Instructions for operation with optional
•
equipment.
Supplementary publications and manuals are available
from Danfoss. See
%3Adocumentation%2Csegment%3Adds for listings.
Document and Software Version
1.3
This manual is regularly reviewed and updated. All
suggestions for improvement are welcome. Table 1.1 shows
the version of the manual and the corresponding software
version.
Manual versionRemarksSoftware version
MG06K1xxFirst edition.1.0x
Table 1.1 Manual and Software Version
www.danfoss.com/en/search/?lter=type
Approvals and Certications
1.4
Drives are designed in compliance with the directives
described in this section.
1.4.1 CE Mark
The CE mark (Conformité Européenne) indicates that the
product manufacturer conforms to all applicable EU
directives.
The EU directives applicable to the design and
manufacture of drives are:
The Low Voltage Directive.
•
The EMC Directive.
•
The Machinery Directive (for units with an
•
integrated safety function).
The CE mark is intended to eliminate technical barriers to
free trade between the EC and EFTA states inside the ECU.
The CE mark does not regulate the quality of the product.
Technical specications cannot be deduced from the CE
mark.
1.4.2 Low Voltage Directive
Drives are classied as electronic components and must be
CE-labeled in accordance with the Low Voltage Directive.
The directive applies to all electrical equipment in the 50–
1000 V AC and the 75–1500 V DC voltage ranges.
The directive mandates that the equipment design must
ensure the safety and health of people and livestock, and
the preservation of material by ensuring the equipment is
properly installed, maintained, and used as intended.
Danfoss CE labels comply with the Low Voltage Directive,
and Danfoss provides a declaration of conformity upon
request.
Electromagnetic compatibility (EMC) means that electromagnetic interference between pieces of equipment does
not hinder their performance. The basic protection
requirement of the EMC Directive 2014/30/EU states that
devices that generate electromagnetic interference (EMI) or
whose operation could be aected by EMI must be
designed to limit the generation of electromagnetic
interference and shall have a suitable degree of immunity
to EMI when properly installed, maintained, and used as
intended.
A drive can be used as stand-alone device or as part of a
more complex installation. Devices in either of these cases
must bear the CE mark. Systems must not be CE-marked
but must comply with the basic protection requirements of
the EMC directive.
Indicates a potentially hazardous situation that could
result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation that could
result in minor or moderate injury. It can also be used to
alert against unsafe practices.
NOTICE
Indicates important information, including situations that
can result in damage to equipment or property.
2.2 Qualied Personnel
Only qualied personnel are allowed to install or operate
this equipment.
WARNING
DISCHARGE TIME
The drive contains DC-link capacitors, which can remain
charged even when the drive is not powered. High
voltage can be present even when the warning LED
indicator lights are o. Failure to wait the specied time
after power has been removed before performing service
or repair work can result in death or serious injury.
Stop the motor.
•
Disconnect AC mains and remote DC-link power
•
supplies, including battery back-ups, UPS, and
DC-link connections to other drives.
Disconnect or lock PM motor.
•
Wait for the capacitors to discharge fully. The
•
minimum waiting time is 20 minutes.
Before performing any service or repair work,
•
use an appropriate voltage measuring device to
make sure that the capacitors are fully
discharged.
Qualied personnel are dened as trained sta, who are
authorized to install, commission, and maintain equipment,
systems, and circuits in accordance with pertinent laws and
regulations. Also, the personnel must be familiar with the
instructions and safety measures described in this manual.
Safety Precautions
2.3
WARNING
HIGH VOLTAGE
Drives contain high voltage when connected to AC mains
input, DC supply, load sharing, or permanent motors.
Failure to use qualied personnel to install, start up, and
maintain the drive can result in death or serious injury.
Only qualied personnel must install, start up,
•
and maintain the drive.
WARNING
LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to ground the
drive properly can result in death or serious injury.
Product Overview and Featur...VLT® AutomationDrive FC 361
3.2 Automated Operational Features
Automated operational features are active when the drive
is operating. Most of them require no programming or setup. The drive has a range of built-in protection functions
to protect itself and the motor when it runs.
33
For details of any set-up required, in particular motor
parameters, refer to the programming guide.
3.2.1 Short-circuit Protection
The overvoltage can be handled either using a brake
function (parameter 2-10 Brake Function) and/or using
overvoltage control (parameter 2-17 Over-voltage Control).
Brake functions
AC brake is an alternative to improving braking without
using a brake resistor. This function controls an overmagnetization of the motor when the motor is acting as a
generator. Increasing the electrical losses in the motor
allows the OVC function to increase the braking torque
without exceeding the overvoltage limit.
NOTICE
Motor (phase-to-phase)
The drive is protected against short circuits on the motor
side by current measurement in each of the 3 motor
phases. A short circuit between 2 output phases causes an
overcurrent in the inverter. The inverter is turned o when
the short circuit current exceeds the allowed value (Alarm16, Trip Lock).
Mains side
A drive that works correctly limits the current it can draw
from the supply. Still, it is recommended to use fuses
and/or circuit breakers on the supply side as protection if
there is component break-down inside the drive (1st fault).
NOTICE
To ensure compliance with IEC 60364 for CE, it is
mandatory to use fuses and/or circuit breakers.
AC brake is not as eective as dynamic braking with a
resistor.
Overvoltage control (OVC)
By automatically extending the ramp-down time, OVC
reduces the risk of the drive tripping due to an
overvoltage on the DC link.
NOTICE
OVC can be activated for a PM motor.
NOTICE
Do not enable OVC in hoisting applications.
3.2.3 Missing Motor Phase Detection
3.2.2 Overvoltage Protection
Motor-generated overvoltage
The voltage in the DC link is increased when the motor
acts as a generator. This situation occurs in the following
cases:
The load rotates the motor at constant output
•
frequency from the drive, that is, the load
generates energy.
During deceleration (ramp-down) if the inertia
•
moment is high, the friction is low, and the rampdown time is too short for the energy to be
dissipated as a loss throughout the drive system.
Incorrect slip compensation setting causing
•
higher DC-link voltage.
Back EMF from PM motor operation. If coasted at
•
high RPM, the PM motor back EMF can
potentially exceed the maximum voltage
tolerance of the drive and cause damage. To help
prevent this situation, the value of
parameter 4-19 Max Output Frequency is automatically limited based on an internal calculation
based on the value of parameter 1-40 Back EMF at1000 RPM, parameter 1-25 Motor Nominal Speed,
and parameter 1-39 Motor Poles.
The missing motor phase function (parameter 4-58 MissingMotor Phase Function) is enabled by default to avoid motor
damage if a motor phase is missing. The default setting is
1000 ms, but it can be adjusted for faster detection.
3.2.4 Supply Voltage Imbalance Detection
Operation under severe supply voltage imbalance reduces
the lifetime of the motor and drive. If the motor is
operated continuously near nominal load, conditions are
considered severe. The default setting trips the drive if
there is supply voltage imbalance
(parameter 14-12 Response to Mains Imbalance).
3.2.5 Switching on the Output
Adding a switch to the output between the motor and the
drive is allowed, however fault messages can appear.
The torque limit feature protects the motor against
overload, independent of the speed. Torque limit is
controlled in parameter 4-16 Torque Limit Motor Mode andparameter 4-17 Torque Limit Generator Mode. The time
before the torque limit warning trips is controlled in
parameter 14-25 Trip Delay at Torque Limit.
Current limit
The current limit is controlled in parameter 4-18 Current
Limit, and the time before the drive trips is controlled in
parameter 14-24 Trip Delay at Current Limit.
Speed limit
Minimum speed limit: Parameter 4-11 Motor Speed Low
Limit [RPM] or parameter 4-12 Motor Speed Low Limit [Hz]
limit the minimum operating speed range of the drive.
Maximum speed limit: Parameter 4-13 Motor Speed HighLimit [RPM] or parameter 4-19 Max Output Frequency limits
the maximum output speed that the drive can provide.
Electronic thermal relay (ETR)
ETR is an electronic feature that simulates a bimetal relay
based on internal measurements. The characteristic is
shown in Illustration 3.1.
Voltage limit
The inverter turns
link capacitors when a certain hard-coded voltage level is
reached.
Overtemperature
The drive has built-in temperature sensors and reacts
immediately to critical values via hard-coded limits.
o to protect the transistors and the DC
3.2.7 Locked Rotor Protection
There can be situations when the rotor is locked due to
excessive load or other factors. The locked rotor cannot
produce enough cooling, which in turn can overheat the
motor winding. The drive is able to detect the locked rotor
situation with PM VVC+ control (parameter 30-22 LockedRotor Protection).
3.2.8 Automatic Derating
The drive constantly checks for the following critical levels:
High temperature on the control card or heat
•
sink.
High motor load.
•
High DC-link voltage.
•
Low motor speed.
•
As a response to a critical level, the drive adjusts the
switching frequency. For high internal temperatures and
low motor speed, the drive can also force the PWM pattern
to SFAVM.
NOTICE
The automatic derating is dierent when
parameter 14-55 Output Filter is set to [2] Sine-Wave Filter
Fixed.
3.2.9 Automatic Energy Optimization
Automatic energy optimization (AEO) directs the drive to
monitor the load on the motor continuously and adjust
the output voltage to maximize eciency. Under light
load, the voltage is reduced and the motor current is
minimized. The motor benets from:
Increased eciency.
•
Reduced heating.
•
Quieter operation.
•
There is no need to select a V/Hz curve because the drive
automatically adjusts motor voltage.
3.2.10 Automatic Switching Frequency
Modulation
The drive generates short electrical pulses to form an AC
wave pattern. The switching frequency is the rate of these
pulses. A low switching frequency (slow pulsing rate)
causes audible noise in the motor, making a higher
switching frequency preferable. A high switching
frequency, however, generates heat in the drive that can
limit the amount of current available to the motor.
Automatic switching frequency modulation regulates these
conditions automatically to provide the highest switching
frequency without overheating the drive. By providing a
regulated high switching frequency, it quiets motor
operating noise at slow speeds, when audible noise control
is critical, and produces full output power to the motor
when required.
3.2.11 Automatic Derating for High
Switching Frequency
The drive is designed for continuous, full-load operation at
switching frequencies between 1.5–2 kHz for 380–480 V.
The frequency range depends on power size and voltage
rating. A switching frequency exceeding the maximum
allowed range generates increased heat in the drive and
requires the output current to be derated.
An automatic feature of the drive is load-dependent
switching frequency control. This feature allows the motor
to benet from as high a switching frequency as the load
allows.
Product Overview and Featur...VLT® AutomationDrive FC 361
3.2.12 Power Fluctuation Performance
The drive withstands mains uctuations such as:
Transients.
•
Momentary drop-outs.
•
33
The drive automatically compensates for input voltages
±10% from the nominal to provide full rated motor voltage
and torque. With auto restart selected, the drive automatically powers up after a voltage trip. With ying start, the
drive synchronizes to motor rotation before start.
Short voltage drops.
•
Surges.
•
3.2.13 Resonance Damping
Resonance damping eliminates the high-frequency motor
resonance noise. Automatic or manually selected frequency
damping is available.
3.2.14 Temperature-controlled Fans
Sensors in the drive regulate the operation of the internal
cooling fans. Often, the cooling fans do not run during low
load operation, or when in sleep mode or standby. These
sensors reduce noise, increase eciency, and extend the
operating life of the fan.
3.2.15 EMC Compliance
Electromagnetic interference (EMI) and radio frequency
interference (RFI) are disturbances that can aect an
electrical circuit due to electromagnetic induction or
radiation from an external source. The drive is designed to
comply with the EMC product standard for drives IEC
61800-3 and the European standard EN 55011. Motor
cables must be shielded and properly terminated to
comply with the emission levels in EN 55011. For more
information regarding EMC performance, see
chapter 7.13.1 EMC Test Results.
The components that make up the galvanic isolation
are:
Supply, including signal isolation.
•
Gatedrive for the IGBTs, trigger transformers, and
•
optocouplers.
The output current Hall eect transducers.
•
3.3 Custom Application Features
Custom application functions are the most common
features programmed in the drive for enhanced system
performance. They require minimum programming or setup. See the programming guide for instructions on
activating these functions.
3.3.1 Automatic Motor Adaptation
Automatic motor adaptation (AMA) is an automated test
procedure used to measure the electrical characteristics of
the motor. AMA provides an accurate electronic model of
the motor, allowing the drive to calculate optimal
performance and eciency. Running the AMA procedure
also maximizes the automatic energy optimization feature
of the drive. AMA is performed without the motor rotating
and without uncoupling the load from the motor.
3.3.2 Built-in PID Controller
The built-in proportional, integral, derivative (PID)
controller eliminates the need for auxiliary control devices.
The PID controller maintains constant control of closedloop systems where regulated pressure, ow, temperature,
or other system requirements must be maintained.
The drive can use 2 feedback signals from 2 dierent
devices, allowing the system to be regulated with dierent
feedback requirements. The drive makes control decisions
by comparing the 2 signals to optimize system
performance.
3.3.3 Motor Thermal Protection
3.2.16 Galvanic Isolation of Control
Terminals
All control terminals and output relay terminals are galvanically isolated from mains power, which completely
protects the controller circuitry from the input current. The
output relay terminals require their own grounding. This
isolation meets the stringent protective extra-low voltage
(PELV) requirements for isolation.
To protect the application from serious damage, the drive
oers several dedicated features.
Torque limit
The torque limit protects the motor from being overloaded
independent of the speed. Torque limit is controlled in
parameter 4-16 Torque Limit Motor Mode and
parameter 4-17 Torque Limit Generator Mode.
Parameter 14-25 Trip Delay at Torque Limit controls the time
before the torque limit warning trips.
Current limit
Parameter 4-18 Current Limit controls the current limit, and
parameter 14-24 Trip Delay at Current Limit controls the
time before the current limit warning trips.
1.21.01.4
30
10
20
100
60
40
50
1.81.62.0
2000
500
200
400
300
1000
600
t [s]
175ZA052.12
f
OUT
= 2 x f
M,N
f
OUT
= 0.2 x f
M,N
f
OUT
= 1 x f
M,N
(par. 1-23)
IMN(par. 1-24)
I
M
Product Overview and Featur...Design Guide
Minimum speed limit
Parameter 4-12 Motor Speed Low Limit [Hz] sets the
minimum output speed that the drive can provide.
Maximum speed limit
Parameter 4-14 Motor Speed High Limit [Hz] or
parameter 4-19 Max Output Frequency sets the maximum
output speed that the drive can provide.
ETR (electronic thermal relay)
The drive ETR function measures the actual current, speed,
and time to calculate motor temperature. The function also
protects the motor from being overheated (warning or
trip). An external thermistor input is also available. ETR is
an electronic feature that simulates a bimetal relay based
on internal measurements. The characteristic is shown in
Illustration 3.1.
The drive can be congured (parameter 14-10 Mains Failure)
to dierent types of behavior during mains drop-out:
Trip lock once the DC-link is exhausted.
•
Coast with ying start whenever mains return
•
(parameter 1-73 Flying Start).
Kinetic back-up.
•
Controlled ramp down.
•
Flying start
This selection makes it possible to catch a motor that is
spinning freely due to a mains drop-out. This option is
relevant for centrifuges and fans.
Kinetic back-up
This selection ensures that the drive runs as long as there
is energy in the system. For short mains drop-out, the
operation is restored after mains return, without bringing
the application to a stop or losing control at any time.
Several variants of kinetic back-up can be selected.
Congure the behavior of the drive at mains drop-out in
parameter 14-10 Mains Failure and parameter 1-73 Flying
Start.
3.3.5 Automatic Restart
33
The drive can be programmed to restart the motor
automatically after a minor trip, such as momentary power
loss or uctuation. This feature eliminates the need for
manual resetting and enhances automated operation for
remotely controlled systems. The number of restart
Illustration 3.1 ETR
The X-axis shows the ratio between I
motor
and I
motor
attempts and the duration between attempts can be
limited.
3.3.6 Full Torque at Reduced Speed
nominal. The Y-axis shows the time in seconds before the
ETR cuts o and trips the drive. The curves show the
characteristic nominal speed at twice the nominal speed
and at 0.2 x the nominal speed.
At lower speed, the ETR cuts o at lower heat due to less
cooling of the motor. In that way, the motor is protected
from being overheated even at low speed. The ETR feature
calculates the motor temperature based on actual current
and speed. The calculated temperature is visible as a
The drive follows a variable V/Hz curve to provide full
motor torque even at reduced speeds. Full output torque
can coincide with the maximum designed operating speed
of the motor. This drive diers from variable torque drives
and constant torque drives. Variable torque drives provide
reduced motor torque at low speed. Constant torque
drives provide excess voltage, heat, and motor noise at less
than full speed.
readout parameter in parameter 16-18 Motor Thermal.
3.3.7 Frequency Bypass
3.3.4 Mains Drop-out
During a mains drop-out, the drive keeps running until the
DC-link voltage drops below the minimum stop level. The
minimum stop level is typically 15% below the lowest
rated supply voltage. The mains voltage before the dropout and the motor load determine how long it takes for
the drive to coast.
In some applications, the system can have operational
speeds that create a mechanical resonance. This
mechanical resonance can generate excessive noise and
possibly damage mechanical components in the system.
The drive has 4 programmable bypass-frequency
bandwidths. The bandwidths allow the motor to step over
speeds that induce system resonance.
. . .
. . .
Par. 13-11
Comparator Operator
Par. 13-43
Logic Rule Operator 2
Par. 13-51
SL Controller Event
Par. 13-52
SL Controller Action
130BB671.13
Coast
Start timer
Set Do X low
Select set-up 2
. . .
Running
Warning
Torque limit
Digital input X 30/2
. . .
=
TRUE longer than..
. . .
. . .
Product Overview and Featur...VLT® AutomationDrive FC 361
3.3.8 Motor Preheat
To preheat a motor in a cold or damp environment, a small
amount of DC current can be trickled continuously into the
motor to protect it from condensation and cold starts. This
function can eliminate the need for a space heater.
33
3.3.9 Programmable Set-ups
The drive has 4 set-ups that can be independently
programmed. Using multi-setup, it is possible to switch
between independently programmed functions activated
by digital inputs or a serial command. Independent set-ups
are used, for example, to change references, or for day/
night or summer/winter operation, or to control multiple
motors. The LCP shows the active set-up.
Set-up data can be copied from drive to drive by
downloading the information from the removable LCP.
3.3.10 Smart Logic Control (SLC)
Smart logic control (SLC) is a sequence of user-dened
actions (see parameter 13-52 SL Controller Action [x])
executed by the SLC when the associated user-dened
event (see parameter 13-51 SL Controller Event [x]) is
evaluated as TRUE by the SLC.
The condition for an event can be a particular status, or
that the output from a logic rule or a comparator operand
becomes TRUE. The condition leads to an associated action
as shown in Illustration 3.2.
Illustration 3.2 SLC Event and Action
Events and actions are each numbered and linked in pairs
(states), which means that when event [0] is fullled
(attains the value TRUE), action [0] is executed. After the 1
action is executed, the conditions of the next event are
evaluated. If this event is evaluated as true, then the
corresponding action is executed. Only 1 event is
evaluated at any time. If an event is evaluated as false,
nothing happens in the SLC during the current scan
interval and no other events are evaluated. When the SLC
starts, it only evaluates event [0] during each scan interval.
Only when event [0] is evaluated as true, the SLC executes
action [0] and starts evaluating the next event. It is
possible to program 1–20 events and actions.
When the last event/action has been executed, the
sequence starts over again from event [0]/action [0].
Illustration 3.3 shows an example with 4 event/actions:
Illustration 3.3 Order of Execution when 4 Events/Actions are
Programmed
Comparators
Comparators are used for comparing continuous variables
(output frequency, output current, analog input, and so on)
to xed preset values.
3.4 Dynamic Braking Overview
Dynamic braking slows the motor using 1 of the following
methods:
AC brake
•
The brake energy is distributed in the motor by
changing the loss conditions in the motor
(parameter 2-10 Brake Function = [2]). The AC
brake function cannot be used in applications
with high cycling frequency since this situation
overheats the motor.
DC brake
•
An overmodulated DC current added to the AC
current works as an eddy current brake
(parameter 2-02 DC Braking Time≠ 0 s).
33
Illustration 3.4 Comparators
Logic rules
Combine up to 3 boolean inputs (TRUE/FALSE inputs) from
timers, comparators, digital inputs, status bits, and events
using the logical operators AND, OR, and NOT.
Product Overview and Featur...VLT® AutomationDrive FC 361
3.5 Back-channel Cooling Overview
A unique back-channel duct passes cooling air over the heat sinks with minimal air passing through the electronics area.
There is an IP54/Type 12 seal between the back-channel cooling duct and the electronics area of the VLT® drive. This backchannel cooling allows 90% of the heat losses to be exhausted directly outside the enclosure. This design improves
reliability and prolongs component life by dramatically reducing interior temperatures and contamination of the electronic
33
components. Dierent back-channel cooling kits are available to redirect the airow based on individual needs.
3.5.1 Airow for J8 & J9 Enclosures
Illustration 3.6 Standard AirowConguration for Enclosures J8 and J9
This section describes the eldbus devices that are
available with the VLT® AutomationDrive FC 361 series.
Using a eldbus device reduces system cost, delivers faster
and more ecient communication, and provides an easier
user interface. For ordering numbers, refer to
chapter 10.2 Ordering Numbers for Options and Accessories.
4.1.1
VLT® PROFIBUS DP-V1 MCA 101
The VLT® PROFIBUS DP-V1 MCA 101 provides:
Wide compatibility, a high level of availability,
•
support for all major PLC vendors, and compatibility with future versions.
Fast, ecient communication, transparent instal-
•
lation, advanced diagnosis, and parameterization
and auto-conguration of process data via a GSD
le.
Acyclic parameterization using PROFIBUS DP-V1,
•
PROFIdrive, or Danfoss FC prole state machines.
4.1.2
VLT® PROFINET MCA 120
The VLT® PROFINET MCA 120 combines the highest
performance with the highest degree of openness. The
option is designed so that many of the features from the
VLT® PROFIBUS MCA 101 can be reused, minimizing user
eort to migrate PROFINET and securing the investment in
a PLC program.
Same PPO types as the VLT® PROFIBUS DP V1
•
MCA 101 for easy migration to PROFINET.
Built-in web server for remote diagnosis and
•
reading out of basic drive parameters.
Supports MRP.
•
Supports DP-V1. Diagnostic allows easy, fast, and
•
standardized handling of warning and fault
information into the PLC, improving bandwidth in
the system.
Implementation in accordance with Conformance
•
Class B.
Functional Extensions
4.2
This section describes the functional extension options that
are available with the VLT® AutomationDrive FC 361 series.
For ordering numbers, refer to chapter 10.2 OrderingNumbers for Options and Accessories.
4.2.1
VLT® General Purpose I/O Module
MCB 101
The VLT® General Purpose I/O Module MCB 101 oers an
extended number of control inputs and outputs:
3 digital inputs 0–24 V: Logic 0 < 5 V; Logic 1 >
•
10 V.
2 analog inputs 0–10 V: Resolution 10 bits plus
•
sign.
2 digital outputs NPN/PNP push-pull.
•
1 analog output 0/4–20 mA.
•
Spring-loaded connection.
•
4.2.2
VLT® Encoder Input MCB 102
The MCB 102 option oers the possibility to connect
various types of incremental and absolute encoders. The
connected encoder can be used for closed-loop speed
control and closed-loop ux motor control.
The following encoder types are supported:
5 V TTL (RS 422).
•
1VPP SinCos.
•
4.2.3
VLT® Resolver Option MCB 103
The MCB 103 option enables connection of a resolver to
provide speed feedback from the motor.
Mains supply (L1, L2, L3)
Supply voltage380–480 V ±10%
Mains voltage low/mains voltage drop-out:
During low mains voltage or a mains drop-out, the drive continues until the DC-link voltage drops below the minimum stop
level, which corresponds typically to 15% below the lowest rated supply voltage of the drive. Power-up and full torque cannot be
expected at mains voltage lower than 10% below the lowest rated supply voltage of the drive.
Supply frequency50/60 Hz ±5%
Maximum imbalance temporary between mains phases3.0% of rated supply voltage
True power factor (λ)≥0.9 nominal at rated load
55
Displacement power factor (cos Φ) near unity(>0.98)
Switching on input supply L1, L2, L3 (power-ups)Maximum 1 time/2 minute
Environment according to EN60664-1Overvoltage category III/pollution degree 2
The drive is suitable for use on a circuit capable of delivering up to 100 kA short circuit current rating (SCCR) at 480/600 V.
1) Calculations based on IEC61800-3.
1)
5.3 Motor Output and Motor Data
Motor output (U, V, W)
Output voltage0–100% of supply voltage
Output frequency0–590 Hz
Output frequency in ux mode0–300 Hz
Switching on outputUnlimited
Ramp times0.01–3600 s
1) Dependent on voltage and power.
1)
Torque characteristics
Starting torque (constant torque)Maximum 150% for 60 s
Overload torque (constant torque)Maximum 150% for 60 s
1) Percentage relates to the nominal current of the drive.
2) Once every 10 minutes.
1), 2)
1), 2)
5.4 Ambient Conditions
Environment
J8/J9 enclosureIP20/Chassis
Vibration test (standard/ruggedized)0.7 g/1.0 g
Relative humidity5%–95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation)
Aggressive environment (IEC 60068-2-43) H2S testClass Kd
Aggressive gases (IEC 60721-3-3)Class 3C3
Test method according to IEC 60068-2-43H2S (10 days)
Ambient temperature (at SFAVM switching mode)
- with deratingMaximum 55 °C (131 °F)
- with full output power of typical EFF2 motors (up to 90% output current)Maximum 50 °C (122 °F)
- at full continuous FC output currentMaximum 45 °C (113 °F)
Minimum ambient temperature during full-scale operation0 °C (32 °F)
Minimum ambient temperature at reduced performance-10 °C (14 °F)
Temperature during storage/transport-25 to +65/70 °C (13 to 149/158 °F)
Maximum altitude above sea level without derating1000 m (3281 ft)
Maximum altitude above sea level with derating3000 m (9842 ft)
1) For more information on derating, see chapter 6.6 Derating.
Cable lengths and cross-sections for control cables
Maximum motor cable length, shielded150 m (492 ft)
Maximum motor cable length, unshielded300 m (984 ft)
Maximum cross-section to motor and mainsSee chapter 5.1 Electrical Data, 380-480 V
Maximum cross-section to control terminals, rigid wire1.5 mm2/16 AWG (2x0.75 mm2)
Maximum cross-section to control terminals, exible cable1 mm2/18 AWG
Maximum cross-section to control terminals, cable with enclosed core0.5 mm2/20 AWG
Minimum cross-section to control terminals0.25 mm2/23 AWG
1) For power cables, see electrical data in chapter 5.1 Electrical Data, 380-480 V.
5.6 Control Input/Output and Control Data
Digital inputs
Programmable digital inputs4 (6)
Terminal number18, 19, 271), 291), 32, 33
LogicPNP or NPN
Voltage level0–24 V DC
Voltage level, logic 0 PNP<5 V DC
Voltage level, logic 1 PNP>10 V DC
Voltage level, logic 0 NPN>19 V DC
Voltage level, logic 1 NPN<14 V DC
Maximum voltage on input28 V DC
Input resistance, R
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminals 27 and 29 can also be programmed as outputs.
i
Approximately 4 kΩ
55
1)
Analog inputs
Number of analog inputs2
Terminal number53, 54
ModesVoltage or current
Mode selectSwitches A53 and A54
Voltage modeSwitch A53/A54=(U)
Voltage level0 V to +10 V (scaleable)
Input resistance, R
Maximum voltage±20 V
Current modeSwitch A53/A54=(I)
Current level0/4 to 20 mA (scaleable)
Input resistance, R
Maximum current30 mA
Resolution for analog inputs10 bit (+ sign)
Accuracy of analog inputsMaximum error 0.5% of full scale
Bandwidth100 Hz
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Pulse inputs
Programmable pulse inputs2
Terminal number pulse29, 33
Maximum frequency at terminal 29, 33 (push-pull driven)110 kHz
Maximum frequency at terminal 29, 33 (open collector)5 kHz
Minimum frequency at terminal 29, 334 Hz
Voltage levelSee Digital Inputs in chapter 5.6 Control Input/Output and Control Data
Maximum voltage on input28 V DC
Input resistance, R
i
Pulse input accuracy (0.1–1 kHz)Maximum error: 0.1% of full scale
Analog output
Number of programmable analog outputs1
Terminal number42
Current range at analog output0/4–20 mA
Maximum resistor load to common at analog output500 Ω
Accuracy on analog outputMaximum error: 0.8% of full scale
Resolution on analog output8 bit
The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control card, RS485 serial communication
Terminal number68 (P, TX+, RX+), 69 (N, TX-, RX-)
Terminal number 61Common for terminals 68 and 69
The RS485 serial communication circuit is functionally separated from other central circuits and galvanically isolated from the
supply voltage (PELV).
Approximately 4 kΩ
Digital output
Programmable digital/pulse outputs2
Terminal number27, 29
Voltage level at digital/frequency output0–24 V
Maximum output current (sink or source)40 mA
Maximum load at frequency output1 kΩ
Maximum capacitive load at frequency output10 nF
Minimum output frequency at frequency output0 Hz
Maximum output frequency at frequency output32 kHz
Accuracy of frequency outputMaximum error: 0.1% of full scale
Resolution of frequency outputs12 bit
1) Terminals 27 and 29 can also be programmed as inputs.
The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control card, 24 V DC output
Terminal number12, 13
Maximum load200 mA
The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital
inputs and outputs.
Relay outputs
Programmable relay outputs2
Maximum cross-section to relay terminals2.5 mm2 (12 AWG)
Minimum cross-section to relay terminals0.2 mm2 (30 AWG)
Length of stripped wire8 mm (0.3 in)
Relay 01 terminal number1–3 (break), 1–2 (make)
Maximum terminal load (AC-1)1) on 1–2 (NO) (Resistive load)
Maximum terminal load (AC-15)1) on 1–2 (NO) (Inductive load @ cosφ 0.4)240 V AC, 0.2 A
Maximum terminal load (DC-1)1) on 1–2 (NO) (Resistive load)80 V DC, 2 A
Maximum terminal load (DC-13)1) on 1–2 (NO) (Inductive load)24 V DC, 0.1 A
Maximum terminal load (AC-1)1) on 1–3 (NC) (Resistive load)240 V AC, 2 A
Maximum terminal load (AC-15)1) on 1–3 (NC) (Inductive load @ cosφ 0.4)240 V AC, 0.2 A
Maximum terminal load (DC-1)1) on 1–3 (NC) (Resistive load)50 V DC, 2 A
Maximum terminal load (DC-13)1) on 1–3 (NC) (Inductive load)24 V DC, 0.1 A
Minimum terminal load on 1–3 (NC), 1–2 (NO)24 V DC 10 mA, 24 V AC 2 mA
Environment according to EN 60664-1Overvoltage category III/pollution degree 2
Relay 02 terminal number4–6 (break), 4–5 (make)
Maximum terminal load (AC-1)1) on 4–5 (NO) (Resistive load)
Maximum terminal load (AC-15)1) on 4–5 (NO) (Inductive load @ cosφ 0.4)240 V AC, 0.2 A
Maximum terminal load (DC-1)1) on 4–5 (NO) (Resistive load)80 V DC, 2 A
Maximum terminal load (DC-13)1) on 4–5 (NO) (Inductive load)24 V DC, 0.1 A
Maximum terminal load (AC-1)1) on 4–6 (NC) (Resistive load)240 V AC, 2 A
Maximum terminal load (AC-15)1) on 4–6 (NC) (Inductive load @ cosφ 0.4)240 V AC, 0.2 A
Maximum terminal load (DC-1)1) on 4–6 (NC) (Resistive load)50 V DC, 2 A
Maximum terminal load (DC-13)1) on 4–6 (NC) (Inductive load)24 V DC, 0.1 A
Minimum terminal load on 4–6 (NC), 4–5 (NO)24 V DC 10 mA, 24 V AC 2 mA
Environment according to EN 60664-1Overvoltage category III/pollution degree 2
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
1) IEC 60947 part 4 and 5.
2) Overvoltage Category II.
2), 3)
2), 3)
400 V AC, 2 A
400 V AC, 2 A
55
Control card, +10 V DC output
Terminal number50
Output voltage10.5 V ±0.5 V
Maximum load25 mA
The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control characteristics
Resolution of output frequency at 0–1000 Hz±0.003 Hz
System response time (terminals 18, 19, 27, 29, 32, 33)≤2 m/s
Speed control range (open loop)1:100 of synchronous speed
Speed accuracy (open loop)30–4000 RPM: Maximum error of ±8 RPM
All control characteristics are based on a 4-pole asynchronous motor.
Control card, USB serial communication
USB standard1.1 (full speed)
USB plugUSB type B device plug
NOTICE
Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
The USB connection is not galvanically isolated from ground. Use only isolated laptop/PC as connection to the USB
connector on the drive or an isolated USB cable/converter.