Danfoss FC 360 Fact sheet

Fact Sheet

VLT® AutomationDrive FC 360

High performer in challenging environments

Dedicated drive for industrial applications in a compact, energy saving package.

The VLT® AutomationDrive FC 360 is a reliable, energy efficient and userfriendly solution placed in a price/ performance sweet spot, making it a preferred choice for OEMs.

Designed to work in harsh and humid environments, the drive provides reliable operation in industries such as textile, plastic & rubber, metal work, material handling, food & beverage, and building materials.

The right mix

of features gives you freedom to achieve your system goals

The drive enables precise and efficient motor control of a wide range of industrial applications such as extruders, winders, conveyors, drawing benches, texturizing, pumps, and fans.

The efficient cooling concept ensures there is no forced air over the printed circuit board, which improves reliability. Also, a removable fan makes it possible to clean the inside of the drive quickly and easily, thereby reducing the risk of downtime.

FC 360 reduces initial costs and effort with a wide range of built-in features that simplify installation and commis-

Feature

Reliable

Maximum ambient temperature 55 °C (up to 45~50 °C without derating in normal opreration)

Coated PCB

Unique cooling concept with no forced air flow over electronics

User friendly

Enhanced numeric LCP Application selection and guidance Removable cooling fan

Integrated DC choke

Built-in EMC filter

Versatile

Automatic Energy Optimizer function Built-in PID controller

Feed-forward PID

Kinetic backup

Built-in brake chopper up to 22 kW

PM motor control up to 75 kW

Torque control

Built-in position controller

sioning, including an EMC filter, built-in brake chopper up to 22 kW, and a userfriendly numeric LCP.

A built-in DC choke reduces ­harmonics to 40-48% ThiD, significantly extending the lifetime of the DC ­capacitors. Application selection guides enable users to set up common applications with ease.

Product range

3 x 380 – 480 V................................0.37-75 kW

Enclosure ratings

IP20

Benefit

Maximum uptime

Reliable operation in many environments

Prepared for harsh environments

Unequalled robustness – maximum uptime

Saves commissioning and operating cost

Easy setup

Easy commissioning

Fast cleaning and extended lifetime Small power cables, less harmonics

Increases reliability and reduces interference with sensitive electronics

Energy saving

Saves 5-15% energy and reduces operation costs Eliminates external controller

Higher stability for workbench

Controlled ramp down at mains fail can reduce material waste

Saves panel space and cost

(no need to buy external braking chopper) High efficiency

Solution for winder applications Saves external position controller

drives.danfoss.com

Danfoss FC 360 Fact sheet

Extruder

Escalator

Winder

Material handling

Specifications

Mains supply (L1, L2, L3)

Supply voltage Supply frequency

Displacement power factor (cos φ) near unity

Switching on input supply L1, L2, L3

Output data (U, V, W)

380-480V -15%/+10% 50/60 Hz

(> 0.98)

max 2 times/min. (0.37-7.5 kW) max 1 times/min. (11-75 kW)

Output voltage

0-100% of supply voltage

Switching on output

Unlimited

Ramp times

0.01-3600 sec.

Output frequency

0-500 Hz

Programmable digital inputs (outputs)

 

Digital inputs (outputs )*

7 (2)

Logic

PNP or NPN

Voltage level

0-24 VDC

*Note: Two digital outputs can be configured as pulse outputs

Pulse/encoder inputs

 

Pulse inputs (encoder inputs)**

2 (1)

Voltage level

0-24 V DC

**Note: One digital input can be configured as pulse input.

Two digital inputs can be configured as encoder inputs

 

Programmable analog inputs

 

Analog inputs

 

2

Modes

Voltage or current

Voltage level

0 V to +10 V (scaleable)

Current level

0/4 to 20 mA (scaleable)

Programmable analog outputs (can be used as digital output)

Analog outputs

2

Current range at analog output

0/4-20 mA

Programmable relay outputs

 

Relay outputs

2

Approvals

 

CE

 

Communication

 

FC Protocol, Modbus RTU, Profibus (option), ProfiNet (option)

Voltage

[V]

J1

J2

 

J3

 

J4

 

J5

 

J6

 

J7

380-480

 

3.0-5.5

 

7.5

 

11-15

 

18.5-22

 

30-45

 

55-75

0.37-2.2

 

 

 

 

 

Dimensions [mm]

Hight A

210

272.5

272.5

317.5

410

515

550

Width B

75

90

115

135

150

233

308

Depth C

168

168

168

245

245

 

 

(with

242

332

(173)

(173)

(173)

(250)

(250)

option B)

 

 

 

 

 

 

 

 

 

Danfoss Drives, Ulsnaes 1, DK-6300 Graasten, Denmark, Tel. +45 74 88 22 22, Fax +45 74 65 25 80, drives.danfoss.com, info@danfoss.com

DKDD.PFP.303.A5.02

© Copyright Danfoss Drives | 2018.12

Loading...