Danfoss FC 302 Operating guide

MAKING MODERN LIVING POSSIBLE
Operating Instructions
VLT® AutomationDrive FC 302 Low Harmonic Drive 132-630 kW
vlt-drives.danfoss.com
Contents Operating Instructions
1 Introduction
1.1 Purpose of the Manual
1.2 Additional Resources
1.3 Product Overview
1.3.1 Intended Use 5
1.3.2 Working Principle 6
1.3.3 Exploded View Drawings 7
1.4 Enclosure Sizes and Power Ratings
1.5 Approvals and Certications
1.5.1 Approvals 15
1.5.2 Compliance with ADN 15
1.6 Harmonics Overview
1.6.1 Harmonics 15
1.6.2 Harmonic Analysis 15
1.6.3 Eect of Harmonics in a Power Distribution System 16
1.6.4 IEC Harmonic Standards 17
1.6.5 IEEE Harmonic Standards 18
5 5 5 5
15 15
15
2 Safety
2.1 Safety
2.2 Qualied Personnel
2.3 Safety Precautions
3 Mechanical Installation
3.1 Installation Site Checklist
3.2 Unpacking
3.2.1 Items Supplied 22
3.3 Mounting
3.3.1 Cooling and Airow 23
3.3.2 Lifting 24
3.3.3 Cable Entry and Anchoring 26
3.3.4 Terminal Locations for Enclosure Size D1n/D2n 30
3.3.5 Terminal Locations for Enclosure Size E9 32
3.3.6 Terminal Locations for Enclsoure Size F18 33
3.3.7 Torque 35
20 20 20 20
21 21 22
23
4 Electrical Installation
4.1 Safety Instructions
4.2 Electromagnetic Compatability (EMC)
4.2.1 EMC Interference 37
MG37A302 Danfoss A/S © Rev. 04/2015 All rights reserved. 1
36 36 37
Contents
VLT® AutomationDrive FC 302 Low Harmonic Drive 132-630 kW
4.3 Power Connections
4.4 Grounding
4.5 Input Options
4.5.1 Extra Protection (RCD) 39
4.5.2 RFI Switch 39
4.5.3 Screened Cables 39
4.6 Motor Connection
4.6.1 Motor Cable 39
4.6.2 Brake Cable 40
4.6.3 Motor Insulation 40
4.6.4 Motor Bearing Currents 41
4.7 AC Mains Connection
4.7.1 Mains Connection 41
4.7.2 External Fan Supply 41
4.7.3 Power and Control Wiring for Unscreened Cables 42
4.7.4 Mains Disconnects 42
4.7.5 F-FrameCircuit Breakers 43
38 38 39
39
41
4.7.6 F-Frame Mains Contactors 43
4.8 Control Wiring
4.8.1 Control Cable Routing 43
4.8.2 Access to Control Terminals 45
4.8.3 Electrical Installation, Control Terminals 45
4.8.4 Electrical Installation, Control Cables 47
4.8.5 Safe Torque O (STO) 49
4.9 Additional Connections
4.9.1 Serial Communication 49
4.9.2 Mechanical Brake Control 49
4.9.3 Parallel Connection of Motors 50
4.9.4 Motor Thermal Protection 50
4.9.5 Voltage/Current Input Selection (Switches) 50
4.10 Final Set-up and Test
4.11 F-frame Options
5 Commissioning
5.1 Safety Instructions
43
49
51 52
54 54
5.2 Applying Power
5.3 Local Control Panel Operation
5.3.1 Local Control Panel 56
5.3.2 LCP Layout 56
5.3.3 Parameter Settings 57
5.3.4 Uploading/Downloading Data to/from the LCP 58
2 Danfoss A/S © Rev. 04/2015 All rights reserved. MG37A302
56 56
Contents Operating Instructions
5.3.5 Changing Parameter Settings 58
5.3.6 Restoring Default Settings 58
5.4 Basic Operational Programming
5.4.1 VLT® Low Harmonic Drive Programming 59
5.4.2 Commissioning with SmartStart 59
5.4.3 Commissioning via [Main Menu] 59
5.4.4 Asynchronous Motor Set-up 60
5.4.5 Permanent Magnet Motor Set-up 60
5.4.6 Automatic Energy Optimisation (AEO) 61
5.4.7 Automatic Motor Adaptation (AMA) 62
5.5 Checking Motor Rotation
5.6 Local Control Test
5.7 System Start-up
6 Application Examples
6.1 Introduction
6.2 Application Examples
7 Diagnostics and Troubleshooting
7.1 Status Messages
59
62 62 62
63 63 63
68 68
7.2 Warning and Alarm Types
7.2.1 Warnings 68
7.2.2 Alarm Trip 68
7.2.3 Alarm Trip-lock 68
7.3 Warnings and Alarm Denitions - Frequency Converter
7.4 Warnings and Alarm Denitions - Active Filter
7.5 Troubleshooting
8 Specications
8.1 Power-Dependent Specications
8.1.1 Mains Supply 3x380–480 V AC 85
8.1.2 Derating for Temperature 88
8.2 Mechanical Dimensions
8.3 General Technical Data
8.4 Fuses
8.4.1 Non-UL Compliance 99
8.4.2 Fuse Tables 99
8.4.3 Supplementary Fuses 100
68
68 77 82
85 85
90 93 98
8.5 General Torque Tightening Values
9 Appendix A - Parameters
9.1 Description of Parameters
MG37A302 Danfoss A/S © Rev. 04/2015 All rights reserved. 3
101
102 102
Contents
VLT® AutomationDrive FC 302 Low Harmonic Drive 132-630 kW
9.2 Frequency Converter Parameter Lists
9.3 Active Filter Parameter Lists
10 Appendix B
10.1 Abbreviations and Conventions
Index
102 108
115 115
116
4 Danfoss A/S © Rev. 04/2015 All rights reserved. MG37A302
Introduction Operating Instructions
1 Introduction
1
1
1.1 Purpose of the Manual
The purpose of this manual is to provide information for the installation and operation of a VLT® AutomationDrive
FC 302 Low Harmonic Drive. The manual includes relevant safety information for installation and operation.
Chapter 1 Introduction, chapter 2 Safety, chapter 3 Mechanical Installation, and chapter 4 Electrical Installation introduce the unit functions and cover proper
mechanical and electrical installation procedures. There are chapters on start-up and commissioning, applications and basic troubleshooting. Chapter 8 Specications provides a quick reference for ratings and dimensions, as well as other operating specications. This manual provides a basic knowledge of the unit and explains set-up and basic operation.
VLT® is a registered trademark.
1.2 Additional Resources
Other resources are available to understand advanced functions and programming.
The VLT® AutomationDrive FC 302 Programming
Guide provides greater detail on working with parameters and many application examples.
®
The VLT
provides detailed capabilities and functionality to design motor control systems.
Supplemental publications and manuals are
available from Danfoss. See vlt-drives.danfoss.com/Support/Technical- Documentation/ for listings.
Optional equipment may change some of the
procedures described. Reference the instructions supplied with those options for specic requirements. Contact the local Danfoss supplier or visit the Danfoss website: vlt-
drives.danfoss.com/Support/Technical­Documentation/ for downloads or additional
information.
The VLT
Instructions provide additional information about the lter portion of the low harmonic drive.
AutomationDrive FC 302 Design Guide
®
Active Filter AAF 006 Operating
1.3
Product Overview
1.3.1 Intended Use
A frequency converter is an electronic motor controller that converts AC mains input into a variable AC waveform output. The frequency and voltage of the output are regulated to control the motor speed or torque. The frequency converter can vary the speed of the motor in response to system feedback, such as with position sensors on a conveyor belt. The frequency converter can also regulate the motor by responding to remote commands from external controllers.
The frequency converter:
Monitors the system and motor status.
Issues warnings or alarms for fault conditions.
Starts and stops the motor.
Optimises energy eciency.
Operation and monitoring functions are available as status indications to an outside control system or serial communi­cation network.
A low harmonic drive (LHD) is a single unit that combines the frequency converter with an advanced active lter (AAF) for harmonic mitigation. The frequency converter and lter are packaged together in an integrated system, but each functions independently. In this manual, there are separate specications for the frequency converter and the lter. Since the frequency converter and lter are in the same enclosure, the unit is transported, installed, and operated as a single entity.
MG37A302 Danfoss A/S © Rev. 04/2015 All rights reserved. 5
Mains 380 to
500 VAC
Optional
RFI
Optional
Fuses
Optional
Manual
Disconnect
HI Reactor
L
m
L
m
L
m
L
ac
L
ac
L
ac
AC Contactor
Relay 12
Control & AUX
Feedback
Soft-Charge
Resistor
Converter Side
Filter
Power Stage
AF Current Sensors
Capacitor
Current Sensors
VLT Drive
Main’s
3
3
3
CTs
L
c
L
c
L
c
CefC
ef
C
ef
R
ef
R
ef
R
ef
I
r
I
s
I
t
130BB406.11
Introduction
VLT® AutomationDrive FC 302 Low Harmonic Drive 132-630 kW
1
1.3.2 Working Principle
The low harmonic drive is a high-power frequency converter with an integrated active lter. An active lter is a device that actively monitors harmonic distortion levels and injects compensative harmonic current onto the line to cancel the harmonics.
Illustration 1.1 Basic Layout for the Low Harmonic Drive
Low harmonic drives are designed to draw an ideal sinusoidal current waveform from the supply grid with a power factor of
1. Where traditional non-linear load draws pulse-shaped currents, the low harmonic drive compensates that via the parallel lter path, lowering the stress on the supply grid. The low harmonic drive meets the highest harmonic standards with a THDi less than 5% at full load for <3% pre-distortion on a 3% unbalanced 3-phase grid.
6 Danfoss A/S © Rev. 04/2015 All rights reserved. MG37A302
130BE136.10
1
2
3
4
5
6
7
8
6
Introduction
1.3.3 Exploded View Drawings
Operating Instructions
1
1
1 Local control panel (LCP) 5 Input/output terminal assembly 2 Control card assembly 6 Capacitor bank assembly 3 Power card assembly 7 D1/D2 assembly 4 Terminal cover sheet 8 EOC assembly
Illustration 1.2 Enclosure Size D1n/D2n, Frequency Converter Enclosure
MG37A302 Danfoss A/S © Rev. 04/2015 All rights reserved. 7
7
4
5
8
9
1
2
3
6
20
22
19
18
16
23
15
21
17
10
11
12
13
14
130BE110.10
1
Introduction
VLT® AutomationDrive FC 302 Low Harmonic Drive 132-630 kW
1 Local control panel (LCP) 13 Mains fuses 2 Active lter card (AFC) 14 Mains disconnect 3 Metal oxide varistor (MOV) 15 Mains terminals 4 Soft charge resistors 16 Heat sink fan 5 AC capacitors discharge board 17 DC capacitor bank 6 Mains contactor 18 Current transformer 7 LC inductor 19 RFI dierential mode lter 8 AC capicators 20 RFI common mode lter 9 Mains bus bar to frequency converter input 21 HI inductor 10 IGBT fuses 22 Power card 11 RFI lter 23 Gate drive card 12 Fuses
Illustration 1.3 Enclosure Size D1n/D2n, Filter Enclosure
8 Danfoss A/S © Rev. 04/2015 All rights reserved. MG37A302
1
3
2
7
5
4
10
9
8
25
24
6
130BX168.10
20
19
18
17
16
15
14
13
12
11
23
22
21
Introduction
Operating Instructions
1
1
1 Control card 14 SCR and diode 2 Control input terminals 15 Fan inductor (not on all units) 3 Local control panel (LCP) 16 Soft charge resistor assembly 4 Control card C option 17 IGBT output bus bar 5 Mounting bracket 18 Fan assembly 6 Power card mounting plate 19 Output motor terminals 7 Power card 20 Current sensor 8 IGBT gate drive card 21 Mains AC power input terminals 9 Upper capacitor bank assembly 22 Input terminal mounting plate 10 Soft charge fuses 23 AC input bus bar 11 DC inductor 24 Soft charge card 12 Fan transformer 25 Lower capacitor bank assembly 13 IGBT module
Illustration 1.4 Enclosure Size E9, Frequency Converter Enclosure
MG37A302 Danfoss A/S © Rev. 04/2015 All rights reserved. 9
130BD572.11
1
5
6
7
9
10
11
12
14
16
17
18
19
20
21
2
3
4
8
13
15
Introduction
VLT® AutomationDrive FC 302 Low Harmonic Drive 132-630 kW
1
1 Local control panel (LCP) 12 AC capacitor current transducers 2 Active lter card (AFC) 13 Heat sink fan 3 Mains contactors 14 Mains terminals 4 Soft charge resistors 15 Mains disconnect 5 RFI dierential mode lter 16 Mains fuses 6 RFI common mode lter 17 LC inductor 7 Current transformer (CT) 18 HI inductor 8 Mains bus bars to drive output 19 Power card 9 AC capacitors 20 Control card 10 RFI 21 LCP cradle 11 Lower DC capacitor bank
Illustration 1.5 Enclosure Size E9, Filter Enclosure
10 Danfoss A/S © Rev. 04/2015 All rights reserved. MG37A302
130BX334.11
2
3
4
5
6
1
Introduction Operating Instructions
1
1
1 Contactor 4 Circuit breaker or disconnect (if purchased) 2 RFI lter 5 AC mains/line fuses (if purchased) 3 Mains AC power input terminals 6 Mains disconnect
Illustration 1.6 Enclosure Size F18, Input Options Cabinet
MG37A302 Danfoss A/S © Rev. 04/2015 All rights reserved. 11
130BD573.10
1
2
5
6
7
10
11
15
17
3
4
8
9
13
14
16
18
12
1
Introduction
VLT® AutomationDrive FC 302 Low Harmonic Drive 132-630 kW
1 Local control panel (LCP) 10 Mains bus bars to frequency converter input 2 Active lter card (AFC) 11 Heat sink fans 3 Soft charge resistors 12 Mains terminals (R/L1, S/L2, T/L3) from options cabinet 4 Metal oxide varistor (MOV) 13 RFI dierential mode lter 5 AC capacitors discharge board 14 RFI common mode lter 6 LC inductor 15 Mains contactor 7 HI inductor 16 Power card 8 Mixing fan 17 Control card 9 IGBT fuses 18 LCP cradle
Illustration 1.7 Enclosure Size F18, Filter Cabinet
12 Danfoss A/S © Rev. 04/2015 All rights reserved. MG37A302
1
2
5
6
7
8
9
10
11
12
4
3
130BX331.11
13
Introduction Operating Instructions
1
1
1 Rectier module 8 Module heat sink fan 2 DC bus bar 9 Fan door cover 3 SMPS fuse 10 SMPS fuse 4 (Optional) back AC fuse mounting bracket 11 Power card 5 (Optional) middle AC fuse mounting bracket 12 Panel connectors 6 (Optional) front AC fuse mounting bracket 13 Control card 7 Module lifting eye bolts (mounted on a vertical strut)
Illustration 1.8 Enclosure Size F18, Rectier Cabinet
MG37A302 Danfoss A/S © Rev. 04/2015 All rights reserved. 13
2
1
16
15
14
13
12
11
10
8
7
6
5
4
9
3
130BX330.11
1
Introduction
VLT® AutomationDrive FC 302 Low Harmonic Drive 132-630 kW
1 Fan transformer 9 Fan door cover 2 DC-link inductor 10 Module heat sink fan 3 Top cover plate 11 Inverter module 4 MDCIC board 12 Panel connectors 5 Control card 13 DC fuse 6 SMPS fuse and fan fuse 14 Mounting bracket 7 Motor output bus bar 15 (+) DC bus bar 8 Brake output bus bar 16 (-) DC bus bar
Illustration 1.9 Enclosure Size F18, Inverter Cabinet
14 Danfoss A/S © Rev. 04/2015 All rights reserved. MG37A302
Introduction Operating Instructions
1.4 Enclosure Sizes and Power Ratings
Enclosure size D1n D2n E9 F18
Enclosure protection
Frequency converter dimensions [mm/inch]
Frequency converter
weights [kg/lbs]
Table 1.1 Mechanical Dimensions, Enclosure Sizes D, E, and F
IP 21/54 21/54 21/54 21/54 NEMA Type 1/Type 12 Type 1/Type 12 Type 1/Type 12 Type 1/Type 12 Height 1740/68.5 1740/68.5 2000.7/78.77 2278.4/89.70 Width 915/36.02 1020/40.16 1200/47.24 2792/109.92 Depth 380/14.96 380/14.96 493.5/19.43 605.8/23.85 Maximum weight Shipping weight 416/917 476/1050 840/1851 2345/5171
353/777 413/910 676/1490 1900/4189
1.5 Approvals and Certications
Harmonic Analysis
1.6.2
1
1
1.5.1 Approvals
Table 1.2 Compliance Marks: CE, UL, and C-Tick
1.5.2 Compliance with ADN
For compliance with the European Agreement concerning International Carriage of Dangerous Goods by Inland Waterways (ADN), refer to ADN-compliant Installation in the Design Guide.
1.6 Harmonics Overview
1.6.1 Harmonics
Non-linear loads such as found with 6-pulse frequency converters do not draw current uniformly from the power line. This non-sinusoidal current has components which are multiples of the fundamental current frequency. These components are referred to as harmonics. It is important to control the total harmonic distortion on the mains supply. Although the harmonic currents do not directly aect electrical energy consumption, they generate heat in wiring and transformers and can impact other devices on the same power line.
Since harmonics increase heat losses, it is important to design systems with harmonics in mind to prevent overloading the transformer, inductors, and wiring.
When necessary, perform an analysis of the system harmonics to determine equipment eects.
A non-sinusoidal current is transformed with a Fourier series analysis into sine-wave currents at dierent frequencies, that is, dierent harmonic currents IN with 50 Hz or 60 Hz as the fundamental frequency.
Abbreviation Description
f
1
I
1
U
1
I
n
U
n
n Harmonic order
Table 1.3 Harmonics-related Abbreviations
Fundamental
Current I Frequency [Hz]
Table 1.4 Fundamental and Harmonic Currents
Current Harmonic current
I Input current 1.0 0.9 0.5 0.2 < 0.1
Fundamental frequency (50 Hz or 60 Hz) Current at the fundamental frequency Voltage at the fundamental frequency Current at the nth harmonic frequency Voltage at the nth harmonic frequency
Harmonic current (In)
current (I1)
RMSI1
I
5
1
50 250 350 550
I
7
I
I
5
7
I
11-49
I
11
Table 1.5 Harmonic Currents Compared to the RMS Input Current
The voltage distortion on the mains supply voltage depends on the size of the harmonic currents multiplied
MG37A302 Danfoss A/S © Rev. 04/2015 All rights reserved. 15
Introduction
VLT® AutomationDrive FC 302 Low Harmonic Drive 132-630 kW
1
by the mains impedance for the frequency in question. The total voltage distortion (THDi) is calculated based on the individual voltage harmonics using this formula:
THDi =
U25 + U27 + ... + U2n
U
1.6.3 Eect of Harmonics in a Power Distribution System
In Illustration 1.10, a transformer is connected on the primary side to a point of common coupling PCC1, on the medium voltage supply. The transformer has an impedance Z
and feeds a number of loads. The point of common
xfr
coupling where all loads are connected is PCC2. Each load is connected through cables that have an impedance Z1, Z2, Z3.
PCC, the conguration of the distribution system and relevant impedances must be known.
A commonly used term for describing the impedance of a grid is the short-circuit ratio R
. R
is dened as the ratio
sce
sce
between the short circuit apparent power of the supply at the PCC (Ssc) and the rated apparent power of the load (S
).
equ
S
sce
sc
=
S
equ
2
U
Z
supply
and S
=
sc
equ
= U × I
equ
R
where S
Negative eects of harmonics
Harmonic currents contribute to system losses (in
cabling, and transformer). Harmonic voltage distortion causes disturbance
to other loads and increases losses in other loads.
PCC Point of common coupling MV Medium voltage LV Low voltage Z
xfr
Z
#
Illustration 1.10 Small Distribution System
Transformer impedance Modeling resistance and inductance in the wiring
Harmonic currents drawn by non-linear loads cause distortion of the voltage because of the voltage drop on the impedances of the distribution system. Higher impedances result in higher levels of voltage distortion.
Current distortion relates to apparatus performance and it relates to the individual load. Voltage distortion relates to system performance. It is not possible to determine the voltage distortion in the PCC knowing only the harmonic performance of the load. To predict the distortion in the
16 Danfoss A/S © Rev. 04/2015 All rights reserved. MG37A302
Introduction
Operating Instructions
1.6.4 IEC Harmonic Standards
The mains voltage is rarely a uniform sinusoidal voltage with constant amplitude and frequency because loads that draw non-sinusoidal currents from the mains have non-linear characteristics.
Harmonics and voltage uctuations are 2 forms of low-frequency mains interference. They have a dierent appearance at their origin than at any other point in the mains system when a load is connected. So, a range of inuences must be determined collectively when assessing the eects of mains interference. These inuences include the mains feed, structure, and loads.
Mains interference can cause the following:
Undervoltage warnings
Incorrect voltage measurements due to distortion of the sinusoidal mains voltage.
Cause incorrect power measurements because only RMS-true measuring takes harmonic content into account.
Higher functional losses
Harmonics reduce the active power, apparent power, and reactive power.
Distort electrical loads resulting in audible interference in other devices, or in worst case, even destruction.
Shorten the lifetime of devices as a result of heating.
1
1
In most of Europe, the basis for the objective assessment of the quality of mains power is the Electromagnetic Compatibility of Devices Act (EMVG). Compliance with these regulations ensures that all devices and networks connected to electrical distribution systems
Standard Denition
EN 61000-2-2, EN 61000-2-4, EN 50160 Dene the mains voltage limits required for public and industrial power grids. EN 61000-3-2, 61000-3-12 Regulate mains interference generated by connected devices in lower current products. EN 50178 Monitors electronic equipment for use in power installations.
Table 1.6 EN Design Standards for Mains Power Quality
There are 2 European standards that address harmonics in the frequency range from 0 Hz to 9 kHz:
EN 61000-2-2 (Compatibility Levels for Low-Frequency Conducted Disturbances and Signalling in Public Low-Voltage Power Supply Systems) states the requirements for compatibility levels for PCC (point of common coupling) of low-voltage AC systems on a public supply network. Limits are specied only for harmonic voltage and total harmonic distortion of the voltage. EN 61000-2-2 does not dene limits for harmonic currents. In situations where the total harmonic distortion THD(V)=8%, PCC limits are identical to those limits specied in the EN 61000-2-4 Class 2.
EN 61000-2-4 (Compatibility Levels for Low-Frequency Conducted Disturbances and Signalling in Industrial Plants) states the requirements for compatibility levels in industrial and private networks. The standard further denes the following 3 classes of electromagnetic environments:
Class 1 relates to compatibility levels that are less than the public supply network, which
sensitive to disturbances (lab equipment, some automation equipment, and certain protection devices). Class 2 relates to compatibility levels that are equal to the public supply network. The class applies to PCCs on the
public supply network and to IPCs (internal points of coupling) on industrial or other private supply networks. Any equipment designed for operation on a public supply network is allowed in this class.
Class 3 relates to compatibility levels greater than the public supply network. This class applies only to IPCs in
industrial environments. Use this class where the following equipment is found:
full their intended purpose without generating problems.
aects equipment
MG37A302 Danfoss A/S © Rev. 04/2015 All rights reserved. 17
Introduction
VLT® AutomationDrive FC 302 Low Harmonic Drive 132-630 kW
1
Large converters.
-
Welding machines.
-
Large motors starting frequently.
-
Loads that change quickly.
-
Typically, a class cannot be dened ahead of time without taking into account the intended equipment and processes to be used in the environment. VLT® AutomationDrive FC 302 Low Harmonic Drive observes the limits of Class 3 under typical
supply system conditions (RSC>10 or
Harmonic order (h) Class 1 (Vh%) Class 2 (Vh%) Class 3 (Vh%)
5 3 6 8
7 3 5 7 11 3 3.5 5 13 3 3 4.5 17 2 2 4
17˂h≤49 2.27 x (17/h) – 0.27 2.27 x (17/h) – 0.27 4.5 x (17/h) – 0.5
Table 1.7 Compatibility Levels for Harmonics
Class 1 Class 2 Class 3 THD(V)
Table 1.8 Compatibility Levels for the Total Harmonic Voltage Distortion THD(V)
Vk Line
<10%).
5% 8% 10%
IEEE Harmonic Standards
1.6.5
The IEEE 519 standard (Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems) provides specic limits for harmonic voltages and currents for individual components within the supply network. The standard also provides limits for the sum of all loads at the point of common coupling (PCC).
To determine permissible harmonic voltage levels, IEEE 519 uses a ratio between the supply short-circuit current and the maximum current of the individual load. For permissible harmonic voltage levels for individual loads, see Table 1.9. For permissible levels for all loads connected to the PCC, see Table 1.10.
ISC/IL (R
10 2.5–3% Weak grid 20 2.0–2.5% 1–2 large loads 50 1.0–1.5% A few high-output loads 100 0.5–1% 5–20 medium-output loads 1000 0.05–0.1% Strong grid
Table 1.9 Permissible Voltage THD at the PCC for Each Individual Load
Voltage at the PCC Permissible individual harmonic voltages Permissible THD(V)
V
Line
Table 1.10 Permissible Voltage THD at the PCC for all Loads
) Permissible individual harmonic voltages Typical areas
SCE
≤69 kV 3% 5%
Limit harmonic currents to
specied levels, as shown in Table 1.11. IEEE 519 utilises a ratio between the supply short-circuit
current and the maximum current consumption at the PCC, averaged over 15 minutes or 30 minutes. In certain instances when dealing with harmonic limits containing low harmonic numbers, the IEEE 519 limits are lower than the 61000-2-4 limits. Low harmonic drives observe the total harmonic distortion as dened in IEEE 519 for all R harmonic current fullls table 10–3 in IEEE 519 for R
18 Danfoss A/S © Rev. 04/2015 All rights reserved. MG37A302
sce
≥20.
. Each individual
sce
Introduction Operating Instructions
ISC/IL (R
<20 4% 2.0% 1.5% 0.6% 0.3% 5% 20<50 7% 3.5% 2.5% 1.0% 0.5% 8% 50<100 10% 4.5% 4.0% 1.5% 0.7% 12% 100<1000 12% 5.5% 5.0% 2.0% 1.0% 15% >1000 15% 7.0% 6.0% 2.5% 1.4% 20%
Table 1.11 Permissible Harmonic Currents at the PCC
The VLT® AutomationDrive FC 302 Low Harmonic Drive complies with the following standards:
) h<11 11≤h<17 17≤h<23 23≤h<35 35≤h Total demand
SCE
IEC61000-2-4
IEC61000-3-4
IEEE 519
G5/4
distortion TDD
1
1
MG37A302 Danfoss A/S © Rev. 04/2015 All rights reserved. 19
2
Safety
2 Safety
2.1 Safety
VLT® AutomationDrive FC 302 Low Harmonic Drive 132-630 kW
2.3
Safety Precautions
The following symbols are used in this document:
WARNING
Indicates a potentially hazardous situation which could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which could result in minor or moderate injury. It may also be used to alert against unsafe practices.
NOTICE
Indicates important information, including situations that may result in damage to equipment or property.
2.2 Qualied Personnel
Correct and reliable transport, storage, installation, operation and maintenance are required for the safe operation of the frequency converter. Only qualied personnel are allowed to install or operate this equipment.
Qualied personnel is dened as trained sta, who are authorised to install, commission, and maintain equipment, systems and circuits in accordance with pertinent laws and regulations. Additionally, qualied personnel are familiar with the instructions and safety measures described in this document.
WARNING
HIGH VOLTAGE
Frequency converters contain high voltage when connected to AC mains input power. Qualied personnel only should perform installation, start up, and maintenance. Failure to perform installation, start up, and maintenance by qualied personnel could result in death or serious injury.
WARNING
UNINTENDED START
When the frequency converter is connected to AC mains, the motor may start at any time. The frequency converter, motor, and any driven equipment must be in operational readiness. Failure to be in operational readiness when the frequency converter is connected to AC mains could result in death, serious injury, equipment, or property damage.
WARNING
DISCHARGE TIME
Frequency converters contain DC-link capacitors that can remain charged even when the frequency converter is not powered. To avoid electrical hazards, disconnect AC mains, any permanent magnet type motors, and any remote DC-link power supplies, including battery back­ups, UPS, and DC-link connections to other frequency converters. Wait for the capacitors to fully discharge before performing any service or repair work. The amount of wait time is listed in the Discharge Time table. Failure to wait the specied time after power has been removed before doing service or repair could result in death or serious injury.
Voltage [V] Power range [kW] Minimum waiting time
(minutes)
380–500
Table 2.1 Discharge Times
20 Danfoss A/S © Rev. 04/2015 All rights reserved. MG37A302
132–200 kW 20 250–630 kW 40
Mechanical Installation Operating Instructions
3 Mechanical Installation
3.1 Installation Site Checklist
3.1.1 Planning the Installation Site
CAUTION
It is important to plan the installation of the frequency converter. Neglecting to plan may result in extra work during and after installation.
Select the best possible operation site by considering the following:
Ambient operating temperature.
Installation method.
How to cool the unit.
Position of the frequency converter.
Cable routing.
Ensure that the power source supplies the correct
voltage and necessary current. Ensure that the motor current rating is within the
maximum current from the frequency converter. If the frequency converter is without built-in
fuses, ensure that the external fuses are rated correctly.
Motor size and frequency converter
-
power must match for proper overload protection.
If frequency converter rating is less than
-
that of the motor, full motor output is impossible.
3 3
Equipment Pre-Installation Checklist
3.1.2
Before unpacking the frequency converter,
examine the packaging for signs of damage. If the unit is damaged, refuse delivery, and immediately contact the shipping company to claim the damage.
Before unpacking the frequency converter, locate
it as close as possible to the Compare the model number on the nameplate to
what was ordered to verify the proper equipment.
Ensure that each of the following are rated for
the same voltage:
Mains (power)
-
Frequency converter
-
Motor
-
Ensure that the output current rating is equal to
or greater than the motor full load current for peak motor performance.
nal installation site.
MG37A302 Danfoss A/S © Rev. 04/2015 All rights reserved. 21
130BD600.10
CHASSIS/ IP20 Tamb.50
C/122 F
V LT
MADE IN DENMARK
R
P/N: 131X3537 S/N: 010122G430
0.37kW/ 0.50HP
IN: 3x200-240V 50/60Hz 2.2A
OUT: 3x0-Vin 0-1000Hz 2.4A
o
CAUTION: See manual for special condition/mains fuse
voir manual de conditions speclales/fusibles
WARNING: Stored charge, wait 4 min. Charge residuelle, attendez 4 min.
* 1 3 1
X
3 5 3 7 0 1 0 1 2 2 G 4 3 0 *
`
Automation Drive www.danfoss.com
T/C: FC-302PK37T2E20H1BGXXXXSXXXXA6BKC4XXXD0
Listed 76X1 E134261 Ind. Contr. Eq.
o
`
1
2
4
5
6
7
8
9
10
3
Mechanical Installation
VLT® AutomationDrive FC 302 Low Harmonic Drive 132-630 kW
3.2 Unpacking
3.2.1 Items Supplied
Items supplied may vary according to product congu-
ration.
33
Make sure that the items supplied and the
information on the nameplate correspond to the order conrmation.
Check the packaging and the frequency converter
visually for damage caused by inappropriate handling during shipment. File any claim for damage with the carrier. Retain damaged parts for clarication.
1 Type code 2 Order number 3 Serial number 4 Power rating
Input voltage, frequency and current (at low/high
5
voltages) Output voltage, frequency and current (at low/high
6
voltages) 7 Enclosure type and IP rating 8 Maximum ambient temperature 9 Certications
10 Discharge time (Warning)
Illustration 3.1 Product Nameplate (Example)
NOTICE
Do not remove the nameplate from the frequency converter (loss of warranty).
22 Danfoss A/S © Rev. 04/2015 All rights reserved. MG37A302
Mechanical Installation Operating Instructions
3.3 Mounting
3.3.1 Cooling and Airow
Cooling
Obtain cooling by taking air in through the plinth in the front and out of the top, in and out the back of the unit, or by combining the cooling possibilities.
Back cooling
The backchannel air can also be ventilated in and out the back. This from outside the facility and return the heat losses outside the facility thus reducing air-conditioning requirements.
Airow
Secure the necessary airow over the heat sink. The ow rate is shown in Table 3.1.
oers a solution where the backchannel could take air
3 3
Enclosure protection Enclosure size
D1n
D2n
IP21/NEMA 1
IP54/NEMA 12
Table 3.1 Heat Sink Air Flow
E9
F18
NOTICE
For the frequency converter section, the fan runs for the following reasons:
AMA.
DC hold.
Pre-mag.
DC brake.
60% of nominal current is exceeded.
Specic heat sink temperature exceeded (power
size dependent). Specic power card ambient temperature
exceeded (power size dependent). Specic control card ambient temperature
exceeded.
Once the fan is started, it runs for minimum 10 minutes.
Door fan/top fan airow Total airow of multiple fans
3 door fans, 442 m3/h 2+1=2x170+102
3 door fan, 544 m3/h 2+1=2x170+204
4 door fans, 680 m3/h (400 cfm) (2+2, 4x170=680)
6 door fans, 3150 m3/h (1854 cfm) (6x525=3150)
Heat sink fan Total airow for multiple fans
2 heat sink fans, 1185 m3/h (1+1=765+544)
2 heat sink fans, 1605 m3/h (1+1=765+840)
2 heat sink fans, 2675 m3/h (1574 cfm) (1+1, 1230+1445=2675)
5 heat sink fans, 4485 m3/h (2639 cfm) 2+1+2, ((2x765)+(3x985)=4485)
NOTICE
For the active lter, the fan runs for the following reasons:
Active lter running.
Active lter not running, but mains current
exceeding the limit (power size dependent). Specic heat sink temperature exceeded (power
size dependent). Specic power card ambient temperature
exceeded (power size dependent). Specic control card ambient temperature
exceeded.
Once the fan is started, it runs for minimum 10 minutes.
External ducts
If additional duct work is added externally to the Rittal cabinet, calculate the pressure drop in the ducting. Use Illustration 3.2, Illustration 3.3, and Illustration 3.4 to derate the frequency converter according to the pressure drop.
MG37A302 Danfoss A/S © Rev. 04/2015 All rights reserved. 23
90
80
70
60
50
40
30
20
10
0
0 0.5 4.9 13 27.3 45.9 66 89.3 115.7 147
(%)
(Pa)
Pressure Increase
Drive Derating
130BB007.10
90
80
70
60
50
40
30
20
10
0
(%)
Drive Derating
0 0.2 0.6 2.2 5.8 11.4 18.1 30.8 152.8 210.8
(Pa)
Pressure Change
130BB011.10
69.5
90
80
70
60
50
40
30
20
10
0
(%)
Drive Derating
0 25 50 75 100 125 150 175 225
130BB190.10
200
Pressure Change
1
130BE111.10
130BC170.10
Lifting Holes
Mechanical Installation
VLT® AutomationDrive FC 302 Low Harmonic Drive 132-630 kW
Lifting
3.3.2
Lift the frequency converter using the dedicated lifting eyes. For all D-frames, use a bar to avoid bending the lifting holes of the frequency converter.
33
Illustration 3.2 D-Enclosure Derating vs. Pressure Change Frequency Converter Air Flow: 450 cfm (765 m3/h)
1 Lifting holes
Illustration 3.5 Recommended Lifting Method, Enclosure Size D1n/D2n
Illustration 3.3 E-Enclosure Derating vs. Pressure Change Frequency Converter Air Flow: 850 cfm (1445 m3/h)
Illustration 3.4 F-Enclosure Derating vs. Pressure Change Frequency Converter Air Flow: 580 cfm (985 m3/h)
24 Danfoss A/S © Rev. 04/2015 All rights reserved. MG37A302
Illustration 3.6 Recommended Lifting Method, Enclosure Size E9
WARNING
The lifting bar must be able to handle the weight of the frequency converter. See chapter 8.2 Mechanical Dimensions for the weight of the dierent enclosure sizes. Maximum diameter for bar is 2.5 cm (1 inch). The angle from the top of the frequency converter to the lifting cable should be 60° or greater.
1
2
130BD574.10
Mechanical Installation Operating Instructions
1 Lifting holes for the lter 2 Lifting holes for the frequency converter
Illustration 3.7 Recommended Lifting Method, Enclosure Size F18
3 3
NOTICE
A spreader bar is also an acceptable way to lift the F­frame.
NOTICE
The F18 pedestal is packaged separately and included in the shipment. Mount the frequency converter on the pedestal in its nal location. The pedestal allows proper airow and cooling.
MG37A302 Danfoss A/S © Rev. 04/2015 All rights reserved. 25
64.5 [2.5]
20.0 [0.8]
40.0 [1.6]
560.0 [22.0]
327.4 [12.9]
289.4 [11.4]
227.8 [9.0]
246.0 [9.7]
350.0 [13.8]
397.3 [15.6]
240.0 [9.4]
220.0 [8.7]
235.0 [9.3]
42.3 [1.7]
8X 14.0 [0.6]
8X 25.0 [1.0]
1
130BE112.10
Mechanical Installation
VLT® AutomationDrive FC 302 Low Harmonic Drive 132-630 kW
3.3.3 Cable Entry and Anchoring
Cables enter the unit through gland plate openings in the bottom. Illustration 3.8, Illustration 3.9, Illustration 3.10, and Illustration 3.11 show gland entry locations and detailed views of anchoring hole dimensions.
33
Bottom View, D1n/D2n
1 Cable entry locations
Illustration 3.8 Cable Entry Diagram, Enclsoure Size D1n
26 Danfoss A/S © Rev. 04/2015 All rights reserved. MG37A302
Loading...
+ 94 hidden pages