Danfoss FC 301, FC 302 Operating guide

Operating Guide
VLT® AutomationDrive FC 301/FC 302
0.25–75 kW, Enclosure sizes A-C
vlt-drives.danfoss.com
VLT® AutomationDrive FC 301/FC 302
Operating Guide
1
Introduction 6
1.1
Purpose of this Operating Guide 6
Trademarks 6
1.2
Additional Resources 6
1.3
1.4
Manual and Software Version 6
1.5
Product Overview 6
1.5.1
Intended Use 6
1.5.2
Exploded Views 7
1.6
Type Approvals and Certifications 7
Safety 9
2
Safety Symbols 9
2.1
Qualified Personnel 9
2.2
Contents
Safety Precautions 9
2.3
Mechanical Installation 12
3
3.1
Unpacking 12
3.1.1
Items Supplied 12
3.1.2
Storage 12
3.2
Installation Environment 13
3.3
Mounting 13
3.3.1
Cooling 13
3.3.2
Lifting 14
3.3.3
Mounting 14
3.3.3.1
4
Electrical Installation 15
4.1
Safety Instructions 15
4.2
EMC-compliant Installation 15
4.3
Grounding 15
Mounting with Mounting Plate and Railings 14
4.4
Wiring Schematic 17
4.5
Connecting the Motor 18
4.5.1
Grounding the Cable Shield 18
4.6
Connecting AC Mains 19
4.6.1
Connecting the Drive to Mains 19
4.7
Control Wiring 19
4.7.1
Safe Torque Off (STO) 19
4.7.2
Mechanical Brake Control 20
AQ267037727118en-000101/130R0300 | 3Danfoss A/S © 2021.01
VLT® AutomationDrive FC 301/FC 302
Operating Guide
4.8
Installation Check List 20
5
Commissioning 22
5.1
Safety Instructions 22
5.1.1
Before Applying Power 22
5.2
Local Control Panel Operation 23
5.3
System Set-up 24
6
Basic I/O Configuration 25
6.1
Application Examples 25
6.1.1
Programming a Closed-loop Drive System 25
6.1.2
Wiring Configuration for Automatic Motor Adaptation (AMA) 26
6.1.3
Wiring Configuration for Automatic Motor Adaptation without T27 26
6.1.4
Wiring Configuration: Speed 27
6.1.5
Wiring Configuration: Feedback 29
Contents
6.1.6
Wiring Configuration: Run/Stop 31
6.1.7
Wiring Configuration: Start/Stop 33
6.1.8
Wiring Configuration: External Alarm Reset 35
6.1.9
Wiring Configuration: RS485 36
6.1.10
Wiring Configuration: Motor Thermistor 36
6.1.11
Wiring for Regen 37
6.1.12
Wiring Configuration for a Relay Setup with Smart Logic Control 38
6.1.13
Wiring Configuration: Mechanical Brake Control 39
6.1.14
Wiring Configuration for the Encoder 39
6.1.15
Wiring Configuration for Torque and Stop Limit 41
7
Maintenance, Diagnostics, and Troubleshooting 43
7.1
Maintenance and Service 43
7.2
Warning and Alarm Types 43
7.3
Warning and Alarm Displays 44
7.4
Descriptions of Warnings and Alarms 44
8
Specifications 60
8.1
Electrical Data 60
8.1.1
Mains Supply 200–240 V 60
8.1.2
Mains Supply 380–500 V 62
8.1.3
Mains Supply 525–600 V (FC 302 only) 65
8.1.4
Mains Supply 525–690 V (FC 302 only) 67
8.1.5
Power Cable Cross-sections 70
8.2
Mains Supply 70
AQ267037727118en-000101/130R03004 | Danfoss A/S © 2021.01
VLT® AutomationDrive FC 301/FC 302
Operating Guide
8.3
Motor Output and Motor Data 71
8.3.1
8.3.2
8.4
Ambient Conditions 71
8.5
Cable Specifications 72
8.5.1
8.6
Control Input/Output and Control Data 72
8.6.1
8.6.2
8.6.3
8.6.4
8.6.5
8.6.6
8.6.7
Contents
Motor Output (U, V, W) 71
Torque Characteristics 71
Cable Lengths and Cross-sections for Control Cables 72
Digital Inputs 72
STO Terminal 37 (Terminal 37 is Fixed PNP Logic) 72
Analog Inputs 73
Pulse/Encoder Inputs 73
Digital Outputs 74
Analog Output 74
Control Card, 24 V DC Output 74
8.6.8
Control Card, +10 V DC Output 74
8.6.9
Control Card, RS485 Serial Communication 74
8.6.10
Control Card, USB Serial Communication 74
8.6.11
Relay Outputs 75
8.6.12
Control Card Performance 75
8.6.13
Control Characteristics 75
8.7
Fuses and Circuit Breakers 76
8.7.1
Fuse Recommendations 76
8.7.2
CE Compliance 76
8.7.3
UL Compliance 79
8.8
Connection Tightening Torques 82
8.9
Power Ratings, Weight, and Dimensions 84
9
Appendix 88
9.1
Symbols and Abbreviations 88
AQ267037727118en-000101/130R0300 | 5Danfoss A/S © 2021.01
Version
Remarks
Software version
AQ267037727118, version 0101
Editorial update.
8.43, 48.4x (IMC)
VLT® AutomationDrive FC 301/FC 302
Operating Guide

Introduction

1 Introduction
1.1 Purpose of this Operating Guide
This Operating Guide provides information for safe installation and commissioning of the AC drive. It is intended for use by qualified personnel. Read and follow the instructions to use the drive safely and professionally. Pay particular attention to the safety instruc­tions and general warnings. Always keep this Operating Guide with the drive.
VLT® is a registered trademark for Danfoss A/S.
1.2 Trademarks
VLT® is a registered trademark for Danfoss A/S.
1.3 Additional Resources
Other resources are available to understand advanced drive functions and programming.
The Programming Guide provides greater detail on working with parameters and shows many application examples.
The Design Guide provides detailed information about capabilities and functionality to design motor control systems.
The Safe Torque Off Operating Guide provides detailed specifications, requirements, and installation instructions for the Safe Torque Off function.
Supplementary publications and manuals are available from Danfoss, see
www.danfoss.com.
1.4 Manual and Software Version
This manual is regularly reviewed and updated. All suggestions for improvement are welcome.
Table 1: Manual and Software Version
1.5 Product Overview
1.5.1 Intended Use
The drive is an electronic motor controller intended for:
Regulation of motor speed in response to system feedback or to remote commands from external controllers. A power drive system consists of the AC drive, the motor, and equipment driven by the motor.
System and motor status surveillance.
The drive can also be used for motor overload protection. Depending on the configuration, the drive can be used in standalone applications or form part of a larger appliance or installation. The drive is allowed for use in residential, industrial, and commercial environments in accordance with local laws and standards.
N O T I C E
In a residential environment, this product can cause radio interference, in which case supplementary mitigation measures can be
required.
Foreseeable misuse
Do not use the drive in applications which are non-compliant with specified operating conditions and environments. Ensure com­pliance with the conditions specified in Ambient Conditions.
OUTPUT FREQUENCY LIMIT
Due to export control regulations, the output frequency of the drive is limited to 590 Hz. For demands exceeding 590 Hz, contact
Danfoss.
N O T I C E
AQ267037727118en-000101 / 130R03006 | Danfoss A/S © 2021.01
1
2
3 4
5
6
7
8
9
10
11
12
13
16
17
18
19
14
6
FAN MOUNTING
QDF-30
DC-
DC+
Remove jumper to activate Safe Stop
Max. 24 Volt !
12 13
18
19
27
29
32
33
20
37
0605 04
0302 01
130BF713.10
1
3
5
20
9
6
13
15
14
6
18
11
10
16, 17
19
14
7
8
4
2
1
Local control panel (LCP)
2
Cover
3
RS485 fieldbus connector
4
Digital input/output connector
5
Digital input/output connector
6
Shielded cable grounding and relief
7
USB connector
8
RS485 termination switch
9
DIP switch for A53 and A54
10
Relay 1 (01, 02, 03)
11
Relay 2 (04, 05, 06)
12
Lifting ring
13
Mounting slot
14
Ground connection (PE)
15
Cable shield connector
16
Brake terminal (-81, +82)
17
Load sharing terminal (-88, +89)
18
Motor terminals 96 (U), 97 (V), 98 (W)
19
Mains input terminals 91 (L1), 92 (L2), 93 (L3)
20
LCP connector
VLT® AutomationDrive FC 301/FC 302
Operating Guide
1.5.2 Exploded Views
Introduction
Illustration 1: Exploded View Enclosure Size A, IP20 (left) and Enclosure Size C, IP55/IP66 (right)
1.6 Type Approvals and Certifications
The following list is a selection of possible type approvals and certifications for Danfoss drives:
Drives of enclosure size T7 (525–690 V) are not UL listed.
Table 2: Type Approvals and Certifications
N O T I C E
AQ267037727118en-000101 / 130R0300 | 7Danfoss A/S © 2021.01
089
VLT® AutomationDrive FC 301/FC 302
Operating Guide
Introduction
N O T I C E
The specific approvals and certification for the drive are on the nameplate of the drive. For more information, contact the local
Danfoss office or partner.
For more information on UL 508C thermal memory retention requirements, refer to the section Motor Thermal Protection in the product-specific Design Guide.
For more information on compliance with the European Agreement concerning International Carriage of Dangerous Goods by In­land Waterways (ADN), refer to the section ADN-compliant Installation in the product-specific Design Guide.
AQ267037727118en-000101 / 130R03008 | Danfoss A/S © 2021.01
VLT® AutomationDrive FC 301/FC 302
Operating Guide
2 Safety
2.1 Safety Symbols
The following symbols are used in this manual:
D A N G E R
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
W A R N I N G
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
C A U T I O N
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
N O T I C E
Indicates information considered important, but not hazard-related (for example, messages relating to property damage).

Safety

2.2 Qualified Personnel
Correct and reliable transport, storage, installation, operation, and maintenance are required for the trouble-free and safe operation of the drive. Only qualified personnel are allowed to install and operate this equipment.
Qualified personnel are defined as trained staff, who are authorized to install, commission, and maintain equipment, systems, and circuits in accordance with pertinent laws and regulations. Also, the qualified personnel must be familiar with the instructions and safety measures described in this manual.
2.3 Safety Precautions
W A R N I N G
HAZARDOUS VOLTAGE
AC drives contain hazardous voltage when connected to the AC mains or connected on the DC terminals. Failure to perform
installation, start-up, and maintenance by skilled personnel can result in death or serious injury.
Only skilled personnel must perform installation, start-up, and maintenance.
-
W A R N I N G
UNINTENDED START
When the drive is connected to the AC mains, DC supply, or load sharing, the motor may start at any time, causing risk of death,
serious injury, and equipment or property damage. The motor may start by activation of an external switch, a fieldbus command,
an input reference signal from the LCP or LOP, via remote operation using MCT 10 Set-up software, or after a cleared fault condi-
tion.
Press [Off] on the LCP before programming parameters.
-
Disconnect the drive from the mains whenever personal safety considerations make it necessary to avoid unintended motor
-
start.
Check that the drive, motor, and any driven equipment are in operational readiness.
-
AQ267037727118en-000101 / 130R0300 | 9Danfoss A/S © 2021.01
Voltage [V]
Minimum waiting time (minutes)
4715
200–240
0.25–3.7 kW (0.34–5 hp)
5.5–37 kW (7.5–50 hp)
380–500
0.25–7.5 kW (0.34–10 hp)
11–75 kW (15–100 hp)
525–600
0.75–7.5 kW (1–10 hp)
11–75 kW (15–100 hp)
525–690
1.5–7.5 kW (2–10 hp)
11–75 kW (15–100 hp)
VLT® AutomationDrive FC 301/FC 302
Operating Guide
Safety
W A R N I N G
DISCHARGE TIME
The drive contains DC-link capacitors, which can remain charged even when the drive is not powered. High voltage can be
present even when the warning indicator lights are off.
Failure to wait the specified time after power has been removed before performing service or repair work could result in death or
serious injury.
Stop the motor.
-
Disconnect AC mains, permanent magnet type motors, and remote DC-link supplies, including battery back-ups, UPS, and
-
DC-link connections to other drives.
Wait for the capacitors to discharge fully. The minimum waiting time is specified in the table Discharge time and is also visible
-
on the nameplate on top of the drive.
Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the capacitors
-
are fully discharged.
Table 3: Discharge Time
W A R N I N G
LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to ground the drive properly can result in death or serious injury.
Ensure that the minimum size of the ground conductor complies with the local safety regulations for high touch current
-
equipment.
W A R N I N G
ROTATING SHAFTS
Contact with rotating shafts and electrical equipment can result in death or serious injury.
Ensure that only trained and qualified personnel perform installation, start-up, and maintenance.
-
Ensure that electrical work conforms to national and local electrical codes.
-
Follow the procedures in this guide.
-
W A R N I N G
UNINTENDED MOTOR ROTATION WINDMILLING
Unintended rotation of permanent magnet motors creates voltage and can charge the unit, resulting in death, serious injury, or
equipment damage.
Ensure that permanent magnet motors are blocked to prevent unintended rotation.
-
AQ267037727118en-000101 / 130R030010 | Danfoss A/S © 2021.01
VLT® AutomationDrive FC 301/FC 302
Operating Guide
C A U T I O N
INTERNAL FAILURE HAZARD
An internal failure in the drive can result in serious injury when the drive is not properly closed.
Ensure that all safety covers are in place and securely fastened before applying power.
-
Safety
AQ267037727118en-000101 / 130R0300 | 11Danfoss A/S © 2021.01
e30bd600.13
R
US LISTED
76 X1 E134261 IND. CONT. EQ.
UL Voltage 525-600 V
DANGER
See manual for special condition/mains fuse voir manual de conditions speclales/fusibles
`
15 min.
VLT
R
Automation Drive
T/C: FC-302P75KT7P21H2XGCXXXSXXXXAXBXCXXXXDX P/N: 134G6302 S/N: 999999G999 55kW / 75 kW; 75kW / 90 kW (NO) IN: 3x525-690V 50/60Hz 87/86A; 161/145A (NO) OUT: 3x0-Vin 0-590Hz 87/83A; 105/100A (NO)
Type 1/ IP21 Tamb. 50
C /122 F
o o
MADE IN DENMARK
Danfoss A/S 6340 NordborgDenmark www.danfoss.com
1 2
3
4
5
6
7
8
9
10
1
Type code
2
Code number
3
Serial number
4
Power rating
5
Input voltage, frequency, and current (at low/high voltages)
6
Output voltage, frequency, and current (at low/high voltages)
7
Enclosure size and IP rating
8
Maximum ambient temperature
9
Certifications
10
Discharge time (Warning)
VLT® AutomationDrive FC 301/FC 302
Operating Guide

Mechanical Installation

3 Mechanical Installation
3.1 Unpacking
3.1.1 Items Supplied
Items supplied vary according to product configuration.
Make sure that the items supplied and the information on the nameplate correspond to the order confirmation.
Check the packaging and the drive visually for damage caused by inappropriate handling during shipment. File any claim for damage with the carrier. Retain damaged parts for clarification.
Illustration 2: Product Nameplate (Example)
Do not remove the nameplate from the drive (loss of warranty).
3.1.2 Storage
Ensure that the requirements for storage are fulfilled, see 8.4 Ambient Conditions.
N O T I C E
AQ267037727118en-000101 / 130R030012 | Danfoss A/S © 2021.01
a
a
e30bd528.10
Enclosure
A1–A5
B1–B4
C1, C3
C2, C4
a [mm (in)]
100 (3.9)
200 (7.8)
200 (7.8)
225 (8.9)
VLT® AutomationDrive FC 301/FC 302
Operating Guide
Mechanical Installation
3.2 Installation Environment
N O T I C E
REDUCED LIFETIME
In environments with airborne liquids, particles, or corrosive gases, ensure that the IP/Type rating of the equipment matches the
installation environment. Failure to meet requirements for ambient conditions can reduce lifetime of the drive.
Ensure that requirements for air humidity, temperature, and altitude are met.
-
Vibration and shock
The drive complies with requirements for units mounted on the walls and floors of production premises, and in panels bolted to walls or floors. For detailed ambient conditions, refer to 8.4 Ambient Conditions.
3.3 Mounting
3.3.1 Cooling
Ensure that top and bottom clearance for air cooling is provided. See Table 4 for clearance requirements.
Illustration 3: Top and Bottom Cooling Clearance
Table 4: Minimum Airflow Clearance Requirements
AQ267037727118en-000101 / 130R0300 | 13Danfoss A/S © 2021.01
e30bd504.11
VLT® AutomationDrive FC 301/FC 302
Operating Guide
Mechanical Installation
3.3.2 Lifting
W A R N I N G
HEAVY LOAD
Unbalanced loads can fall and loads can tip over. Failure to take proper lifting precautions increases risk of death, serious injury,
or equipment damage.
Never walk under suspended loads.
-
To guard against injury, wear personal protective equipment such as gloves, safety glasses, and safety shoes.
-
Be sure to use lifting devices with the appropriate weight rating. To determine a safe lifting method, check the weight of the
-
unit.
The angle from the top of the drive module to the lifting cables has an impact on the maximum load force on the cable. This
-
angle must be 65° or greater. Attach and dimension the lifting cables properly.
To determine a safe lifting method, check the weight of the unit in 8.9 Power Ratings, Weight, and Dimensions.
Ensure that the lifting device is suitable for the task.
If necessary, plan for a hoist, crane, or forklift with the appropriate rating to move the unit.
For lifting, use hoist rings on the unit, when provided.
3.3.3 Mounting
Procedure
1.
Ensure that the strength of the mounting location supports the unit weight.
The drive allows side-by-side installation.
2.
Locate the unit as near to the motor as possible. Keep the motor cables as short as possible.
3.
Mount the unit vertically to a solid flat surface or to the optional backplate to provide cooling airflow.
4.
Use the slotted mounting holes on the unit for wall mount, when provided.
3.3.3.1 Mounting with Mounting Plate and Railings
A mounting plate is required when mounted on railings.
Illustration 4: Proper Mounting with Mounting Plate
AQ267037727118en-000101 / 130R030014 | Danfoss A/S © 2021.01
VLT® AutomationDrive FC 301/FC 302
Operating Guide

Electrical Installation

4 Electrical Installation
4.1 Safety Instructions
See 2.3 Safety Precautions for general safety instructions.
W A R N I N G
INDUCED VOLTAGE
Induced voltage from output motor cables that run together can charge equipment capacitors, even with the equipment turned
off and locked out. Failure to run output motor cables separately or to use shielded cables could result in death or serious injury.
Run output motor cables separately or use shielded cables.
-
Simultaneously lock out all the drives.
-
W A R N I N G
SHOCK HAZARD
The unit can cause a DC current in the PE conductor. Failure to use a Type B residual current-operated protective device (RCD)
may lead to the RCD not providing the intended protection and therefore may result in death or serious injury.
When an RCD is used for protection against electrical shock, only a Type B device is allowed on the supply side.
-
Overcurrent protection
Extra protective equipment, such as short-circuit protection or motor thermal protection between drive and motor, is required for applications with multiple motors.
Input fusing is required to provide short circuit and overcurrent protection. If not factory-supplied, the installer must provide fuses. See maximum fuse ratings in 8.7.2 CE Compliance and 8.7.3 UL Compliance.
Wire type and ratings
All wiring must comply with local and national regulations regarding cross-section and ambient temperature requirements.
Power connection wire recommendation: Minimum 75 °C (167 °F) rated copper wire. See Table 29 to Table 40, and 8.5.1 Cable
Lengths and Cross-sections for Control Cables for recommended wire sizes and types.
4.2 EMC-compliant Installation
To obtain an EMC-compliant installation, follow the instructions provided in 4.3 Grounding, 4.4 Wiring Schematic, 4.5 Connecting
the Motor, and 4.7 Control Wiring.
N O T I C E
POTENTIAL EQUALIZATION
Risk of burst transient when the ground potential between the drive and the control system is different. Install equalizing cables
between the system components. Recommended cable cross-section: 16 mm2 (6 AWG).
4.3 Grounding
W A R N I N G
LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to ground the drive properly can result in death or serious injury.
Ensure that the minimum size of the ground conductor complies with the local safety regulations for high touch current
-
equipment.
For electrical safety
Ground the drive in accordance with applicable standards and directives.
Use a dedicated ground wire for input power, motor power, and control wiring.
Do not ground 1 drive to another in a daisy-chain fashion (see Illustration 5.)
AQ267037727118en-000101 / 130R0300 | 15Danfoss A/S © 2021.01
e30bc500.11
FC 1
FC 1
FC 2
FC 2
FC 3
FC 3
PE
PE
VLT® AutomationDrive FC 301/FC 302
Operating Guide
Keep the ground wire connections as short as possible.
Follow motor manufacturer wiring requirements.
Minimum cable cross-section for the ground wires: 10 mm2 (7 AWG).
Separately terminate individual ground wires, both complying with the dimension requirements.
Electrical Installation
Illustration 5: Grounding Principle
For EMC-compliant installation
Establish electrical contact between the cable shield and the drive enclosure by using metal cable glands or by using the clamps provided on the equipment.
Use high-strand wire to reduce burst transient.
Do not use pigtails.
N O T I C E
POTENTIAL EQUALIZATION
Risk of burst transient when the ground potential between the drive and the control system is different. Install equalizing cables
between the system components. Recommended cable cross-section: 16 mm2 (6 AWG).
AQ267037727118en-000101 / 130R030016 | Danfoss A/S © 2021.01
130BD599.11
––
Motor
Analog Output
ON=Terminated OFF=Open
91 (L1) 92 (L2) 93 (L3)
PE
88 (-) 89 (+)
53 (A IN)
54 (A IN)
37 (D IN)
1)
18 (D IN)
10
V DC
15 mA 130/200 mA
+ - + -
(U) 96 (V) 97 (W) 98 (PE) 99
(P RS485) 68
(N RS485) 69
0 V
5V
S801
0/4–20 mA
RS-485
03
240 V AC, 2 A
24 V DC
02
01
05
04
06
24
V (NPN)
0 V (PNP)
0 V (PNP)
24
V (NPN)
19 (D IN)
24
V (NPN)
0 V (PNP)
24
V
0
V
0
V (PNP)
24 V (NPN)
(D IN/OUT
)
1)
0 V
24
V
29
24
V (NPN)
0 V (PNP)
0
V (PNP)
24 V (NPN)
33 (D IN)
32 (D IN)
1 2
ON
S201
ON
21
S202
ON=0/4–20 mA
95
P 5-00
21
ON
S801
(R+) 82
(R-) 81
: Chassis
240 V AC, 2 A
400 V AC, 2 A
: PE
3-phase power input
+10 V DC
DC bus
0/-10 V DC to +10 V DC
0/4–20 mA
0/-10 V DC to +10 V DC
0/4–20 mA
50 (+10 V OUT)
55 (COM A IN)
12 (+24 V OUT)
13 (+24 V OUT)
20 (COM D IN)
27 (D IN/OUT)
Switch mode power supply
Brake resistor
Relay 1
Relay 2
1)
(COM A OUT) 39
(A OUT) 42
: Ground
: Ground 1
: Ground 2
(COM RS485) 61
2)
RS485 interface
OFF=0/-10 V DC to +10 V DC
A
Analog
D
Digital
1
Terminal 37 (optional) is used for Safe Torque Off (STO). For installation instructions, refer to the VLT
®
Safe Torque Off Operating Guide. For FC 301, termi­nal 37 is only included in enclosure size A1. Relay 2 and terminal 29 have no function in FC 301.
2
Do not connect cable shield.
VLT® AutomationDrive FC 301/FC 302
Operating Guide
4.4 Wiring Schematic
Electrical Installation
Illustration 6: Basic Wiring Schematic
Read more in EMC-Compliant Installation.
AQ267037727118en-000101 / 130R0300 | 17Danfoss A/S © 2021.01
e30bd531.11
U
V
W
96
97
98
VLT® AutomationDrive FC 301/FC 302
Operating Guide
Electrical Installation
4.5 Connecting the Motor
W A R N I N G
INDUCED VOLTAGE
Induced voltage from output motor cables that run together can charge equipment capacitors, even with the equipment turned
off and locked out. Failure to run output motor cables separately or to use shielded cables could result in death or serious injury.
Run output motor cables separately or use shielded cables.
-
Simultaneously lock out all the drives.
-
Run output separately or
Use shielded cables.
Comply with local and national electrical codes for cable sizes. For maximum wire sizes, see Table 29 to Table 40.
Follow motor manufacturer wiring requirements.
Motor wiring knockouts or access panels are provided at the base of IP21 (NEMA 1/12) and higher units.
Do not wire a starting or pole-changing device (for example a Dahlander motor or slip ring asynchronous motor) between the drive and the motor.
4.5.1 Grounding the Cable Shield
Procedure
1.
Strip a section of the outer cable insulation.
2.
Position the stripped wire under the cable clamp to esatblish mechanical fixation and electrical contact between the cable shield and ground.
3.
Connect the ground wire to the nearest grounding terminal in accordance with the grounding instructions, see 4.3
Grounding.
4.
Connect the 3-phase motor wiring to terminals 96 (U), 97 (V), and 98 (W).
5.
Torque-tighten the terminals, see 8.8 Connection Tightening Torques.
Example
Mains input, motor, and grounding for basic drives. Actual configurations vary with unit types and optional equipment.
AQ267037727118en-000101 / 130R030018 | Danfoss A/S © 2021.01
+DC
BR-
B
M A I N S
L1 L2 L3
91 92 93
RELAY 1 RELAY 2
99
U V W
MOTOR
99
130BF048.11
VLT® AutomationDrive FC 301/FC 302
Operating Guide
Electrical Installation
Illustration 7: Example of Motor, Mains, and Ground Wiring
4.6 Connecting AC Mains
Size the wiring based on the input current of the drive. For maximum wire sizes, see Table 29 to Table 40.
Comply with local and national electrical codes for cable sizes.
4.6.1 Connecting the Drive to Mains
Procedure
1.
Connect the 3-phase AC input power wiring to terminals L1, L2, and L3.
2.
Depending on the configuration of the equipment, connect the input power to the mains input terminals or the input dis­connect.
3.
Ground the cable in accordance with the grounding instructions, see 4.3 Grounding and 4.5.1 Grounding the Cable Shield.
4.
When supplied from an isolated mains source (IT mains or floating delta) or TT/TN-S mains with a grounded leg (grounded delta), ensure that parameter 14-50 RFI Filter is set to [0] Off. This setting prevents damage to the DC link and reduces ground capacity currents in accordance with IEC 61800-3.
4.7 Control Wiring
Isolate the control wiring from the high-power components in the drive.
When the drive is connected to a thermistor, enusre that the thermistor control wiring is shielded and reinforced/double insula­ted. A 24 V DC supply voltage is recommended.
4.7.1 Safe Torque Off (STO)
To run STO, additional wiring for the drive is required. Refer to the VLT® Frequency Converters Safe Torque Off Operating Guide for further information.
AQ267037727118en-000101 / 130R0300 | 19Danfoss A/S © 2021.01
e30ba902.11
L1 L2 L3
U V W
02 01
A1 A2
Drive
Output
relay
Command circuit
220 V AC
Mechanical
brake
Shaft
Motor
Frewheeling diode
Brake
380 V AC
Output contactor input
power circuit
Inspect for
Description
Auxiliary equipment
Look for auxiliary equipment, switches, disconnects, or input fuses/circuit breakers residing on the in­put power side of the drive, or output side to the motor. Ensure that they are ready for full-speed oper­ation.
Check the function and installation of any sensors used for feedback to the drive.
Remove any power factor correction capacitors on the motor.
Adjust any power factor correction capacitors on the mains side and ensure that they are dampened.
Cable routing
Ensure that the motor wiring and control wiring are separated, shielded, or in 3 separate metallic con­duits for high-frequency interference isolation.
VLT® AutomationDrive FC 301/FC 302
Operating Guide
Electrical Installation
4.7.2 Mechanical Brake Control
In hoisting/lowering applications, it is necessary to control an electro-mechanical brake.
Control the brake using any relay output or digital output (terminal 27 or 29).
Keep the output closed (voltage-free) as long as the drive is unable to keep the motor at standstill, for example due to the load being too heavy.
Select [32] Mechanical brake control in parameter group 5-4* Relays for applications with an electromechanical brake.
The brake is released when the motor current exceeds the value in parameter 2-20 Release Brake Current.
The brake is engaged when the output frequency is less than the frequency set in parameter 2-21 Activate Brake Speed [RPM] or parameter 2-22 Activate Brake Speed [Hz], and only if the drive carries out a stop command.
If the drive is in alarm mode or in an overvoltage situation, the mechanical brake immediately closes.
N O T I C E
The drive is not a safety device. It is the responsibility of the system designer to integrate safety devices according to relevant
national crane/lift regulations.
Illustration 8: Connecting the Mechanical Brake to the Drive
4.8 Installation Check List
Before completing installation of the unit, inspect the entire installation as detailed in the following table. Check and mark the items when completed.
Table 5: Installation Check List
AQ267037727118en-000101 / 130R030020 | Danfoss A/S © 2021.01
•••
•••••
•••
Inspect for
Description
Control wiring
Check for broken or damaged wires and loose connections.
Check that the control wiring is isolated from power and motor wiring for noise immunity.
Check the voltage source of the signals, if necessary.
The use of shielded cable or twisted pair is recommended. Ensure that the shield is terminated correctly.
Cooling clear­ance
Ensure that the top and bottom clearance is adequate to ensure proper airflow for cooling, see 3.3.1
Cooling.
Ambient con­ditions
Check that requirements for ambient conditions are met.
Fusing and cir­cuit breakers
Check for proper fusing or circuit breakers.
Check that all fuses are inserted firmly and are in operational condition, and that all circuit breakers are in the open position.
Grounding
Check for sufficient ground connections and ensure that those connections are tight and free of oxida­tion.
Grounding to conduit, or mounting the back panel to a metal surface, is not a suitable grounding.
Input and out­put power wir­ing
Check for loose connections.
Check that the motor and mains cables are in separate conduit or separated shielded cables.
Panel interior
Inspect that the unit interior is free of dirt, metal chips, moisture, and corrosion.
Check that the unit is mounted on an unpainted metal surface.
Switches
Ensure that all switch and disconnect settings are in the proper positions.
Vibration
Check that the unit is mounted solidly, or that shock mounts are used, as necessary.
Check for an unusual amount of vibration.
VLT® AutomationDrive FC 301/FC 302
Operating Guide
Electrical Installation
C A U T I O N
INTERNAL FAILURE HAZARD
An internal failure in the drive can result in serious injury when the drive is not properly closed.
Ensure that all safety covers are in place and securely fastened before applying power.
-
AQ267037727118en-000101 / 130R0300 | 21Danfoss A/S © 2021.01
VLT® AutomationDrive FC 301/FC 302
Operating Guide

Commissioning

5 Commissioning
5.1 Safety Instructions
See chapter Safety for general safety instructions.
W A R N I N G
HAZARDOUS VOLTAGE
AC drives contain hazardous voltage when connected to the AC mains or connected on the DC terminals. Failure to perform
installation, start-up, and maintenance by skilled personnel can result in death or serious injury.
Only skilled personnel must perform installation, start-up, and maintenance.
-
N O T I C E
The front covers with warning signs are an integrated part of the drive and considered safety covers. The covers must be in place
before applying power and at all times.
5.1.1 Before Applying Power
Procedure
1.
Close the safety cover properly.
2.
Check that all cable glands are firmly tightened.
3.
Ensure that input power to the unit is off and locked out. Do not rely on the drive disconnect switches for input power isolation.
4.
Verify that there is no voltage on input terminals L1 (91), L2 (92), and L3 (93), phase-to-phase, and phase-to-ground.
5.
Verify that there is no voltage on output terminals 96 (U), 97 (V), and 98 (W), phase-to-phase, and phase-to-ground.
6.
Confirm continuity of the motor by measuring Ω values on U–V (96–97), V–W (97–98), and W–U (98–96).
7.
Check for proper grounding of the drive and the motor.
8.
Inspect the drive for loose connections on the terminals.
9.
Confirm that the supply voltage matches the voltage of the drive and the motor.
AQ267037727118en-000101 / 130R030022 | Danfoss A/S © 2021.01
e30bf714.11
Auto
On
Reset
Hand
On
Off
Status
Quick Menu
Main
Menu
Alarm
Log
Back
Cancel
Info
OK
Status
1(1)
36.4 kW
Auto Remote Ramping
0.000
On
Alarm
Warn.
7.83 A
799 RPM
53.2 %
1
2
3
16
17
4
15
14
13
12
5
6
7
8 9 10 11
1
The information shown in the display area depends on the selected function or menu (in this case Quick Menu Q3-13 Display Settings).
2
[Status] shows operational status.
3
[Quick Menu] allows access to programming param­eters for initial set-up instructions and many de­tailed application instructions.
4
[Back] reverts to the previous step or list in the menu structure.
5
A green indicator light indicates that power is on.
6
A yellow indicator light comes on when a warning is active. A text appears in the display area identifying the problem.
7
A red flashing indicator light indicates a fault condi­tion, and an alarm text is shown.
8
[Hand On] puts the drive in local control mode, so that it responds to the LCP.
An external stop signal by control input or serial communication overrides local [Hand On] key.
9
[Off] stops the motor but does not remove power to the drive.
10
[Auto On] puts the system in remote operational mode.
Responds to an external start command by con­trol terminals or serial communication.
11
[Reset] resets the drive manually after a fault has been cleared.
12
[OK] gives access to parameter groups or enables a selection.
13
[][] [] [] enables moving between items in the menu.
14
[Info] shows a definition of the function being shown.
15
[Cancel] cancels the last change or command as long as the display mode is not changed.
16
[Main Menu] gives access to all programming pa­rameters.
17
[Alarm Log] shows a list of current warnings, the last 10 alarms, and the maintenance log.
VLT® AutomationDrive FC 301/FC 302
Operating Guide
5.2 Local Control Panel Operation
Commissioning
Illustration 9: Graphical Local Control Panel (GLCP)
AQ267037727118en-000101 / 130R0300 | 23Danfoss A/S © 2021.01
Parameter 1-10 Motor Construction
ASM
SPM
IPM
SynRM
PMaSynRM
Parameter 1-20 Motor Power [kW]/parameter 1-21 Motor Power [hp]XParameter 1-22 Motor Voltage
X
Parameter 1-23 Motor Frequency
XXX
Parameter 1-24 Motor Current
XXXXX
Parameter 1-25 Motor Nominal Speed
XXXXX
Parameter 1-26 Motor Cont. Rated
XXX
X
Parameter 1-39 Motor Poles
XXX
X
VLT® AutomationDrive FC 301/FC 302
Operating Guide
5.3 System Set-up
Procedure
1.
Perform automatic motor adaption (AMA):
a.
Set the basic motor parameters before performing AMA.
Table 6: Basic Parameters to be Checked before AMA
Commissioning
b.
Optimize the compatibility between motor and drive via parameter 1-29 Automatic Motor Adaptation (AMA).
2.
Check motor rotatation.
3.
If encoder feedback is used, perform the following steps:
a.
Select [0] Speed open loop in parameter 1-00 Configuration Mode.
b.
Select [1] 24V encoder in parameter 7-00 Speed PID Feedback Source. Press [Hand On].
c. d.
Press [] for positive speed reference (parameter 1-06 Clockwise Direction at [0]).
e.
In parameter 16-57 Feedback [RPM], check that the feedback is positive.
AQ267037727118en-000101 / 130R030024 | Danfoss A/S © 2021.01
e30bt865.10
Encoder
Mechanical brake
Motor
Gearbox
Load
Transmission
Brake resistor
VLT® AutomationDrive FC 301/FC 302
Operating Guide

Basic I/O Configuration

6 Basic I/O Configuration
6.1 Application Examples
The examples in this section are intended as a quick reference for common applications.
Parameter settings are the regional default values unless otherwise indicated (selected in parameter 0-03 Regional Settings).
Parameters associated with the terminals and their settings are shown next to the drawings.
Required switch settings for analog terminals A53 or A54 are also shown.
6.1.1 Programming a Closed-loop Drive System
A closed-loop drive system usually consists of:
Motor.
Drive.
Encoder (as feedback system).
Mechanical brake.
Brake resistor (for dynamic braking).
Transmission.
Gear box.
Load.
Applications demanding mechanical brake control typically need a brake resistor.
Illustration 10: Basic Set-up for Closed-loop Speed Control
AQ267037727118en-000101 / 130R0300 | 25Danfoss A/S © 2021.01
Parameters
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
e30bb929.11
Drive
Function
Setting
Parameter 1-29 Automatic Motor Adaptation (AMA)
[1] Enable complete AMA
Parameter 5-12 Terminal 27 Digital Input
[2]* Coast inverse
*=Default value
Notes/comments:
Set parameter group 1-2* Motor Data according to motor nameplate.
Parameters
Drive
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
e30bb930.11
Function
Setting
Parameter 1-29 Automatic Motor Adaptation (AMA)
[1] Enable complete AMA
Parameter 5-12 Terminal 27 Digital Input
[0] No operation
*=Default value
Notes/comments:
Parameter group 1-2* Motor Data must be set according to motor.
VLT® AutomationDrive FC 301/FC 302
Operating Guide
6.1.2 Wiring Configuration for Automatic Motor Adaptation (AMA)
Table 7: Wiring Configuration for AMA with T27 Connected
Basic I/O Configuration
6.1.3 Wiring Configuration for Automatic Motor Adaptation without T27
Table 8: AMA without T27 Connected
AQ267037727118en-000101 / 130R030026 | Danfoss A/S © 2021.01
Parameters
+10
V
A IN A IN COM A OUT COM
50 53 54 55 42 39
A53
U - I
0–10 V
+
-
e30bb926.11
Drive
Function
Setting
Parameter 6-10 Terminal 53 Low Voltage
0.07 V*
Parameter 6-11 Terminal 53 High Voltage
10 V*
Parameter 6-14 Terminal 53 Low Ref./Feedb. value
0 Hz
Parameter 6-15 Terminal 53 High Ref./Feedb. Value
50 Hz
*=Default value
Notes/comments:
D IN 37 is an option.
Parameters
+10
V
A IN
A IN
COM
A OUT
COM
50
53
54
55
42
39
+
-
e30bb927.11
A53
U - I
4-20mA
Drive
Function
Setting
Parameter 6-12 Terminal 53 Low Current
4 mA*
Parameter 6-13 Terminal 53 High Current
20 mA*
Parameter 6-14 Terminal 53 Low Ref./Feedb. value
0 Hz
Parameter 6-15 Terminal 53 High Ref./Feedb. Value
50 Hz
*=Default value
Notes/comments:
D IN 37 is an option.
VLT® AutomationDrive FC 301/FC 302
Operating Guide
6.1.4 Wiring Configuration: Speed
Table 9: Analog Speed Reference (Voltage)
Table 10: Analog Speed Reference (Current)
Basic I/O Configuration
AQ267037727118en-000101 / 130R0300 | 27Danfoss A/S © 2021.01
Parameters
+10
V
A IN
A IN
COM
A OUT
COM
50
53
54
55
42
39
A53
U - I
5k
e30bb683.11
Drive
Function
Setting
Parameter 6-10 Terminal 53 Low Voltage
0.07 V*
Parameter 6-11 Terminal 53 High Voltage
10 V*
Parameter 6-14 Terminal 53 Low Ref./Feedb. value
0 Hz
Parameter 6-15 Terminal 53 High Ref./Feedb. Value
50 Hz
*=Default value
Notes/comments:
D IN 37 is an option.
Parameter
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
12
13
18
19
20
27
29
32
33
37
e30bb804.12
Drive
Function
Setting
Parameter 5-10 Terminal 18 Digital Input
[8] Start*
Parameter 5-12 Terminal 27 Digital Input
[19] Freeze Reference
Parameter 5-13 Terminal 29 Digital Input
[21] Speed Up
Parameter 5-14 Terminal 32 Digital Input
[22] Speed Down
*=Default value
Notes/comments:
D IN 37 is an option.
e30bb840.12
Speed
Reference
Start (18)
Freeze ref (27)
Speed up (29)
Speed down (32)
VLT® AutomationDrive FC 301/FC 302
Operating Guide
Table 11: Speed Reference (Using a Manual Potentiometer)
Table 12: Speed Up/Down
Basic I/O Configuration
Illustration 11: Speed Up/Down
AQ267037727118en-000101 / 130R030028 | Danfoss A/S © 2021.01
Loading...
+ 64 hidden pages