Danfoss FC 301, FC 302 Programming guide

ENGINEERING TOMORROW
Programming Guide
VLT® AutomationDrive FC 301/302
Software versions, control card MK I: 7.62, 48.2X Software version, control card MK II: 8.10
www.DanfossDrives.com
Contents Programming Guide
1 Introduction
1.1 Software Version
1.2 Approvals
1.3 Denitions
1.3.1 Frequency Converter 4
1.3.2 Input 4
1.3.3 Motor 4
1.3.4 References 5
1.3.5 Miscellaneous 5
1.4 Safety
1.5 Electrical Wiring
1.6 Integrated Motion Controller
2 How to Program
2.1 Graphical and Numerical Local Control Panels
2.1.1 LCD Display 14
2.1.2 Quick Transfer of Parameter Settings between Multiple Frequency Con­verters 16
4
4
4
4
7
9
12
13
13
2.1.3 Display Mode 16
2.1.4 Display Mode - Selection of Readouts 16
2.1.5 Parameter Set-up 18
2.1.6 Quick Menu Key Functions 18
2.1.7 Initial Commissioning 19
2.1.8 Main Menu Mode 20
2.1.9 Parameter Selection 20
2.1.10 Changing Data 20
2.1.11 Changing a Text Value 21
2.1.12 Changing a Data Value 21
2.1.13 Innitely Variable Change of Numeric Data Value 21
2.1.14 Value, Step by Step 21
2.1.15 Readout and Programming of Indexed Parameters 22
2.1.16 How to Program on the Numerical Local Control Panel 22
2.1.17 LCP Keys 23
3 Parameter Descriptions
3.1 Parameters: 0-** Operation and Display
25
25
3.2 Parameters: 1-** Load and Motor
3.3 Parameters: 2-** Brakes
MG33MO22 Danfoss A/S © 01/2018 All rights reserved.
37
64
Contents
VLT® AutomationDrive FC 301/302
3.4 Parameters: 3-** Reference/Ramps
3.5 Parameters: 4-** Limits/Warnings
3.6 Parameters: 5-** Digital In/Out
3.7 Parameters: 6-** Analog In/Out
3.8 Parameters: 7-** Controllers
3.9 Parameters: 8-** Communications and Options
3.10 Parameters: 9-** PROFIBUS
3.11 Parameters: 10-** DeviceNet CAN Fieldbus
3.12 Parameters: 12-** Ethernet
3.13 Parameters: 13-** Smart Logic Control
3.14 Parameters: 14-** Special Functions
3.15 Parameters: 15-** Drive Information
3.16 Parameters: 16-** Data Readouts
3.17 Parameters: 17-** Feedback
3.18 Parameters: 18-** Data Readouts 2
3.19 Parameters: 19-** Application Parameters
3.20 Parameters: 23-** Time-based Functions
71
84
95
120
130
141
151
151
151
152
176
188
196
204
212
215
215
3.21 Parameters: 30-** Special Features
3.22 Parameters: 32-** MCO Basic Settings
3.23 Parameters: 33-** MCO Advanced Settings
3.24 Parameters: 34-** MCO Data Readouts
3.25 Parameters: 35-** Sensor Input Option
3.26 Parameters: 36-** Programmable I/O Option
3.27 Parameters: 40-** Special Settings
3.28 Parameters: 42-** Safety Functions
3.29 Parameters: 43-** Unit Readouts
4 Integrated Motion Controller
4.1 Introduction
4.2 Positioning, Homing, Synchronization
4.3 Control
5 Parameter Lists
5.1 Introduction
5.2 Parameter Lists and Options, Software Version 8.10 (Standard)
223
227
227
227
227
230
233
233
233
236
236
237
239
242
242
243
5.3 Parameter Lists and Options, Software Version 48.20 (IMC)
6 Troubleshooting
6.1 Status Messages
Danfoss A/S © 01/2018 All rights reserved. MG33MO22
274
297
297
Contents Programming Guide
7 Appendix
7.1 Symbols, Abbreviations, and Conventions
Index
312
312
314
MG33MO22 Danfoss A/S © 01/2018 All rights reserved.
Introduction
VLT® AutomationDrive FC 301/302
11
1 Introduction
1.1 Software Version
Programming Guide
Software versions:
Control card MK I: 7.62, 48.2X, and earlier versions
Control card MK II: 8.10
The software version number can be read from parameter 15-43 Software Version.
Table 1.1 Software Version
1.1.1 Control Card MK II
Software version 8.03 and later can only be installed on control card MK II. Software version 7.62 and earlier can only be installed on control card MK I. Identify the control card version by the color of the USB port: MK I: Black USB port. MK II: White USB port.
1.2 Approvals
1.3 Denitions
1.3.1 Frequency Converter
I
VLT,MAX
Maximum output current.
I
VLT,N
Rated output current supplied by the frequency converter.
U
VLT,MAX
Maximum output voltage.
1.3.2 Input
Control command
Start and stop the connected motor with LCP and digital inputs. Functions are divided into 2 groups.
Functions in group 1 have higher priority than functions in group 2.
Group 1 Reset, coast stop, reset and coast stop, quick stop,
DC brake, stop, the [OFF] key.
Group 2 Start, pulse start, reversing, start reversing, jog,
freeze output.
Table 1.2 Function Groups
1.3.3 Motor
Motor running
Torque generated on output shaft and speed from 0 RPM to maximum speed on motor.
f
JOG
Motor frequency when the jog function is activated (via digital terminals).
f
M
Motor frequency.
f
MAX
Maximum motor frequency.
f
MIN
Minimum motor frequency.
f
M,N
Rated motor frequency (nameplate data).
I
M
Motor current (actual).
I
M,N
Rated motor current (nameplate data).
n
M,N
Nominal motor speed (nameplate data).
n
s
Synchronous motor speed.
2 × par . 1 23 × 60s
ns=
n
slip
Motor slip.
P
M,N
Rated motor power (nameplate data in kW or hp).
T
M,N
Rated torque (motor).
U
M
Instant motor voltage.
U
M,N
Rated motor voltage (nameplate data).
par . 1 39
4 Danfoss A/S © 01/2018 All rights reserved. MG33MO22
175ZA078.10
Pull-out
RPM
Torque
Introduction Programming Guide
1 1
Break-away torque
Figure 1.1 Break-away Torque
η
VLT
The eciency of the frequency converter is dened as the ratio between the power output and the power input.
Start-disable command
A stop command belonging to Group 1 control commands
- see Table 1.2.
Stop command
A stop command belonging to Group 1 control commands
- see Table 1.2.
1.3.4 References
Analog reference
A signal transmitted to the analog inputs 53 or 54 (voltage or current).
Binary reference
A signal transmitted to the serial communication port.
Preset reference
A dened preset reference to be set from -100% to +100% of the reference range. Selection of 8 preset references via the digital terminals.
Pulse reference
A pulse frequency signal transmitted to the digital inputs (terminal 29 or 33).
Ref
MAX
Determines the relationship between the reference input at 100% full scale value (typically 10 V, 20 mA) and the resulting reference. The maximum reference value is set in parameter 3-03 Maximum Reference.
Ref
MIN
Determines the relationship between the reference input at 0% value (typically 0 V, 0 mA, 4 mA) and the resulting reference. The minimum reference value is set in parameter 3-02 Minimum Reference.
1.3.5 Miscellaneous
Analog inputs
The analog inputs are used for controlling various functions of the frequency converter. There are 2 types of analog inputs: Current input, 0–20 mA, and 4–20 mA Voltage input, -10 V DC to +10 V DC.
Analog outputs
The analog outputs can supply a signal of 0–20 mA, 4–20 mA.
Automatic motor adaptation, AMA
AMA algorithm determines the electrical parameters for the connected motor at standstill.
Brake resistor
The brake resistor is a module capable of absorbing the brake power generated in regenerative braking. This regenerative brake power increases the DC-link voltage and a brake chopper ensures that the power is transmitted to the brake resistor.
CT characteristics
Constant torque characteristics used for all applications such as conveyor belts, displacement pumps, and cranes.
Digital inputs
The digital inputs can be used for controlling various functions of the frequency converter.
Digital outputs
The frequency converter features 2 solid-state outputs that can supply a 24 V DC (maximum 40 mA) signal.
DSP
Digital signal processor.
ETR
Electronic thermal relay is a thermal load calculation based on present load and time. Its purpose is to estimate the motor temperature.
Hiperface
Hiperface® is a registered trademark by Stegmann.
Initializing
If initializing is carried out (parameter 14-22 Operation Mode), the frequency converter returns to the default
setting.
®
MG33MO22 Danfoss A/S © 01/2018 All rights reserved. 5
Introduction
VLT® AutomationDrive FC 301/302
11
Intermittent duty cycle
An intermittent duty rating refers to a sequence of duty cycles. Each cycle consists of an on-load and an o-load period. The operation can be either periodic duty or non­periodic duty.
LCP
The local control panel makes up a complete interface for control and programming of the frequency converter. The control panel is detachable and can be installed up to 3 m (10 ft) from the frequency converter, that is, in a front panel with the installation kit option.
NLCP
Numerical local control panel interface for control and programming of the frequency converter. The display is numerical and the panel is used to show process values. The NLCP has no storage and copy functions.
lsb
Least signicant bit.
msb
Most signicant bit.
MCM
Short for mille circular mil, an American measuring unit for cable cross-section. 1 MCM=0.5067 mm2.
Online/oine parameters
Changes to online parameters are activated immediately after the data value is changed. Press [OK] to activate changes to o-line parameters.
Process PID
The PID control maintains the required speed, pressure, temperature, and so on, by adjusting the output frequency to match the varying load.
PCD
Process control data.
Power cycle
Switch o the mains until display (LCP) is dark, then turn power on again.
Pulse input/incremental encoder
An external, digital pulse transmitter used for feeding back information on motor speed. The encoder is used in applications where great accuracy in speed control is required.
RCD
Residual current device.
Set-up
Save parameter settings in 4 set-ups. Change between the 4 parameter set-ups and edit 1 set-up, while another set­up is active.
SFAVM
Switching pattern called stator ux-oriented asynchronous vector modulation (parameter 14-00 Switching Pattern).
Slip compensation
The frequency converter compensates for the motor slip by giving the frequency a supplement that follows the measured motor load keeping the motor speed almost constant.
SLC
The SLC (smart logic control) is a sequence of user-dened actions executed when the associated user-dened events are evaluated as true by the SLC. (See chapter 3.13 Parameters: 13-** Smart Logic Control).
STW
Status word.
FC standard bus
Includes RS485 bus with FC protocol or MC protocol. See parameter 8-30 Protocol.
THD
Total harmonic distortion states the total contribution of harmonic.
Thermistor
A temperature-dependent resistor placed on the frequency converter or the motor.
Trip
A state entered in fault situations, for example if the frequency converter is subject to an overtemperature or when the frequency converter is protecting the motor, process, or mechanism. The frequency converter prevents a restart until the cause of the fault has disappeared. To cancel the trip state, restart the frequency converter. Do not use the trip state for personal safety.
Trip lock
The frequency converter enters this state in fault situations to protect itself. The frequency converter requires physical intervention, for example when there is a short circuit on the output. A trip lock can only be canceled by discon­necting mains, removing the cause of the fault, and reconnecting the frequency converter. Restart is prevented until the trip state is canceled by activating reset or, sometimes, by being programmed to reset automatically. Do not use the trip lock state for personal safety.
VT characteristics
Variable torque characteristics used for pumps and fans.
+
VVC
If compared with standard voltage/frequency ratio control, voltage vector control (VVC+) improves the dynamics and the stability, both when the speed reference is changed and in relation to the load torque.
60° AVM
60° asynchronous vector modulation (parameter 14-00 Switching Pattern).
6 Danfoss A/S © 01/2018 All rights reserved. MG33MO22
Introduction Programming Guide
1 1
Power factor
The power factor is the relation between I1 and I
2
 + I
1
3xUxI1cosϕ
3xUxI
I1xcosϕ1
I
RMS
2
2
 + I
 + .. + I
5
7
RMS
 = 
I
1
sincecosϕ1 = 1
I
RMS
2
n
RMS
Powerfactor = 
The power factor for 3-phase control:
Powerfactor = 
The power factor indicates to which extent the frequency converter imposes a load on the mains supply. The lower the power factor, the higher the I same kW performance.
I
= 
RMS
In addition, a high-power factor indicates that the dierent harmonic currents are low. The DC coils in the frequency converters produce a high­power factor, which minimizes the imposed load on the mains supply.
Target position
The nal target position specied by positioning commands. The prole generator uses this position to calculate the speed prole.
Commanded position
The actual position reference calculated by the prole generator. The frequency converter uses the commanded position as setpoint for position PI.
Actual position
The actual position from an encoder, or a value that the motor control calculates in open loop. The frequency converter uses the actual position as feedback for position PI.
Position error
Position error is the dierence between the actual position and the commanded position. The position error is the input for the position PI controller.
Position unit
The physical unit for position values.
I
.
RMS
for the
Safety
1.4
WARNING
HIGH VOLTAGE
Frequency converters contain high voltage when connected to AC mains input, DC supply, or load sharing. Failure to perform installation, start-up, and maintenance by qualied personnel can result in death or serious injury.
Only qualied personnel must perform instal-
lation, start-up, and maintenance.
Before performing any service or repair work,
use an appropriate voltage measuring device to make sure that there is no remaining voltage on the drive.
Safety regulations
Disconnect mains supply to the frequency
converter whenever repair work is to be carried out. Check that the mains supply has been disconnected and that the necessary time has elapsed before removing motor and mains supply plugs. For information about the discharge time, see Table 1.3.
[O] does not disconnect the mains supply and
must not be used as a safety switch.
Ground the equipment properly, protect the user
against supply voltage, and protect the motor against overload in accordance with applicable national and local regulations.
The ground leakage current exceeds 3.5 mA.
Ensure correct grounding of the equipment by a certied electrical installer.
Do not remove the plugs for the motor and
mains supply while the frequency converter is connected to mains. Check that the mains supply has been disconnected and that the necessary time has elapsed before removing motor and mains plugs.
The frequency converter has more voltage
sources than L1, L2, and L3, when load sharing (linking of DC intermediate circuit) or external 24 V DC is installed. Check that all voltage sources have been disconnected and that the necessary time has elapsed before commencing repair work. For information about the discharge time, see Table 1.3.
MG33MO22 Danfoss A/S © 01/2018 All rights reserved. 7
Introduction
VLT® AutomationDrive FC 301/302
11
WARNING
UNINTENDED START
When the frequency converter is connected to AC mains, DC supply, or load sharing, the motor may start at any time. Unintended start during programming, service, or repair work can result in death, serious injury, or property damage. The motor can start via an external switch, a eldbus command, an input reference signal from the LCP, or after a cleared fault condition.
To prevent unintended motor start:
Disconnect the frequency converter from the
mains.
Press [O/Reset] on the LCP before
programming parameters.
Completely wire and assemble the frequency
converter, motor, and any driven equipment before connecting the frequency converter to AC mains, DC supply, or load sharing.
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors, which can remain charged even when the frequency converter is not powered. High voltage can be present even when the warning LED indicator lights are o. Failure to wait the specied time after power has been removed before performing service or repair work can result in death or serious injury.
Stop the motor.
Disconnect AC mains and remote DC-link power
supplies, including battery back-ups, UPS, and DC-link connections to other frequency converters.
Disconnect or lock PM motor.
Wait for the capacitors to discharge fully. The
minimum duration of waiting time is specied in Table 1.3 and is also visible on the product label on top of the frequency converter.
Before performing any service or repair work,
use an appropriate voltage measuring device to make sure that the capacitors are fully discharged.
Voltage [V] Minimum waiting time (minutes)
4 7 15
200–240 0.25–3.7 kW
(0.34–5 hp)
380–500 0.25–7.5 kW
(0.34–10 hp)
525–600 0.75–7.5 kW
(1–10 hp)
525–690 1.5–7.5 kW
Table 1.3 Discharge Time
5.5–37 kW
(7.5–50 hp)
11–75 kW
(15–100 hp)
11–75 kW
(15–100 hp)
(2–10 hp)
(15–100 hp)
11–75 kW
NOTICE!
When using the Safe Torque O, always follow the
instructions in VLT® Frequency Converters - Safe Torque
O Operating Instructions.
NOTICE!
Control signals from, or internally within, the frequency converter may in rare cases be activated in error, be delayed, or fail to occur entirely. When used in situations where safety is critical, for example when controlling the electromagnetic brake function of a hoist application, do not rely on these control signals exclusively.
NOTICE!
Hazardous situations must be identied by the machine builder/integrator who is responsible for considering the necessary preventive means. More monitoring and protective devices may be included, always according to valid national safety regulations, for example law on mechanical tools and regulations for the prevention of accidents.
Crane, lifts, and hoists
The controlling of external brakes must always have a redundant system. The frequency converter can in no circumstances be the primary safety circuit. Comply with relevant standards, for example: Hoists and cranes: IEC 60204-32 Lifts: EN 81
Protection mode
Once a hardware limit on motor current or DC-link voltage is exceeded, the frequency converter enters the protection mode. Protection mode means a change of the PWM modulation strategy and a low switching frequency to minimize losses. This continues for 10 s after the last fault and increases the reliability and the robustness of the frequency converter while re-establishing full control of the motor.
8 Danfoss A/S © 01/2018 All rights reserved. MG33MO22
3 Phase power
input
DC bus
Switch Mode Power Supply
Motor
Analog Output
Interface
relay 1
relay 2
ON=Terminated OFF=Open
Brake resistor
130BC931.12
91 (L1) 92 (L2) 93 (L3)
PE
88 (-) 89 (+)
50 (+10 V OUT)
53 (A IN)
54 (A IN)
55 (COM A IN)
0/4-20 mA
12 (+24 V OUT)
13 (+24 V OUT)
37 (D IN)
18 (D IN)
20 (COM D IN)
10 V DC 15 mA 130/200 mA
+ - + -
(U) 96 (V) 97 (W) 98 (PE) 99
(COM A OUT) 39
(A OUT) 42
(P RS485) 68
(N RS485) 69
(COM RS485) 61
0V
5V
S801
0/4-20 mA
RS485
RS485
03
+10 V DC
0/-10 V DC -
+10 V DC
+10 V DC 0/4-20 mA
0/-10 V DC -
240 V AC, 2 A
24 V DC
02
01
05
04
06
240 V AC, 2 A
24 V (PNP)
0 V (NPN)
0 V (NPN)
24 V (PNP)
19 (D IN)
24 V (PNP)
0 V (NPN)
27
24 V
0 V
(D IN/OUT)
0 V (NPN)
24 V (PNP)
(D IN/OUT)
0 V
24 V
29
24 V (PNP)
0 V (NPN)
0 V (NPN)
24 V (PNP)
33 (D IN)
32 (D IN)
1 2
ON
S201
ON
21
S202
ON=0/4-20 mA OFF=0/-10 V DC ­ +10 V DC
95
400 V AC, 2 A
Par. E-00
21
ON
S801
(R+) 82
(R-) 81
: Chassis
: Earth
1)
2)
1)
1)
Introduction Programming Guide
1 1
In hoist applications, protection mode is not usable because the frequency converter is unable to leave this mode again and therefore it extends the time before activating the brake, which is not recommended. Protection mode can be disabled by setting parameter 14-26 Trip Delay at Inverter Fault to 0, which means that the frequency converter trips immediately if 1 of the hardware limits is exceeded.
1.5 Electrical Wiring
NOTICE!
Disabling protection mode in hoisting applications (parameter 14-26 Trip Delay at Inverter Fault = 0) is recommended.
Figure 1.2 Basic Wiring Schematic Drawing
A=Analog, D=Digital Terminal 37 is used for Safe Torque O. For Safe Torque O installation instructions, refer to the VLT® Frequency Converters -
Safe Torque O Operating Instructions.
MG33MO22 Danfoss A/S © 01/2018 All rights reserved. 9
12 13 18 19 27 29 32 33 20 37
+24 V DC
0 VDC
130BT106.10
PNP (Source)
Digital input wiring
NPN (Sink) Digital input wiring
12 13 18 19 27 29 32 33 20 37
+24 V DC
0 VDC
130BT107.11
130BA681.10
Introduction
VLT® AutomationDrive FC 301/302
11
1) Terminal 37 is not included in FC 301 (except enclosure type A1). Relay 2 and terminal 29 have no function in FC 301.
2) Do not connect cable shield.
Very long control cables and analog signals may in rare cases, and depending on installation, result in 50/60 Hz ground loops due to noise from mains supply cables.
If 50/60 Hz ground loops occur, consider breaking the shield or insert a 100 nF capacitor between shield and enclosure.
To avoid ground currents from both groups to
aect other groups, connect the digital and analog inputs and outputs separately to the common inputs (terminals 20, 55, and 39) of the frequency converter. For example, switching on the digital input may disturb the analog input signal.
Input polarity of control terminals
NOTICE!
Control cables must be shielded/armored.
See the section Grounding of Shielded Control Cables in the design guide for the correct termination of control cables.
Figure 1.3 PNP (Source)
Figure 1.4 NPN (Sink)
10 Danfoss A/S © 01/2018 All rights reserved. MG33MO22
Figure 1.5 Grounding of Shielded/Armored Control Cables
Introduction Programming Guide
1 1
1.5.1 Start/Stop
Terminal 18 = Parameter 5-10 Terminal 18 Digital Input [8] Start. Terminal 27 = Parameter 5-12 Terminal 27 Digital Input [0] No operation (Default [2] Coast inverse). Terminal 37 = Safe Torque O (where available).
1.5.2 Pulse Start/Stop
Terminal 18 = Parameter 5-10 Terminal 18 Digital Input, [9] Latched start. Terminal 27 = Parameter 5-12 Terminal 27 Digital Input, [6] Stop inverse. Terminal 37 = Safe Torque O (where available).
Figure 1.6 Start/Stop
Figure 1.7 Pulse Start/Stop
MG33MO22 Danfoss A/S © 01/2018 All rights reserved. 11
12
18
27
29
32
37
+24V
Par. 5-10
Par. 5-12
Par. 5-13
Par. 5-14
130BA021.12
130BA154.11
Speed RPM P 6-15
Ref. voltage P 6-11 10 V
1 k
+10 V/30 mA
Introduction
VLT® AutomationDrive FC 301/302
11
1.5.3 Speed up/Speed Down
Terminals 29/32 = Speed up/Speed down
Terminal 18 = Parameter 5-10 Terminal 18 Digital Input [9] Start (default).
Terminal 27 = Parameter 5-12 Terminal 27 Digital Input [19] Freeze reference.
Terminal 29 = Parameter 5-13 Terminal 29 Digital Input [21] Speed up.
Terminal 32 = Parameter 5-14 Terminal 32 Digital Input [22] Speed down.
NOTICE!
Terminal 29 only in FC x02 (x=series type).
1.5.4 Potentiometer Reference
Voltage reference via a potentiometer
Reference source 1 = [1] Analog input 53 (default).
Terminal 53, low voltage = 0 V.
Terminal 53, high voltage = 10 V.
Terminal 53, low reference/feedback = 0 RPM.
Terminal 53, high reference/feedback = 1500 RPM.
Switch S201 = OFF (U)
Figure 1.8 Speed up/Speed down
Figure 1.9 Potentiometer Reference
1.6 Integrated Motion Controller
The integrated motion controller (IMC) enables position control. For more information about IMC, see chapter 4 Integrated Motion Controller.
12 Danfoss A/S © 01/2018 All rights reserved. MG33MO22
Auto
on
Reset
Hand
on
O
Status
Quick Menu
Main
Menu
Alarm
Log
Back
Cancel
Info
OK
Status
1(0)
1234rpm 10,4A 43,5Hz
Run OK
43,5Hz
On
Alarm
Warn.
130BA018.13
1
2
3
4
b
a
c
How to Program Programming Guide
2 How to Program
2.1 Graphical and Numerical Local Control Panels
Easy programming of the frequency converter is done via the graphical LCP (LCP 102). For information about using the numerical local control panel (LCP 101), see
chapter 2.1.16 How to Program on the Numerical Local Control Panel.
The LCP is divided into 4 functional groups:
1. Graphical display with status lines.
2. Menu keys and indicator lights - changing parameters and switching between display functions.
3. Navigation keys and indicator lights.
4. Operation keys and indicator lights.
The LCP display can show up to 5 items of operating data while showing Status.
Display lines:
a. Status line: Status messages showing icons and
graphics.
b. Line 1–2: Operator data lines showing data
dened or selected. Add up to 1 extra line by pressing [Status].
c. Status line: Status messages showing text.
2 2
NOTICE!
If start-up is delayed, the LCP shows the INITIALIZING message until it is ready. Adding or removing options can delay the start-up.
MG33MO22 Danfoss A/S © 01/2018 All rights reserved. 13
Figure 2.1 LCP
Top section
Middle section
Bottom section
Status
43 RPM
1.4 Hz
Auto Remote Running
! Pwr.card temp (W29)
2.9%
5.44 A 25.3 kW
1(1)
130BP074.10
!
On
Warn.
Alarm
130BP044.10
130BP045.10
Status
Quick Menu
Main Menu
Alarm
Log
How to Program
VLT® AutomationDrive FC 301/302
2.1.1 LCD Display
Flashing Red LED/Alarm: Indicates an alarm.
22
The display has backlight and a total of 6 alpha-numeric lines. The display lines show the direction of rotation (arrow), the selected set-up, and the programming set-up. The display is divided into 3 sections.
Top section
The top section shows up to 2 measurements in normal operating status.
Middle section
The top line shows up to 5 measurements with related unit, regardless of status (except in the case of alarm/ warning).
Bottom section
The bottom section always shows the state of the frequency converter in Status mode.
Figure 2.3 Indicator Lights
LCP keys
The control keys are divided into functions. The keys below the display and indicator lights are used for parameter set­up, including option of display indication during normal operation.
Figure 2.4 LCP Keys
Figure 2.2 Display
The active set-up (selected as the active set-up in parameter 0-10 Active Set-up) is shown. When programming another set-up than the active set-up, the number of the programmed set-up appears to the right.
Display contrast adjustment
Press [Status] and [▲] for darker display. Press [Status] and [▼] for brighter display.
Most parameter set-ups can be changed immediately via the LCP, unless a password has been created via
parameter 0-60 Main Menu Password or via parameter 0-65 Quick Menu Password.
Indicator lights
If certain threshold values are exceeded, the alarm and/or warning indicator lights up. A status and alarm text appear on the LCP. The ON indicator light is activated when the frequency converter receives mains voltage or via a DC bus terminal or 24 V external supply. At the same time, the back indicator light is on.
Green LED/On: Control section is working.
Yellow LED/Warn: Indicates a warning.
14 Danfoss A/S © 01/2018 All rights reserved. MG33MO22
[Status]
Indicates the status of the frequency converter and/or the motor. Select between 3 dierent readouts by pressing [Status]: 5 line readouts, 4 line readouts, or smart logic control. Press [Status] for selecting the mode of display or for changing back to display mode from either the quick menu mode, the main menu mode, or the alarm mode. Also use [Status] to toggle single or double readout mode.
[Quick Menu]
Allows quick access to dierent quick menus such as:
My personal menu.
Quick set-up.
Changes made.
Loggings.
Press [Quick Menu] to program the parameters belonging to the Quick Menu. It is possible to switch directly between quick menu mode and main menu mode.
[Main Menu]
Is used for programming all parameters. It is possible to switch directly between main menu mode and quick menu mode.
B
a
c
k
C
a
n
c
e
l
I
n
f
o
130BP046.10
Hand
on
O
Auto
on
Reset
How to Program Programming Guide
Parameter shortcut can be carried out by pressing down [Main Menu] for 3 s. The parameter shortcut allows direct access to any parameter.
[Alarm Log]
Shows an alarm list of the 5 latest alarms (numbered A1– A5). To obtain extra details about an alarm, press the navigation keys to maneuver to the alarm number and press [OK]. Information is shown about the condition of the frequency converter before it enters the alarm mode.
[Back]
Returns to the previous step or layer in the navigation structure.
[Cancel]
Last change or command is canceled as long as the display has not been changed.
[Info]
Supplies information about a command, parameter, or function in any display window. [Info] provides detailed information whenever help is needed. Exit Info mode by pressing either [Info], [Back], or [Cancel].
Figure 2.5 Back
Figure 2.6 Cancel
Figure 2.7 Info
Navigation keys
The 4 navigation keys are used to navigate between the dierent options available in Quick Menu, Main Menu, and Alarm Log. Press the keys to move the cursor.
[OK]
Press for selecting a parameter marked by the cursor and for enabling the change of a parameter.
Local control keys
Local control keys are at the bottom of the LCP.
Figure 2.8 Local Control Keys
[Hand On]
Enables control of the frequency converter via the LCP. [Hand On] also starts the motor, and it is now possible to enter the motor speed data with the navigation keys. The key can be selected as [1] Enable or [0] Disable via parameter 0-40 [Hand on] Key on LCP. External stop signals activated with control signals or a eldbus override a start command via the LCP.
The following control signals are still active when [Hand On] is activated:
[Hand on] - [O] - [Auto On].
Reset.
Coast stop inverse.
Reversing.
Set-up select bit 0 - Set-up select bit 1.
Stop command from serial communication.
Quick stop.
DC brake.
[O]
Stops the connected motor. The key can be selected as [1] Enable or [0] Disable via parameter 0-41 [O] Key on LCP. If
no external stop function is selected and the [O] key is inactive, the motor can be stopped by disconnecting the voltage.
[Auto On]
Enables the frequency converter to be controlled via the control terminals and/or serial communication. When a start signal is applied on the control terminals and/or the bus, the frequency converter starts. The key can be selected as [1] Enable or [0] Disable via parameter 0-42 [Auto on] Key on LCP.
NOTICE!
An active HAND-OFF-AUTO signal via the digital inputs has higher priority than the control keys [Hand On] – [Auto On].
[Reset]
Is used for resetting the frequency converter after an alarm (trip). It can be selected as [1] Enable or [0] Disable via parameter 0-43 [Reset] Key on LCP.
2 2
MG33MO22 Danfoss A/S © 01/2018 All rights reserved. 15
Auto
on
Reset
Hand
on
O
Status
Quick Menu
Main
Menu
Alarm
Log
Back
Cancel
Info
OK
On
Alarm
Warn.
130BA027.10
How to Program
VLT® AutomationDrive FC 301/302
The parameter shortcut can be carried out by pressing
22
down the [Main Menu] key for 3 s. The parameter shortcut provides direct access to any parameter.
2.1.2 Quick Transfer of Parameter Settings between Multiple Frequency Converters
Once the set-up of a frequency converter is complete, store the data in the LCP or on a PC via MCT 10 Set-up Software.
NOTICE!
Stop the motor before performing this operation.
To transfer the data from the LCP to the frequency converter:
1. Go to parameter 0-50 LCP Copy.
2. Press the [OK] key.
3. Select [2] All from LCP.
4. Press the [OK] key.
The parameter settings stored in the LCP are now transferred to the frequency converter indicated by the progress bar. When 100% is reached, press [OK].
2.1.3 Display Mode
In normal operation, up to 5 dierent operating variables can be indicated continuously in the middle section: 1.1,
1.2, and 1.3, as well as 2 and 3.
2.1.4 Display Mode - Selection of Readouts
orstår detIt is possible to toggle between 3 status readout screens by pressing [Status]. Operating variables with dierent formatting are shown in each status view further in this section.
Figure 2.9 LCP
Data storage in LCP
NOTICE!
Stop the motor before performing this operation.
To store the data in the LCP:
1. Go to parameter 0-50 LCP Copy.
2. Press the [OK] key.
3. Select [1] All to LCP.
4. Press the [OK] key.
All parameter settings are now stored in the LCP indicated by the progress bar. When 100% is reached, press [OK].
Connect the LCP to another frequency converter and copy the parameter settings to this frequency converter as well.
Data transfer from LCP to frequency converter
Table 2.1 shows the measurements that can be linked to each of the operating variables. When options are mounted, additional measurements are available.
Dene the links via
Parameter 0-20 Display Line 1.1 Small.
Parameter 0-21 Display Line 1.2 Small.
Parameter 0-22 Display Line 1.3 Small.
Parameter 0-23 Display Line 2 Large.
Parameter 0-24 Display Line 3 Large.
Each readout parameter selected in parameter 0-20 Display Line 1.1 Small to parameter 0-24 Display Line 3 Large has its
own scale and digits after a possible decimal point. The larger the numeric value of a parameter is, the fewer digits are shown after the decimal point. Example: Current readout 5.25 A, 15.2 A, 105 A.
Operating variable Unit
Parameter 16-00 Control Word hex Parameter 16-01 Reference [Unit] [Unit] Parameter 16-02 Reference [%] % Parameter 16-03 Status Word hex Parameter 16-05 Main Actual Value [%] %
16 Danfoss A/S © 01/2018 All rights reserved. MG33MO22
1.1
2
3
1.3
1.2
130BP041.10
799 RPM
Auto Remote Ramping
1 (1)
36.4 kW7.83 A
0.000
53.2%
Status
1.1
1.2
2
1.3
130BP062.10
207RPM
Auto Remote Running
1 (1)
24.4 kW5.25A
6.9Hz
Status
130BP063.10
778 RPM
Auto Remote Running
1 (1)
4.0 kW0.86 A
State: 0 o 0 (o) When: ­Do: -
Status
How to Program Programming Guide
Operating variable Unit
Parameter 16-10 Power [kW] [kW] Parameter 16-11 Power [hp] [hp] Parameter 16-12 Motor Voltage [V ] Parameter 16-13 Frequency [Hz] Parameter 16-14 Motor current [A] Parameter 16-16 Torque [Nm] Nm Parameter 16-17 Speed [RPM] [RPM] Parameter 16-18 Motor Thermal %
Parameter 16-20 Motor Angle Parameter 16-30 DC Link Voltage V Parameter 16-32 Brake Energy /s kW Parameter 16-33 Brake Energy Average kW
Parameter 16-34 Heatsink Temp. Parameter 16-35 Inverter Thermal % Parameter 16-36 Inv. Nom. Current A Parameter 16-37 Inv. Max. Current A
Parameter 16-38 SL Controller State
Parameter 16-39 Control Card Temp.
Parameter 16-40 Logging Buer Full
Parameter 16-50 External Reference
Parameter 16-51 Pulse Reference Parameter 16-52 Feedback [Unit] [Unit]
Parameter 16-53 Digi Pot Reference Parameter 16-60 Digital Input bin Parameter 16-61 Terminal 53 Switch Setting V
Parameter 16-62 Analog Input 53 Parameter 16-63 Terminal 54 Switch Setting V
Parameter 16-64 Analog Input 54 Parameter 16-65 Analog Output 42 [mA] [mA] Parameter 16-66 Digital Output [bin] [bin] Parameter 16-67 Pulse Input #29 [Hz] [Hz] Parameter 16-68 Freq. Input #33 [Hz] [Hz] Parameter 16-69 Pulse Output #27 [Hz] [Hz] Parameter 16-70 Pulse Output #29 [Hz] [Hz]
Parameter 16-71 Relay Output [bin]
Parameter 16-72 Counter A
Parameter 16-73 Counter B Parameter 16-80 Fieldbus CTW 1 hex Parameter 16-82 Fieldbus REF 1 hex Parameter 16-84 Comm. Option Status hex Parameter 16-85 FC Port CTW 1 hex Parameter 16-86 FC Port REF 1 hex
Parameter 16-90 Alarm Word
Parameter 16-92 Warning Word
Parameter 16-94 Ext. Status Word
Table 2.1 Units
°C
°C
Status view I
This readout state is standard after start-up or initialization. Press [Info] to obtain information about the units linked to the shown operating variables (1.1, 1.2, 1.3, 2 and 3). See the operating variables shown in Figure 2.10.
Figure 2.10 Status View I
Status view II
See the operating variables (1.1, 1.2, 1.3, and 2) shown in Figure 2.11. In the example, speed, motor current, motor power, and frequency are selected as variables in the 1st and 2nd lines.
Figure 2.11 Status View II
Status view III
This state shows the event and action of the smart logic control. For further information, see chapter 3.13 Parameters: 13-** Smart Logic Control.
Figure 2.12 Status View III
2 2
MG33MO22 Danfoss A/S © 01/2018 All rights reserved. 17
130BC916.10
Q1 My Personal Menu
Q2 Quick Setup
Q4 Smart Setup
Q5 Changes Made
0RPM 0.00A 1(1)
Quick Menus
How to Program
VLT® AutomationDrive FC 301/302
2.1.5 Parameter Set-up
22
The frequency converter can be used for practically all assignments. The frequency converter oers an option between 2 programming modes:
Main menu mode.
Quick menu mode.
Main menu provides access to all parameters. Quick menu takes the user through a few parameters, making it possible to start operating the frequency converter. Change a parameter in either main menu mode or quick menu mode.
2.1.6 Quick Menu Key Functions
Press [Quick Menu] to enter a list of dierent areas contained in the Quick Menu. Select Q1 My Personal Menu to show the selected personal parameters. These parameters are selected in parameter 0-25 My Personal Menu. Up to 50 dierent parameters can be added in this menu.
Parameter Setting
Parameter 0-01 LanguageParameter 0-01 L
anguage Parameter 1-20 Motor Power [kW] [kW] Parameter 1-22 Motor Voltage [V ] Parameter 1-23 Motor Frequency [Hz] Parameter 1-24 Motor Current [A] Parameter 1-25 Motor Nominal Speed [RPM]
Parameter 5-12 Terminal 27 Digital Input
Parameter 1-29 Automatic Motor
Adaptation (AMA) Parameter 3-02 Minimum Reference [RPM] Parameter 3-03 Maximum Reference [RPM] Parameter 3-41 Ramp 1 Ramp-up Time [s] Parameter 3-42 Ramp 1 Ramp-down Time [s] Parameter 3-13 Reference Site
Table 2.2 Selection of Parameter
1) If terminal 27 is set to [0] No function, no connection to +24 V on
terminal 27 is necessary.
[0] No function [1] Enable complete AMA
1)
Select Changes made to get information about:
The last 10 changes. Use the [▲] [▼] navigation
keys to scroll between the last 10 changed parameters.
The changes made since default setting.
Select Loggings to get information about the show line readouts. The information is shown as graphs. Only parameters selected in parameter 0-20 Display Line 1.1
Figure 2.13 Quick Menus
Small and parameter 0-24 Display Line 3 Large can be viewed. It is possible to store up to 120 samples in the memory for later reference.
Select Q2 Quick Setup to go through a selection of parameters to get the motor running almost optimally. The default settings for the other parameters consider the required control functions and the conguration of signal inputs/outputs (control terminals).
The parameter selection is eected with the navigation keys. The parameters in Table 2.2 are accessible.
18 Danfoss A/S © 01/2018 All rights reserved. MG33MO22
Quick Menu
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
How to Program Programming Guide
2.1.7 Initial Commissioning
The easiest way of carrying out the initial commissioning is by pressing [Quick Menu] and following the quick set-up procedure using LCP 102 (read Table 2.3 from left to right). The example applies to open-loop applications.
Press
Q2 Quick Menu.
2 2
Parameter 0-01 LanguageParameter 0-
01 Language
Parameter 1-20 Motor Power [kW]
Parameter 1-22 Motor Voltage
Parameter 1-23 Motor Frequency
Parameter 1-24 Motor Current
Parameter 1-25 Motor Nominal Speed
Parameter 5-12 Terminal 27 Digital
Input
Parameter 1-29 Automatic Motor
Adaptation (AMA)
Set language.
Set motor nameplate power.
Set nameplate voltage.
Set nameplate frequency.
Set nameplate current.
Set nameplate speed in RPM.
If terminal default is [2] Coast inverse, it is possible to change this setting to [0] No function. No connection to terminal 27 is then needed for running AMA. Set desired AMA function. Enable complete AMA is recommended.
Parameter 3-02 Minimum Reference
Parameter 3-03 Maximum Reference
Set the minimum speed of the motor shaft.
Set the maximum speed of the motor shaft.
Set the ramp-up time with
Parameter 3-41 Ramp 1 Ramp-up Time
Parameter 3-42 Ramp 1 Ramp-down
Time
Parameter 3-13 Reference Site
reference to synchronous motor speed, ns. Set the ramp-down time with reference to synchronous motor speed, ns.
Set the site from where the reference must work.
Table 2.3 Quick Set-up Procedure
MG33MO22 Danfoss A/S © 01/2018 All rights reserved. 19
130BP066.10
1107 RPM
0 - ** Operation/Display
1 - ** Load/Motor
2 - ** Brakes
3 - ** Reference / Ramps
3.84 A 1 (1)
Main Menu
130BP067.10
740RPM
0 -01 Language
[0] English
10.64A 1 [1] 0-0*
Basic Settings
How to Program
VLT® AutomationDrive FC 301/302
Another easy way of commissioning the frequency
22
converter is by using the smart application set-up (SAS), which can also be found by pressing [Quick Menu]. To set up the applications listed, follow the instructions on the successive screens.
The [Info] key can be used throughout the SAS to see help information for various selections, settings, and messages. The following 3 applications are included:
Mechanical brake.
Conveyor.
Pump/fan.
The following 4 eldbusses can be selected:
PROFIBUS.
PROFINET.
DeviceNet.
EtherNet/IP.
NOTICE!
The frequency converter ignores the start conditions when SAS is active.
Each parameter has a name and number which remain the same regardless of the programming mode. In the main menu mode, the parameters are divided into groups. The rst digit of the parameter number (from the left) indicates the parameter group number.
All parameters can be changed in the Main Menu. However, depending on the choice of conguration (parameter 1-00 Conguration Mode), some parameters can be hidden. For example, open loop hides all the PID parameters, and other enabled options make more parameter groups visible.
2.1.9 Parameter Selection
In the main menu mode, the parameters are divided into groups. Select a parameter group with the navigation keys.
After selecting a parameter group, select a parameter with the navigation keys. The middle section on the display shows the parameter number and name, and the selected parameter value.
NOTICE!
The smart set-up runs automatically on the rst power­up of the frequency converter or after a reset to factory settings. If no action is taken, the SAS screen automat­ically disappears after 10 minutes.
2.1.8 Main Menu Mode
Press [Main Menu] to enter the main menu mode. The readout in Figure 2.14 appears on the display. The middle and bottom sections in the display show a list of parameter groups, which can be selected by toggling the [▲] and [▼] keys.
Figure 2.14 Main Menu Mode
Figure 2.15 Parameter Selection
2.1.10 Changing Data
The procedure for changing data is the same in the quick menu mode and the main menu mode. Press [OK] to change the selected parameter. The procedure for changing data depends on whether the selected parameter represents a numeric data value or a text value.
20 Danfoss A/S © 01/2018 All rights reserved. MG33MO22
130BP068.10
740RPM
0 -01 Language
[0] English
10.64 A 1 [1] 0-0*
Basic Settings
130BP069.10
1- 6*
113 RPM 1.78 A 1(1)
Load depen. setting
1 - 60 Low speed load
compensation
1
0
0%
130BP070.10
1 - 60 Low speed load compensation
1 0%
Load depen. setting 1- 6*
729RPM 6.21A 1(1)
6
130BP072.10
957RPM
1-71 High starting torque time
0. s
11.58A 1 (1)
1-7*Start Adjustments
4
How to Program Programming Guide
2.1.11 Changing a Text Value
If the selected parameter is a text value, change the text value with the [▲] [▼] keys. Place the cursor on the value to save and press [OK].
Figure 2.16 Changing a Text Value
2.1.12 Changing a Data Value
If the selected parameter shows a numeric data value, change the selected data value with the [◀] [▶] navigation keys and the [▲] [▼] navigation keys. Press [◀] [▶] keys to move the cursor horizontally.
2.1.13 Innitely Variable Change of Numeric Data Value
If the selected parameter shows a numeric data value, select a digit with [◀] [▶].
Figure 2.19 Selecting a Digit
Change the selected digit innitely variably with [▲] [▼]. The cursor indicates the selected digit. Place the cursor on the digit to save and press [OK].
2 2
Figure 2.17 Changing a Data Value
Figure 2.20 Saving
2.1.14 Value, Step by Step
Press [▲] [▼] keys to change the data value. [▲] increases the data value, and [▼] decreases the data value. Place the cursor on the value to save and press [OK].
Figure 2.18 Saving a Data Value
MG33MO22 Danfoss A/S © 01/2018 All rights reserved. 21
Certain parameters can be changed step by step. This applies to:
Parameter 1-20 Motor Power [kW].
Parameter 1-22 Motor Voltage.
Parameter 1-23 Motor Frequency.
The parameters are changed both as a group of numeric data values and as numeric data values that are
innitely
varying.
130BA191.10
1
Auto
on
Reset
Hand
on
O
Menu
Status
Quick Setup
Main Menu
Back
2
3
4
OK
On
Alarm
Warn.
Setup
130BP077.10
22.8
rpm
Setup 1
How to Program
VLT® AutomationDrive FC 301/302
2.1.15 Readout and Programming of
22
Parameters are indexed when placed in a rolling stack.
Parameter 15-30 Fault Log: Error Code to parameter 15-32 Alarm Log: Time contain a fault log, which
can be read out. Select a parameter, press [OK], and press the keys [▲] [▼] to scroll through the value log.
For example, parameter 3-10 Preset Reference is changed as follows:
Indexed Parameters
1.
Select the parameter, press [OK], and press [▲] [▼] to scroll through the indexed values.
2. To change the parameter value, select the indexed value and press [OK].
3.
Change the value by pressing [▲] [▼].
4. Press [OK] to accept the new setting.
5. Press [Cancel] to abort. Press [Back] to leave the parameter.
2.1.16 How to Program on the Numerical Local Control Panel
The following instructions are valid for the numerical LCP (LCP 101). The control panel is divided into 4 functional groups:
Numerical display.
Menu keys and indicator lights - changing
parameters and switching between display functions.
Navigation keys and indicator lights.
Operation keys and indicator lights.
Display line
Status messages showing icons and numeric value.
Indicator lights
Green LED/On: Indicates if control section is on.
Yellow LED/Wrn: Indicates a warning.
Flashing red LED/Alarm: Indicates an alarm.
LCP keys [Menu]
Select 1 of the following modes:
Status.
Quick set-up.
Main menu.
Figure 2.21 LCP Keys
Status mode
Status mode shows the status of the frequency converter or the motor. If an alarm occurs, the NLCP automatically switches to status mode. Several alarms can be shown.
NOTICE!
Parameter copy is not possible with LCP 101 numerical local control panel.
Figure 2.22 Status Mode
22 Danfoss A/S © 01/2018 All rights reserved. MG33MO22
Setup 1
130BP078.10
A 17
130BP046.10
Hand
on
O
Auto
on
Reset
How to Program Programming Guide
Figure 2.23 Alarm
Main Menu/Quick Set-up
Are used for programming all parameters or only the parameters in the Quick Menu (see also description of the LCP 102 in chapter 2.1 Graphical and Numerical Local Control Panels). When the value ashes, press [▲] or [▼] to change parameter values.
1. Press [Main Menu] to select main menu.
2. Select the parameter group [xx-__] and press [OK].
3. Select the parameter [__-xx] and press [OK].
4. If the parameter is an array parameter, select the array number and press [OK].
5. Select the required data value and press [OK].
Parameters with functional options show values such as [1], [2], and so on. For a description of the dierent options, see the individual parameter descriptions in chapter 3 Parameter Descriptions.
[Back]
Used for stepping backwards. [▲] [▼] are used for maneuvering between commands and within parameters.
2.1.17 LCP Keys
Keys for local control are at the bottom of the LCP.
Figure 2.25 LCP Keys
[Hand On]
Enables control of the frequency converter via the LCP. [Hand On] also starts the motor and it is now possible to enter the motor speed data with the navigation keys. The key can be selected as [1] Enable or [0] Disable via parameter 0-40 [Hand on] Key on LCP. External stop signals activated with control signals, or a eldbus, override a start command via the LCP.
The following control signals are still active when [Hand On] is activated:
[Hand On] - [O] - [Auto On].
Reset.
Coast stop inverse.
Reversing.
Set-up select lsb - Set-up select msb.
Stop command from serial communication.
Quick stop.
DC brake.
[O]
Stops the connected motor. The key can be selected as [1] Enable or [0] Disable via parameter 0-41 [O] Key on LCP.
If no external stop function is selected and the [O] key is inactive, stop the motor by disconnecting the voltage.
2 2
Figure 2.24 Main Menu/Quick Set-up
MG33MO22 Danfoss A/S © 01/2018 All rights reserved. 23
How to Program
VLT® AutomationDrive FC 301/302
[Auto On]
22
Enables control of the frequency converter via the control terminals and/or serial communication. When a start signal is applied on the control terminals and/or the bus, the frequency converter starts. The key can be selected as [1]
Enable or [0] Disable via parameter 0-42 [Auto on] Key on LCP.
NOTICE!
An active HAND-OFF-AUTO signal via the digital inputs has higher priority than the control keys [Hand On] and [Auto On].
[Reset]
Is used for resetting the frequency converter after an alarm (trip). It can be selected as [1] Enable or [0] Disable via parameter 0-43 [Reset] Key on LCP.
2.1.18 Initialization to Default Settings
Manual initialization
1. Disconnect from mains and wait until the display turns o.
2. 2a Press [Status] - [Main Menu] - [OK] at
the same time while powering up the LCP 102, graphical display.
2b Press [Menu] - [OK] while powering up
the LCP 101, numerical display.
3. Release the keys after 5 s.
4. The frequency converter is now programmed according to default settings.
This procedure initializes all except:
Parameter 15-00 Operating hours.
Parameter 15-03 Power Up's.
Parameter 15-04 Over Temp's.
Parameter 15-05 Over Volt's.
NOTICE!
Initialize the frequency converter to default settings in 2 ways.
Recommended initialization (via parameter 14-22 Operation Mode)
1. Select parameter 14-22 Operation Mode.
2. Press [OK].
3. Select [2] initialization.
4. Press [OK].
5. Disconnect the mains supply and wait until the display turns o.
6. Reconnect the mains supply. The frequency converter is now reset.
Parameter 14-22 Operation Mode initializes all except:
Parameter 14-50 RFI Filter.
Parameter 8-30 Protocol.
Parameter 8-31 Address.
Parameter 8-32 FC Port Baud Rate.
Parameter 8-35 Minimum Response Delay.
Parameter 8-36 Max Response Delay.
Parameter 8-37 Max Inter-Char Delay.
Parameter 15-00 Operating hours to
parameter 15-05 Over Volt's.
Parameter 15-20 Historic Log: Event to
parameter 15-22 Historic Log: Time.
Parameter 15-30 Fault Log: Error Code to
parameter 15-32 Alarm Log: Time.
A manual initialization also resets serial communication, RFI lter settings (parameter 14-50 RFI Filter), and fault log settings.
24 Danfoss A/S © 01/2018 All rights reserved. MG33MO22
Parameter Descriptions Programming Guide
3 Parameter Descriptions
3.1 Parameters: 0-** Operation and Display
Parameters related to the fundamental functions of the frequency converter, function of the LCP keys, and congu- ration of the LCP display.
0-01 Language
Option: Function:
Denes display language. The frequency converter is delivered with 4 dierent language packages. English and German are included in all packages. English cannot be erased or manipulated.
[0] * English Part of language packages 1–4
[1] Deutsch Part of language packages 1–4
[2] Francais Part of language package 1
[3] Dansk Part of language package 1
[4] Spanish Part of language package 1
[5] Italiano Part of language package 1
[6] Svenska Part of language package 1
[7] Nederlands Part of language package 1
[10] Chinese Part of language package 2
[20] Suomi Part of language package 1
[22] English US Part of language package 4
0-01 Language
Option: Function:
[49] Russian Part of language package 3
[50] Thai Part of language package 2
[51] Bahasa
Indonesia
[52] Hrvatski Part of language package 3
[53] Arabic
Part of language package 2
0-02 Motor Speed Unit
Option: Function:
NOTICE!
This parameter cannot be adjusted while the motor is running.
The information shown in the display depends on settings in parameter 0-02 Motor Speed Unit and parameter 0-03 Regional Settings. The default settings of parameter 0-02 Motor Speed Unit and parameter 0-03 Regional Settings depend on to which region of the world the frequency converter is supplied.
NOTICE!
Changing the motor speed unit resets certain parameters to their initial value. Select the motor speed unit before modifying other parameters.
3 3
[27] Greek Part of language package 4
[28] Bras.port Part of language package 4
[36] Slovenian Part of language package 3
[39] Korean Part of language package 2
[40] Japanese Part of language package 2
[41] Turkish Part of language package 4
[42] Trad.Chinese Part of language package 2
[43] Bulgarian Part of language package 3
[44] Srpski Part of language package 3
[45] Romanian Part of language package 3
[46] Magyar Part of language package 3
[47] Czech Part of language package 3
[48] Polski Part of language package 4
MG33MO22 Danfoss A/S © 01/2018 All rights reserved. 25
[0] RPM Select to show motor speed variables and parameters
using motor speed (RPM).
[1] * Hz Select to show motor speed variables and parameters
using output frequency (Hz).
0-03 Regional Settings
Option: Function:
NOTICE!
This parameter cannot be adjusted while the motor is running.
[0] * Interna-
tional
[1] US Activate parameter 1-20 Motor Power [kW] for
Activate parameter 1-20 Motor Power [kW] for setting the motor power in kW and set the default value of parameter 1-23 Motor Frequency to 50 Hz.
setting the motor power in hp and set the
Parameter Descriptions
VLT® AutomationDrive FC 301/302
0-03 Regional Settings
Option: Function:
default value of parameter 1-23 Motor Frequency to 60 Hz.
33
0-04 Operating State at Power-up (Hand)
Option: Function:
Select the operating mode upon reconnection of the frequency converter to mains voltage after power down in hand-on mode.
[0] Resume Restart the frequency converter, maintaining
the start/stop settings (applied by [Hand On/ O]) selected before the power-down of the frequency converter.
[1] * Forced stop,
ref=old
[2] Forced stop,
ref=0
3.1.1 0-1* Set-up Operations
Dene and control the individual parameter set-ups. The frequency converter has 4 parameter set-ups that can be programmed independently of each other. This makes the frequency converter very exible and able to solve advanced control functionality problems, often saving the cost of external control equipment. Parameter set-ups can be used to program the frequency converter to operate according to 1 control scheme in 1 set-up (for example motor 1 for horizontal movement) and another control scheme in another set-up (for example motor 2 for vertical
Restart the frequency converter with a saved local reference after mains voltage reappears and after pressing [Hand On].
Reset the local reference to 0 upon restarting the frequency converter.
up to the one being edited. By using parameter 0-51 Set-up Copy, it is possible to copy parameter settings between the set-ups to enable quicker commissioning if similar parameter settings are required in dierent set-ups.
0-10 Active Set-up
Option: Function:
Select the set-up to control the frequency converter functions.
[0] Factory
setup
[1] * Set-up 1 [1] Set-up 1 to [4] Set-up 4 are the 4 separate
[2] Set-up 2 [3] Set-up 3 [4] Set-up 4 [9] Multi
setup
Cannot be changed. It contains the Danfoss data set and can be used as a data source when returning the other set-ups to a known state.
parameter set-ups within which all parameters can be programmed.
Remote set-up selections using digital inputs and the serial communication port. This set-up uses the settings from parameter 0-12 This Set- up Linked to. Stop the frequency converter before making changes to open and closed­loop functions.
Use parameter 0-51 Set-up Copy to copy a set-up to 1 or all other set-ups. Stop the frequency converter before switching between set-ups where parameters marked not
changeable during operation have dierent values. To avoid conicting settings of the same parameter within 2 dierent set-ups, link the set-ups together using
parameter 0-12 This Set-up Linked to. Parameters which are not changeable during operation are marked FALSE in the
parameter lists in chapter 5 Parameter Lists.
movement). Alternatively, parameter set-ups can be used by an OEM machine builder to identically program all their factory-tted frequency converters for dierent machine types within a range to have the same parameters. During production/commissioning, simply select a specic set-up depending on which machine the frequency converter is installed on. The active set-up (that is the set-up in which the frequency converter is currently operating) can be selected in parameter 0-10 Active Set-up and is shown in the LCP. By using multi set-up, it is possible to switch between set-ups with the frequency converter running, or it can be stopped via digital input or serial communication commands. If it is necessary to change set-ups while the frequency converter is running, ensure that parameter 0-12 This Set-up Linked to is programmed as required. By using parameter 0-11 Edit Set-up, it is possible to edit parameters within any of the
0-11 Edit Set-up
Option: Function:
Select the set-up to be edited (that is programmed) during operation; either the active set-up or 1 of the inactive set-ups.
[0] Factory
setup
[1] * Set-up 1 [1] Set-up 1 to [4] Set-up 4 can be edited freely
[2] Set-up 2 [3] Set-up 3 [4] Set-up 4
Cannot be edited but it is useful as a data source to return the other set-ups to a known state.
during operation, independently of the active set-up.
set-ups while continuing the operation of the frequency converter in its active set-up, which can be a dierent set-
26 Danfoss A/S © 01/2018 All rights reserved. MG33MO22
130BP075.10
130BP076.10
Parameter Descriptions Programming Guide
0-11 Edit Set-up
Option: Function:
[9] Active Set-upCan also be edited during operation. Edit the
selected set-up from a range of sources: LCP, FC RS485, FC USB, or up to 5 eldbus sites.
0-12 This Set-up Linked to
Option: Function:
by the label FALSE in the parameter lists in
chapter 5 Parameter Lists.
Parameter 0-12 This Set-up Linked to is used by [9] Multi set-up in parameter 0-10 Active Set-up.
Multi set-up is used to move from 1 set-up to another during operation (that is while the motor runs). Example: Use multi set-up to shift from set-up 1 to set-up 2 while the motor runs. Program in set-up 1 rst, then ensure that set-up 1 and set-up 2 are synchronized (or linked). Synchronization can be performed in 2 ways:
1. Select the following options:
[2] Set-up 2 in parameter 0-11 Edit Set-
up.
parameter 0-12 This Set-up Linked to to
[1] Set-up 1.
This starts the linking (synchronizing) process.
3 3
Figure 3.1 Edit Set-up
0-12 This Set-up Linked to
Option: Function:
To enable conict-free changes from 1 set-up to another during operation, link set-ups containing parameters which are not changeable during operation. The link ensures synchronizing of the not changeable during operation­parameter values when moving from 1 set-up to another during operation. Not changeable during operation-parameters can be identied
Figure 3.2 Set-up 1
OR
2. While still in set-up 1, copy set-up 1 to set-up
2. Then set parameter 0-12 This Set-up Linked to to [2] Set-up 2. This starts the linking process.
Figure 3.3 Set-up 2
When completed, parameter 0-13 Readout: Linked Set-ups reads {1,2} to indicate that all not changeable during operation-parameters are now
the same in set-up 1 and set-up 2. If there are changes to a not changeable during operation­parameter, for example parameter 1-30 Stator Resistance (Rs), in set-up 2, they are also changed automatically in set-up 1. A switch
MG33MO22 Danfoss A/S © 01/2018 All rights reserved. 27
Parameter Descriptions
VLT® AutomationDrive FC 301/302
0-12 This Set-up Linked to
Option: Function:
between set-up 1 and set-up 2 during operation is now possible.
33
[0] * Not linked [1] Set-up 1 [2] Set-up 2 [3] Set-up 3 [4] Set-up 4
0-15 Readout: actual setup
Range: Function:
0* [0 - 255] Makes it possible to read out the active set-up,
also when [9] Multi set-up is selected in parameter 0-10 Active Set-up.
0-13 Readout: Linked Set-ups
Array [5]
Range: Function:
0* [0 -
255 ]
View a list of all the set-ups linked by parameter 0-12 This Set-up Linked to. The parameter has 1 index for each parameter set-up. The value for each index shows which set-ups are linked to that parameter set-up.
Index LCP value
0 {0} 1 {1,2} 2 {1,2} 3 {3} 4 {4}
Table 3.1 Set-up Link Example
0-14 Readout: Edit Set-ups / Channel
Range: Function:
0
[-2147483648 -
N/A*
2147483647 N/A]
View the setting of parameter 0-11 Edit Set-up for each of the 4 dierent communication channels. When the number is shown as a hex number, as it is in the LCP, each number represents 1 channel. Numbers 1–4 represent a set-up number; F means factory setting; and A means active set-up. The channels are, from right to left: LCP, FC bus, USB, HPFB1-5. Example: The number AAAAAA21h means the following:
The frequency converter
received the setting set-up 2 via a eldbus channel. This selection is reected in parameter 0-11 Edit Set-up.
A user selected set-up 1 via the
LCP.
All other channels are using the
active set-up.
28 Danfoss A/S © 01/2018 All rights reserved. MG33MO22
Loading...
+ 290 hidden pages