This design guide is intended for project and systems
engineers, design consultants, and application and product
specialists. Technical information is provided to understand
the capabilities of the frequency converter for integration
into motor control and monitoring systems. Details
concerning operation, requirements, and recommendations
for system integration are described. Information is
provided for input power characteristics, output for motor
control, and ambient operating conditions for the
frequency converter.
Also included are:
Safety features.
•
Fault condition monitoring.
•
Operational status reporting.
•
Serial communication capabilities.
•
Programmable options and features.
•
Design details such as site requirements, cables, fuses,
control wiring, the size and weight of units, and other
critical information necessary to plan for system integration
are also provided.
Reviewing the detailed product information in the design
stage enables developing a well-conceived system with
optimal functionality and
VLT® is a registered trademark.
Additional Resources
1.2
eciency.
Denitions
1.3
1.3.1 Frequency Converter
Coast
The motor shaft is in free mode. No torque on the motor.
I
VLT,MAX
Maximum output current.
I
VLT,N
Rated output current supplied by the frequency converter.
U
VLT,MAX
Maximum output voltage.
1.3.2 Input
Control commands
Start and stop the connected motor with LCP and digital
inputs.
Functions are divided into 2 groups.
Functions in group 1 have higher priority than functions in
group 2.
Group 1Precise stop, coast and reset stop, precise stop
and coast stop, quick stop, DC braking, stop, and
[OFF].
Group 2Start, pulse start, reversing, start reversing, jog,
and freeze output.
Table 1.1 Function Groups
1.3.3 Motor
11
Resources available to understand operations and
programming of the frequency converter:
VLT® Midi Drive FC 280 Operating Guide, provides
•
information about the installation, commissioning,
application, and maintenance of the frequency
converter.
VLT® Midi Drive FC 280 Programming Guide,
•
provides information on how to program and
includes complete parameter descriptions.
Supplementary publications and manuals are available
from Danfoss. See drives.danfoss.com/knowledge-center/technical-documentation/ for listings.
Torque generated on the output shaft and speed from
0 RPM to maximum speed on the motor.
f
JOG
Motor frequency when the jog function is activated (via
digital terminals or bus).
f
M
Motor frequency.
f
MAX
Maximum motor frequency.
f
MIN
Minimum motor frequency.
f
M,N
Rated motor frequency (nameplate data).
I
M
Motor current (actual).
I
M,N
Nominal motor current (nameplate data).
175ZA078.10
Pull-out
RPM
Torque
Introduction
VLT® Midi Drive FC 280
11
n
M,N
Nominal motor speed (nameplate data).
n
s
Synchronous motor speed.
2 × Parameter 1−23 × 60s
ns=
n
slip
Parameter 1−39
Motor slip.
P
M,N
Rated motor power (nameplate data in kW or hp).
T
M,N
Rated torque (motor).
U
M
Instantaneous motor voltage.
U
M,N
Rated motor voltage (nameplate data).
Break-away torque
Preset reference
A dened preset reference to be set from -100% to +100%
of the reference range. Selection of 8 preset references via
the digital terminals. Selection of 4 preset references via
the bus.
Pulse reference
A pulse frequency signal transmitted to the digital inputs
(terminal 29 or 33).
Ref
MAX
Determines the relationship between the reference input at
100% full scale value (typically 10 V, 20 mA) and the
resulting reference. The maximum reference value is set in
parameter 3-03 Maximum Reference.
Ref
MIN
Determines the relationship between the reference input at
0% value (typically 0 V, 0 mA, 4 mA) and the resulting
reference. The minimum reference value is set in
parameter 3-02 Minimum Reference.
1.3.5 Miscellaneous
Analog inputs
The analog inputs are used for controlling various
functions of the frequency converter.
There are 2 types of analog inputs:
Current input: 0–20 mA and 4–20 mA.
•
Voltage input: 0–10 V DC.
•
Analog outputs
The analog outputs can supply a signal of 0–20 mA, or 4–
20 mA.
Automatic motor adaptation, AMA
Illustration 1.1 Break-away Torque
η
VLT
The eciency of the frequency converter is dened as the
ratio between the power output and the power input.
Start-disable command
A start-disable command belonging to the control
commands in group 1. See Table 1.1 for more details.
Stop command
A stop command belonging to the control commands in
group 1. See Table 1.1 for more details.
1.3.4 References
Analog reference
A signal transmitted to the analog inputs 53 or 54 can be
voltage or current.
Binary reference
A signal transmitted via the serial communication port.
The AMA algorithm determines the electrical parameters
for the connected motor at standstill.
Brake resistor
The brake resistor is a module capable of absorbing the
brake power generated in regenerative braking. This
regenerative brake power increases the DC-link voltage,
and a brake chopper ensures that the power is transmitted
to the brake resistor.
CT characteristics
Constant torque characteristics used for all applications
such as conveyor belts, displacement pumps, and cranes.
Digital inputs
The digital inputs can be used for controlling various
functions of the frequency converter.
Digital outputs
The frequency converter features 2 solid-state outputs that
can supply a 24 V DC (maximum 40 mA) signal.
Electronic thermal relay is a thermal load calculation based
on present load and time. Its purpose is to estimate the
motor temperature.
FC standard bus
Includes RS485 bus with FC protocol or MC protocol. See
parameter 8-30 Protocol.
Initializing
If initializing is carried out (parameter 14-22 Operation
Mode), the frequency converter returns to the default
setting.
Intermittent duty cycle
An intermittent duty rating refers to a sequence of duty
cycles. Each cycle consists of an on-load and an o-load
period. The operation can be either periodic duty or nonperiodic duty.
LCP
The local control panel makes up a complete interface for
control and programming of the frequency converter. The
LCP is detachable. With the installation kit option, the LCP
can be installed up to 3 m (9.8 ft) from the frequency
converter in a front panel.
NLCP
The numerical local control panel interface for control and
programming of the frequency converter. The display is
numerical and the panel is used to show process values.
The NLCP has storing and copy functions.
GLCP
The graphic local control panel interface for control and
programming of the frequency converter. The display is
graphic and the panel is used to show process values. The
GLCP has storing and copy functions.
lsb
Least signicant bit.
msb
Most signicant bit.
MCM
Short for mille circular mil, an American measuring unit for
cable cross-section. 1 MCM = 0.5067 mm2.
On-line/o-line parameters
Changes to on-line parameters are activated immediately
after the data value is changed. To activate changes to o-line parameters, press [OK].
Process PID
The PID control maintains speed, pressure, and
temperature by adjusting the output frequency to match
the varying load.
PCD
Process control data.
PFC
Power factor correction.
Power cycle
Switch o the mains until the display (LCP) is dark, then
turn power on again.
Power factor
The power factor is the relation between I1 and I
Power factor =
For FC 280 frequency converters,
Power factor =
3xUxI1cosϕ1
3xUxI
I1xcosϕ1
I
RMS
RMS
=
I
RMS
cosϕ
I
1
1 = 1, therefore:
RMS
.
The power factor indicates to which extent the frequency
converter imposes a load on the mains supply.
The lower the power factor, the higher the I
RMS
for the
same kW performance.
I
RMS
=
I
+ I
1
5
+ I
2
+ .. + I
7
2
n
2
2
In addition, a high power factor indicates that the dierent
harmonic currents are low.
The built-in DC coils (T2/T4) and PFC (S2) produce a high
power factor, minimizing the imposed load on the mains
supply.
Pulse input/incremental encoder
An external, digital pulse transmitter used for feeding back
information on motor speed. The encoder is used in
applications where great accuracy in speed control is
required.
RCD
Residual current device.
Set-up
Save parameter settings in 4 set-ups. Change among the 4
parameter set-ups and edit 1 set-up while this set-up is
inactive.
SFAVM
Acronym describing the switching pattern stator uxoriented asynchronous vector modulation.
Slip compensation
The frequency converter compensates for the motor slip by
giving the frequency a supplement that follows the
measured motor load, keeping the motor speed almost
constant.
Smart logic control (SLC)
The SLC is a sequence of user-dened actions executed
when the smart logic controller evaluates the associated
user-dened events as true (Parameter group 13-** Smart
Logic Control).
STW
Status word.
THD
Total harmonic distortion states the total contribution of
harmonic distortion.
Thermistor
A temperature-dependent resistor placed where the
temperature is monitored (frequency converter or motor).
Trip is a state entered in fault situations. Examples of fault
situations:
The frequency converter is subject to an over
•
voltage.
The frequency converter protects the motor,
•
process, or mechanism.
Restart is prevented until the cause of the fault has
disappeared, and the trip state is canceled by activating
reset or, in some cases, by being programmed to reset
automatically. Do not use trip for personal safety.
Trip lock
Trip lock is a state entered in fault situations when the
frequency converter is protecting itself and requiring
physical intervention. For example, a short circuit on the
output triggers a trip lock. A locked trip can only be
canceled by cutting o mains, removing the cause of the
fault, and reconnecting the frequency converter. Restart is
prevented until the trip state is canceled by activating
reset or, sometimes, by being programmed to reset
automatically. Do not use trip lock for personal safety.
VT characteristics
Variable torque characteristics used for pumps and fans.
+
VVC
If compared with standard voltage/frequency ratio control,
voltage vector control (VVC+) improves the dynamics and
stability, both when the speed reference is changed and in
relation to the load torque.
60° AVM
Refer to the switching pattern 60° asynchronous vector
modulation.
Document and Software Version
1.4
1.5.1 CE Mark
The CE mark (Communauté européenne) indicates that the
product manufacturer conforms to all applicable EU
directives.
The EU directives applicable to the design and
manufacture of frequency converters are:
The Low Voltage Directive.
•
The EMC Directive.
•
The Machinery Directive (for units with an
•
integrated safety function).
The CE mark is intended to eliminate technical barriers to
free trade between the EC and EFTA states inside the ECU.
The CE mark does not regulate the quality of the product.
Technical specications cannot be deduced from the CE
mark.
1.5.2 Low Voltage Directive
Frequency converters are classied as electronic
components and must be CE labeled in accordance with
the Low Voltage Directive. The directive applies to all
electrical equipment in the 50–1000 V AC and the 75–
1500 V DC voltage ranges.
The directive mandates that the equipment design must
ensure the safety and health of people and livestock, and
the preservation of material by ensuring the equipment is
properly installed, maintained, and used as intended.
Danfoss CE labels comply with the Low Voltage Directive,
and Danfoss provides a declaration of conformity at
request.
This manual is regularly reviewed and updated. All
suggestions for improvement are welcome. Table 1.2 shows
the document version and the corresponding software
version.
EditionRemarks
MG07B3
1.5
Frequency converters are designed in compliance with the
directives described in this section.
Electromagnetic compatibility (EMC) means that electromagnetic interference between pieces of equipment does
not hinder their performance. The basic protection
requirement of the EMC Directive 2014/30/EU states that
devices that generate electromagnetic interference (EMI) or
whose operation could be aected by EMI must be
designed to limit the generation of electromagnetic
interference and shall have a suitable degree of immunity
to EMI when properly installed, maintained, and used as
intended.
A frequency converter can be used as standalone device or
as part of a more complex installation. Devices in either of
these cases must bear the CE mark. Systems must not be
CE marked but must comply with the basic protection
requirements of the EMC directive.
IntroductionDesign Guide
1.5.4 UL Compliance
UL-listed
Illustration 1.2 UL
Applied standards and compliance for STO
Using STO on terminals 37 and 38 requires fulllment of all
provisions for safety including relevant laws, regulations,
and guidelines. The integrated STO function complies with
the following standards:
IEC/EN 61508:2010, SIL2
•
IEC/EN 61800-5-2:2007, SIL2
•
IEC/EN 62061:2015, SILCL of SIL2
•
EN ISO 13849-1:2015, Category 3 PL d
•
Frequency converters can be subject to regional and/or
national export control regulations.
An ECCN number is used to classify all frequency
converters that are subject to export control regulations.
11
The ECCN number is provided in the documents
accompanying the frequency converter.
In case of re-export, it is the responsibility of the exporter
to ensure compliance with the relevant export control
regulations.
Safety
1.6
Frequency converters contain high-voltage components
and have the potential for fatal injury if handled
improperly. Only qualied personnel are allowed to install
and operate the equipment. Do not attempt repair work
without rst removing power from the frequency converter
and waiting the designated duration of time for stored
electrical energy to dissipate.
Refer to the operating instructions shipped with the unit,
and available online for:
Discharge time.
•
Detailed safety instructions and warnings.
•
Strict adherence to safety precautions and notices is
mandatory for safe operation of the frequency converter.
Induced voltage from output motor cables that run
together can charge equipment capacitors, even when
the equipment is turned o and locked out. Failure to
run output motor cables separately or use shielded
cables could result in death or serious injury.
Run output motor cables separately.
•
Use shielded cables.
•
Comply with local and national electrical codes
•
for cable sizes. For maximum cable sizes, see
chapter 7.1 Electrical Data.
Follow motor manufacturer wiring requirements.
•
Motor wiring knockouts or access panels are
•
provided at the base of IP21 (NEMA type 1) units.
Do not wire a starting or pole-changing device
•
(for example Dahlander motor or slip ring
induction motor) between the frequency
converter and the motor.
Procedure
1.Strip a section of the outer cable insulation.
Recommended length is 10–15 mm (0.4–0.6 in).
2.Position the stripped cable under the cable clamp
to establish mechanical xation and electrical
contact between the cable shield and ground.
3.Connect the ground cable to the nearest
grounding terminal in accordance with the
grounding instructions provided in chapter
Grounding in the VLT® Midi Drive FC 280 Operating
Guide. See Illustration 2.4.
4.Connect the 3-phase motor wiring to terminals
96 (U), 97 (V), and 98 (W), as shown in
Illustration 2.4.
5.Tighten the terminals in accordance with the
information provided in chapter 7.7 ConnectionTightening Torques.
Illustration 2.4 Motor Connection
The mains, motor, and grounding connection for singlephase and 3-phase frequency converters are shown in
Illustration 2.5, Illustration 2.6, and Illustration 2.7, respectively. Actual congurations vary with unit types and
optional equipment.
NOTICE
In motors without phase insulation, paper, or other
insulation reinforcement suitable for operation with
voltage supply, use a sine-wave lter on the output of
the frequency converter.
Illustration 2.5 Mains, Motor, and Grounding Connection for
Single-phase Units (K1, K2)
Illustration 2.6 Mains, Motor, and Grounding Connection for 3-
phase Units (K1, K2, K3)
Illustration 2.7 Mains, Motor, and Grounding Connection for 3-
phase Units (K4, K5)
2.2.2 AC Mains Connection
Size the wiring based on the input current of the
•
frequency converter. For maximum wire sizes, see
chapter 7.1 Electrical Data.
Comply with local and national electrical codes
•
for cable sizes.
Procedure
1.Connect the AC input power cables to terminals
N and L for single-phase units (see
Illustration 2.5), or to terminals L1, L2, and L3 for
3-phase units (see Illustration 2.6 and
Illustration 2.7).
2.Depending on the conguration of the
equipment, connect the input power to the
mains input terminals or the input disconnect.
3.Ground the cable in accordance with the
grounding instructions in chapter Grounding in
®
the VLT
4.When supplied from an isolated mains source (IT
mains or oating delta) or TT/TN-S mains with a
grounded leg (grounded delta), ensure that the
RFI lter screw is removed. Removing the RFI
screw prevents damage to the DC link and
reduces ground capacity currents in accordance
with IEC 61800-3 (see Illustration 7.13, the RFI
screw locates on the side of the frequency
converter).
Illustration 2.8 shows the removable frequency converter
connectors. Terminal functions and default settings are
summarized in Table 2.3 and Table 2.4.
Illustration 2.8 Control Terminal Locations
Illustration 2.9 Terminal Numbers
See chapter 7.6 Control Input/Output and Control Data for
terminal ratings details.
TerminalParameter
Digital I/O, pulse I/O, encoder
12, 13–+24 V DC
Parameter 5-10
18
19
27
Terminal 18
Digital Input
Parameter 5-11
Terminal 19
Digital Input
Parameter 5-01
Terminal 27
Mode
Parameter 5-12
Terminal 27
Digital Input
Parameter 5-30
Terminal 27
Digital Output
Default
setting
[8] Start
[10] Reversing
DI [2] Coast
inverse
DO [0] No
operation
Description
24 V DC supply
voltage. Maximum
output current is
100 mA for all
24 V loads.
Digital inputs.
Selectable for
either digital
input, digital
output, or pulse
output. The
default setting is
digital input.
TerminalParameter
Parameter 5-13
29
32
33
37, 38–STO
42
50–+10 V DC
53
54
55––
Table 2.3 Terminal Descriptions - Digital Inputs/Outputs,
Control terminal connectors can be unplugged from the
frequency converter for ease of installation, as shown in
Illustration 2.8.
For details about STO wiring, refer to chapter 4 Safe TorqueO (STO).
NOTICE
Keep control cables as short as possible and separate
them from high-power cables to minimize interference.
1.Loosen the screws for the terminals.
2.Insert sleeved control cables into the slots.
3.Fasten the screws for the terminals.
4.Ensure that the contact is rmly established and
not loose. Loose control wiring can be the source
of equipment faults or less than optimal
operation.
See chapter 7.5 Cable Specications for control terminal
cable sizes and chapter 3 Application Examples for typical
control cable connections.
22
Table 2.4 Terminal Descriptions - Serial Communication
A frequency converter recties AC voltage from mains into
22
DC voltage. Then the DC voltage is converted into an AC
current with a variable amplitude and frequency.
The motor is supplied with variable voltage/current and
frequency, enabling
phased standard AC motors and permanent magnet
synchronous motors.
innitely variable speed control of 3-
Speed/torque reference
The reference to these controls can be either a single
reference or the sum of various references including
relatively scaled references. Reference handling is explained
in detail in chapter 2.4 Reference Handling.
Process control
There are 2 types of process control:
2.3.1 Control Modes
The frequency converter controls either the speed or the
torque on the motor shaft. The frequency converter also
controls the process for some applications which use
process data as reference or feedback, for example,
temperature and pressure. Setting parameter 1-00 Congu-ration Mode determines the type of control.
Speed control
There are 2 types of speed control:
Speed open-loop control, which does not require
•
any feedback from the motor (sensorless).
Speed closed-loop PID control, which requires a
•
speed feedback to an input. A properly optimized
speed closed-loop control has higher accuracy
than a speed open-loop control.
Select which input to use as speed PID feedback in
parameter 7-00 Speed PID Feedback Source.
Torque control
The torque control function is used in applications where
the torque on motor output shaft controls the application
as tension control. Select [2] Torque closed loop or [4]Torque open loop in parameter 1-00 Conguration Mode.
Torque setting is done by setting an analog, digital, or buscontrolled reference. When running torque control, it is
recommended to run a full AMA procedure, because
correct motor data is important in achieving optimal
performance.
works for 2 directions. The torque is calculated
from the internal current measurement in the
frequency converter.
Process closed-loop control, which runs speed
•
open-loop to control the motor internally, is a
basic process PID controller.
Extended PID speed open-loop control, which
•
also runs speed open-loop to control the motor
internally, extends the function of the basic
process PID controller by adding more functions.
For example, feed forward control, clamping,
reference/feedback lter, and gain scaling.
Closed loop in VVC+ mode. This function is used
•
in applications with low to medium dynamic
variation of shaft and oers excellent
performance in all 4 quadrants and at all motor
speeds. The speed feedback signal is mandatory.
Ensure that the encoder resolution is at least
1024 PPR, and the shield cable of the encoder is
properly grounded, because the accuracy of the
speed feedback signal is important. Tune
parameter 7-06 Speed PID Lowpass Filter Time to
get the best speed feedback signal.
Open loop in VVC+ mode. The function is used in
•
mechanically robust applications, but the
accuracy is limited. Open-loop torque function
VLT® Midi Drive FC 280 is a general-purpose frequency converter for variable speed applications. The control principle is
based on VVC+.
FC 280 frequency converters can handle asynchronous motors and permanent magnet synchronous motors up to 22 kW
(30 hp).
The current-sensing principle in FC 280 frequency converters is based on the current measurement by a resistor in the DC
link. The ground fault protection and short circuit behavior are handled by the same resistor.
22
Illustration 2.10 Control Diagram
2.3.3
Control Structure in VVC
Illustration 2.11 Control Structure in VVC+ Open-loop Congurations and Closed-loop Congurations
In the conguration shown in Illustration 2.11, parameter 1-01 Motor Control Principle is set to [1] VVC+ and
parameter 1-00 Conguration Mode is set to [0] Speed open loop. The resulting reference from the reference handling system
is received and fed through the ramp limitation and speed limitation before being sent to the motor control. The output of
the motor control is then limited by the maximum frequency limit.
VLT® Midi Drive FC 280
22
If parameter 1-00 Conguration Mode is set to [1] Speed closed loop, the resulting reference is passed from the ramp
limitation and speed limitation into a speed PID control. The speed PID control parameters are in parameter group 7-0*Speed PID Ctrl. The resulting reference from the speed PID control is sent to the motor control limited by the frequency limit.
Select [3] Process in parameter 1-00
pressure in the controlled application. The process PID parameters are in parameter groups 7-2* Process Ctrl. Feedb and 7-3*Process PID Ctrl.
Conguration Mode to use the process PID control for closed-loop control of speed or
The frequency converter features an integral current limit
control. This feature is activated when the motor current,
and thus the torque, is higher than the torque limits set in
parameter 4-16 Torque Limit Motor Mode,
parameter 4-17 Torque Limit Generator Mode, and
parameter 4-18 Current Limit.
When the frequency converter is at the current limit during
motor operation or regenerative operation, the frequency
converter tries to get below the preset torque limits as
quickly as possible without losing control of the motor.
2.3.5 Local (Hand On) and Remote (Auto
On) Control
Operate the frequency converter manually via the local
control panel (graphic LCP or numerical LCP) or remotely
via analog/digital inputs or eldbus.
Start and stop the frequency converter by pressing the
[Hand On] and [Reset] keys on the LCP. Set-up is required
via the following parameters:
22
Parameter 0-40 [Hand on] Key on LCP.
•
Parameter 0-44 [O/Reset] Key on LCP.
•
Parameter 0-42 [Auto on] Key on LCP.
•
Reset alarms via the [Reset] key or via a digital input, when
the terminal is programmed to Reset.
Illustration 2.12 GLCP Control Keys
Illustration 2.13 NLCP Control Keys
Local reference forces the
loop, independent of the setting in parameter 1-00 Congu-ration Mode.
conguration mode to open
Local reference is restored when the frequency converter
powers down.
The remote reference is calculated once in every scan
interval and initially consists of 2 types of reference
inputs:
1.X (the external reference): A sum (see
parameter 3-04 Reference Function) of up to 4
externally selected references, comprising any
combination (determined by the setting of
parameter 3-15 Reference 1 Source,
parameter 3-16 Reference 2 Source, and
parameter 3-17 Reference 3 Source) of a xed
preset reference (parameter 3-10 Preset Reference),
variable analog references, variable digital pulse
references, and various eldbus references in any
unit the frequency converter is monitoring ([Hz],
[RPM], [Nm], and so on).
2.Y (the relative reference): A sum of 1 xed preset
reference (parameter 3-14 Preset Relative Reference)
and 1 variable analog reference
(parameter 3-18 Relative Scaling ReferenceResource) in [%].
The 2 types of reference inputs are combined in the
following formula:
Remote reference=X+X*Y/100%.
If relative reference is not used, set parameter 3-18 Relative
Scaling Reference Resource to [0] No function and
parameter 3-14 Preset Relative Reference to 0%. The digital
inputs on the frequency converter can activate both the
catch up/slow down function and the freeze reference
function. The functions and parameters are described in
the VLT® Midi Drive FC 280 Programming Guide.
The scaling of analog references is described in parametergroups 6-1* Analog Input 53 and 6-2* Analog Input 54, and
the scaling of digital pulse references is described in
parameter group 5-5* Pulse Input.
Reference limits and ranges are set in parameter group 3-0*Reference Limits.
2.4.1 Reference Limits
Parameter 3-00 Reference Range, parameter 3-02 Minimum
Reference, and parameter 3-03 Maximum Reference dene
the allowed range of the sum of all references. The sum of
all references is clamped when necessary. The relation
between the resulting reference (after clamping) and the
sum of all references are shown in Illustration 2.15 and
Illustration 2.16.
Illustration 2.15 Sum of All References When Reference Range
Illustration 2.16 Sum of All References When Reference Range
is Set to 1
The value of parameter 3-02 Minimum Reference cannot be
set to less than 0, unless parameter 1-00 CongurationMode is set to [3] Process. In that case, the following
relations between the resulting reference (after clamping)
and the sum of all references are as shown in
Illustration 2.17.
130BA186.11
P 3-03
P 3-02
Sum of all
references
P 3-00 Reference Range= [0] Min to Max
Resulting reference
Resource output
[Hz]
Resource input
Terminal X
high
High reference/
feedback value
130BD431.10
8
[V]
50
10
P1
P2
10
Low reference/
feedback value
Product Overview
VLT® Midi Drive FC 280
2.4.3 Scaling of Analog and Pulse
References and Feedback
22
References and feedback are scaled from analog and pulse
inputs in the same way. The only dierence is that a
reference above or below the specied minimum and
maximum endpoints (P1 and P2 in Illustration 2.18) are
clamped while feedbacks above or below are not.
Illustration 2.17 Sum of All References When Minimum
Reference is Set to a Minus Value
2.4.2 Scaling of Preset References and Bus
References
Preset references are scaled according to the following
rules:
When parameter 3-00 Reference Range is set to [0]
•
Min–Max, 0% reference equals 0 [unit] where unit
can be any unit, for example RPM, m/s, and bar.
100% reference equals the maximum (absolute
value of parameter 3-03 Maximum Reference,
absolute value of parameter 3-02 MinimumReference).
When parameter 3-00 Reference Range is set to [1]
•
-Max–+Max, 0% reference equals 0 [unit], and
100% reference equals maximum reference.
Bus references are scaled according to the following
rules:
When parameter 3-00 Reference Range is set to [0]
•
Min–Max, 0% reference equals minimum
reference and 100% reference equals maximum
reference.
When parameter 3-00 Reference Range is set to [1]
•
-Max–+Max, -100% reference equals -maximum
reference, and 100% reference equals maximum
reference.
The endpoints P1 and P2 are dened in Table 2.5 depending on the choice of input.
InputAnalog 53
voltage mode
P1=(Minimum input value, minimum reference value)
Minimum reference valueParameter 6-14 Te
rminal 53 Low
Ref./Feedb. Value
Minimum input valueParameter 6-10 Te
rminal 53 Low
Voltage [V]
P2=(Maximum input value, maximum reference value)
Maximum reference valueParameter 6-15 Te
rminal 53 High
Ref./Feedb. Value
Maximum input valueParameter 6-11 Te
rminal 53 High
Voltage [V]
Table 2.5 P1 and P2 Endpoints
Analog 54
voltage mode
Parameter 6-24 Te
rminal 54 Low
Ref./Feedb. Value
Parameter 6-20 Te
rminal 54 Low
Voltage [V]
Parameter 6-25 Te
rminal 54 High
Ref./Feedb. Value
Parameter 6-21 Te
rminal 54 High
Voltage [V]
Analog 54
current mode
Parameter 6-24 Ter
minal 54 Low Ref./
Feedb. Value
Parameter 6-22 Ter
minal 54 Low
Current [mA]
Parameter 6-25 Ter
minal 54 High Ref./
Feedb. Value
Parameter 6-23 Ter
minal 54 High
Current [mA]
Pulse input 29Pulse input 33
Parameter 5-52 Ter
m. 29 Low Ref./
Feedb. Value
Parameter 5-50 Ter
m. 29 Low
Frequency [Hz]
Parameter 5-53 Ter
m. 29 High Ref./
Feedb. Value
Parameter 5-51 Ter
m. 29 High
Frequency [Hz]
Parameter 5-57 Term. 33
Low Ref./Feedb. Value
Parameter 5-55 Term. 33
Low Frequency [Hz]
Parameter 5-58 Term. 33
High Ref./Feedb. Value
Parameter 5-56 Term. 33
High Frequency [Hz]
2.4.4 Dead Band Around Zero
Sometimes, the reference (in rare cases also the feedback) should have a dead band around 0 to ensure that the machine is
stopped when the reference is near 0.
22
To make the dead band active and to set the amount of dead band, do the following:
P1 or P2
Set either the minimum reference value (see Table 2.5 for relevant parameter) or maximum reference value at 0. In
•
other words, either P1 or P2 must be on the X-axis in Illustration 2.19.
Ensure that both points dening the scaling graph are in the same quadrant.
•
denes the size of the dead band as shown in Illustration 2.19.
Low reference 0 Hz
High reference 20 Hz
Low voltage 1 V
High voltage 10 V
Ext. source 1
Range:
0.0% (0 Hz)
150.0% (30 Hz)
150.0% (30 Hz)
Ext. reference
Range:
0.0% (0 Hz)
30 Hz 10 V
Ext. Reference
Absolute
0 Hz 1 V
Reference
algorithm
Reference
100.0% (20 Hz)
0.0% (0 Hz)
Range:
Limited to:
-100%- +100%
(-20 Hz- +20 Hz)
Limited to: -200%- +200%
(-40 Hz- +40 Hz)
Reference is scaled
according to
max reference giving a
speed.!!!
Scale to
speed
+20 Hz
-20 Hz
Range:
Speed
setpoint
Motor
control
Range:
–10 Hz
+10 Hz
Motor
Digital input 19
Low No reversing
High Reversing
Limits Speed Setpoint
according to min max speed.!!!
Motor PID
Dead band
Digital input
General Reference
parameters:
Reference Range: -Max - Max
Minimum Reference: Don't care
Maximum Reference: 20 Hz (100.0%)
General Motor
parameters:
Motor speed direction: Both directions
Motor speed Low limit: 0 Hz
Motor speed high limit: 10 Hz
Product OverviewDesign Guide
Case 2: Positive reference with dead band, digital input to trigger reverse, part II
Illustration 2.21 shows how reference input with limits outside -maximum to +maximum limits clamps to the input low and
high limits before adding to external reference, and how the external reference is clamped to -maximum to +maximum by
the reference algorithm.
22
Illustration 2.21 Clamping of Reference Input with Limits outside -Maximum to +Maximum
In this example, the speed PID control is used to maintain a constant motor speed regardless of the changing load on the
motor. The required motor speed is set via a potentiometer connected to terminal 53. The speed range is 0–1500 RPM
corresponding to 0–10 V over the potentiometer. A switch connected to terminal 18 controls starting and stopping. The
speed PID monitors the actual RPM of the motor by using a 24 V (HTL) incremental encoder as feedback. The feedback
sensor is an encoder (1024 pulses per revolution) connected to terminals 32 and 33. The pulse frequency range to terminals
32 and 33 is 4 Hz–32 kHz.
22
Illustration 2.22 Speed Control Programming
Follow the steps in Table 2.8 to program the speed control (see explanation of settings in the programming guide)
In Table 2.8, it is assumed that all other parameters and switches remain at their default setting.
FunctionParameter numberSetting
1) Make sure that the motor runs properly. Do the following:
Set the motor parameters using the data on the
nameplate.
Perform an AMA.Parameter 1-29 Automatic
2) Check that the motor is running and that the encoder is attached properly. Do the following:
Press [Hand On]. Check that the motor is running and note
the rotation direction (referred to as the positive direction).
3) Make sure that the frequency converter limits are set to safe values:
Set acceptable limits for the references.Parameter 3-02 Minimum
Check that the ramp settings are within frequency
converter capabilities and allowed application operating
The process PID control can be used to control application parameters that can be measured by a sensor (for example
pressure, temperature, ow) and aected by the connected motor through a pump, fan, or other connected devices.
Table 2.9 shows the control congurations in which the process control is possible. Refer to chapter 2.3 Control Structures to
see where the speed control is active.
Parameter 1-00 Conguration ModeParameter 1-01 Motor Control Principle
U/f
VVC
+
[3] ProcessProcessProcess
Table 2.9 Control Conguration
NOTICE
The process control PID works under the default parameter setting, but tuning the parameters is recommended to
optimize the application control performance.
Illustration 2.24 is an example of a process PID control used
in a ventilation system:
Illustration 2.24 Process PID Control in a Ventilation System
In a ventilation system, the temperature can be set from -5
to +35 °C (23–95 °F) with a potentiometer of 0–10 V. To
keep the set temperature constant, use the process control.
Illustration 2.25 2-wire Transmitter
The control is inverse, which means that when the
temperature increases, the ventilation speed is increased as
well to generate more air. When the temperature drops,
the speed is reduced. The transmitter used is a
temperature sensor with a working range of -10 to +40 °C
(14–104 °F), 4–20 mA.
1.Start/stop via the switch connected to terminal
18.
2.Temperature reference via potentiometer (-5 to
+35 °C (23–95 °F), 0–10 V DC) connected to
terminal 53.
3.Temperature feedback via transmitter (-10 to
+40 °C (14–104 °F), 4–20 mA) connected to
terminal 54.
FunctionParameter
number
Initialize the frequency converter.Parameter 14-2
2 Operation
Mode
1) Set motor parameters:
Set the motor parameters according to nameplate
data.
Parameter
group 1-2*
Motor Data
Perform a full AMA.Parameter 1-29
Automatic
Motor
Adaption
2) Check that motor is running in the correct direction.
When the motor is connected to the frequency converter with straight forward phase order as U-U; V-V; W-W, the motor shaft usually
turns clockwise seen into shaft end.
Press [Hand On]. Check the shaft direction by
applying a manual reference.
(AMA)
Setting
[2] Initialisation - make a power cycling - press reset.
After conguring the basic settings as described in
chapter 2.5.5 Programming Order, optimize the proportional
gain, the integration time, and the dierentiation time
(parameter 7-33 Process PID Proportional Gain,
parameter 7-34 Process PID Integral Time, and
parameter 7-35 Process PID Dierentiation Time). In most
processes, complete the following procedure:
1.Start the motor.
2.Set parameter 7-33 Process PID Proportional Gain
to 0.3 and increase it until the feedback signal
again begins to vary continuously. Reduce the
value until the feedback signal has stabilized.
Lower the proportional gain by 40–60%.
3.Set parameter 7-34 Process PID Integral Time to
20 s and reduce the value until the feedback
signal again begins to vary continuously. Increase
the integration time until the feedback signal
stabilizes, followed by an increase of 15–50%.
4.Only use parameter 7-35 Process PID DierentiationTime for fast-acting systems (dierentiation time).
The typical value is 4 times the set integration
time. Use the dierentiator when the setting of
the proportional gain and the integration time
has been fully optimized. Make sure that the
lowpass lter dampens the oscillations on the
feedback signal suciently.
NOTICE
If necessary, start/stop can be activated several times to
provoke a variation of the feedback signal.
4.Use Table 2.12 to calculate the necessary PID
control parameters.
22
Danfoss recommends the Ziegler Nichols tuning method.
To tune the PID controls of the frequency converter,
The process operator can do the nal tuning of the control
iteratively to yield satisfactory control.
NOTICE
Do not use the Ziegler Nichols Tuning method in
applications that could be damaged by the oscillations
created by marginally stable control settings.
The criteria for adjusting the parameters are based on
evaluating the system at the limit of stability rather than
on taking a step response. Increase the proportional gain
until observing continuous oscillations (as measured on
the feedback), that is, until the system becomes marginally
stable. The corresponding gain (Ku) is called the ultimate
gain and is the gain, at which the oscillation is obtained.
The period of the oscillation (Pu) (called the ultimate
period) is determined as shown in Illustration 2.26 and
should be measured when the amplitude of oscillation is
small.
1.Select only proportional control, meaning that
the integral time is set to the maximum value,
while the dierentiation time is set to 0.
2.Increase the value of the proportional gain until
the point of instability is reached (sustained
oscillations) and the critical value of gain, Ku, is
reached.
3.Measure the period of oscillation to obtain the
critical time constant, Pu.
Illustration 2.26 Marginally Stable System
Type of
control
PI-control0.45 x K
PID tight
control
PID some
overshoot
Table 2.12 Ziegler Nichols Tuning for Regulator
Proportional
gain
u
0.6 x K
u
0.33 x K
u
Integral timeDierentiation
0.833 x P
0.5 x P
0.5 x P
u
u
u
time
0.125 x P
0.33 x P
–
u
u
EMC Emission and Immunity
2.6
2.6.1 General Aspects of EMC Emission
Burst transient is conducted at frequencies in the range 150 kHz to 30 MHz. Airborne interference from the frequency
converter system in the range 30 MHz to 1 GHz is generated from the frequency converter, motor cable, and motor.
Capacitive currents in the motor cable coupled with a high dU/dt from the motor voltage generate leakage currents.
Using a shielded motor cable increases the leakage current (see Illustration 2.27) because shielded cables have higher
capacitance to ground than unshielded cables. If the leakage current is not
mains in the radio frequency range below approximately 5 MHz. Since the leakage current (I1) is carried back to the unit
through the shield (I3), there is only a small electro-magnetic eld (I4) from the shielded motor cable.
The shield reduces the radiated interference but increases the low-frequency interference on the mains. Connect the motor
cable shield to the frequency converter enclosure and the motor enclosure. This is best done by using integrated shield
clamps to avoid twisted shield ends (pigtails). The shield clamps increase the shield impedance at higher frequencies, which
reduces the shield
eect and increases the leakage current (I4).
Mount the shield on the enclosure at both ends if a shielded cable is used for the following purposes:
In some situations, however, it is necessary to break the shield to avoid current loops.
22
1Ground cable
2Shield
3AC mains supply
4Frequency converter
5Shielded motor cable
6Motor
Illustration 2.27 EMC Emission
If placing the shield on a mounting plate for the frequency converter, use a metal mounting plate to convey the shield
currents back to the unit. Ensure good electrical contact from the mounting plate through the mounting screws to the
frequency converter chassis.
When using unshielded cables, some emission requirements are not complied with, although the immunity requirements are
observed.
To reduce the interference level from the entire system (unit and installation), make motor and brake cables as short as
possible. Avoid placing cables with a sensitive signal level alongside mains, motor, and brake cables. Radio interference
higher than 50 MHz (airborne) is especially generated by the control electronics.
VLT® Midi Drive FC 280 complies with the industrial environment requirements, which are higher than the requirements for
the home and oce environments. Therefore, FC 280 also complies with the lower requirements for home and oce
environments with a large safety margin.
To document immunity against burst transient from electrical phenomena, the following immunity tests have been made on
a system consisting of:
A frequency converter (with options if relevant).
•
A shielded control cable.
•
A control box with potentiometer, motor cable, and motor.
•
The tests were performed in accordance with the following basic standards:
EN 61000-4-2 (IEC 61000-4-2) Electrostatic discharges (ESD): Simulation of electrostatic discharges from human
•
beings.
EN 61000-4-3 (IEC 61000-4-3) Radiated immunity: Amplitude modulated simulation of the
•
eects of radar and
radio communication equipment and mobile communications equipment.
EN 61000-4-4 (IEC 61000-4-4) Burst transients: Simulation of interference caused by switching a contactor, relay,
•
or similar devices.
EN 61000-4-5 (IEC 61000-4-5) Surge transients: Simulation of transients caused by, for example, lightning that
•
strikes near installations.
EN 61000-4-6 (IEC 61000-4-6) Conducted immunity: Simulation of the eect from radio-transmission equipment
•
joined by connection cables.
FC 280 follows IEC 61800-3 standard. See Table 2.15 for details.
PELV oers protection through extra low voltage.
Protection against electric shock is ensured when the
electrical supply is of the PELV type and the installation is
made as described in local/national regulations on PELV
supplies.
All control terminals and relay terminals 01–03 comply
with PELV (protective extra low voltage). This does not
apply to grounded Delta leg above 400 V.
Galvanic (ensured) isolation is obtained by fullling
requirements for higher isolation and by providing the
relevant creapage/clearance distances. These requirements
are described in the EN 61800-5-1 standard.
The components that make up the electrical isolation, as
shown in Illustration 2.28, also comply with the
requirements for higher isolation and the relevant test as
described in EN 61800-5-1.
The PELV galvanic isolation can be shown in 3 locations
(see Illustration 2.28):
WARNING
Before touching any electrical parts, ensure that other
voltage inputs have been disconnected, such as load
sharing (linkage of DC intermediate circuit) and the
motor connection for kinetic back-up. Observe the
discharge time stated in chapter Safety in the VLT® Midi
Drive FC 280 Operating Guide. Failure to follow
recommendations could result in death or serious injury.
2.8 Ground Leakage Current
Follow national and local codes regarding protective
grounding of equipment with a leakage current >3.5 mA.
Frequency converter technology implies high frequency
switching at high power. This switching generates a
leakage current in the ground connection. A fault current
in the frequency converter at the output power terminals
might contain a DC component, which can charge the
lter capacitors and cause a transient ground current.
The ground leakage current is made up of several contributions and depends on various system congurations
including RFI ltering, shielded motor cables, and
frequency converter power.
22
To maintain PELV, all connections made to the control
terminals must be PELV, for example, the thermistor must
be reinforced/double insulated.
1 Power supply (SMPS) for control cassette
2 Communication between power card and control cassette
3 Isolation between STO inputs and IGBT circuit
4 Customer relay
Illustration 2.28 Galvanic Isolation
The functional galvanic isolation (a and b on
Illustration 2.28) is for the 24 V back-up option and the
RS485 standard bus interface.
Illustration 2.29 Inuence the Cable Length and Power Size on
Leakage Current, Pa>P
b
The leakage current also depends on the line distortion.
Illustration 2.31 Mains Contributions to Leakage Current
Illustration 2.30 Inuence of Line Distortion on Leakage
Current
NOTICE
High leakage current may cause the RCDs to switch o.
To avoid this problem, remove the RFI screw when a
lter is being charged.
EN/IEC61800-5-1 (Power Drive System Product Standard)
requires special care if the leakage current exceeds 3.5 mA.
Grounding must be reinforced in 1 of the following ways:
Ground wire (terminal 95) of at least 10 mm
•
(8 AWG).
2 separate ground wires that comply with the
•
dimensioning rules.
See EN/IEC61800-5-1 for further information.
Using RCDs
Where residual current devices (RCDs), also known as earth
leakage circuit breakers (ELCBs), are used, comply with the
following:
Use RCDs of type B only, which are capable of
•
detecting AC and DC currents.
Use RCDs with an inrush delay to prevent faults
•
caused by transient ground currents.
Dimension RCDs according to the system congu-
•
ration and environmental considerations.
2
Illustration 2.32 Inuence of Cut-o Frequency of the RCD on
what is Responded to/Measured
For more details, refer to the RCD Application Note.
Brake Functions
2.9
2.9.1 Mechanical Holding Brake
A mechanical holding brake mounted directly on the
motor shaft normally performs static braking.
NOTICE
When the holding brake is included in a safety chain, a
frequency converter cannot provide a safe control of a
mechanical brake. Include a redundancy circuitry for the
brake control in the total installation.
overvoltage under a certain threshold by
directing the brake energy from the motor to the
connected brake resistor (parameter 2-10 BrakeFunction = [1] Resistor brake).
Adjust the threshold in parameter 2-14 Brakevoltage reduce, with 70 V range for 3x380–480 V.
AC brake: The brake energy is distributed in the
•
motor by changing the loss conditions in the
motor. The AC brake function cannot be used in
applications with high cycling frequency as this
overheats the motor (parameter 2-10 BrakeFunction = [2] AC brake).
DC brake: An overmodulated DC current added to
•
the AC current works as an eddy current brake
(parameter 2-02 DC Braking Time≠0 s).
2.9.3 Brake Resistor Selection
To handle higher demands by generatoric braking, a brake
resistor is necessary. Using a brake resistor ensures that the
heat is absorbed in the brake resistor and not in the
frequency converter. For more information, see the VLTBrake Resistor MCE 101 Design Guide.
If the amount of kinetic energy transferred to the resistor
in each braking period is not known, calculate the average
power based on the cycle time and braking time. The
resistor intermittent duty cycle is an indication of the duty
cycle at which the resistor is active. Illustration 2.33 shows a
typical braking cycle.
The intermittent duty cycle for the resistor is calculated as
follows:
®
Illustration 2.33 Typical Braking Cycle
Power range:
0.37–22 kW (0.5–30 hp) 3x380–480 V
0.37–3.7 kW (0.5–5 hp) 3x200–240 V
Cycle time (s)120
Braking duty cycle at 100% torqueContinuous
Braking duty cycle at overtorque
(150/160%)
Table 2.16 Braking at High Overload Torque Level
40%
Danfoss oers brake resistors with duty cycles of 10% and
40%. If a 10% duty cycle is applied, the brake resistors are
able to absorb brake power for 10% of the cycle time. The
remaining 90% of the cycle time is used for dissipating
excess heat.
NOTICE
Make sure that the resistor is designed to handle the
required braking time.
The maximum allowed load on the brake resistor is stated
as a peak power at a given intermittent duty cycle and can
be calculated as:
22
Duty cycle = tb/T
tb is the braking time in seconds.
T = cycle time in seconds.
Brake resistance calculation
2
U
x0 . 83
Ω =
dc,br
P
peak
R
br
where
P
peak
= P
x Mbr [%] x η
motor
motor
x η
VLT
[W]
As shown, the brake resistance depends on the DC-link
voltage (Udc).
The threshold can be adjusted in parameter 2-14 Brake
2.9.4 Control with Brake Function
voltage reduce, with 70 V range.
The brake is protected against short-circuiting of the brake
22
NOTICE
The greater the reduction value, the faster the reaction
to a generator overload. Should only be used if there are
problems with overvoltage in the DC-link voltage.
resistor, and the brake transistor is monitored to ensure
that short-circuiting of the transistor is detected. A relay/
digital output can be used for protecting the brake resistor
from overloading caused by a fault in the frequency
converter.
In addition, the brake enables readout of the momentary
NOTICE
Make sure that the brake resistor can cope with a
voltage of 410 V or 800 V.
power and the mean power for the latest 120 s. The brake
can also monitor the power energizing and make sure that
it does not exceed a limit selected in parameter 2-12 Brake
Power Limit (kW).
Danfoss recommends calculating the brake resistance R
according to the following formula. The recommended
brake resistance guarantees that the frequency converter is
able to brake at the highest braking torque (M
br(%)
160%.
2
U
x100x0.83
R
Ω =
rec
η
is typically at 0.80 (≤7.5 kW (10 hp)); 0.85 (11–22 kW
motor
dc
P
motor
xM
br( % )
xη
VLT
xη
motor
(15–30 hp))
η
is typically at 0.97
VLT
) of
rec
NOTICE
Monitoring the brake power is not a safety function. A
thermal switch is required to prevent the brake power
from exceeding the limit. The brake resistor circuit is not
ground leakage protected.
Overvoltage control (OVC) (exclusive brake resistor) can be
selected as an alternative brake function in
parameter 2-17 Over-voltage Control. This function is active
for all units. The function ensures that a trip can be
avoided if the DC-link voltage increases. This is done by
For FC 280, R
at 160% braking torque is written as:
rec
increasing the output frequency to limit the voltage from
the DC link. It is a useful function, for example if the ramp-
480
480
V: R
V: R
rec
rec
396349
=
397903
=
P
P
motor
motor
Ω
Ω
1)
2)
1) For frequency converters ≤7.5 kW (10 hp) shaft output.
2) For frequency converters 11–22 kW (15–30 hp) shaft
output.
down time is too short to avoid tripping of the frequency
converter. In this situation, the ramp-down time is
extended.
NOTICE
OVC can be activated when running a PM motor (when
parameter 1-10 Motor Construction is set to [1] PM non-
salient SPM).
NOTICE
The resistance of the brake resistor should not be higher
than the value recommended by Danfoss. For brake
resistors with a higher ohmic value, the 160% braking
torque may not be achieved because the frequency
converter might cut out for safety reasons.
The resistance should be bigger than R
min
.
NOTICE
If a short circuit in the brake transistor occurs, prevent
power dissipation in the brake resistor by using a mains
switch or contactor to disconnect the mains for the
frequency converter. The frequency converter can control
the contactor.
NOTICE
Do not touch the brake resistor because it can get hot
during braking. To avoid re risk, place the brake resistor
in a secure environment.
2.10 Motor Insulation
Modern design of motors for use with frequency
converters have a high degree of insulation to account for
new generation high-eciency IGBTs with high dU/dt. For
retrot in old motors it is necessary to conrm the motor
insulation or to mitigate with a dU/dt lter or if necessary
a sine-wave lter.
2.10.1 Sine-wave Filters
When a frequency converter controls a motor, resonance
noise is heard from the motor. This noise, which is the
result of the motor design, occurs every time an inverter
switch in the frequency converter is activated. The
frequency of the resonance noise thus corresponds to the
Coast
Start timer
Set Do X low
Select set-up 2
. . .
Running
Warning
Torque limit
Digital input X 30/2
. . .
=
TRUE longer than..
. . .
. . .
130BA062.14
State 1
13-51.0
13-52.0
State 2
13-51.1
13-52.1
Start
event P13-01
State 3
13-51.2
13-52.2
State 4
13-51.3
13-52.3
Stop
event P13-02
Stop
event P13-02
Stop
event P13-02
Product OverviewDesign Guide
Danfoss supplies a sine-wave lter to dampen the acoustic
motor noise.
The lter reduces the ramp-up time of the voltage, the
peak load voltage U
, and the ripple current ΔI to the
PEAK
motor, which means that current and voltage become
almost sinusoidal. So, the acoustic motor noise is reduced
to a minimum.
The ripple current in the sine-wave lter coils also causes
some noise. Solve the problem by integrating the lter in a
cabinet or similar.
2.10.2 dU/dt Filters
Danfoss supplies dU/dt lters. dU/dt lters are dierential
mode, low-pass lters that reduce motor terminal phaseto-phase peak voltages and reduce the rise time to a level
that lowers the stress on the insulation at the motor
windings. This is especially an issue with short motor
cables.
Compared to the sine-wave lters (see chapter 2.10.1 Sine-wave Filters), the dU/dt lters have a cut-o frequency
above the switching frequency.
Smart Logic Controller
2.11
Smart logic control (SLC) is a sequence of user-dened
actions (see parameter 13-52 SL Controller Action [x])
executed by the SLC when the associated user-dened
event (see parameter 13-51 SL Controller Event [x]) is
evaluated as true by the SLC.
The condition for an event can be a particular status or
that the output from a logic rule or a comparator operand
becomes true. That leads to an associated action as shown
in Illustration 2.34.
22
Illustration 2.34 Associated Action
Events and actions are each numbered and linked in pairs
(states). This means that when event [0] is fullled (attains
the value true), action [0] is executed. After this, the
conditions of event [1] are evaluated and if evaluated true,
action [1] is executed, and so on. Only 1 event is evaluated
at any time. If an event is evaluated as false, nothing
happens (in the SLC) during the current scan interval, and
no other events are evaluated. When the SLC starts, it
evaluates event [0] (and only event [0]) each scan interval.
Only when event [0] is evaluated true, the SLC executes
action [0] and starts evaluating event [1]. It is possible to
program 1–20 events and actions.
When the last event/action has been executed, the
sequence starts over again from event [0]/action [0].
Illustration 2.35 shows an example with 3 event/actions:
Comparators are used for comparing continuous variables
(for example output frequency, output current, and analog
input) to xed preset values.
The control unit may attempt to correct the ramp if
possible (parameter 2-17 Over-voltage Control).
Incorrect slip compensation setting may cause
•
higher DC-link voltage.
The frequency converter turns o to protect the transistors
and the DC link capacitors when a certain voltage level is
reached.
To select the method used for controlling the DC-link
voltage level, see parameter 2-10 Brake Function and
parameter 2-17 Over-voltage Control.
Mains drop-out
Illustration 2.36 Comparators
During a mains drop-out, the frequency converter keeps
running until the DC-link voltage drops below the
minimum stop level, which is:
Logic rules
Combine up to 3 boolean inputs (true/false inputs) from
timers, comparators, digital inputs, status bits, and events
using the logical operators and, or, and not.
314 V for 3x380–480 V.
•
202 V for 3x200–240 V.
•
225 V for 1x200–240 V.
•
The mains voltage before the drop-out and the motor load
determines how long it takes for the inverter to coast.
Static overload in VVC+ mode
When the frequency converter is overloaded, the torque
limit in parameter 4-16 Torque Limit Motor Mode/
parameter 4-17 Torque Limit Generator Mode is reached, the
control unit reduces the output frequency to reduce the
Illustration 2.37 Logic Rules
load.
If the overload is excessive, a overcurrent which makes the
frequency converter cut out after approximately 5–10 s
may occur.
2.12 Extreme Running Conditions
Short circuit (motor phase-to-phase)
Operation within the torque limit is limited in time (0–60 s)
in parameter 14-25 Trip Delay at Torque Limit.
The frequency converter is protected against short circuits
by current measurement in each of the 3 motor phases or
2.12.1 Motor Thermal Protection
in the DC link. A short circuit between 2 output phases
causes an overcurrent in the frequency converter. The
frequency converter is turned o individually when the
To protect the application from serious damage, VLT® Midi
Drive FC 280 oers several dedicated features.
short-circuit current exceeds the allowed value (alarm 16,
trip lock).
Switching on the output
Switching on the output between the motor and the
frequency converter is fully allowed, and does not damage
the frequency converter. However, fault messages may
appear.
Motor-generated overvoltage
The voltage in the DC link is increased when the motor
acts as a generator. This occurs in following cases:
The load drives the motor (at constant output
•
frequency from the frequency converter).
If the inertia moment is high during deceleration
•
(ramp-down), the friction is low and the rampdown time is too short for the energy to be
dissipated as a loss in the frequency converter,
The torque limit protects the motor from being overloaded
independent of the speed. Torque limit is controlled in
parameter 4-16 Torque Limit Motor Mode and
parameter 4-17 Torque Limit Generator Mode.
Parameter 14-25 Trip Delay at Torque Limit controls the time
before the torque limit warning trips.
Current limit
Parameter 4-18 Current Limit controls the current limit, and
parameter 14-24 Trip Delay at Current Limit controls the
time before the current limit warning trips.
Minimum speed limit
Parameter 4-12 Motor Speed Low Limit [Hz] sets the
minimum output speed that the frequency converter can
provide.
1.21.01.4
30
10
20
100
60
40
50
1.81.62.0
2000
500
200
400
300
1000
600
t [s]
175ZA052.12
f
OUT
= 2 x f
M,N
f
OUT
= 0.2 x f
M,N
f
OUT
= 1 x f
M,N
(par. 1-23)
IMN(par. 1-24)
I
M
Product OverviewDesign Guide
Maximum speed limit
Parameter 4-14 Motor Speed High Limit [Hz] or
parameter 4-19 Max Output Frequency sets the maximum
output speed that the frequency converter can provide.
ETR (electronic thermal relay)
The frequency converter ETR function measures the actual
current, speed, and time to calculate motor temperature.
The function also protects the motor from being
overheated (warning or trip). An external thermistor input
is also available. ETR is an electronic feature that simulates
a bimetal relay based on internal measurements. The
characteristic is shown in Illustration 2.38.
22
Illustration 2.38 ETR
The X-axis shows the ratio between I
motor
and I
motor
nominal. The Y-axis shows the time in seconds before the
ETR cuts o and trips the frequency converter. The curves
show the characteristic nominal speed at twice the
nominal speed and at 0.2 x the nominal speed.
At lower speed, the ETR cuts o at lower heat due to less
cooling of the motor. In that way, the motor is protected
from being overheated even at low speed. The ETR feature
calculates the motor temperature based on actual current
and speed. The calculated temperature is visible as a
readout parameter in parameter 16-18 Motor Thermal.
The purpose of this guideline is to ease the set-up of
encoder connection to the frequency converter. Before
setting up the encoder, the basic settings for a closed-loop
speed control system are shown.
Illustration 3.2 24 V Incremental Encoder, Maximum Cable
Length 5 m (16.4 ft)
3.1.2 Encoder Direction
The order in which the pulses enter the frequency
converter determines the direction of the encoder.
Clockwise direction means that channel A is 90 electrical
degrees before channel B.
Counterclockwise direction means that channel B is 90
electrical degrees before A.
The direction is determined by looking into the shaft end.
3.1.3 Closed-loop Drive System
A drive system usually consists of more elements such as:
Motor.
•
Brake (gearbox, mechanical brake).
Illustration 3.1 24 V Encoder
•
Frequency converter.
•
Encoder as feedback system.
•
Brake resistor for dynamic brake.
•
Transmission.
•
Load.
•
Applications demanding mechanical brake control usually
Parameter 13-52
SL Controller
Action
Parameter 5-40 F
unction Relay
* = Default value
Notes/comments:
If the limit in the feedback
monitor is exceeded, warning61, feedback monitor is issued.
The SLC monitors warning 61,
feedback monitor. If warning 61,
feedback monitor becomes true,
relay 1 is triggered.
External equipment could
indicate that service is required.
If the feedback error goes
below the limit again within
5 s, the frequency converter
continues, and the warning
disappears. Relay 1 persists
[O/Reset] is pressed.
until
61
[22]
Comparator 0
[32] Set
digital out A
low
[80] SL digital
output A
Safe Torque O (STO)
VLT® Midi Drive FC 280
4 Safe Torque O (STO)
The Safe Torque O (STO) function is a component in a
safety control system. STO prevents the unit from
generating the energy that is required to rotate the motor,
thus ensuring safety in emergency situations.
44
The STO function is designed and approved suitable for
the requirements of:
IEC/EN 61508: SIL2
•
IEC/EN 61800-5-2: SIL2
•
IEC/EN 62061: SILCL of SIL2
•
EN ISO 13849-1: Category 3 PL d
•
To achieve the required level of operational safety, select
and apply the components in the safety control system
appropriately. Before using STO, carry out a thorough risk
analysis on the installation to determine whether the STO
function and safety levels are appropriate and sucient.
For more information on safe torque o (STO), see chapter
RS485 is a 2-wire bus interface compatible with multi-drop network topology. The nodes can be connected as a bus, or via
drop cables from a common trunk line. A total of 32 nodes can be connected to 1 network segment.
Repeaters divide network segments, see Illustration 5.1.
55
Illustration 5.1 RS485 Bus Interface
NOTICE
Each repeater functions as a node within the segment in
which it is installed. Each node connected within a given
network must have a unique node address across all
segments.
Terminate each segment at both ends, using either the
termination switch (S801) of the frequency converters or a
biased termination resistor network. Always use shielded
twisted pair (STP) cable for bus cabling and follow good
common installation practice.
Low-impedance ground connection of the shield at every
node is important, including at high frequencies. Thus,
connect a large surface of the shield to ground, for
example with a cable clamp or a conductive cable gland.
Sometimes, it is necessary to apply potential-equalizing
cables to maintain the same ground potential throughout
the network, particularly in installations with long cables.
To prevent impedance mismatch, use the same type of
cable throughout the entire network. When connecting a
motor to the frequency converter, always use shielded
motor cable.
CableShielded twisted pair (STP)
Impedance [Ω]
Cable length [m
(ft)]
Table 5.1 Cable Specications
120
Maximum 1200 (3937) (including drop lines).
Maximum 500 (1640) station-to-station.
5.1.2 Network Connection
Connect the frequency converter to the RS485 network as
follows (see also Illustration 5.2):
1.Connect signal wires to terminal 68 (P+) and
terminal 69 (N-) on the main control board of the
frequency converter.
To reduce noise between conductors, use shielded,
twisted-pair cables.
5.1.5 EMC Precautions
To achieve interference-free operation of the RS485
network, Danfoss recommends the following EMC
precautions.
NOTICE
Observe relevant national and local regulations, for
example regarding protective earth connection. To avoid
Illustration 5.2 Network Connection
55
5.1.3 Hardware Set-up
To terminate the RS485 bus, use the terminator switch on
the main control board of the frequency converter.
The factory setting for the switch is OFF.
5.1.4 Parameter Settings for Modbus
Communication
ParameterFunction
Parameter 8-30 Prot
ocol
Parameter 8-31 Add
ress
Parameter 8-32 Bau
d Rate
Select the application protocol to run for
the RS485 interface.
Set the node address.
NOTICE
The address range depends on the
protocol selected in
parameter 8-30 Protocol.
Set the baud rate.
NOTICE
The default baud rate depends on the
protocol selected in
parameter 8-30 Protocol.
coupling of high-frequency noise between the cables,
keep the RS485 communication cable away from motor
and brake resistor cables. Normally, a distance of
200 mm (8 in) is sucient. Maintain the greatest possible
distance between the cables, especially where cables run
in parallel over long distances. When crossing is
unavoidable, the RS485 cable must cross motor and
brake resistor cables at an angle of 90°.
5.2 FC Protocol
5.2.1 Overview
The FC protocol, also referred to as FC bus or standard bus,
is the Danfoss standard eldbus. It denes an access
technique according to the master/slave principle for
communications via a eldbus.
One master and a maximum of 126 slaves can be
connected to the bus. The master selects the individual
slaves via an address character in the telegram. A slave
itself can never transmit without rst being requested to
do so, and direct telegram transfer between the individual
slaves is not possible. Communications occur in the halfduplex mode.
The master function cannot be transferred to another node
(single-master system).
The default selection depends on the
protocol selected in
parameter 8-30 Protocol.
Specify a minimum delay time between
receiving a request and transmitting a
response. This function is for overcoming
modem turnaround delays.
Specify a maximum delay time between
transmitting a request and receiving a
response.
01324567
195NA036.10
Start
bit
Even Stop
Parity bit
STXLGEADRDATABCC
195NA099.10
RS485 Installation and Set-...Design Guide
The physical layer is RS485, thus utilizing the RS485 port
built into the frequency converter. The FC protocol
supports dierent telegram formats:
A short format of 8 bytes for process data.
•
A long format of 16 bytes that also includes a
•
parameter channel.
A format used for texts.
•
5.2.2 FC with Modbus RTU
The FC protocol provides access to the control word and
bus reference of the frequency converter.
The control word allows the Modbus master to control
several important functions of the frequency converter:
Start.
•
Stop of the frequency converter in various ways:
•
-Coast stop.
-Quick stop.
-DC brake stop.
-Normal (ramp) stop.
Reset after a fault trip.
•
Run at various preset speeds.
•
Run in reverse.
•
Change of the active set-up.
•
Control of the 2 relays built into the frequency
•
converter.
The bus reference is commonly used for speed control. It is
also possible to access the parameters, read their values,
and where possible, write values to them. Accessing the
parameters oers a range of control options, including
controlling the setpoint of the frequency converter when
its internal PI controller is used.
Network Conguration
5.3
FC Protocol Message Framing Structure
5.4
5.4.1 Content of a Character (byte)
Each character transferred begins with a start bit. Then 8
data bits are transferred, corresponding to a byte. Each
character is secured via a parity bit. This bit is set at 1
when it reaches parity. Parity is when there are an equal
number of 1s in the 8 data bits and the parity bit in total.
A stop bit completes a character, consisting of 11 bits in
all.
Illustration 5.3 Content of a Character
5.4.2 Telegram Structure
Each telegram has the following structure:
Start character (STX) = 02 hex.
•
A byte denoting the telegram length (LGE).
•
A byte denoting the frequency converter address
•
(ADR).
Several data bytes (variable, depending on the type of
telegram) follow.
A data control byte (BCC) completes the telegram.
Illustration 5.4 Telegram Structure
5.4.3 Telegram Length (LGE)
55
To enable the FC protocol for the frequency converter, set
the following parameters.
The telegram length is the number of data bytes plus the
address byte ADR and the data control byte BCC.
4 data bytesLGE=4+1+1=6 bytes
12 data bytesLGE=12+1+1=14 bytes
Telegrams containing texts
Table 5.4 Length of Telegrams
1) The 10 represents the
(depending on the length of the text).
xed characters, while the n is variable
101)+n bytes
ADRLGESTXPCD1PCD2BCC
130BA269.10
PKEINDADRLGESTXPCD1PCD2BCC
130BA271.10
PWE
high
PWE
low
PKEIND
130BA270.10
ADRLGESTXPCD1PCD2BCCCh1Ch2Chn
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
130BB918.10
PKEIND
PWE
high
PWE
low
AKPNU
Parameter
commands
and replies
Parameter
number
RS485 Installation and Set-...
VLT® Midi Drive FC 280
5.4.4 Frequency Converter Address (ADR)
Address format 1–126
Bit 7 = 1 (address format 1–126 active).
•
Bit 0–6 = frequency converter address 1–126.
•
Bit 0–6 = 0 broadcast.
•
5.4.7 The PKE Field
The PKE eld contains 2 subelds:
Parameter command and response (AK)
•
Parameter number (PNU)
•
The slave returns the address byte unchanged to the
master in the response telegram.
5.4.5 Data Control Byte (BCC)
55
The checksum is calculated as an XOR-function. Before the
rst byte in the telegram is received, the calculated
checksum is 0.
5.4.6 The Data Field
The structure of data blocks depends on the type of
telegram. There are 3 telegram types, and the type applies
for both control telegrams (master⇒slave) and response
telegrams (slave⇒master).
The 3 types of telegram are:
Illustration 5.8 PKE Field
Bits 12–15 transfer parameter commands from master to
slave and return processed slave responses to the master.
Process block (PCD)
The PCD is made up of a data block of 4 bytes (2 words)
and contains:
Control word and reference value (from master to
•
slave)
Status word and present output frequency (from
•
slave to master)
Illustration 5.5 Process Block
Parameter block
The parameter block is used to transfer parameters
between master and slave. The data block is made up of
12 bytes (6 words) and also contains the process block.
Illustration 5.6 Parameter Block
Text block
The text block is used to read or write texts via the data
block.
If the command cannot be performed, the slave sends
0111 Command cannot be performed response and issues
the following fault reports in Table 5.7.
RS485 Installation and Set-...Design Guide
Fault codeFC specication
0Illegal parameter number.
1Parameter cannot be changed.
2Upper or lower limit is exceeded.
3Subindex is corrupted.
4No array.
5Wrong data type.
6Not used.
7Not used.
9Description element is not available.
11No parameter write access.
15No text available.
17Not applicable while running.
18Other errors.
100–
>100–
130No bus access for this parameter.
131Write to factory set-up is not possible.
132No LCP access.
252Unknown viewer.
253Request is not supported.
254Unknown attribute.
255No error.
Table 5.7 Slave Report
5.4.8 Parameter Number (PNU)
Bits 0–11 transfer parameter numbers. The function of the
relevant parameter is dened in the parameter description
in the VLT® Midi Drive FC 280 Programming Guide.
5.4.9 Index (IND)
parameter 0-01 Language, select the data value by entering
the value in the PWE block. Serial communication is only
capable of reading parameters containing data type 9 (text
string).
Parameter 15-40 FC Type to parameter 15-53 Power Card
Serial Number contain data type 9.
For example, read the unit size and mains voltage range in
parameter 15-40 FC Type. When a text string is transferred
(read), the length of the telegram is variable, and the texts
are of dierent lengths. The telegram length is dened in
the 2nd byte of the telegram (LGE). When using text
transfer, the index character indicates whether it is a read
or a write command.
To read a text via the PWE block, set the parameter
command (AK) to F hex. The index character high-byte
must be 4.
5.4.11 Data Types Supported by the
Frequency Converter
Unsigned means that there is no operational sign in the
telegram.
Data typesDescription
3Integer 16
4Integer 32
5Unsigned 8
6Unsigned 16
7Unsigned 32
9Text string
Table 5.8 Data Types
55
The index is used with the parameter number to read/
write access parameters with an index, for example,
parameter 15-30 Alarm Log: Error Code. The index consists
of 2 bytes: a low byte and a high byte.
Only the low byte is used as an index.
5.4.10 Parameter Value (PWE)
5.4.12 Conversion
The programming guide contains the descriptions of
attributes of each parameter. Parameter values are
transferred as whole numbers only. Conversion factors are
used to transfer decimals.
Parameter 4-12 Motor Speed Low Limit [Hz] has a conversion
factor of 0.1. To preset the minimum frequency to 10 Hz,
The parameter value block consists of 2 words (4 bytes),
and the value depends on the dened command (AK). The
master prompts for a parameter value when the PWE block
transfer the value 100. A conversion factor of 0.1 means
that the value transferred is multiplied by 0.1. The value
100 is thus perceived as 10.0.
contains no value. To change a parameter value (write),
write the new value in the PWE block and send from the
master to the slave.
When a slave responds to a parameter request (read
command), the present parameter value in the PWE block
is transferred and returned to the master. If a parameter
contains several data options, for example
Danfoss assumes that the installed controller supports the
interfaces in this manual, and strictly observes all
requirements and limitations stipulated in the controller
and frequency converter.
The built-in Modbus RTU (remote terminal unit) is
designed to communicate with any controller that
supports the interfaces dened in this manual. It is
assumed that the user has full knowledge of the
capabilities and limitations of the controller.
5.6.2 Overview
Regardless of the type of physical communication
networks, this section describes the process that a
controller uses to request access to another device. This
process includes how the Modbus RTU responds to
requests from another device, and how errors are detected
and reported. It also establishes a common format for the
layout and contents of telegram elds.
During communications over a Modbus RTU network, the
protocol:
Determines how each controller learns its device
•
address.
Recognizes a telegram addressed to it.
•
Determines which actions to take.
•
Extracts any data or other information contained
•
in the telegram.
If a reply is required, the controller constructs the reply
telegram and sends it.
Controllers communicate using a master/slave technique in
which only the master can initiate transactions (called
queries). Slaves respond by supplying the requested data
to the master, or by acting as requested in the query.
The master can address individual slaves, or initiate a
broadcast telegram to all slaves. Slaves return a response
to queries that are addressed to them individually. No
responses are returned to broadcast queries from the
master.
The Modbus RTU protocol establishes the format for the
master query by providing the following information:
The device (or broadcast) address.
•
A function code dening the requested action.
•
Any data to be sent.
•
An error-checking eld.
•
The response telegram of the slave device is also
constructed using Modbus protocol. It contains eldsconrming the action taken, any data to be returned, and
an error-checking eld. If an error occurs in receipt of the
telegram, or if the slave is unable to perform the requested
action, the slave constructs and sends an error message.
Alternatively, a timeout occurs.
5.6.3 Frequency Converter with Modbus
RTU
The frequency converter communicates in Modbus RTU
format over the built-in RS485 interface. Modbus RTU
provides access to the control word and bus reference of
the frequency converter.
The control word allows the Modbus master to control
several important functions of the frequency converter:
Start.
•
Various stops:
•
-Coast stop.
-Quick stop.
-DC brake stop.
-Normal (ramp) stop.
Reset after a fault trip.
•
Run at various preset speeds.
•
Run in reverse.
•
Change the active set-up.
•
Control built-in relay of the frequency converter.
•
The bus reference is commonly used for speed control. It is
also possible to access the parameters, read their values,
and, where possible, write values to them. Accessing the
parameters
controlling the setpoint of the frequency converter when
its internal PI controller is used.
5.7
To enable Modbus RTU on the frequency converter, set the
following parameters:
Telegrams start with a silent period of at least 3.5 character
5.8.1 Introduction
The controllers are set up to communicate on the Modbus
network using RTU (remote terminal unit) mode, with each
byte in a telegram containing 2 4-bit hexadecimal
characters. The format for each byte is shown in Table 5.12.
Start
55
bit
Table 5.12 Format for Each Byte
Coding system8-bit binary, hexadecimal 0–9, A–F.
Bits per byte
Error check eldCyclic redundancy check (CRC).
Table 5.13 Byte Details
Data byteStop/
2 hexadecimal characters contained in each
8-bit eld of the telegram.
1 start bit.
•
8 data bits, least signicant bit sent rst.
•
1 bit for even/odd parity; no bit for no
•
parity.
1 stop bit if parity is used; 2 bits if no
•
parity.
Stop
parity
5.8.2 Modbus RTU Telegram Structure
The transmitting device places a Modbus RTU telegram
into a frame with a known beginning and ending point.
This allows receiving devices to begin at the start of the
telegram, read the address portion, determine which
device is addressed (or all devices, if the telegram is
broadcast), and to recognize when the telegram is
completed. Partial telegrams are detected and errors set as
a result. Characters for transmission must be in
hexadecimal 00–FF format in each eld. The frequency
converter continuously monitors the network bus, also
during silent intervals. When the rsteld (the address
eld) is received, each frequency converter or device
decodes it to determine which device is being addressed.
Modbus RTU telegrams addressed to 0 are broadcast
telegrams. No response is permitted for broadcast
telegrams. A typical telegram frame is shown in Table 5.14.
StartAddress FunctionData
T1-T2-T3-
T4
Table 5.14 Typical Modbus RTU Telegram Structure
8 bits8 bitsN x 8 bits 16 bits
CRC
check
End
T1-T2-T3-
T4
intervals. The silent period is implemented as a multiple of
character intervals at the selected network baud rate
(shown as Start T1-T2-T3-T4). The rst eld to be
transmitted is the device address. Following the last
transmitted character, a similar period of at least 3.5
character intervals marks the end of the telegram. A new
telegram can begin after this period.
Transmit the entire telegram frame as a continuous stream.
If a silent period of more than 1.5 character intervals
occurs before completion of the frame, the receiving
device
ushes the incomplete telegram and assumes that
the next byte is the address eld of a new telegram.
Similarly, if a new telegram begins before 3.5 character
intervals after a previous telegram, the receiving device
considers it a continuation of the previous telegram. This
behavior causes a timeout (no response from the slave),
since the value in the nal CRC eld is not valid for the
combined telegrams.
5.8.4 Address Field
The address eld of a telegram frame contains 8 bits. Valid
slave device addresses are in the range of 0–247 decimal.
The individual slave devices are assigned addresses in the
range of 1–247. 0 is reserved for broadcast mode, which all
slaves recognize. A master addresses a slave by placing the
slave address in the address eld of the telegram. When
the slave sends its response, it places its own address in
this address eld to let the master know which slave is
responding.
5.8.5 Function Field
The function eld of a telegram frame contains 8 bits. Valid
codes are in the range of 1–FF. Function elds are used to
send telegrams between master and slave. When a
telegram is sent from a master to a slave device, the
function code eld tells the slave what kind of action to
perform. When the slave responds to the master, it uses
the function code eld to indicate either a normal (errorfree) response, or that some kind of error occurred (called
an exception response).
For a normal response, the slave simply echoes the original
function code. For an exception response, the slave returns
a code that is equivalent to the original function code with
its most
places a unique code into the data eld of the response
telegram. This code tells the master what kind of error
occurred, or the reason for the exception. Also refer to
chapter 5.8.10 Function Codes Supported by Modbus RTU and
chapter 5.8.11 Modbus Exception Codes.
signicant bit set to logic 1. In addition, the slave
The data eld is constructed using sets of 2 hexadecimal
digits, in the range of 00–FF hexadecimal. These digits are
made up of 1 RTU character. The data eld of telegrams
sent from a master to a slave device contains additional
information which the slave must use to perform
accordingly.
The information can include items such as:
Coil or register addresses.
•
The quantity of items to be handled.
•
The count of actual data bytes in the
•
eld.
5.8.7 CRC Check Field
Telegrams include an error-checking eld, operating based
on a cyclic redundancy check (CRC) method. The CRC eld
checks the contents of the entire telegram. It is applied
regardless of any parity check method used for the
individual characters of the telegram. The transmitting
device calculates the CRC value and appends the CRC as
the last eld in the telegram. The receiving device
recalculates a CRC during receipt of the telegram and
compares the calculated value to the actual value received
in the CRC eld. 2 unequal values result in bus timeout.
The error-checking eld contains a 16-bit binary value
implemented as 2 8-bit bytes. After the implementation,
the low-order byte of the eld is appended rst, followed
by the high-order byte. The CRC high-order byte is the last
byte sent in the telegram.
5.8.8 Coil Register Addressing
In Modbus, all data is organized in coils and holding
registers. Coils hold a single bit, whereas holding registers
hold a 2 byte word (that is 16 bits). All data addresses in
Modbus telegrams are referenced to 0. The rst occurrence
of a data item is addressed as item number 0. For example:
The coil known as coil 1 in a programmable controller is
addressed as coil 0000 in the data address eld of a
Modbus telegram. Coil 127 decimal is addressed as coil
007Ehex (126 decimal).
Holding register 40001 is addressed as register 0000 in the
data address eld of the telegram. The function code eld
already species a holding register operation. Therefore,
the 4XXXX reference is implicit. Holding register 40108 is
addressed as register 006Bhex (107 decimal).
Coil
number
1–16Frequency converter control word
17–32Frequency converter speed or
33–48Frequency converter status word
49–64Open-loop mode: Frequency
65
66–65536 Reserved.–
Table 5.15 Coil Register
Coil01
01Preset reference lsb
02Preset reference msb
03DC brakeNo DC brake
04Coast stopNo coast stop
05Quick stopNo quick stop
06Freeze frequencyNo freeze frequency
07Ramp stopStart
08No resetReset
09No jogJog
10Ramp 1Ramp 2
11Data not validData valid
12Relay 1 oRelay 1 on
13Relay 2 oRelay 2 on
14Set up lsb
15–
16No reversingReversing
Table 5.16 Frequency Converter Control Word (FC Prole)
This section describes codes which can be used in the
function and data elds of a Modbus RTU telegram.
5.8.10 Function Codes Supported by
Modbus RTU
Modbus RTU supports use of the following function codes
in the function eld of a telegram:
FunctionFunction code (hex)
Read coils1
Read holding registers3
Write single coil5
Write single register6
Write multiple coilsF
Write multiple registers10
Get comm. event counterB
Report slave ID11
Table 5.19 Function Codes
FunctionFunction
code
Diagnostics 81Restart communication.
Table 5.20 Function Codes
Subfunction
code
2Return diagnostic
10Clear counters and
11Return bus message
12Return bus communi-
13Return slave error count.
14Return slave message
Subfunction
register.
diagnostic register.
count.
cation error count.
count.
5.8.11 Modbus Exception Codes
For a full explanation of the structure of an exception code
response, refer to chapter 5.8.5 Function Field.
CodeNameMeaning
The function code received in the query is
not an allowable action for the server (or
slave). This may be because the function
code is only applicable to newer devices
1
2
3
4
Table 5.21 Modbus Exception Codes
Illegal
function
Illegal data
address
Illegal data
value
Slave device
failure
and was not implemented in the unit
selected. It could also indicate that the
server (or slave) is in the wrong state to
process a request of this type, for example
because it is not congured and is being
asked to return register values.
The data address received in the query is
not an allowable address for the server (or
slave). More specically, the combination
of reference number and transfer length is
invalid. For a controller with 100 registers,
a request with oset 96 and length 4
succeeds, while a request with oset 96
and length 5 generates exception 02.
A value contained in the query data eld
is not an allowable value for server (or
slave). This indicates a fault in the
structure of the remainder of a complex
request, such as that the implied length is
incorrect. It does NOT mean that a data
item submitted for storage in a register
has a value outside the expectation of the
application program, since the Modbus
protocol is unaware of the signicance of
any value of any register.
An unrecoverable error occurred while the
server (or slave) was attempting to
perform the requested action.
55
How to Access Parameters
5.9
5.9.1 Parameter Handling
The PNU (parameter number) is translated from the
register address contained in the Modbus read or write
telegram. The parameter number is translated to Modbus
as (10 x parameter number) decimal.
Examples
Reading parameter 3-12 Catch up/slow Down Value (16 bit):
The holding register 3120 holds the parameters value. A
value of 1352 (decimal), means that the parameter is set to
12.52%.
Reading parameter 3-14 Preset Relative Reference (32 bit):
The holding registers 3410 and 3411 hold the parameters
values. A value of 11300 (decimal), means that the
parameter is set to 1113.00.
For information on the parameters, size, and conversion
index, see the VLT® Midi Drive FC 280 Programming Guide.
5.9.2 Storage of Data
The coil 65 decimal determines whether data written to
the frequency converter is stored in EEPROM and RAM (coil
65 = 1), or only in RAM (coil 65 = 0).
55
5.9.3 IND (Index)
Some parameters in the frequency converter are array
parameters, for example parameter 3-10 Preset Reference.
Since the Modbus does not support arrays in the holding
registers, the frequency converter has reserved the holding
register 9 as pointer to the array. Before reading or writing
an array parameter, set the holding register 9. Setting
holding register to the value of 2 causes all following read/
write to array parameters to be to the index 2.
5.9.4 Text Blocks
Parameters stored as text strings are accessed in the same
way as the other parameters. The maximum text block size
is 20 characters. If a read request for a parameter is for
more characters than the parameter stores, the response is
truncated. If the read request for a parameter is for fewer
characters than the parameter stores, the response is space
lled.
5.9.5 Conversion Factor
A parameter value can only be transferred as a whole
number. To transfer decimals, use a conversion factor.
5.9.6 Parameter Values
Standard data types
Standard data types are int 16, int 32, uint 8, uint 16, and
uint 32. They are stored as 4x registers (40001–4FFFF). The
parameters are read using function 03 hex read holding
registers. Parameters are written using the function 6 hex
preset single register for 1 register (16 bits), and the
function 10 hex preset multiple registers for 2 registers (32
bits). Readable sizes range from 1 register (16 bits) up to
10 registers (20 characters).
Non-standard data types
Non-standard data types are text strings and are stored as
4x registers (40001–4FFFF). The parameters are read using
function 03 hex read holding registers and written using
function 10 hex preset multiple registers. Readable sizes
range from 1 register (2 characters) up to 10 registers (20
characters).
Examples
5.10
The following examples show various Modbus RTU
commands.
5.10.1 Read Coil Status (01 hex)
Description
This function reads the ON/OFF status of discrete outputs
(coils) in the frequency converter. Broadcast is never
supported for reads.
Query
The query telegram species the starting coil and quantity
of coils to be read. Coil addresses start at 0, that is, coil 33
is addressed as 32.
Example of a request to read coils 33–48 (status word)
from slave device 01.
Field nameExample (hex)
Slave address01 (frequency converter address)
Function01 (read coils)
Starting address HI00
Starting address LO20 (32 decimals) coil 33
Number of points HI00
Number of points LO10 (16 decimals)
Error check (CRC)–
Table 5.22 Query
Response
The coil status in the response telegram is packed as 1 coil
per bit of the data eld. Status is indicated as: 1 = ON; 0 =
OFF. The lsb of the rst data byte contains the coil
addressed in the query. The other coils follow toward the
high-order end of this byte, and from low order to high
order in subsequent bytes.
If the returned coil quantity is not a multiple of 8, the
remaining bits in the nal data byte are padded with
values 0 (toward the high-order end of the byte). The byte
count eldspecies the number of complete bytes of data.
Field nameExample (hex)
Slave address01 (frequency converter address)
Function01 (read coils)
Byte count02 (2 bytes of data)
Data (coils 40–33)07
Data (coils 48–41)06 (STW = 0607hex)
Error check (CRC)–
Table 5.23 Response
NOTICE
Coils and registers are addressed explicitly with an oset of -1 in Modbus.
This function forces the coil to either ON or OFF. When
broadcast, the function forces the same coil references in
all attached slaves.
Query
The query telegram species the coil 65 (parameter write
control) to be forced. Coil addresses start at 0, that is, coil
65 is addressed as 64. Force data = 00 00 hex (OFF) or FF
00 hex (ON).
Field nameExample (hex)
Slave address01 (Frequency converter address)
Function05 (write single coil)
Coil address HI00
Coil address LO40 (64 decimal) Coil 65
Force data HIFF
Force data LO00 (FF 00 = ON)
Error check (CRC)–
Table 5.24 Query
Response
The normal response is an echo of the query, returned
after the coil state has been forced.
Field nameExample (hex)
Slave address01
Function05
Force data HIFF
Force data LO00
Quantity of coils HI00
Quantity of coils LO01
Error check (CRC)–
Table 5.25 Response
5.10.3 Force/Write Multiple Coils (0F hex)
Description
This function forces each coil in a sequence of coils to
either on or o. When broadcasting, the function forces
the same coil references in all attached slaves.
Query
The query telegram species the coils 17–32 (speed
setpoint) to be forced.
NOTICE
Coil addresses start at 0, that is, coil 17 is addressed as
16.
Field nameExample (hex)
Slave address01 (frequency converter address)
Function0F (write multiple coils)
Coil address HI00
Coil address LO10 (coil address 17)
Quantity of coils HI00
Quantity of coils LO10 (16 coils)
Byte count02
Force data HI
(Coils 8–1)
Force data LO
(Coils 16–9)
Error check (CRC)–
Table 5.26 Query
20
00 (reference = 2000 hex)
Response
The normal response returns the slave address, function
code, starting address, and quantity of coils forced.
Field nameExample (hex)
Slave address01 (frequency converter address)
Function0F (write multiple coils)
Coil address HI00
Coil address LO10 (coil address 17)
Quantity of coils HI00
Quantity of coils LO10 (16 coils)
Error check (CRC)–
Table 5.27 Response
5.10.4 Read Holding Registers (03 hex)
Description
This function reads the contents of holding registers in the
slave.
Query
The query telegram species the starting register and
quantity of registers to be read. Register addresses start at
0, that is, registers 1–4 are addressed as 0–3.
Example: Read parameter 3-03 Maximum Reference, register
The register data in the response telegram is packed as 2
bytes per register, with the binary contents right justied
within each byte. For each register, the 1st byte contains
the high-order bits, and the 2nd contains the low-order
bits.
Example: hex 000088B8 = 35.000 = 35 Hz.
Description
This function presets values into a sequence of holding
registers.
Query
The query telegram species the register references to be
preset. Register addresses start at 0, that is, register 1 is
Field nameExample (hex)
Slave address01
Function03
55
Byte count04
Data HI (register 3030)00
Data LO (register 3030)16
Data HI (register 3031)E3
Data LO (register 3031)60
Error check (CRC)–
Table 5.29 Response
5.10.5 Preset Single Register (06 hex)
Description
This function presets a value into a single holding register.
Query
The query telegram species the register reference to be
preset. Register addresses start at 0, that is, register 1 is
addressed as 0.
Example: Write to parameter 1-00 Conguration Mode,
addressed as 0. Example of a request to preset 2 registers
(set parameter 1-24 Motor Current to 738 (7.38 A)):
Field nameExample (hex)
Slave address01
Function10
Starting address HI04
Starting address LO07
Number of registers HI00
Number of registers LO02
Byte count04
Write data HI (Register 4: 1049)00
Write data LO (Register 4: 1049)00
Write data HI (Register 4: 1050)02
Write data LO (Register 4: 1050)E2
Error check (CRC)–
Table 5.32 Query
Response
The normal response returns the slave address, function
code, starting address, and quantity of registers preset.
register 1000.
Field nameExample (hex)
Field nameExample (hex)
Slave address01
Function06
Register address HI03 (register address 999)
Register address LOE7 (register address 999)
Preset data HI00
Preset data LO01
Error check (CRC)–
Table 5.30 Query
Slave address01
Function10
Starting address HI04
Starting address LO19
Number of registers HI00
Number of registers LO02
Error check (CRC)–
Table 5.33 Response
Response
The normal response is an echo of the query, returned
after the register contents have been passed.
Bit 02 = 0: Leads to DC braking and stop. Set braking
current and duration in parameter 2-01 DC Brake Current
and parameter 2-02 DC Braking Time.
Bit 02 = 1: Leads to ramping.
Bit 03, Coasting
Bit 03 = 0: The frequency converter immediately releases
the motor (the output transistors are shut o), and it
coasts to a standstill.
Bit 03 = 1: If the other starting conditions are met, the
frequency converter starts the motor.
In parameter 8-50 Coasting Select, dene how bit 03 gates
with the corresponding function on a digital input.
Bit 04, Quick stop
Bit 04 = 0: Makes the motor speed ramp down to stop (set
in parameter 3-81 Quick Stop Ramp Time).
Bit 05, Hold output frequency
Bit 05 = 0: The present output frequency (in Hz) freezes.
Change the frozen output frequency only with the digital
inputs programmed to [21] Speed up and [22] Speed down
(parameter 5-10 Terminal 18 Digital Input toparameter 5-13 Terminal 29 Digital Input).
NOTICE
If freeze output is active, the frequency converter can
only be stopped in 1 of the following ways:
Bit 03 coast stop.
•
Bit 02 DC brake.
•
Digital input programmed to [5] DC brake
•
inverse, [2] Coast inverse, or [3] Coast and reset
inv (parameter 5-10 Terminal 18 Digital Input to
parameter 5-13 Terminal 29 Digital Input).
Bit 06, Ramp stop/start
Bit 06 = 0: Causes a stop and makes the motor speed
ramp down to stop via the selected ramp-down parameter.
Bit 06 = 1: Allows the frequency converter to start the
motor if the other starting conditions are met.
In parameter 8-53 Start Select, dene how bit 06 ramp stop/
start gates with the corresponding function on a digital
input.
Bit 07, Reset
Bit 07 = 0: No reset.
Bit 07 = 1: Resets a trip. Reset is activated on the leading
signal edge, that is, when changing from logic 0 to logic 1.
Bit 08, Jog
Bit 08 = 1: Parameter 3-11 Jog Speed [Hz] determines the
output frequency.
Bit 09, Selection of ramp 1/2
Bit 09 = 0: Ramp 1 is active (parameter 3-41 Ramp 1 Ramp
Up Time to parameter 3-42 Ramp 1 Ramp Down Time).
Bit 09 = 1: Ramp 2 (parameter 3-51 Ramp 2 Ramp Up Time
to parameter 3-52 Ramp 2 Ramp Down Time) is active.
55
Output freq.STW
Bit
no.:
Follower-master
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
130BA273.11
RS485 Installation and Set-...
VLT® Midi Drive FC 280
Bit 10, Data not valid/Data valid
Tell the frequency converter whether to use or ignore the
5.11.2 Status Word According to FC Prole
(STW)
control word.
Bit 10 = 0: The control word is ignored.
Set parameter 8-30 Protocol to [0] FC.
Bit 10 = 1: The control word is used. This function is
relevant because the telegram always contains the control
word, regardless of the telegram type. If the control word
is not needed when updating or reading parameter, turn it
o.
Bit 11, Relay 01
Bit 11 = 0: Relay not activated.
55
selected in parameter 5-40 Function Relay.
Bit 11 = 1: Relay 01 activated if [36] Control word bit 11 is
Illustration 5.14 Status Word
Bit 12, Relay 02
Bit 12 = 0: Relay 02 is not activated.
Bit 12 = 1: Relay 02 is activated if [37] Control word bit 12 is
selected in parameter 5-40 Function Relay.
Bit 13, Set-up selection
Use bit 13 to select from the 2 menu set-ups according to
Table 5.36.
Set-upBit 13
10
21
Table 5.36 Menu Set-ups
The function is only possible when [9] Multi set-ups is
selected in parameter 0-10 Active Set-up.
To dene how bit 13 gates with the corresponding
function on the digital inputs, use parameter 8-55 Set-upSelect.
BitBit=0Bit=1
00Control not readyControl ready
01Frequency converter not
ready
02CoastingEnable
03No errorTrip
04No errorError (no trip)
05Reserved–
06No errorTriplock
07No warningWarning
08
09Local operationBus control
10Out of frequency limitFrequency limit OK
11No operationIn operation
12Frequency converter OKStopped, auto start
13Voltage OKVoltage exceeded
14Torque OKTorque exceeded
15Timer OKTimer exceeded
Speed≠reference
Frequency converter ready
Speed=reference
Bit 15 Reverse
Bit 15 = 0: No reversing.
Bit 15 = 1: Reversing. In the default setting, reversing is set
to digital in parameter 8-54 Reversing Select. Bit 15 causes
reversing only when serial communication, [2] Logic OR or
[3] Logic AND is selected.
Bit 00=0: The frequency converter trips.
Bit 00=1: The frequency converter controls are ready but
the power component does not necessarily receive any
supply (if there is 24 V external supply to controls).
Bit 01, Frequency converter ready
Bit 01=0: The frequency converter is not ready.
Bit 01=1: The frequency converter is ready for operation.
Bit 02, Coast stop
Bit 02=0: The frequency converter releases the motor.
Bit 02=1: The frequency converter starts the motor with a
start command.
Bit 03, No error/trip
Bit 03=0: The frequency converter is not in fault mode.
Bit 03=1: The frequency converter trips. To re-establish
operation, press [Reset].
RS485 Installation and Set-...Design Guide
Bit 04, No error/error (no trip)
Bit 04=0: The frequency converter is not in fault mode.
Bit 04=1: The frequency converter shows an error but does
not trip.
Bit 05, Not used
Bit 05 is not used in the status word.
Bit 06, No error/triplock
Bit 06=0: The frequency converter is not in fault mode.
Bit 06=1: The frequency converter is tripped and locked.
Bit 07, No warning/warning
Bit 07=0: There are no warnings.
Bit 07=1: A warning has occurred.
Bit 08, Speed reference/speed=reference
Bit 08=0: The motor runs, but the present speed is
dierent from the preset speed reference. It might happen
when the speed ramps up/down during start/stop.
Bit 08=1: The motor speed matches the preset speed
reference.
Bit 09, Local operation/bus control
Bit 09=0: [O/Reset] is activated on the control unit or [2]
Local in parameter 3-13 Reference Site is selected. It is not
possible to control the frequency converter via serial
communication.
Bit 09=1: It is possible to control the frequency converter
via the eldbus/serial communication.
Bit 10, Out of frequency limit
Bit 10=0: The output frequency has reached the value in
parameter 4-12 Motor Speed Low Limit [Hz] or
parameter 4-14 Motor Speed High Limit [Hz].
Bit 10=1: The output frequency is within the dened limits.
Bit 11, No operation/in operation
Bit 11=0: The motor is not running.
Bit 11=1: The frequency converter has a start signal
without coast.
Bit 12, Frequency converter OK/stopped, auto start
Bit 12=0: There is no temporary overtemperature on the
frequency converter.
Bit 12=1: The frequency converter stops because of
overtemperature but the unit does not trip and resumes
operation once the overtemperature normalizes.
Bit 13, Voltage OK/limit exceeded
Bit 13=0: There are no voltage warnings.
Bit 13=1: The DC voltage in the frequency converter’s DC
link is too low or too high.
Bit 14, Torque OK/limit exceeded
Bit 14=0: The motor current is lower than the current limit
selected in parameter 4-18 Current Limit.
Bit 14=1: The current limit in parameter 4-18 Current Limit is
exceeded.
Bit 15, Timer OK/limit exceeded
Bit 15=0: The timers for motor thermal protection and
thermal protection are not exceeded 100%.
Bit 15=1: 1 of the timers exceeds 100%.
Speed reference value is transmitted to the frequency converter in a relative value in %. The value is transmitted in the form
of a 16-bit word. The integer value 16384 (4000 hex) corresponds to 100%. Negative gures are formatted using 2’s
complement. The actual output frequency (MAV) is scaled in the same way as the bus reference.
The type code is a string of characters describing the
frequency converter’s conguration, see Illustration 6.1.
Illustration 6.1 Type Code
The numbers shown in Table 6.1 refer to the letter/gure
position in the type code string, read from left to right.
Product groups1–2
Frequency converter series4–6
Power rating7–10
Phases11
Mains voltage12
Enclosure13–15
RFI lter16–17
Brake18
Display (LCP)19
Coating PCB20
Mains option21
Adaptation A22
Adaptation B23
Software release24–27
Software language28
A options29–30
Ordering Numbers: Options,
6.2
Accessories, and Spare Parts
Options and accessoriesOrdering number
VLT® Memory Module MCM 102
VLT® Memory Module Programmer
MCM 101
VLT® Control Panel LCP 21 (Numeric)
VLT® Control Panel LCP 102 (Graphical)
Graphical LCP adapter132B0281
VLT® Control Panel LCP Blind Cover
IP21/Type 1 conversion kit, K1132B0335
IP21/Type 1 conversion kit, K2132B0336
IP21/Type 1 conversion kit, K3132B0337
IP21/Type 1 conversion kit, K4132B0338
IP21/Type 1 conversion kit, K5132B0339
Adapter plate, VLT® 2800 size A
Adapter plate, VLT® 2800 size B
Adapter plate, VLT® 2800 size C
Adapter plate, VLT® 2800 size D
VLT® 24 V DC supply MCB 106
LCP Remote Mounting Kit, w/3 m (10
ft) cable
LCP Mounting Kit, w/no LCP130B1117
1) Available in the middle of 2017.
1)
1)
Table 6.2 Ordering Numbers for Options and Accessories
132B0359
134B0792
132B0254
130B1107
132B0262
132B0363
132B0364
132B0365
132B0366
132B0368
132B0102
6
6
Table 6.1 Type Code Character Positions
From the online Drive
Congurator, a customer can
congure the right frequency converter for a given
application and generate the type code string. The Drive
Congurator automatically generates an 8-digit sales
number to be delivered to the local sales oce.
Another option is to establish a project list with several
products and send it to a Danfoss sales representative.
Danfoss oers a wide variety of dierent resistors that are specially designed for our frequency converters. See
chapter 2.9.4 Control with Brake Function for the dimensioning of brake resistors. This section lists the ordering numbers for
the brake resistors. The resistance of the brake resistor given by ordering number may be bigger than R
. In this case, the
rec
actual braking torque could be smaller than the highest braking torque which the frequency converter can provide.
6.3.1 Ordering Numbers: Brake Resistors 10%
Power
rating
3-phase
380–480 V
(T4)
PK370.37 (0.5)8901041.98989
PK550.55 (0.75)593693.79659
PK750.75 (1.0)434508.78483
P1K11.1 (1.5)288338.05321
P1K51.5 (2.0)208244.41232
P2K22.2 (3.0)139163.95155
P3K03 (4.0)100118.86112
P4K04 (5.0)7487.9383
P5K55.5 (7.5)5463.3360
P7K57.5 (10)3846.0543
P11K11 (15)2732.9931
P15K15 (20)1924.0222
P18K18.5 (25)1619.3618
P22K22 (30)1618.0017
P
m (HO)
[kW (hp)]
R
[Ω][Ω][Ω]
min
R
br. nom
R
rec
P
br avg
[kW (hp)]175Uxxxx[s]
0.030
(0.040)
0.045
(0.060)
0.061
(0.080)
0.092
(0.120)
0.128
(0.172)
0.190
(0.255)
0.262
(0.351)
0.354
(0.475)
0.492
(0.666)
0.677
(0.894)
0.945
(1.267)
1.297
(1.739)
1.610
(2.158)
1.923
(2.578)
Ordering
number
30001201.5 (16)0.3139
30011201.5 (16)0.4131
30021201.5 (16)0.4129
30041201.5 (16)0.5132
30071201.5 (16)0.8145
30081201.5 (16)0.9131
33001201.5 (16)1.3131
33351201.5 (16)1.9128
33361201.5 (16)2.5127
33371201.5 (16)3.3132
33381201.5 (16)5.2130
33391201.5 (16)6.7129
33401201.5 (16)8.3132
33571201.5 (16)10.1128
PeriodCable
cross-
section
[mm
(AWG)]
Thermal
relay
1)
2
[A][%]
Maximum
brake torque
with resistor
6
6
Table 6.4 FC 280 - Mains: 3-phase 380–480 V (T4), 10% Duty Cycle
Suggested parameter settings for operation with sine-wave lter are as follows:
Set [1] Sine-Wave Filter in parameter 14-55 Output Filter.
•
Set suitable value for individual lter in parameter 14-01 Switching Frequency. When [1] Sine-Wave Filter is set in
•
parameter 14-55 Output Filter, the options which are lower than 5 kHz in parameter 14-01 Switching Frequency are
removed automatically.
6.5 Ordering Numbers: dU/dt Filters
Frequency converter power and current ratingsFilter current ratingOrdering number
380@ 60 Hz
380-440 V441-480 V
[kW (hp)][A][kW (hp)][A][A][A]–––
11 (15)2311 (15)21
15 (20)3115 (20)27
18.5 (25)3718.5 (25)34
22 (30)42.522 (30)40
Table 6.9 dU/dt Filters for Frequency Converters with 380-480 V
200–400/440
@ 50 Hz
4440130B2835130B2836130B2837
460/480 @
60 Hz
500/525 @
50 Hz
IP00IP20IP54
6
6
6.6 Ordering Numbers: External EMC Filters
For K1S2 and K2S2, with external EMC lters listed in Table 6.10, the maximum shielded cable length of 100 m (328 ft)
according to EN/IEC 61800-3 C2 (EN 55011 A1), or 40 m (131.2 ft) according to EN/IEC 61800-3 C1 (EN 55011 B) can be
achieved.
For K1T4, K2T4 and K3T4 with internal A1 lter, with external EMC lters listed in Table 6.10, the maximum shielded cable
length of 100 m (328 ft) according to EN/IEC 61800-3 C2 (EN 55011 A1), or 25 m (82 ft) according to EN/IEC 61800-3 C1 (EN
55011 B) can be achieved.
Illustration 6.2 Dimensions of EMC Filter for K1–K3
For K4T4 and K5T4 with internal A1 lter, with external EMC lters listed in Table 6.11, the maximum shielded cable length
of 100 m (328 ft) according to EN/IEC 61800-3 C2 (EN 55011 A1), or 25 m (82 ft) according to EN/IEC 61800-3 C1 (EN 55011
B) can be achieved.
1) The frequency converter can run at -25% input voltage with reduced performance. The maximum output power of the
frequency converter is 75% if input voltage is -25%, and 85% if input voltage is -15%.
Full torque cannot be expected at mains voltage lower than 10% below the lowest rated supply voltage of the frequency
converter.
Supply frequency50/60 Hz ±5%
Maximum imbalance temporary between mains phases3.0% of rated supply voltage
True power factor (λ)≥0.9 nominal at rated load
Displacement power factor (cos ϕ)Near unity (>0.98)
Switching on input supply (L1/N, L2/L, L3) (power-ups) ≤7.5 kW (10 hp)Maximum 2 times/minute
Switching on input supply (L1/N, L2/L, L3) (power-ups) 11–22 kW (15–30 hp)Maximum 1 time/minute
7.3 Motor Output and Motor Data
Motor output (U, V, W)
Output voltage0–100% of supply voltage
Output frequency0–500 Hz
Output frequency in VVC+ mode0–200 Hz
Switching on outputUnlimited
Ramp time0.01–3600 s
Torque characteristics
Starting torque (constant torque)Maximum 160% for 60 s
Overload torque (constant torque)Maximum 160% for 60 s
Starting currentMaximum 200% for 1 s
Torque rise time in VVC+ mode (independent of fsw)Maximum 50 ms
1) Percentage relates to the nominal torque. It is 150% for 11–22 kW (15–30 hp) frequency converters.
Ambient conditions
IP classIP20 (IP21/NEMA type 1 as option)
Vibration test, all enclosure sizes1.14 g
Relative humidity5–95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
Ambient temperature (at DPWM switching mode)
- with deratingMaximum 55 °C (131 °F)
- at full constant output currentMaximum 45 °C (113 °F)
Minimum ambient temperature during full-scale operation0 °C (32 °F)
Minimum ambient temperature at reduced performance-10 °C (14 °F)
Temperature during storage/transport-25 to +65/70 °C (-13 to +149/158 °F)
Maximum altitude above sea level without derating1000 m (3280 ft)
Maximum altitude above sea level with derating3000 m (9243 ft)
EN 61800-3, EN 61000-3-2, EN 61000-3-3, EN 61000-3-11,
EMC standards, emission
EMC standards, immunity
77
Energy eciency class
1) Refer to chapter 7.12 Special Conditions for:
Derating for high ambient temperature.
•
Derating for high altitude.
•
2) For PROFIBUS, PROFINET, EtherNet/IP, and POWERLINK variant of VLT
overtemperature, avoid full digital/analog I/O load at ambient temperature higher than 45 °C (113 °F).
3) Ambient temperature for K1S2 with derating is maximun 50
4) Ambient temperature for K1S2 at full constant output current is maximun 40 °C (104 °F).
5) Determined according to EN 50598-2 at:
Rated load.
•
90% rated frequency.
•
Switching frequency factory setting.
•
Switching pattern factory setting.
•
Open type: Surrounding air temperature 45 °C (113 °F).
•
Type 1 (NEMA kit): Ambient temperature 45 °C (113 °F).
•
5)
°
C (122 °F).
EN 61000-3-12, EN 61000-6-3/4, EN 55011, IEC 61800-3
EN 61800-3, EN 61000-6-1/2, EN 61000-4-2, EN 61000-4-3
EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 61326-3-1
®
Midi Drive FC 280, to prevent the control card from
1)2)3)
4)
IE2
Cable Specications
7.5
Cable lengths
Maximum motor cable length, shielded50 m (164 ft)
Maximum motor cable length, unshielded75 m (246 ft)
Maximum cross-section of control terminals, exible/rigid wire2.5 mm2/14 AWG
Minimum cross-section of control terminals0.55 mm2/30 AWG
Maximum STO input cable length, unshielded20 m (66 ft)
1) For power cables cross-sections, see Table 7.1, Table 7.2, Table 7.3, and Table 7.4.
When complying with EN 55011 1A and EN 55011 1B the motor cable must in certain instances be reduced. See
chapter 2.6.2 EMC Emission for more details.
Terminal number18, 19, 271), 29, 32, 33
LogicPNP or NPN
Voltage level0–24 V DC
Voltage level, logic 0 PNP<5 V DC
Voltage level, logic 1 PNP>10 V DC
Voltage level, logic 0 NPN>19 V DC
Voltage level, logic 1 NPN<14 V DC
Maximum voltage on input28 V DC
Pulse frequency range4–32 kHz
(Duty cycle) minimum pulse width4.5 ms
Input resistance, R
1) Terminal 27 can also be programmed as output.
STO inputs
Terminal number37, 38
Voltage level0–30 V DC
Voltage level, low<1.8 V DC
Voltage level, high>20 V DC
Maximum voltage on input30 V DC
Minimum input current (each pin)6 mA
Terminal number531), 54
ModesVoltage or current
Mode selectSoftware
Voltage level0–10 V
Input resistance, R
i
Approximately 10 kΩ
Maximum voltage-15 V to +20 V
Current level0/4 to 20 mA (scaleable)
Input resistance, R
i
Approximately 200 Ω
Maximum current30 mA
Resolution for analog inputs11 bit
Accuracy of analog inputsMaximum error 0.5% of full scale
Bandwidth100 Hz
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminal 53 supports only voltage mode and can also be used as digital input.
77
Illustration 7.1 Galvanic Isolation
NOTICE
HIGH ALTITUDE
For installation at altitudes above 2000 m (6562 ft), contact Danfoss hotline regarding PELV.
Pulse inputs
Programmable pulse inputs2
Terminal number pulse29, 33
Maximum frequency at terminal 29, 3332 kHz (push-pull driven)
Maximum frequency at terminal 29, 335 kHz (open collector)
Minimum frequency at terminal 29, 334 Hz
Voltage levelSee the section on digital input
Maximum voltage on input28 V DC
Input resistance, R
i
Pulse input accuracyMaximum error: 0.1% of full scale
Digital outputs
Programmable digital/pulse outputs1
Terminal number27
Voltage level at digital/frequency output0–24 V
Maximum output current (sink or source)40 mA
Maximum load at frequency output1 kΩ
Maximum capacitive load at frequency output10 nF
Minimum output frequency at frequency output4 Hz
Maximum output frequency at frequency output32 kHz
Accuracy of frequency outputMaximum error: 0.1% of full scale
Resolution of frequency output10 bit
1) Terminal 27 can also be programmed as input.
The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Analog outputs
Number of programmable analog outputs1
Terminal number42
Current range at analog output0/4–20 mA
Maximum resistor load to common at analog output500 Ω
Accuracy on analog outputMaximum error: 0.8% of full scale
Resolution on analog output10 bit
The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control card, 24 V DC output
Terminal number12, 13
Maximum load100 mA
The 24 V DC supply is galvanically isolated from the supply voltage (PELV). However, the supply has the same potential as the
analog and digital inputs and outputs.
1)
77
Control card, +10 V DC output
Terminal number50
Output voltage10.5 V ±0.5 V
Maximum load15 mA
The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control card, RS485 serial communication
Terminal number68 (P,TX+, RX+), 69 (N,TX-, RX-)
Terminal number 61Common for terminals 68 and 69
The RS485 serial communication circuit is galvanically isolated from the supply voltage (PELV).
Control card, USB serial communication
USB standard1.1 (full speed)
USB plugUSB type B plug
Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
The USB ground connection is not galvanically isolated from protective earth. Use only an isolated laptop as PC connection to
the USB connector on the frequency converter.
Maximum terminal load (AC-1)1) on 01–02 (NO) (resistive load)250 V AC, 3 A
Maximum terminal load (AC-15)1) on 01–02 (NO) (inductive load @ cosφ 0.4)250 V AC, 0.2 A
Maximum terminal load (DC-1)1) on 01–02 (NO) (resistive load)30 V DC, 2 A
Maximum terminal load (DC-13)1) on 01–02 (NO) (inductive load)24 V DC, 0.1 A
Maximum terminal load (AC-1)1) on 01–03 (NC) (resistive load)250 V AC, 3 A
Maximum terminal load (AC-15)1)on 01–03 (NC) (inductive load @ cosφ 0.4)250 V AC, 0.2 A
Maximum terminal load (DC-1)1) on 01–03 (NC) (resistive load)30 V DC, 2 A
Minimum terminal load on 01–03 (NC), 01–02 (NO)24 V DC 10 mA, 24 V AC 20 mA
1) IEC 60947 parts 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation.
Control card performance
Scan interval1 ms
77
Control characteristics
Resolution of output frequency at 0–500 Hz±0.003 Hz
System response time (terminals 18, 19, 27, 29, 32, and 33)≤2 ms
Speed control range (open loop)1:100 of synchronous speed
Speed accuracy (open loop)±0.5% of nominal speed
Speed accuracy (closed loop)±0.1% of nominal speed
All control characteristics are based on a 4-pole asynchronous motor.
Connection Tightening Torques
7.7
Make sure to use the right torques when tightening all electrical connections. Too low or too high torque sometimes causes
electrical connection problems. To ensure that correct torques are applied, use a torque wrench. Recommended slot
screwdriver type is SZS 0.6x3.5 mm.
Use fuses and/or circuit breakers on the supply side to
protect service personnel and equipment from injuries and
damage if there is component breakdown inside the
frequency converter (rst fault).
Branch circuit protection
Protect all branch circuits in an installation (including
switch gear and machines) against short circuit and
overcurrent according to national/international regulations.
NOTICE
Integral solid-state short-circuit protection does not
provide branch circuit protection. Provide branch circuit
protection in accordance with the national and local
rules and regulations.
Table 7.6 lists the recommended fuses and circuit breakers
that have been tested.
CAUTION
PERSONAL INJURY AND EQUIPMENT DAMAGE
RISK
Malfunction or failing to follow the recommendations
may result in personal risk and damage to the frequency
converter and other equipment.
Select fuses according to recommendations.
•
Possible damage can be limited to be inside the
frequency converter.
NOTICE
EQUIPMENT DAMAGE
Using fuses and/or circuit breakers is mandatory to
ensure compliance with IEC 60364 for CE. Failure to
follow the protection recommendations can result in
damage to the frequency converter.
Danfoss recommends using the fuses and circuit breakers
in Table 7.6 to ensure compliance with UL 508C or IEC
61800-5-1. For non-UL applications, design circuit breakers
for protection in a circuit capable of delivering a maximum
of 50000 A
frequency converter short-circuit current rating (SCCR) is
suitable for use on a circuit capable of delivering not more
than 100000 A
by Class T fuses.
The load on the frequency converter has little eect on its
eciency. In general, the eciency is the same at the
rated motor frequency f
. This rule also applies even if
M,N
the motor supplies 100% of the rated shaft torque or only
75%, for example if there is part loads.
This also means that the eciency of the frequency
converter does not change even if other U/f characteristics
are selected.
However, the U/f characteristics inuence the eciency of
the motor.
The eciency declines a little when the switching
frequency is set to a value above the default value. If the
mains voltage is 480 V, or if the motor cable is longer than
30 m (98.4 ft), the eciency is also slightly reduced.
Frequency converter eciency calculation
Calculate the eciency of the frequency converter at
dierent loads based on Illustration 7.2. Multiply the factor
in Illustration 7.2 by the speciceciency factor listed in
the specication tables in chapter 7.1 Electrical Data:
The eciency of a motor connected to the frequency
converter depends on the magnetizing level. In general,
the eciency is as good as with mains operation. The
eciency of the motor depends on the type of motor.
In the range of 75–100% of the rated torque, the eciency
of the motor is practically constant, both when controlled
by the frequency converter and when running directly on
mains.
SpecicationsDesign Guide
In small motors, the inuence from the U/f characteristic
on eciency is marginal. However, in motors from 11 kW
(14.8 hp) and up, the advantages are signicant.
In general, the switching frequency does not aect the
eciency of small motors. Motors from 11 kW (14.8 hp)
and up have their eciency improved 1–2% because the
sine shape of the motor current is almost perfect at high
switching frequency.
Eciency of the system (η
SYSTEM
)
To calculate the system eciency, the eciency of the
frequency converter (η
the motor (η
η
SYSTEM
= η
VLT
MOTOR
x η
MOTOR
) is multiplied by the eciency of
VLT
):
7.10 Acoustic Noise
The acoustic noise from the frequency converter comes
from 3 sources:
DC intermediate circuit coils.
•
Integral fan.
•
RFI lter choke.
•
The typical values measured at a distance of 1 m (3.3 ft)
from the unit:
Enclosure size
[kW (hp)]
K1
0.37–2.2
(0.5–3.0)
K2
3.0–5.5 (4.0–7.5)
K3
7.5 (10)
K4
11–15 (15–20)
K5
18.5–22 (25–30)
Table 7.7 Typical Measured Values
80% fan
speed [dBA]
41.442.733
50.354.332.9
5154.233
5961.132.9
64.665.632.9
Full fan speed
[dBA]
Background
noise
If the peak voltage is too high, motors without phase coil
insulation are aected. The longer the motor cable, the
higher the rise time and peak voltage.
Switching of the IGBTs cause peak voltage on the motor
terminals. The VLT® Midi Drive FC 280 complies with IEC
60034-25 regarding motors designed to be controlled by
frequency converters. The FC 280 also complies with IEC
60034-17 regarding Norm motors controlled by frequency
converters.
The following dU/dt data are measured at the motor
terminal side:
Cable
length
[m (ft)]
5 (16.4)4000.09040.7186.41
50 (164)4000.2921.052.84
5 (16.4)4800.1080.8356.20
50 (164)4800.321.253.09
Table 7.8 dU/dt Data for FC 280, 2.2 kW (3.0 hp), 3x380–480 V
Cable
length
[m (ft)]
5 (16.4)4000.0960.6325.31
50 (164)4000.3060.992.58
5 (16.4)4800.1180.6944.67
50 (164)4800.3081.183.05
Table 7.9 dU/dt Data for FC 280, 5.5 kW (7.5 hp), 3x380–480 V
Cable
length
[m (ft)]
5 (16.4)4000.1280.7324.54
50 (164)4000.3541.012.27
5 (16.4)4800.1340.8355.03
50 (164)4800.361.212.69
Mains
voltage
[V]
Mains
voltage
[V]
Mains
voltage
[V]
Rise time
[μsec]
Rise time
[μsec]
Rise time
[μsec]
U
[kV]
U
[kV]
U
[kV]
PEAK
PEAK
PEAK
dU/dt
[kV/μsec]
dU/dt
[kV/μsec]
dU/dt
[kV/μsec]
77
dU/dt Conditions
7.11
When a transistor in the frequency converter bridge
switches, the voltage across the motor increases by a
dU/dt ratio depending on the following factors:
The motor cable type.
•
The cross-section of the motor cable.
•
The length of the motor cable.
•
Whether the motor cable is shielded or not.
•
Inductance.
•
The natural induction causes an overshoot U
PEAK
in the
Table 7.10 dU/dt Data for FC 280, 7.5 kW (10 hp), 3x380–480 V
Cable
length
[m (ft)]
5 (16.4)4000.260.842.57
50 (164)4000.7381.071.15
5 (16.4)4800.3340.992.36
50 (164)4800.6921.251.44
Table 7.11 dU/dt Data for FC 280, 15 kW (20 hp), 3x380–480 V
Mains
voltage
[V]
Rise time
[μsec]
U
PEAK
[kV]
dU/dt
[kV/μsec]
motor voltage before it stabilizes itself at a level
depending on the voltage in the DC link. The rise time and
the peak voltage U
Under some special conditions, where the operation of the
frequency converter is challenged, consider derating. In
some conditions, derating must be done manually.
In other conditions, the frequency converter automatically
performs a degree of derating when necessary. Derating is
done to ensure the performance at critical stages where
Table 7.12 dU/dt Data for FC 280, 22 kW (30 hp), 3x380–480 V
Cable
length
[m (ft)]
5 (16.4)2400.07120.4845.44
50 (164)2400.2240.5942.11
Table 7.13 dU/dt Data for FC 280, 1.5 kW (2.0 hp), 3x200–240 V
77
Cable
length
[m (ft)]
5 (16.4)2400.0720.4685.25
50 (164)2400.2080.5922.28
Table 7.14 dU/dt Data for FC 280, 2.2 kW (3.0 hp), 3x200–240 V
Mains
voltage
[V]
Mains
voltage
[V]
Rise time
[μsec]
Rise time
[μsec]
U
PEAK
[kV]
U
PEAK
[kV]
dU/dt
[kV/μsec]
dU/dt
[kV/μsec]
the alternative could be a trip.
Cable
length
[m (ft)]
5 (16.4)2400.0920.5264.56
50 (164)2400.280.61.72
Table 7.15 dU/dt Data for FC 280, 3.7 kW (5.0 hp), 3x200–240 V
Cable
length
[m (ft)]
5 (16.4)2400.0880.4143.79
50 (164)2400.1960.5932.41
Table 7.16 dU/dt Data for FC 280, 1.5 kW (2.0 hp), 1x200–240 V
Cable
length
[m (ft)]
5 (16.4)2400.1120.3682.64
50 (164)2400.1160.3622.51
Table 7.17 dU/dt Data for FC 280, 2.2 kW (3.0 hp), 1x200–240 V