Danfoss FC 280 Programming guide

ENGINEERING TOMORROW
Programming Guide
VLT® Midi Drive FC 280
vlt-drives.danfoss.com
Contents Programming Guide
Contents
1 Introduction
1.1 How to Read This Programming Guide
1.2 Denitions
1.3 Electrical Wiring - Control Cables
2 Safety
2.1 Safety Symbols
2.2 Qualied Personnel
2.3 Safety Precautions
3 Programming
3.1 Local Control Panel Operation
3.1.1 Numeric Local Control Panel (NLCP) 14
3.1.2 The Right-key Function on NLCP 15
3.1.3 Quick Menu on NLCP 16
3.1.4 Main Menu on NLCP 18
3.1.5 Graphic Local Control Panel (GLCP) 20
3.1.6 Parameter Settings 21
12
12
12
12
14
14
3.1.7 Changing Parameter Settings with GLCP 21
3.1.8 Uploading/Downloading Data to/from the LCP 21
3.1.9 Restoring Default Settings with LCP 22
3.2 Basic Programming
3.2.2 PM Motor Set-up in VVC
3.2.3 Automatic Motor Adaptation (AMA) 24
+
4 Parameter Descriptions
4.1 Parameters: 0-** Operation and Display
4.2 Parameters: 1-** Load and Motor
4.3 Parameters: 2-** Brakes
4.4 Parameters: 3-** Reference/Ramps
4.5 Parameters: 4-** Limits/Warnings
4.6 Parameters: 5-** Digital In/Out
4.7 Parameters: 6-** Analog In/Out
4.8 Parameters: 7-** Controllers
4.9 Parameters: 8-** Communications and Options
4.10 Parameters: 9-** PROFIdrive
22
23
25
25
37
49
51
57
60
70
73
78
83
4.11 Parameters: 10-** CAN Fieldbus
4.12 Parameters: 12-** Ethernet
4.13 Parameters: 13-** Smart Logic Control
4.14 Parameters: 14-** Special Functions
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 1
83
83
83
90
Contents
VLT® Midi Drive FC 280
4.15 Parameters: 15-** Drive Information
4.16 Parameters: 16-** Data Readouts
4.17 Parameters: 18-** Data Readouts 2
4.18 Parameters: 21-** Ext. Closed Loop
4.19 Parameters: 22-** Application Functions
4.20 Parameters: 30-** Special Features
4.21 Parameters: 31-** Special Option
4.22 Parameters: 32-** Motion Control Basic Settings
4.23 Parameters: 33-** Motion Control Adv. Settings
4.24 Parameters: 34-** Motion Control Data Readouts
4.25 Parameters: 37-** Application Settings
5 Parameter Lists
5.1 Introduction
5.2 Parameter Lists
6 Troubleshooting
6.1 Warnings and Alarms
96
98
102
103
105
107
107
108
108
110
111
113
113
116
136
136
Index
6.1.3 Warning/Alarm Messages 136
6.1.4 Warning and Alarm Code List 137
146
2 Danfoss A/S © 02/2019 All rights reserved. MG07C402
Introduction Programming Guide
1 Introduction
1.1 How to Read This Programming Guide
1.1.1 Purpose of the Manual
This programming guide provides information about controlling the frequency converter, accessing parameters, programming, and troubleshooting. The programming guide is intended for use by
personnel who are familiar with the VLT® Midi Drive FC 280 frequency converter. Read the instructions before programming and follow the procedures in this manual.
VLT® is a registered trademark.
1.1.2 Additional Resources
Additional resources include:
VLT® Midi Drive FC 280 Operating Guide, provides
the necessary information for getting the frequency converter up and running.
VLT® Midi Drive FC 280 Design Guide, provides
detailed technical information about the frequency converter, customer design, and applications.
Contact the local Danfoss supplier or go to
drives.danfoss.com/knowledge-center/technical-documen­tation/ to download the documentation.
1.1.3 Document and Software Version
This manual is regularly reviewed and updated. All suggestions for improvement are welcome. Table 1.1 shows the document version and the corresponding software version.
Edition Remarks Software
MG07C4 Update due to new software
version release.
Table 1.1 Document and Software Version
qualied
version
1.6
°C °F
AC Alternating current AEO Automatic energy optimization ACP Application control processor AWG American wire gauge AMA Automatic motor adaptation DC Direct current
EEPROM
EMC Electromagnetic compatibility EMI Electromagnetic interference ESD Electrostatic discharge ETR Electronic thermal relay f
M,N
FC Frequency converter IGBT Insulated-gate bipolar transistor IP Ingress protection I
LIM
I
INV
I
M,N
I
VLT,MAX
I
VLT,N
L
d
L
q
LCP Local control panel LED Light-emitting diode MCP Motor control processor N.A. Not applicable
NEMA
P
M,N
PCB Printed circuit board PE Protective earth PELV Protective extra low voltage PWM Pulse width modulation R
s
Regen Regenerative terminals RPM Revolutions per minute RFI Radio frequency interference SCR Silicon controlled rectier SMPS Switch mode power supply T
LIM
U
M,N
X
h
Degrees Celsius Fahrenheit
Electrically erasable programmable read-only memory
Nominal motor frequency
Current limit Rated inverter output current Nominal motor current Maximum output current Rated output current supplied by the frequency converter Motor d-axis inductance Motor q-axis inductance
National Electrical Manufacturers Association Nominal motor power
Stator resistance
Torque limit Nominal motor voltage Motor main reactance
1 1
Table 1.2 Abbreviations
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 3
089
Introduction
VLT® Midi Drive FC 280
11
Denitions
1.2
1.2.1 Frequency Converter
Coast
The motor shaft is in free mode. No torque on the motor.
I
VLT,MAX
Maximum output current.
I
VLT,N
Rated output current supplied by the frequency converter.
U
VLT,MAX
Maximum output voltage.
1.2.2 Input
For compliance with the European Agreement concerning International Carriage of Dangerous Goods by Inland Waterways (ADN), refer to the chapter ADN-compliant Instal-
®
lation in the VLT
The frequency converter complies with UL 508C thermal memory retention requirements. For more information,
refer to the chapter Motor Thermal Protection in the VLT Midi Drive FC 280 Design Guide.
Applied standards and compliance for STO
Using STO on terminals 37 and 38 requires fulllment of all provisions for safety including relevant laws, regulations, and guidelines. The integrated STO function complies with the following standards:
IEC/EN 61508:2010, SIL2
IEC/EN 61800-5-2:2007, SIL2
IEC/EN 62061:2015, SILCL of SIL2
EN ISO 13849-1:2015, Category 3 PL d
Midi Drive FC 280 Design Guide.
®
Control commands
Start and stop the connected motor with the LCP and digital inputs. Functions are divided into 2 groups.
Functions in group 1 have higher priority than functions in group 2.
Group 1 Precise stop, coast stop, precise stop and coast
stop, quick stop, DC braking, stop, and [OFF].
Group 2 Start, pulse start, start reversing, jog, freeze
output, and [Hand On].
Table 1.3 Function Groups
4 Danfoss A/S © 02/2019 All rights reserved. MG07C402
175ZA078.10
Pull-out
RPM
Torque
Introduction Programming Guide
1.2.3 Motor
Motor running
Torque generated on the output shaft and speed from 0 RPM to maximum speed on the motor.
f
JOG
Motor frequency when the jog function is activated (via digital terminals or bus).
f
M
Motor frequency.
f
MAX
Maximum motor frequency.
f
MIN
Minimum motor frequency.
f
M,N
Rated motor frequency (nameplate data).
I
M
Motor current (actual).
I
M,N
Nominal motor current (nameplate data).
n
M,N
Nominal motor speed (nameplate data).
n
s
Synchronous motor speed.
2 × Parameter 123 × 60s
ns=
n
slip
Motor slip.
P
M,N
Rated motor power (nameplate data in kW or hp).
T
M,N
Rated torque (motor).
U
M
Instantaneous motor voltage.
U
M,N
Rated motor voltage (nameplate data).
Parameter 139
Break-away torque
Illustration 1.1 Break-away Torque
η
VLT
The eciency of the frequency converter is dened as the ratio between the power output and the power input.
Start-disable command
A start-disable command belonging to the control commands in group 1. See Table 1.3 for more details.
Stop command
A stop command belonging to the control commands in group 1. See Table 1.3 for more details.
1.2.4 References
Analog reference
A signal transmitted to the analog inputs 53 or 54 can be voltage or current.
Binary reference
A signal transmitted via the serial communication port.
Preset reference
A dened preset reference to be set from -100% to +100% of the reference range. Selection of 8 preset references via the digital terminals. Selection of 4 preset references via the bus.
Pulse reference
A pulse frequency signal transmitted to the digital inputs (terminal 29 or 33).
Ref
MAX
Determines the relationship between the reference input at 100% full scale value (typically 10 V, 20 mA) and the resulting reference. The maximum reference value is set in parameter 3-03 Maximum Reference.
Ref
MIN
Determines the relationship between the reference input at 0% value (typically 0 V, 0 mA, 4 mA) and the resulting reference. The minimum reference value is set in parameter 3-02 Minimum Reference.
1 1
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 5
Introduction
VLT® Midi Drive FC 280
11
1.2.5 Miscellaneous
GLCP
The graphic local control panel (LCP 102) interface for
Analog inputs
The analog inputs are used for controlling various functions of the frequency converter.
There are 2 types of analog inputs:
Current input, 0–20 mA and 4–20 mA.
Voltage input, 0 to +10 V DC.
Analog outputs
The analog outputs can supply a signal of 0–20 mA, or 4– 20 mA.
Automatic motor adaptation, AMA
The AMA algorithm determines the electrical parameters for the connected motor at standstill.
Brake resistor
The brake resistor is a module capable of absorbing the brake power generated in regenerative braking. This regenerative brake power increases the intermediate circuit voltage, and a brake chopper ensures that the power is transmitted to the brake resistor.
CT characteristics
Constant torque characteristics used for all applications such as conveyor belts, displacement pumps, and cranes.
Digital inputs
The digital inputs can be used for controlling various functions of the frequency converter.
Digital outputs
The frequency converter features 2 solid-state outputs that can supply a 24 V DC (maximum 40 mA) signal.
ETR
Electronic thermal relay is a thermal load calculation based on present load and time. Its purpose is to estimate the motor temperature.
FC standard bus
Includes RS485 bus with FC protocol or MC protocol. See parameter 8-30 Protocol.
Initializing
If initializing is carried out (parameter 14-22 Operation Mode or 2
nger reset), the frequency converter returns to the
default setting.
Intermittent duty cycle
An intermittent duty rating refers to a sequence of duty cycles. Each cycle consists of an on-load and an o-load period. The operation can be either periodic duty or non­periodic duty.
LCP
The local control panel makes up a complete interface for control and programming of the frequency converter. The control panel is detachable and can be installed up to 3 m (9.8 ft) from the frequency converter, that is, in a front panel with the installation kit option.
control and programming of the frequency converter. The display is graphic and the panel is used to show process values. The GLCP has storing and copy functions.
NLCP
The numerical local control panel (LCP 21) interface for control and programming of the frequency converter. The display is numerical and the panel is used to show process values. The NLCP has storing and copy functions.
lsb
Least signicant bit.
msb
Most signicant bit.
MCM
Short for mille circular mil, an American measuring unit for cable cross-section. 1 MCM = 0.5067 mm2.
On-line/o-line parameters
Changes to on-line parameters are activated immediately after the data value is changed. Press [OK] to activate changes to o-line parameters.
Process PID
The PID control maintains speed, pressure, and temperature by adjusting the output frequency to match the varying load.
PCD
Process control data.
Power cycle
Switch o the mains until the display (LCP) is dark, then turn power on again.
Power factor
The power factor is the relation between I1 and I
Powerfactor = 
3xUxI1cosϕ1
3xUxI
RMS
RMS
.
cosϕ1 = 1, therefore:
Powerfactor = 
I1xcosϕ1
I
RMS
 = 
I
I
RMS
1
The power factor indicates to which extent the frequency converter imposes a load on the mains supply. The lower the power factor, the higher the I
RMS
for the
same kW performance.
I
RMS
=  I
 + I
1
5
 + I
2
 + .. + I
7
2
n
2
2
In addition, a high power factor indicates that the dierent harmonic currents are low. The built-in DC coils produce a high power factor, minimizing the imposed load on the mains supply.
Pulse input/incremental encoder
An external, digital pulse transmitter used for feeding back information on motor speed. The encoder is used in applications where great accuracy in speed control is required.
6 Danfoss A/S © 02/2019 All rights reserved. MG07C402
Introduction Programming Guide
RCD
Residual current device.
Set-up
Save parameter settings in 4 set-ups. Change among the 4 parameter set-ups and edit 1 set-up while this set-up is inactive.
SFAVM
Acronym describing the switching pattern stator ux­oriented asynchronous vector modulation.
Slip compensation
The frequency converter compensates for the motor slip by giving the frequency a supplement that follows the measured motor load, keeping the motor speed almost constant.
Smart logic control (SLC)
The SLC is a sequence of user-dened actions executed when the associated user-dened events are evaluated as true by the smart logic controller (parameter group 13-** Smart Logic Control).
STW
Status word.
THD
Total harmonic distortion states the total contribution of harmonic distortion.
Thermistor
A temperature-dependent resistor placed where the temperature is monitored (frequency converter or motor).
Trip
A state entered in fault situations, for example if the frequency converter is subject to overvoltage or when it is protecting the motor, process, or mechanism. Restart is prevented until the cause of the fault has disappeared, and the trip state is canceled by activating reset or, sometimes, by being programmed to reset automatically. Do not use trip for personal safety.
Trip lock
A state entered in fault situations when the frequency converter is protecting itself and requiring physical intervention, for example if the frequency converter is subject to a short circuit on the output. A locked trip can only be canceled by cutting o mains, removing the cause of the fault, and reconnecting the frequency converter. Restart is prevented until the trip state is canceled by activating reset or, in some cases, by being programmed to reset automatically. Do not use trip lock for personal safety.
VT characteristics
Variable torque characteristics used for pumps and fans.
+
VVC
If compared with standard voltage/frequency ratio control, voltage vector control (VVC+) improves the dynamics and stability, both when the speed reference is changed and in relation to the load torque.
60° AVM
Refers to the switching pattern 60° asynchronous vector modulation.
1 1
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 7
Power input
Switch mode
power supply
Motor
Analog output
interface
(PNP) = Source (NPN) = Sink
ON = Terminated OFF = Open
Brake resistor
91 (L1/N) 92 (L2/L) 93 (L3)
PE
50 (+10 V OUT)
53 (A IN)
2)
54 (A IN)
55 (COM digital/analog I/O)
0/420 mA
12 (+24 V OUT)
13 (+24 V OUT)
18 (D IN)
10 V DC 15 mA 100 mA
+ - + -
(U) 96
(V) 97
(W) 98
(PE) 99
(A OUT) 42
(P RS485) 68
(N RS485) 69
(COM RS485) 61
0 V
5 V
S801
0/420 mA
RS485
RS485
03
+10 V DC
010 V DC
24 V DC
02
01
24 V (NPN) 0 V (PNP)
0 V (PNP)
24 V (NPN)
19 (D IN)
24 V (NPN) 0 V (PNP)
17 V
0 V
0 V (PNP)
24 V (NPN)
29 (D IN)
24 V (NPN) 0 V (PNP)
0 V (PNP)
24 V (NPN)
33 (D IN)
32 (D IN)
38 (STO2)
4)
37 (STO1)
4)
95
P 5-00
21
ON
(+DC/R+) 89
(R-) 81
010 V DC
(-DC) 88
RFI
0 V
250 V AC, 3 A
Relay 1
1)
3)
5)
5)
130BE202.19
27 (D IN/OUT)
6)
Introduction
VLT® Midi Drive FC 280
11
1.3 Electrical Wiring - Control Cables
1.3.1 Overview
Illustration 1.2 Basic Wiring Schematic Drawing
A=Analog, D=Digital
1) Built-in brake chopper is only available on 3-phase units.
2) Terminal 53 can also be used as digital input.
3) Switch S801 (bus terminal) can be used to enable termination on the RS485 port (terminals 68 and 69).
4) Refer to chapter 6 Safe Torque O (STO) in the operating guide for the correct STO wiring.
5) The S2 drive doesn’t support load sharing application.
8 Danfoss A/S © 02/2019 All rights reserved. MG07C402
130BE730.10
12 13 18 19 27 29 32 33 55
+24 VDC
0 VDC
PNP (Source)
Digital input wiring
NPN (Sink) Digital input wiring
12 13 18 19 27 29 32 33 55
+24 VDC
0 VDC
130BE731.10
130BA681.10
130BE732.11
12 13 18 322719 29 33
P 5-12 [2]
P 5-10 [8]
Start/Stop
+24V
Speed
Start
[18]
Introduction Programming Guide
In rare cases, long control cables and analog signals result in 50/60 Hz ground loops due to noise from mains supply cables. If this occurs, break the shield or insert a 100 nF capacitor between shield and chassis.
Connect the digital and analog inputs and outputs separately to the common inputs (terminal 55) of the frequency converter to avoid that ground currents from both groups aect other groups. For example, switching on the digital input could disturb the analog input signal.
Input polarity of control terminals
See the section Using Shielded Control Cables in the design guide for the correct termination of control cables.
1 1
Illustration 1.3 PNP (Source)
Illustration 1.4 NPN (Sink)
Illustration 1.5 Grounding of Shielded/Armored Control Cables
1.3.2 Start/Stop
Terminal 18 = Parameter 5-10 Terminal 18 Digital Input [8] Start. Terminal 27 = Parameter 5-12 Terminal 27 Digital Input [0] No operation (Default coast inverse).
Illustration 1.6 Start/Stop
NOTICE
Control cables must be shielded/armored.
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 9
1312 18 19 322927 33
P 5 - 12 [6]
P 5 - 10 [9]
+24 V
Speed
Latched start Stop inverse
Latched start (18)
Stop inverse (27)
130BF101.11
FC
+24 V
+24 V
D IN
D IN
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
12
13
18
19
27
29
32
33
50
53
54
55
42
130BF095.10
Introduction
VLT® Midi Drive FC 280
11
1.3.3 Latched Start/Stop Inverse
Terminal 18 = Parameter 5-10 Terminal 18 Digital Input [9] Latched start. Terminal 27 = Parameter 5-12 Terminal 27 Digital Input [6] Stop inverse.
1.3.4 Speed Up/Down
Terminals 29/32 = Speed up/down
Terminal 18 = Parameter 5-10 Terminal 18 Digital Input [9] Start (default).
Terminal 27 = Parameter 5-12 Terminal 27 Digital Input [19] Freeze reference.
Terminal 29 = Parameter 5-13 Terminal 29 Digital Input [21] Speed up.
Terminal 32 = Parameter 5-14 Terminal 32 Digital Input [22] Speed down.
Illustration 1.8 Speed Up/Down
Illustration 1.7 Latched Start/Stop Inverse
10 Danfoss A/S © 02/2019 All rights reserved. MG07C402
130BD381.12
555342 54 50
Speed P 6-15
1 kΩ
+10V/15mA
Ref. voltage P 6-11 10V
Introduction Programming Guide
1.3.5 Potentiometer Reference
Voltage reference via a potentiometer
Reference source 1 = [1] Analog input 53 (default).
Terminal 53, low voltage = 0 V.
Terminal 53, high voltage = 10 V.
Terminal 53, low ref./feedback = 0 Hz.
Terminal 53, high ref./feedback = 50 Hz.
Parameter 6-19 Terminal 53 mode = [1] Voltage.
1 1
Illustration 1.9 Potentiometer Reference
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 11
Safety
VLT® Midi Drive FC 280
2 Safety
22
2.1 Safety Symbols
The following symbols are used in this document:
WARNING
Indicates a potentially hazardous situation that could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation that could result in minor or moderate injury. It can also be used to alert against unsafe practices.
NOTICE
Indicates important information, including situations that can result in damage to equipment or property.
2.2 Qualied Personnel
Correct and reliable transport, storage, installation, operation, and maintenance are required for the trouble­free and safe operation of the frequency converter. Only qualied personnel are allowed to install or operate this equipment.
Qualied personnel are dened as trained sta, who are authorized to install, commission, and maintain equipment, systems, and circuits in accordance with pertinent laws and regulations. Also, the personnel must be familiar with the instructions and safety measures described in this guide.
Safety Precautions
2.3
WARNING
HIGH VOLTAGE
Drives contain high voltage when connected to AC mains input, DC supply, or load sharing. Failure to perform installation, start-up, and maintenance by qualied personnel can result in death or serious injury.
Only qualied personnel must perform instal-
lation, start-up, and maintenance.
Before performing any service or repair work,
use an appropriate voltage measuring device to make sure that there is no remaining voltage on the drive.
WARNING
UNINTENDED START
When the frequency converter is connected to AC mains, DC supply, or load sharing, the motor may start at any time. Unintended start during programming, service, or repair work can result in death, serious injury, or property damage. The motor can start with an external switch, a eldbus command, an input reference signal from the LCP, via remote operation using MCT 10 Set-up Software, or after a cleared fault condition.
To prevent unintended motor start:
Disconnect the frequency converter from the
mains.
Press [O/Reset] on the LCP before
programming parameters.
Completely wire and assemble the frequency
converter, motor, and any driven equipment before connecting the frequency converter to AC mains, DC supply, or load sharing.
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors, which can remain charged even when the frequency converter is not powered. High voltage can be present even when the warning LED indicator lights are o. Failure to wait the specied time after power has been removed before performing service or repair work can result in death or serious injury.
Stop the motor.
Disconnect AC mains and remote DC-link
supplies, including battery back-ups, UPS, and DC-link connections to other frequency converters.
Disconnect or lock PM motor.
Wait for the capacitors to discharge fully. The
minimum waiting time is specied in Table 2.1.
Before performing any service or repair work,
use an appropriate voltage measuring device to make sure that the capacitors are fully discharged.
12 Danfoss A/S © 02/2019 All rights reserved. MG07C402
Safety Programming Guide
Voltage [V]
200–240 0.37–3.7 (0.5–5) 4
380–480
Table 2.1 Discharge Time
Power range
[kW (hp)]
0.37–7.5 (0.5–10) 4 11–22 (15–30) 15
Minimum waiting time
(minutes)
WARNING
LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to ground the drive properly can result in death or serious injury.
Ensure the correct grounding of the equipment
by a certied electrical installer.
WARNING
EQUIPMENT HAZARD
Contact with rotating shafts and electrical equipment can result in death or serious injury.
Ensure that only trained and qualied personnel
perform installation, start-up, and maintenance.
Ensure that electrical work conforms to national
and local electrical codes.
Follow the procedures in this guide.
2 2
CAUTION
INTERNAL FAILURE HAZARD
An internal failure in the drive can result in serious injury when the drive is not properly closed.
Ensure that all safety covers are in place and
securely fastened before applying power.
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 13
130BC506.10
Setup 1
A
B
C
D
5
12
13 14 15
10
11
10
9
6
7
8
4
1
2
3
Menu
Status
Quick Menu
Main Menu
Hand
On
O
Reset
Auto
On
Back
OK
On
Warn
Alarm
130BD135.10
Setup 1234
INDEX
AHP VkW
srpm Hz%
n2n1
n3
p5 p4
p3 p2 p1
Programming
3 Programming
VLT® Midi Drive FC 280
3.1 Local Control Panel Operation
A. Numeric display
The LCD display is backlit with 1 numeric line. All data is
33
The frequency converter supports numerical local control panel (NLCP), graphic local control panel (GLCP), and blind cover. This section describes the operations with NLCP and GLCP.
NOTICE
The frequency converter can also be programmed from the MCT 10 Set-up Software on PC via RS485 communi­cation port or USB port. This software can be ordered using ordering number 130B1000 or downloaded from the Danfoss website: drives.danfoss.com/downloads/pc- tools/#/.
shown in the NLCP.
The set-up number shows the active set-up and the edit set-up. If the same set-up acts as both active and edit set­up, only that set-up number is shown (factory setting).
1
When active and edit set-up dier, both numbers are shown in the display (for example set-up 12). The number
ashing indicates the edit set-up. 2 Parameter number. 3 Parameter value.
Motor direction is shown at the bottom left of the display. 4
A small arrow indicates the direction.
The triangle indicates whether the LCP is in Status, Quick 5
Menu, or Main Menu.
3.1.1 Numeric Local Control Panel (NLCP)
Table 3.1 Legend to Illustration 3.1, Section A
The numerical local control panel (NLCP) is divided into 4 functional sections.
A. Numeric display.
B. Menu key.
C. Navigation keys and indicator lights (LEDs).
D. Operation keys and indicator lights (LEDs).
Illustration 3.2 Display Information
B. Menu key
To select between Status, Quick Menu, or Main Menu, press [Menu].
Illustration 3.1 View of the NLCP
14 Danfoss A/S © 02/2019 All rights reserved. MG07C402
130BC440.10
Setup 1
Setup 1
Setup 1
Setup 1
Setup 1
Programming Programming Guide
C. Indicator lights (LEDs) and navigation keys
Indicator Light Function
ON turns on when the frequency
6 On Green
7 Warn Yellow
8 Alarm Red
Table 3.2 Legend to Illustration 3.1, Indicator Lights (LEDs)
9 [Back]
10
11 [OK]
12
Key Function
[▲] [▼]
[]
converter receives power from the mains voltage, a DC bus terminal, or a 24 V external supply. When warning conditions are met, the yellow WARN LED turns on, and text appears in the display area identifying the problem. A fault condition causes the red alarm LED to ash and an alarm text is shown.
For moving to the previous step or layer in the navigation structure. For switching between parameter groups, parameters, and within parameters, or increasing/decreasing parameter values. Arrows can also be used for setting local reference. Press to access parameter groups or to enable a selection. Press to move from left to right within the parameter value to change each digit individually.
WARNING
ELECTRICAL HAZARD
Even after pressing the [O/Reset] key, voltage is present at the terminals of the frequency converter. Pressing the [O/Reset] key does not disconnect the frequency converter from mains. Touching live parts can result in death or serious injury.
Do not touch any live parts.
3.1.2 The Right-key Function on NLCP
Press [] to edit any of the 4 digits on the display individually. When pressing [] once, the cursor moves to the rst digit, and the digit starts ashing as shown in Illustration 3.3. Press the [▲] [▼] to change the value. Pressing [] does not change the value of the digits, or move the decimal point.
3 3
Table 3.3 Legend to Illustration 3.1, Navigation Keys
D. Operation keys and indicator lights (LEDs)
Key Function
Starts the frequency converter in local control.
An external stop signal by control input or
13 Hand On
14 O/Reset
15 Auto On
Table 3.4 Legend to Illustration 3.1, Section D
serial communication overrides the local hand on.
Stops the motor but does not remove power to the frequency converter or resets the frequency converter manually after a fault has been cleared. If in alarm mode, the alarm is reset if the alarm condition is removed. Puts the system in remote operational mode.
Responds to an external start command by
control terminals or serial communication.
Illustration 3.3 Right-key Function
[] can also be used for moving between parameter groups. When in Main Menu, press [] to move to the rst parameter in the next parameter group (for example, move from parameter 0-03 Regional Settings [0] International to parameter 1-00 Conguration Mode [0] Open loop).
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 15
Programming
VLT® Midi Drive FC 280
NOTICE
During start-up, the NLCP shows the message LCP ON. When this message is no longer shown, the frequency converter is ready for operation. Adding or removing options can extend the duration of start-up.
33
3.1.3 Quick Menu on NLCP
The Quick Menu gives easy access to the most frequently used parameters.
1. To enter Quick Menu, press [Menu] until the indicator in the display is placed above Quick Menu.
2.
Press [▲] [▼] to select either QM1 or QM2, then press [OK].
3.
Press [▲] [▼] to browse through the parameters in Quick Menu.
4. Press [OK] to select a parameter.
5.
Press [▲] [▼] to change the value of a parameter setting.
6. Press [OK] to accept the change.
7. To exit, press either [Back] twice (or 3 times if in QM2 and QM3) to enter Status, or press [Menu] once to enter Main Menu.
16 Danfoss A/S © 02/2019 All rights reserved. MG07C402
130BC445.13
1-22 XXXX V
Motor
nominal
speed
QM 1
0-01 [0]
1-10 [0]
1-24 XXXX A
Language
Motor Type
1-20 XXXX kW
Motor power
Motor voltage
1-26 XXXX 1-23 XXXX
Stator
Motor frequency
1-25 XXXX
1-30 XXXX
1-39 XXXX
1-40 XXXX
1-37 XXXX
1-25 XXXX
1-24 XXXX
A
3-02 XXXX
3-03 XXXX
3-41 XXXX S
3-42 XXXX S
5-12
[2]
1-29 [1]
AMA
Back EMF at
1000 RPM
d-axis
QM 2
BMS
AMS
ES
5-70 XXXX
5-71 [0]
1-30 XXXX
1-39 XXXX
1-90 [0]
2-10 [0]
4-16 XXXX %
4-17 XXXX %
4-18 XXXX %
1-00 [0]
1-01 [1]
1-10 [0]
1-24 XXXX A 1-20 XXXX kW
1-22 XXXX V
Motor
nominal
speed
Motor power
Motor voltage
1-26 XXXX 1-23 XXXX
Motor frequency
1-25 XXXX
1-30 XXXX
1-40 XXXX
1-37 XXXX
1-25 XXXX
1-24 XXXX
A
Back EMF at
1000 RPM
d-axis
1-39 XXXX
4-14 XXXX
4-19 XXXX
Stator
QM 3
QM 4 QM 5
L10C
SFS
TBD
Motor
nominal
speed
Motor
nominal
speed
Motor current
Motor cont.
rated torque
Resistance (Rs)
Motor poles
inductance (Ld)
Asynchronous motor
Motor current
Minimum reference
Maximum reference
Ramp 1 ramp-up time
Ramp 1 ramp-down time
Terminal 27 digital input
Basic motor set-up
mode
Motor control
principle
Motor type
PM motor
PM motor
Motor
current
Motor cont.
rated torque
Stator
Resistance (Rs)
Motor poles
inductance (Ld)
Motor speed high limit [Hz]
Maximum output frequency
Asynchronous motor
Motor current
RPM
RPM
RPM
Hz
RPM
Hz
Hz
Hz
Hz
Hz
Adv. motor set-up
Resistance (Rs)
Motor poles
Motor thermal
protection
Brake function
Torque limit motor mode
Torque limit generator mode
Current limit
Encoder set-up
Terminal 32/33
pulses per revolution
Terminal 32/33
encoder direction
Changes made
Last 10 changes Since factory setting
Alarm log
Programming Programming Guide
3 3
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 17
Illustration 3.4 Quick Menu Structure
130BC446.10
Setup 1
Setup 1
Setup 1
Setup 1
Setup 1
Setup 1
Setup 1
Setup 1
1
2
3
4
5
6
7
10
11
12
OK
OK
Back
8
Back
Setup 1
2 x
+
OK
9
OK
Programming
VLT® Midi Drive FC 280
3.1.4 Main Menu on NLCP
The Main Menu gives access to all parameters.
1. To enter Main Menu, press [Menu] until the
33
See Illustration 3.5, Illustration 3.6, and Illustration 3.7 for the principles of changing the value of continuous, enumerated, and array parameters, respectively. The actions in the illustrations are described in Table 3.5, Table 3.6, and Table 3.7.
indicator in the display is placed above Main Menu.
2.
[▲] [▼]: Browse through the parameter groups.
3. Press [OK] to select a parameter group.
4.
[▲] [▼]: Browse through the parameters in the specic group.
5. Press [OK] to select the parameter.
6.
[] and [▲]/ [▼]: Set/change the parameter value.
7. Press [OK] to accept the value.
8. To exit, press either [Back] twice (or 3 times for array parameters) to enter Main Menu, or press [Menu] once to enter Status.
Illustration 3.5 Main Menu Interactions - Continuous
Parameters
18 Danfoss A/S © 02/2019 All rights reserved. MG07C402
130BC447.11
Setup 1
Setup 1
Setup 1
1
2
3
4
5
6
OK
OK
Back
7
OK
Back
130BC448.10
1
2
4
5
6
7
8
9
10
OK
Back
Back
Back
5 x
Setup 1
Setup 1
Setup 1
Setup 1
%
INDEX
%
INDEX
%
INDEX
Setup 1
INDEX
%
OK
OK
OK
Programming Programming Guide
1 [OK]: The rst parameter in the group is shown. 2
Press [▼] repeatedly to move down to the parameter.
3 Press [OK] to start editing. 4
[]: First digit ashing (can be edited).
5
[]: Second digit ashing (can be edited).
6
[]: Third digit ashing (can be edited).
7
[▼]: Decrease the parameter value, the decimal point changes automatically.
8
[▲]: Increase the parameter value.
9 [Back]: Cancel changes, return to 2.
[OK]: Accept changes, return to 2.
10
[▲][▼]: Select parameter within the group.
11 [Back]: Remove the value and show the parameter group. 12
[▲][▼]: Select group.
Table 3.5 Changing Values in Continuous Parameters
For enumerated parameters, the interaction is similar, but the parameter value is shown in brackets because of the digits limitation (4 large digits) on the NLCP, and the enum can be greater than 99. When the enum value is greater than 99, the LCP can only show the
rst part of the
bracket.
Array parameters function as follows:
3 3
Illustration 3.7 Main Menu Interactions - Array Parameters
1 [OK]: Show parameter numbers and the value in the rst
index. 2 [OK]: Index can be selected. 3
[▲][▼]: Select index.
4 [OK]: Value can be edited. 5
[▲][▼]: Change parameter value (ashing).
6 [Back]: Cancel changes.
[OK]: Accept changes. 7 [Back]: Cancel editing index, select a new parameter. 8
[▲][▼]: Select parameter within the group.
9 [Back]: Remove parameter index value and show the
Illustration 3.6 Main Menu Interactions - Enumerated
Parameters
1 [OK]: The rst parameter in the group is shown. 2 Press [OK] to start editing. 3
[▲][▼]: Change parameter value (ashing).
4 Press [Back] to cancel changes or [OK] to accept changes
(return to screen 2).
5
[▲][▼]: Select a parameter within the group.
6 [Back]: Remove the value and show the parameter group. 7
[▲][▼]: Select a group.
Table 3.6 Changing Values in Enumerated Parameters
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 19
parameter group. 10
[▲][▼]: Select group.
Table 3.7 Changing Values in Array Parameters
130BD598.10
Auto
On
Reset
Hand
On
O
Status
Quick
Menu
Main
Menu
Alarm
Log
Back
Cancel
Info
OK
Status
1(1)
36.4 kW
Auto Remote Ramping
0.000
On
Alarm
Warn.
A
7.83 A
799 RPM
B
C
D
53.2 %
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18 19 20 21
Programming
VLT® Midi Drive FC 280
3.1.5 Graphic Local Control Panel (GLCP)
B. Display menu keys
Menu keys are used for menu access for parameter set-up,
The GLCP is divided into 4 functional groups (see Illustration 3.8).
33
A. Display area.
B. Display menu keys.
C. Navigation keys and indicator lights (LEDs).
D. Operation keys and reset.
toggling through status display modes during normal operation, and viewing fault log data.
Key Function
6 Status Shows operational information.
Quick
7
Menu
8 Main Menu
9 Alarm Log
Table 3.9 Legend to Illustration 3.8, Display Menu Keys
Allows access to programming parameters for initial set-up instructions and many detailed application instructions. Allows access to all programming parameters. Shows a list of current warnings, the last 10 alarms, and the maintenance log.
C. Navigation keys and indicator lights (LEDs)
Navigation keys are used for programming functions and moving the display cursor. The navigation keys also provide speed control in local operation. There are also 3 frequency converter status indicator lights in this area.
Key Function
10 Back
11 Cancel
12 Info
Navigation
13
keys
14 OK
Reverts to the previous step or list in the menu structure. Cancels the last change or command as long as the display mode has not changed. Press for a denition of the function being shown. To move between items in the menu, use the 4 navigation keys. Press to access parameter groups or to enable a selection.
Table 3.10 Legend to Illustration 3.8, Navigation Keys
Illustration 3.8 Graphic Local Control Panel (GLCP)
A. Display area
The display area is activated when the frequency converter receives power from the mains voltage, a DC bus terminal, or a 24 V DC external supply.
The information shown on the LCP can be customized for user applications. Select options in the Quick Menu Q3-13 Display Settings.
Display Parameter number Default setting
1 0-20 [1602] Reference [%] 2 0-21 [1614] Motor Current 3 0-22 [1610] Power [kW] 4 0-23 [1613] Frequency 5 0-24 [1502] kWh Counter
Table 3.8 Legend to Illustration 3.8, Display Area
20 Danfoss A/S © 02/2019 All rights reserved. MG07C402
Indicator Light Function
ON turns on when the frequency
15 On Green
converter receives power from the mains voltage, a DC bus terminal, or a 24 V external supply. When warning conditions are met,
16 Warn Yellow
the yellow WARN LED turns on, and text appears in the display area identifying the problem. A fault condition causes the red
17 Alarm Red
alarm LED to ash, and an alarm text is shown.
Table 3.11 Legend to Illustration 3.8, Indicator Lights (LEDs)
Programming Programming Guide
D. Operation keys and reset
Operation keys are at the bottom of the LCP.
Key Function
Starts the frequency converter in hand-on mode.
An external stop signal by control input
18 Hand On
19 O
20 Auto On
21 Reset
Table 3.12 Legend to Illustration 3.8, Operation Keys and Reset
or serial communication overrides the local hand on.
Stops the motor but does not remove power to the frequency converter. Puts the system in remote operational mode.
Responds to an external start command
by control terminals or serial communi­cation.
Resets the frequency converter manually after a fault has been cleared.
NOTICE
To adjust the display contrast, press [Status] and the [▲]/[▼] keys.
3.1.6 Parameter Settings
Establishing the correct programming for applications often requires setting functions in several related parameters. Parameter details are provided in chapter 4 Parameter Descriptions.
Programming data is stored internally in the frequency converter.
For back-up, upload data into the LCP memory.
To download data to another frequency
converter, connect the LCP to that unit and download the stored settings.
Restoring factory default settings does not
change data stored in the LCP memory.
3.1.7 Changing Parameter Settings with GLCP
Access and change parameter settings from the Quick Menu or from the Main Menu. The Quick Menu only gives access to a limited number of parameters.
1. Press [Quick Menu] or [Main Menu] on the LCP.
2.
Press [▲] [▼] to browse through the parameter groups, press [OK] to select a parameter group.
3.
Press [▲] [▼] to browse through the parameters, press [OK] to select a parameter.
4.
Press [▲] [▼] to change the value of a parameter setting.
5.
Press [] [] to shift digit when a decimal parameter is in the editing state.
6. Press [OK] to accept the change.
7. Press either [Back] twice to enter Status, or press [Main Menu] once to enter the Main Menu.
View changes
Quick Menu Q5 - Changes Made lists all parameters changed from default settings.
The list only shows parameters, which have been
changed in the current edit set-up.
Parameters which have been reset to default
values are not listed.
The message Empty indicates that no parameters
have been changed.
3.1.8 Uploading/Downloading Data to/from the LCP
1. Press [O] to stop the motor before uploading or downloading data.
2. Press [Main Menu] parameter 0-50 LCP Copy and press [OK].
3. Select [1] All to LCP to upload data to the LCP or select [2] All from LCP to download data from the LCP.
4. Press [OK]. A progress bar shows the uploading or downloading progress.
5. Press [Hand On] or [Auto On] to return to normal operation.
3 3
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 21
Programming
VLT® Midi Drive FC 280
3.1.9 Restoring Default Settings with LCP
NOTICE
Risk of losing programming, motor data, localization, and monitoring records by restoration of default settings. To
33
provide a back-up, upload data to the LCP before initiali­zation.
Manual initialization does not reset the following frequency converter information:
Parameter 15-00 Operating hours.
Parameter 15-03 Power Up's.
Parameter 15-04 Over Temp's.
Parameter 15-05 Over Volt's.
3.2 Basic Programming
Restoring the default parameter settings is done by initiali­zation of the frequency converter. Initialization is carried out through parameter 14-22 Operation Mode (recommended) or manually. Initialization does not reset the settings for parameter 1-06 Clockwise Direction and parameter 0-03 Regional Settings.
Initialization using parameter 14-22 Operation
Mode does not reset frequency converter settings, such as operating hours, serial communication selections, fault log, alarm log, and other monitoring functions.
Manual initialization erases all motor,
programming, localization, and monitoring data and restores factory default settings.
Recommended initialization procedure, via
parameter 14-22 Operation Mode
1. Select parameter 14-22 Operation Mode and press [OK].
2. Select [2] Initialisation and press [OK].
3. Remove power to the unit and wait until the display turns o.
4. Apply power to the unit.
Default parameter settings are restored during start-up. This may take slightly longer than normal.
5. Alarm 80, Drive initialised to default value is shown.
6. Press [Reset] to return to operation mode.
Manual initialization procedure
1. Remove power to the unit and wait until the display turns o.
2. Press and hold [Status], [Main Menu], and [OK] at the same time on the GLCP, or press [Menu] and [OK] at the same time on the NLCP while applying power to the unit (approximately 5 s or until a click is heard and the fan starts).
Factory default parameter settings are restored during start-up. This may take slightly longer than normal.
3.2.1 Asynchronous Motor Set-up
Enter the following motor data in the listed order. Find the information on the motor nameplate.
1. Parameter 1-20 Motor Power.
2. Parameter 1-22 Motor Voltage.
3. Parameter 1-23 Motor Frequency.
4. Parameter 1-24 Motor Current.
5. Parameter 1-25 Motor Nominal Speed.
For optimum performance in VVC+ mode, extra motor data is required to set up the following parameters.
6. Parameter 1-30 Stator Resistance (Rs).
7. Parameter 1-31 Rotor Resistance (Rr).
8. Parameter 1-33 Stator Leakage Reactance (X1).
9. Parameter 1-35 Main Reactance (Xh).
The data is found in the motor datasheet (this data is typically not available on the motor nameplate). Run a complete AMA using parameter 1-29 Automatic Motor Adaption (AMA) [1] Enable Complete AMA or enter the parameters manually.
Application-specic adjustment when running VVC
VVC+ is the most robust control mode. In most situations, it provides optimum performance without further adjustments. Run a complete AMA for best performance.
+
22 Danfoss A/S © 02/2019 All rights reserved. MG07C402
Programming Programming Guide
3.2.2
PM Motor Set-up in VVC
+
Initial programming steps
1. Set parameter 1-10 Motor Construction to the following options to activate PM motor operation:
1a [1] PM, non salient SPM
1b [3] PM, salient IPM
2. Select [0] Open Loop in parameter 1-00 Congu- ration Mode.
NOTICE
Encoder feedback is not supported for PM motors.
Programming motor data
After selecting 1 of the PM motor options in parameter 1-10 Motor Construction, the PM motor-related parameters in parameter groups 1-2* Motor Data, 1-3* Adv. Motor Data, and 1-4* Adv. Motor Data II are active. Find the information on the motor nameplate and in the motor datasheet.
Program the following parameters in the listed order:
1. Parameter 1-24 Motor Current.
2. Parameter 1-26 Motor Cont. Rated Torque.
3. Parameter 1-25 Motor Nominal Speed.
4. Parameter 1-39 Motor Poles.
5. Parameter 1-30 Stator Resistance (Rs). Enter line-to-common stator winding resistance (Rs). If only line-line data is available, divide the line-line value by 2 to achieve the line-to­common (starpoint) value. It is also possible to measure the value with an ohmmeter, which also takes the resistance of the cable into account. Divide the measured value by 2 and enter the result.
6. Parameter 1-37 d-axis Inductance (Ld). Enter line-to-common direct axis inductance of the PM motor. If only line-to-line data is available, divide the line-line value by 2 to achieve the line-common (starpoint) value. It is also possible to measure the value with an inductance meter, which also takes the inductance of the cable into account. Divide the measured value by 2 and enter the result.
7. Parameter 1-40 Back EMF at 1000 RPM. Enter line-to-line back EMF of the PM motor at 1000 RPM mechanical speed (RMS value). Back EMF is the voltage generated by a PM motor when no frequency converter is connected and the shaft is turned externally. Back EMF is normally specied for nominal motor speed or for 1000 RPM measured between 2 lines. If the value
is not available for a motor speed of 1000 RPM, calculate the correct value as follows: For example, if back EMF at 1800 RPM is 320 V, the back EMF at 1000 RPM is: Back EMF=(Voltage/ RPM)x1000=(320/1800)x1000=178. Program this value for parameter 1-40 Back EMF at 1000 RPM.
Test motor operation
1. Start the motor at low speed (100–200 RPM). If the motor does not turn, check installation, general programming, and motor data.
Parking
This function is the recommended option for applications where the motor rotates at slow speed (for example windmilling in fan applications). Parameter 2-06 Parking Current and parameter 2-07 Parking Time are adjustable. Increase the factory setting of these parameters for applications with high inertia.
Start the motor at nominal speed. If the application does not run well, check the VVC+ PM settings. Table 3.13 shows recommendations in dierent applications.
Application Settings
Low inertia applications I
Load/IMotor
Medium inertia applications 50>I High inertia applications I
Load/IMotor
High load at low speed <30% (rated speed)
<5
Load/IMotor
Table 3.13 Recommendations in Dierent Applications
>5
>50
Increase the value for
parameter 1-17 Voltage lter time const. by factor 5–10.
Reduce the value for
parameter 1-14 Damping Gain.
Reduce the value (<100%) for
parameter 1-66 Min. Current at Low Speed.
Keep calculated values.
Increase the values for
parameter 1-14 Damping Gain,
parameter 1-15 Low Speed Filter Time Const., and parameter 1-16 High
Speed Filter Time Const.
Increase the value for
parameter 1-17 Voltage lter time
const.
Increase the value for
parameter 1-66 Min. Current at Low Speed (>100% for longer time can
overheat the motor).
If the motor starts oscillating at a certain speed, increase parameter 1-14 Damping Gain. Increase the value in small steps.
3 3
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 23
Programming
Starting torque can be adjusted in parameter 1-66 Min. Current at Low Speed. 100% provides nominal torque as
starting torque.
VLT® Midi Drive FC 280
3.2.3 Automatic Motor Adaptation (AMA)
33
To optimize compatibility between the frequency converter and the motor in VVC+ mode, run AMA.
The frequency converter builds a mathematical
model of the motor for regulating output motor current, thus enhancing motor performance.
Some motors may be unable to run the complete
version of the test. In that case, select [2] Enable reduced AMA in parameter 1-29 Automatic Motor Adaption (AMA).
If warnings or alarms occur, see
chapter 6.1 Warnings and Alarms.
For best results, run this procedure on a cold
motor.
To run AMA using the LCP
1. By default parameter setting, connect terminals 13 and 27 before running AMA.
2. Enter the Main Menu.
3. Go to parameter group 1-** Load and Motor.
4. Press [OK].
5. Set motor parameters using nameplate data for parameter group 1-2* Motor Data.
6. Set motor cable length in parameter 1-42 Motor Cable Length.
7. Go to parameter 1-29 Automatic Motor Adaption (AMA).
8. Press [OK].
9. Select [1] Enable complete AMA.
10. Press [OK].
11. The test runs automatically and indicates when it is complete.
Depending on the power size, the AMA takes 3– 10 minutes to complete.
NOTICE
The AMA function does not cause the motor to run and it does not harm the motor.
24 Danfoss A/S © 02/2019 All rights reserved. MG07C402
0-03 Regional Settings
Option: Function:
NOTICE
This parameter cannot be adjusted while the motor is running.
[0] International Activate parameter 1-20 Motor Power
[kW] for setting the motor power in
kW and set the default value of parameter 1-23 Motor Frequency to 50 Hz.
[1] North America Activate parameter 1-20 Motor Power
[kW] for setting the motor power in hp and set the default value of parameter 1-23 Motor Frequency to 60 Hz.
0-04 Operating State at Power-up (Hand)
Option: Function:
Select the operating mode upon reconnection of the frequency converter to mains voltage after power-down in hand-on mode.
[0] Resume Restart the frequency converter,
maintaining the start/stop settings (applied by [Hand On/O]) selected before power-down of the frequency converter.
[1] * Forced stop,
ref=old
Restart the frequency converter with a saved local reference after mains voltage reappears and after pressing [Hand On].
[2] Forced stop,
ref=0
Reset the local reference to 0 upon restarting the frequency converter.
0-07 Auto DC Braking
Option: Function:
Protective function against overvoltage at coast in IT grid environment. This parameter is active only when [1] On is selected in this parameter, and IT-grid options are selected in parameter 0-06 GridType.
[0] O This function is not active.
[1] * On This function is active.
0-10 Active Set-up
Select the set-up to control the frequency converter functions. Program parameters in set-ups 1–4. Use the factory set-up to return to the initial state. Use multi set-up for remote control.
Option: Function:
[1] * Set-up 1 [2] Set-up 2 [3] Set-up 3 [4] Set-up 4 [9] Multi Set-up
Parameter Descriptions Programming Guide
4 Parameter Descriptions
4.1 Parameters: 0-** Operation and Display
0-01 Language
Select the language to be used in the display.
Option: Function:
[0] * English [1] Deutsch [2] Francais [3] Dansk [4] Spanish [5] Italiano [28] Portuguese
0-06 GridType
Select the supply voltage, frequency, and type.
Option: Function:
[0] 200-240V/50Hz/IT-grid [1] 200-240V/50Hz/Delta [2] 200-240V/50Hz [10] 380-440V/50Hz/IT-grid [11] 380-440V/50Hz/Delta [12] 380-440V/50Hz [20] 440-480V/50Hz/IT-grid [21] 440-480V/50Hz/Delta [22] 440-480V/50Hz [100] 200-240V/60Hz/IT-grid [101] 200-240V/60Hz/Delta [102] 200-240V/60Hz [110] 380-440V/60Hz/IT-grid [111] 380-440V/60Hz/Delta [112] 380-440V/60Hz [120] 440-480V/60Hz/IT-grid [121] 440-480V/60Hz/Delta [122] 440-480V/60Hz
4 4
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 25
0-11 Programming Set-up
Select the set-up to be programmed during operation; either the active set-up or the inactive set-up. The set-up number being edited ashes in the LCP.
Option: Function:
[1] Set-up 1 [2] Set-up 2 [3] Set-up 3 [4] Set-up 4 [9] * Active Set-up
0-12 Link Setups
Option: Function:
The link ensures synchronizing of the Not changeable during operation parameter values enabling shift from 1 set-up to another during operation.
If the set-ups are not linked, a change between them is not possible while the motor is running. Thus the set-up change does not occur until the motor is coasted.
[0] Not linked Leave parameters unchanged in
both set-ups. These parameters cannot be changed while the motor is running.
[20] * Linked Copy Not changeable during
operation parameters from 1 set-up to the other, so they are identical in both set-ups.
0-14 Readout: Edit Set-ups / Channel
Range: Function:
0* [-2147483647
­2147483647 ]
View the setting of parameter 0-11 Programming Set-up. Edit set-up for each communication channel. A means active set-up; F means factory; numbers indicate set-up code. Communication channels from right to left are LCP, FC-bus, USB, and HPFB1-5.
0-16 Application Selection
Option: Function:
Select integrated application functions. When an application is selected, a set of related parameters are set automatically.
[0] * None [1] Simple Process
Close Loop
[2] Local/Remote
0-16 Application Selection
Option: Function:
[3] Speed Open
Loop
[4] Simple Speed
Close Loop [5] Multi Speed [6] OGD LA10 [7] OGD V210 [8] Hoist
0-20 Display Line 1.1 Small
Select a variable to be shown in line 1, left position.
Option: Function:
[0] None [37] Display Text 1 [38] Display Text 2 [39] Display Text 3 [748] PCD Feed
Forward [953] Probus
Warning Word [1005] Readout
Transmit Error
Counter [1006] Readout
Receive Error
Counter [1230] Warning
Parameter [1501] Running Hours [1502] kWh Counter [1600] Control Word [1601] Reference
[Unit] [1602] * Reference [%] [1603] Status Word [1605] Main Actual
Value [%] [1609] Custom
Readout [1610] Power [kW] [1611] Power [hp] [1612] Motor Voltage [1613] Frequency [1614] Motor current [1615] Frequency [%] [1616] Torque [Nm] [1617] Speed [RPM] [1618] Motor Thermal [1620] Motor Angle [1622] Torque [%] [1630] DC Link
Voltage
Parameter Descriptions
44
26 Danfoss A/S © 02/2019 All rights reserved. MG07C402
VLT® Midi Drive FC 280
0-20 Display Line 1.1 Small
Select a variable to be shown in line 1, left position.
Option: Function:
[1633] Brake
Energy /2 min [1634] Heatsink
Temp. [1635] Inverter
Thermal [1636] Inv. Nom.
Current [1637] Inv. Max.
Current [1638] SL Controller
State [1639] Control Card
Temp. [1650] External
Reference [1652] Feedback[Unit] [1653] Digi Pot
Reference [1657] Feedback
[RPM] [1660] Digital Input [1661] Terminal 53
Setting [1662] Analog input
53 [1663] Terminal 54
Setting [1664] Analog input
54 [1665] Analog output
42 [mA] [1666] Digital Output [1667] Pulse input 29
[Hz] [1668] Pulse input 33
[Hz] [1669] Pulse output
27 [Hz] [1671] Relay output [1672] Counter A [1673] Counter B [1674] Prec. Stop
Counter [1680] Fieldbus CTW
1 [1682] Fieldbus REF 1 [1684] Comm. Option
STW [1685] FC Port CTW 1 [1686] FC Port REF 1 [1690] Alarm Word
0-20 Display Line 1.1 Small
Select a variable to be shown in line 1, left position.
Option: Function:
[1691] Alarm Word 2 [1692] Warning Word [1693] Warning Word
2 [1694] Ext. Status
Word [1695] Ext. Status
Word 2 [1697] Alarm Word 3 [1698] Warning Word
3 [1890] Process PID
Error [1891] Process PID
Output [1892] Process PID
Clamped
Output [1893] Process PID
Gain Scaled
Output [2117] Ext. 1
Reference
[Unit] [2118] Ext. 1
Feedback
[Unit] [2119] Ext. 1 Output
[%] [3401] PCD 1 Write
For
Application [3402] PCD 2 Write
For
Application [3403] PCD 3 Write
For
Application [3404] PCD 4 Write
For
Application [3405] PCD 5 Write
For
Application [3406] PCD 6 Write
For
Application [3407] PCD 7 Write
For
Application [3408] PCD 8 Write
For
Application
Parameter Descriptions Programming Guide
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 27
4 4
0-20 Display Line 1.1 Small
Select a variable to be shown in line 1, left position.
Option: Function:
[3409] PCD 9 Write
For
Application [3410] PCD 10 Write
For
Application [3421] PCD 1 Read
For
Application [3422] PCD 2 Read
For
Application [3423] PCD 3 Read
For
Application [3424] PCD 4 Read
For
Application [3425] PCD 5 Read
For
Application [3426] PCD 6 Read
For
Application [3427] PCD 7 Read
For
Application [3428] PCD 8 Read
For
Application [3429] PCD 9 Read
For
Application [3430] PCD 10 Read
For
Application [3450] Actual Position [3456] Track Error
0-21 Display Line 1.2 Small
Select a variable to be shown in line 1, middle position.
Option: Function:
[0] None [37] Display Text 1 [38] Display Text 2 [39] Display Text 3 [748] PCD Feed
Forward [953] Probus
Warning Word
0-21 Display Line 1.2 Small
Select a variable to be shown in line 1, middle position.
Option: Function:
[1005] Readout
Transmit Error
Counter [1006] Readout
Receive Error
Counter [1230] Warning
Parameter [1501] Running Hours [1502] kWh Counter [1600] Control Word [1601] Reference
[Unit] [1602] Reference [%] [1603] Status Word [1605] Main Actual
Value [%] [1609] Custom
Readout [1610] Power [kW] [1611] Power [hp] [1612] Motor Voltage [1613] Frequency [1614] * Motor current [1615] Frequency [%] [1616] Torque [Nm] [1617] Speed [RPM] [1618] Motor Thermal [1620] Motor Angle [1622] Torque [%] [1630] DC Link
Voltage [1633] Brake
Energy /2 min [1634] Heatsink
Temp. [1635] Inverter
Thermal [1636] Inv. Nom.
Current [1637] Inv. Max.
Current [1638] SL Controller
State [1639] Control Card
Temp. [1650] External
Reference [1652] Feedback[Unit] [1653] Digi Pot
Reference
Parameter Descriptions
44
28 Danfoss A/S © 02/2019 All rights reserved. MG07C402
VLT® Midi Drive FC 280
0-21 Display Line 1.2 Small
Select a variable to be shown in line 1, middle position.
Option: Function:
[1657] Feedback
[RPM] [1660] Digital Input [1661] Terminal 53
Setting [1662] Analog input
53 [1663] Terminal 54
Setting [1664] Analog input
54 [1665] Analog output
42 [mA] [1666] Digital Output [1667] Pulse input 29
[Hz] [1668] Pulse input 33
[Hz] [1669] Pulse output
27 [Hz] [1671] Relay output [1672] Counter A [1673] Counter B [1674] Prec. Stop
Counter [1680] Fieldbus CTW
1 [1682] Fieldbus REF 1 [1684] Comm. Option
STW [1685] FC Port CTW 1 [1686] FC Port REF 1 [1690] Alarm Word [1691] Alarm Word 2 [1692] Warning Word [1693] Warning Word
2 [1694] Ext. Status
Word [1695] Ext. Status
Word 2 [1697] Alarm Word 3 [1698] Warning Word
3 [1890] Process PID
Error [1891] Process PID
Output [1892] Process PID
Clamped
Output
0-21 Display Line 1.2 Small
Select a variable to be shown in line 1, middle position.
Option: Function:
[1893] Process PID
Gain Scaled
Output [2117] Ext. 1
Reference
[Unit] [2118] Ext. 1
Feedback
[Unit] [2119] Ext. 1 Output
[%] [3401] PCD 1 Write
For
Application [3402] PCD 2 Write
For
Application [3403] PCD 3 Write
For
Application [3404] PCD 4 Write
For
Application [3405] PCD 5 Write
For
Application [3406] PCD 6 Write
For
Application [3407] PCD 7 Write
For
Application [3408] PCD 8 Write
For
Application [3409] PCD 9 Write
For
Application [3410] PCD 10 Write
For
Application [3421] PCD 1 Read
For
Application [3422] PCD 2 Read
For
Application [3423] PCD 3 Read
For
Application [3424] PCD 4 Read
For
Application
Parameter Descriptions Programming Guide
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 29
4 4
0-21 Display Line 1.2 Small
Select a variable to be shown in line 1, middle position.
Option: Function:
[3425] PCD 5 Read
For
Application [3426] PCD 6 Read
For
Application [3427] PCD 7 Read
For
Application [3428] PCD 8 Read
For
Application [3429] PCD 9 Read
For
Application [3430] PCD 10 Read
For
Application [3450] Actual Position [3456] Track Error
0-22 Display Line 1.3 Small
Select a variable to be shown in line 1, right position.
Option: Function:
[0] None [37] Display Text 1 [38] Display Text 2 [39] Display Text 3 [748] PCD Feed
Forward [953] Probus
Warning Word [1005] Readout
Transmit Error
Counter [1006] Readout
Receive Error
Counter [1230] Warning
Parameter [1501] Running Hours [1502] kWh Counter [1600] Control Word [1601] Reference
[Unit] [1602] Reference [%] [1603] Status Word [1605] Main Actual
Value [%] [1609] Custom
Readout [1610] * Power [kW ]
0-22 Display Line 1.3 Small
Select a variable to be shown in line 1, right position.
Option: Function:
[1611] Power [hp] [1612] Motor Voltage [1613] Frequency [1614] Motor current [1615] Frequency [%] [1616] Torque [Nm] [1617] Speed [RPM] [1618] Motor Thermal [1620] Motor Angle [1622] Torque [%] [1630] DC Link
Voltage [1633] Brake
Energy /2 min [1634] Heatsink
Temp. [1635] Inverter
Thermal [1636] Inv. Nom.
Current [1637] Inv. Max.
Current [1638] SL Controller
State [1639] Control Card
Temp. [1650] External
Reference [1652] Feedback[Unit] [1653] Digi Pot
Reference [1657] Feedback
[RPM] [1660] Digital Input [1661] Terminal 53
Setting [1662] Analog input
53 [1663] Terminal 54
Setting [1664] Analog input
54 [1665] Analog output
42 [mA] [1666] Digital Output [1667] Pulse input 29
[Hz] [1668] Pulse input 33
[Hz] [1669] Pulse output
27 [Hz] [1671] Relay output
Parameter Descriptions
44
30 Danfoss A/S © 02/2019 All rights reserved. MG07C402
VLT® Midi Drive FC 280
0-22 Display Line 1.3 Small
Select a variable to be shown in line 1, right position.
Option: Function:
[1672] Counter A [1673] Counter B [1674] Prec. Stop
Counter [1680] Fieldbus CTW
1 [1682] Fieldbus REF 1 [1684] Comm. Option
STW [1685] FC Port CTW 1 [1686] FC Port REF 1 [1690] Alarm Word [1691] Alarm Word 2 [1692] Warning Word [1693] Warning Word
2 [1694] Ext. Status
Word [1695] Ext. Status
Word 2 [1697] Alarm Word 3 [1698] Warning Word
3 [1890] Process PID
Error [1891] Process PID
Output [1892] Process PID
Clamped
Output [1893] Process PID
Gain Scaled
Output [2117] Ext. 1
Reference
[Unit] [2118] Ext. 1
Feedback
[Unit] [2119] Ext. 1 Output
[%] [3401] PCD 1 Write
For
Application [3402] PCD 2 Write
For
Application [3403] PCD 3 Write
For
Application
0-22 Display Line 1.3 Small
Select a variable to be shown in line 1, right position.
Option: Function:
[3404] PCD 4 Write
For
Application [3405] PCD 5 Write
For
Application [3406] PCD 6 Write
For
Application [3407] PCD 7 Write
For
Application [3408] PCD 8 Write
For
Application [3409] PCD 9 Write
For
Application [3410] PCD 10 Write
For
Application [3421] PCD 1 Read
For
Application [3422] PCD 2 Read
For
Application [3423] PCD 3 Read
For
Application [3424] PCD 4 Read
For
Application [3425] PCD 5 Read
For
Application [3426] PCD 6 Read
For
Application [3427] PCD 7 Read
For
Application [3428] PCD 8 Read
For
Application [3429] PCD 9 Read
For
Application [3430] PCD 10 Read
For
Application [3450] Actual Position [3456] Track Error
Parameter Descriptions Programming Guide
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 31
4 4
0-23 Display Line 2 Large
Select a variable to be shown in line 2.
Option: Function:
[0] None [37] Display Text 1 [38] Display Text 2 [39] Display Text 3 [748] PCD Feed
Forward [953] Probus
Warning Word [1005] Readout
Transmit Error
Counter [1006] Readout
Receive Error
Counter [1230] Warning
Parameter [1501] Running Hours [1502] kWh Counter [1600] Control Word [1601] Reference
[Unit] [1602] Reference [%] [1603] Status Word [1605] Main Actual
Value [%] [1609] Custom
Readout [1610] Power [kW] [1611] Power [hp] [1612] Motor Voltage [1613] * Frequency [1614] Motor current [1615] Frequency [%] [1616] Torque [Nm] [1617] Speed [RPM] [1618] Motor Thermal [1620] Motor Angle [1622] Torque [%] [1630] DC Link
Voltage [1633] Brake
Energy /2 min [1634] Heatsink
Temp. [1635] Inverter
Thermal [1636] Inv. Nom.
Current [1637] Inv. Max.
Current [1638] SL Controller
State
0-23 Display Line 2 Large
Select a variable to be shown in line 2.
Option: Function:
[1639] Control Card
Temp. [1650] External
Reference [1652] Feedback[Unit] [1653] Digi Pot
Reference [1657] Feedback
[RPM] [1660] Digital Input [1661] Terminal 53
Setting [1662] Analog input
53 [1663] Terminal 54
Setting [1664] Analog input
54 [1665] Analog output
42 [mA] [1666] Digital Output [1667] Pulse input 29
[Hz] [1668] Pulse input 33
[Hz] [1669] Pulse output
27 [Hz] [1671] Relay output [1672] Counter A [1673] Counter B [1674] Prec. Stop
Counter [1680] Fieldbus CTW
1 [1682] Fieldbus REF 1 [1684] Comm. Option
STW [1685] FC Port CTW 1 [1686] FC Port REF 1 [1690] Alarm Word [1691] Alarm Word 2 [1692] Warning Word [1693] Warning Word
2 [1694] Ext. Status
Word [1695] Ext. Status
Word 2 [1697] Alarm Word 3 [1698] Warning Word
3
Parameter Descriptions
44
32 Danfoss A/S © 02/2019 All rights reserved. MG07C402
VLT® Midi Drive FC 280
0-23 Display Line 2 Large
Select a variable to be shown in line 2.
Option: Function:
[1890] Process PID
Error [1891] Process PID
Output [1892] Process PID
Clamped
Output [1893] Process PID
Gain Scaled
Output [2117] Ext. 1
Reference
[Unit] [2118] Ext. 1
Feedback
[Unit] [2119] Ext. 1 Output
[%] [3401] PCD 1 Write
For
Application [3402] PCD 2 Write
For
Application [3403] PCD 3 Write
For
Application [3404] PCD 4 Write
For
Application [3405] PCD 5 Write
For
Application [3406] PCD 6 Write
For
Application [3407] PCD 7 Write
For
Application [3408] PCD 8 Write
For
Application [3409] PCD 9 Write
For
Application [3410] PCD 10 Write
For
Application [3421] PCD 1 Read
For
Application
0-23 Display Line 2 Large
Select a variable to be shown in line 2.
Option: Function:
[3422] PCD 2 Read
For
Application [3423] PCD 3 Read
For
Application [3424] PCD 4 Read
For
Application [3425] PCD 5 Read
For
Application [3426] PCD 6 Read
For
Application [3427] PCD 7 Read
For
Application [3428] PCD 8 Read
For
Application [3429] PCD 9 Read
For
Application [3430] PCD 10 Read
For
Application [3450] Actual Position [3456] Track Error
0-24 Display Line 3 Large
Select a variable to be shown in line 3.
Option: Function:
[0] None [37] Display Text 1 [38] Display Text 2 [39] Display Text 3 [748] PCD Feed
Forward [953] Probus
Warning Word [1005] Readout
Transmit Error
Counter [1006] Readout
Receive Error
Counter [1230] Warning
Parameter [1501] Running Hours [1502] * kWh Counter [1600] Control Word
Parameter Descriptions Programming Guide
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 33
4 4
0-24 Display Line 3 Large
Select a variable to be shown in line 3.
Option: Function:
[1601] Reference
[Unit] [1602] Reference [%] [1603] Status Word [1605] Main Actual
Value [%] [1609] Custom
Readout [1610] Power [kW] [1611] Power [hp] [1612] Motor Voltage [1613] Frequency [1614] Motor current [1615] Frequency [%] [1616] Torque [Nm] [1617] Speed [RPM] [1618] Motor Thermal [1620] Motor Angle [1622] Torque [%] [1630] DC Link
Voltage [1633] Brake
Energy /2 min [1634] Heatsink
Temp. [1635] Inverter
Thermal [1636] Inv. Nom.
Current [1637] Inv. Max.
Current [1638] SL Controller
State [1639] Control Card
Temp. [1650] External
Reference [1652] Feedback[Unit] [1653] Digi Pot
Reference [1657] Feedback
[RPM] [1660] Digital Input [1661] Terminal 53
Setting [1662] Analog input
53 [1663] Terminal 54
Setting [1664] Analog input
54
0-24 Display Line 3 Large
Select a variable to be shown in line 3.
Option: Function:
[1665] Analog output
42 [mA] [1666] Digital Output [1667] Pulse input 29
[Hz] [1668] Pulse input 33
[Hz] [1669] Pulse output
27 [Hz] [1671] Relay output [1672] Counter A [1673] Counter B [1674] Prec. Stop
Counter [1680] Fieldbus CTW
1 [1682] Fieldbus REF 1 [1684] Comm. Option
STW [1685] FC Port CTW 1 [1686] FC Port REF 1 [1690] Alarm Word [1691] Alarm Word 2 [1692] Warning Word [1693] Warning Word
2 [1694] Ext. Status
Word [1695] Ext. Status
Word 2 [1697] Alarm Word 3 [1698] Warning Word
3 [1890] Process PID
Error [1891] Process PID
Output [1892] Process PID
Clamped
Output [1893] Process PID
Gain Scaled
Output [2117] Ext. 1
Reference
[Unit] [2118] Ext. 1
Feedback
[Unit] [2119] Ext. 1 Output
[%]
Parameter Descriptions
44
34 Danfoss A/S © 02/2019 All rights reserved. MG07C402
VLT® Midi Drive FC 280
0-24 Display Line 3 Large
Select a variable to be shown in line 3.
Option: Function:
[3401] PCD 1 Write
For
Application [3402] PCD 2 Write
For
Application [3403] PCD 3 Write
For
Application [3404] PCD 4 Write
For
Application [3405] PCD 5 Write
For
Application [3406] PCD 6 Write
For
Application [3407] PCD 7 Write
For
Application [3408] PCD 8 Write
For
Application [3409] PCD 9 Write
For
Application [3410] PCD 10 Write
For
Application [3421] PCD 1 Read
For
Application [3422] PCD 2 Read
For
Application [3423] PCD 3 Read
For
Application [3424] PCD 4 Read
For
Application [3425] PCD 5 Read
For
Application [3426] PCD 6 Read
For
Application [3427] PCD 7 Read
For
Application
0-24 Display Line 3 Large
Select a variable to be shown in line 3.
Option: Function:
[3428] PCD 8 Read
For
Application [3429] PCD 9 Read
For
Application [3430] PCD 10 Read
For
Application [3450] Actual Position [3456] Track Error
0-30 Custom Readout Unit
Set a value to be shown in the LCP. The value has a linear, squared, or cubed relation to speed. This relation depends on the unit selected.
Option: Function:
[0] None [1] * % [5] PPM [10] 1/min [11] RPM [12] Pulse/s [20] l/s [21] l/min [22] l/h [23] m³/s [24] m³/min [25] m³/h [30] kg/s [31] kg/min [32] kg/h [33] t/min [34] t/h [40] m/s [41] m/min [45] m [60] °C [70] mbar [71] bar [72] Pa [73] kPa [74] m WG [80] kW [120] GPM [121] gal/s [122] gal/min [123] gal/h [124] CFM [127] ft³/h [140] ft/s
Parameter Descriptions Programming Guide
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 35
4 4
0-30 Custom Readout Unit
Set a value to be shown in the LCP. The value has a linear, squared, or cubed relation to speed. This relation depends on the unit selected.
Option: Function:
[141] ft/min [160] °F [170] psi [171] lb/in2 [172] in WG [173] ft WG [180] HP
0-31 Custom Readout Min Value
Range: Function:
0 Custom­ReadoutUni t*
[ 0 -
999999.99
CustomRea-
doutUnit]
This parameter sets the minimum value of the custom readout (occurs at 0 speed). It is only possible to select a value dierent from 0 when selecting a linear unit in
parameter 0-30 Custom Readout Unit. For quadratic and cubic units,
the minimum value is 0.
0-32 Custom Readout Max Value
Range: Function:
100 Custom­ReadoutUni t*
[ 0.0 -
999999.99
CustomRea-
doutUnit]
This parameter sets the maximum value to be shown when the motor speed has reached the value set in
parameter 4-14 Motor Speed High Limit [Hz].
0-37 Display Text 1
Range: Function:
[0 - 0 ] Free text, for example used for the
device tag of eldbus application.
0-38 Display Text 2
Range: Function:
[0 - 0 ] Free text, for example used for the
location tag of eldbus application.
0-39 Display Text 3
Range: Function:
[0 - 0 ] Free text, for example used for the
help tag of eldbus application.
0-40 [Hand on] Key on LCP
Option: Function:
[0] Disabled Avoid accidental start of the
frequency converter in hand-on mode.
[1] * Enabled [Hand On] is enabled.
0-42 [Auto on] Key on LCP
Option: Function:
[0] Disabled Avoid accidental start of the
freqeuncy converter from LCP.
[1] * Enabled [Auto On] is enabled.
0-44 [O/Reset] Key on LCP
Option: Function:
[0] Disabled Select [0] Disabled to avoid
accidental stop or reset of the frequency converter from LCP. Setting can be locked by
parameter 0-60 Main Menu Password.
[1] * Enabled [7] Enable Reset
Only
0-50 LCP Copy
Option: Function:
[0] * No copy No function.
[1] All to LCP Copy all parameters in all set-ups
from the frequency converter memory to the LCP. For service purposes, copy all parameters to the LCP after commissioning.
[2] All from LCP Copy all parameters in all set-ups
from the LCP memory to the frequency converter memory.
[3] Size indep.
from LCP
Copy only the parameters that are independent of the motor size. This selection can be used to program several frequency converters with the same function without disturbing motor data that is already set.
0-51 Set-up Copy
Use this parameter to copy parameters between set-ups.
Option: Function:
[0] * No copy [1] Copy from
setup 1 [2] Copy from
setup 2 [3] Copy from
setup 3 [4] Copy from
setup 4 [9] Copy from
Factory setup
Parameter Descriptions
VLT® Midi Drive FC 280
44
36 Danfoss A/S © 02/2019 All rights reserved. MG07C402
0-60 Main Menu Password
Range: Function:
0* [0 - 999 ] Dene the password for accessing
the Main Menu via the [Main Menu] key. Setting the value to 0 disables the password function.
1-00 Conguration Mode
Option: Function:
Select the application control principle to be used when a remote reference (that is analog input or eldbus) is active.
[0] * Open Loop Enable speed control (without
feedback signal from motor) with automatic slip compensation for almost constant speed at varying loads. Compensations are active, but can be disabled in parameter group 1-0* Load and Motor.
[1] Speed closed
loop
Enable speed closed-loop control with feedback. For increased speed accuracy, provide a feedback signal and set the speed PID control. The speed control parameters are set in
parameter group 7-0* Speed PID Control.
[2] Torque closed
loop
Enable torque closed-loop control with speed feedback. Only possible when option [1] VVC+ is selected in
parameter 1-01 Motor Control Principle.
[3] Process Closed
Loop
Enable the use of process control in the frequency converter. The process control parameters are set in parameter groups 7-2* Process
Ctrl. Feedback and 7-3* Process PID Ctrl.
[4] Torque open
loop
Enable the use of torque open loop in the frequency converter.
[7] Extended PID
Speed OL
Enable the use of extended PID speed OL in the frequency converter.
1-01 Motor Control Principle
Option: Function:
[0] U/f
NOTICE
When running U/f, control slip and load compensations are not included.
1-01 Motor Control Principle
Option: Function:
Used for parallel-connected motors and/or special motor applications. Set the U/f settings in
parameter 1-55 U/f Characteristic - U and parameter 1-56 U/f Charac­teristic - F.
[1] * VVC+
NOTICE
When parameter 1-10 Motor Construction is set to PM-
enabled options, only VVC
+
option is available.
Normal running mode, including slip and load compensations.
1-03 Torque Characteristics
Option: Function:
Select the torque characteristic required. VT and AEO are both energy-saving operations.
[0] * Constant
torque
Motor shaft output provides constant torque under variable speed control.
[1] Variable
Torque
Motor shaft output provides variable torque under variable speed control. Set the variable torque level in parameter 14-40 VT Level.
[2] Auto Energy
Optim. CT
Automatically optimizes energy consumption by minimizing magnetization and frequency via
parameter 14-41 AEO Minimum Magnetisation.
1-06 Clockwise Direction
Option: Function:
NOTICE
This parameter cannot be adjusted while the motor is running.
This parameter denes the term clockwise corresponding to the LCP direction arrow. Used for easy change of direction of shaft rotation without swapping motor wires.
[0] * Normal The motor shaft turns in clockwise
direction when frequency converter is connected UU; VV; and WW to motor.
Parameter Descriptions Programming Guide
4.2 Parameters: 1-** Load and Motor
4 4
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 37
1-06 Clockwise Direction
Option: Function:
[1] Inverse The motor shaft turns in counter-
clockwise direction when frequency converter is connected UU; VV; and WW to motor.
1-14 Damping Gain
Range: Function:
120 %* [ 0 - 250 %] The damping gain stabilizes the PM
machine. The value of damping gain controls the dynamic performance of the PM machine. High damping gain gives high dynamic performance, and low damping gain gives low dynamic performance. The dynamic performance is related to the machine data and load type. If the damping gain is too high or low, the control becomes unstable.
1-15 Low Speed Filter Time Const.
Range: Function:
Size related*
[ 0.01 - 20 s] This time constant is used below
10% rated speed. Obtain quick control through a short damping time constant. However, if this value is too short, the control becomes unstable.
1-16 High Speed Filter Time Const.
Range: Function:
Size related*
[ 0.01 - 20 s] This time constant is used above
10% rated speed. Obtain quick control through a short damping time constant. However, if this value is too short, the control becomes unstable.
1-17 Voltage lter time const.
Range: Function:
Size related*
[ 0.001 - 1 s] Reduce the inuence of high
frequency ripple and system resonance in the calculation of supply voltage. Without this lter, the ripples in the currents can distort the calculated voltage and aect the stability of the system.
1-20 Motor Power
Option: Function:
[2] 0.12 kW - 0.16
hp [3] 0.18 kW - 0.25
hp [4] 0.25 kW - 0.33
hp [5] 0.37 kW - 0.5
hp [6] 0.55 kW - 0.75
hp [7] 0.75 kW - 1 hp [8] 1.1 kW - 1.5
hp [9] 1.5 kW - 2 hp [10] 2.2 kW - 3 hp [11] 3 kW - 4 hp [12] 3.7 kW - 5 hp [13] 4 kW - 5.4 hp [14] 5.5 kW - 7.5
hp [15] 7.5 kW - 10 hp [16] 11 kW - 15 hp [17] 15 kW - 20 hp [18] 18.5 kW - 25
hp [19] 22 kW - 30 hp [20] 30 kW - 40 hp
1-22 Motor Voltage
Range: Function:
Size related*
[50 - 1000 V] Enter the nominal motor voltage
according to the motor nameplate data. The default value corresponds
Parameter Descriptions
VLT® Midi Drive FC 280
1-08 Motor Control Bandwidth
44
Option: Function:
[0] High Suitable for high dynamic response. [1] * Medium Suitable for smooth steady-state operation. [2] Low Suitable for smooth steady-state operation with
lowest dynamic response.
[3] Adaptive 1 Optimized for smooth steady-state operation,
with extra active damping.
[4] Adaptive 2 Focus on low-inductance PM motors. This
option is an alternative to [3] Adaptive 1.
4.2.1 1-10 Motor Construction
1-10 Motor Construction
Option: Function:
[0] * Asynchron For asynchronous motors. [1] PM, non
[3] PM, salient
salient SPM
IPM
For permanent magnet (PM) motors with surface-mounted (non-salient) magnets. Refer to parameter 1-14 Damping Gain to parameter 1-17 Voltage lter time const. for details about optimizing the motor operation. For permanent magnet (PM) motors with interior (salient) magnets.
38 Danfoss A/S © 02/2019 All rights reserved. MG07C402
1-22 Motor Voltage
Range: Function:
to the nominal rated output of the unit.
1-23 Motor Frequency
Range: Function:
NOTICE
This parameter cannot be adjusted while the motor is running.
Size related*
[ 20 - 500 Hz] Select the motor frequency value
from the motor nameplate. For 87 Hz operation with 230/440 V motors, set the value according to the nameplate data for 230 V/50 Hz. Adapt parameter 4-14 Motor
Speed High Limit [Hz] and
parameter 3-03 Maximum Reference
to the 87 Hz application.
1-24 Motor Current
Range: Function:
Size related*
[ 0.01 -
1000.00 A]
Enter the nominal motor current value from the motor nameplate data. This data is used for calculating motor torque, motor thermal protection, and so on.
1-25 Motor Nominal Speed
Range: Function:
Size related*
[50 - 60000
RPM]
Enter the nominal motor speed value from the motor nameplate data. This data is used for calculating automatic motor compensations.
1-26 Motor Cont. Rated Torque
Range: Function:
Size related*
[0.1 -
10000.0 Nm]
Enter the value from the motor nameplate data. The default value corresponds to the nominal rated output. This parameter is available when parameter 1-10 Motor
Construction is set to [1] PM, non salient SPM or [3] PM, salient IPM,
that is, the parameter is valid for PM, non-salient SPM and PM, salient IPM motors only.
1-29 Automatic Motor Adaption (AMA)
Option: Function:
NOTICE
This parameter cannot be adjusted while the motor is running.
NOTICE
Terminal 27 digital input (parameter 5-12 Terminal 27 Digital Input) has coast inverse as the default setting. This setting means that AMA cannot be performed if terminal 27 is switched o.
The AMA function optimizes dynamic motor performance by automatically optimizing the advanced motor parameters.
[0] * O No function.
[1] Enable
Complete
AMA
Depending on the option selected in parameter 1-10 Motor Construction, the AMA is performed on dierent parameters.
If [0] Asynchron is selected, the AMA is performed on:
- Parameter 1-30 St
ator Resistance (Rs).
- Parameter 1-31 R
otor Resistance (Rr).
- Parameter 1-33 St
ator Leakage Reactance (X1).
- Parameter 1-35 M
ain Reactance (Xh).
If [1] PM, non-salient SPM is selected, the AMA is performed on:
- Parameter 1-30 St
ator Resistance (Rs).
- Parameter 1-37 d-
axis Inductance (Ld).
If [3] PM, salient IPM is selected, the AMA is performed on:
Parameter Descriptions Programming Guide
4 4
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 39
1-29 Automatic Motor Adaption (AMA)
Option: Function:
- Parameter 1-30 St
ator Resistance (Rs).
- Parameter 1-37 d-
axis Inductance (Ld).
- Parameter 1-38 q-
axis Inductance (Lq).
- Parameter 1-44 d-
axis Inductance Sat. (LdSat).
- Parameter 1-45 q-
axis Inductance Sat. (LqSat).
[2] Enable
Reduced AMA
Perform a reduced AMA of the stator resistance R
s
(parameter 1-30 Stator Resistance (Rs)) in the system only. If an LC lter is used between the frequency converter and the motor, select this option. (This option is only for asynchronous motors.)
1-30 Stator Resistance (Rs)
Range: Function:
Size related*
[ 0.0 -
9999.000
Ohm]
NOTICE
This parameter cannot be adjusted while the motor is running.
Set the stator resistance value. Enter the value from a motor datasheet or perform an AMA on a cold motor.
1-31 Rotor Resistance (Rr)
Range: Function:
Size related*
[ 0 -
9999.000
Ohm]
NOTICE
This parameter cannot be adjusted while the motor is running.
Enter the rotor resistance value. Obtain the value from a motor datasheet or by performing an AMA on a cold motor. The default setting is calculated by the frequency converter from the motor nameplate data.
1-33 Stator Leakage Reactance (X1)
Range: Function:
Size related*
[ 0.0 -
9999.000
Ohm]
NOTICE
This parameter cannot be adjusted while the motor is running.
Set the stator leakage reactance value. Obtain the value from a motor datasheet or perform an AMA on a cold motor. The default setting is calculated by the frequency converter from the motor nameplate data.
1-35 Main Reactance (Xh)
Range: Function:
Size related*
[ 0.0 -
9999.00 Ohm]
NOTICE
This parameter cannot be adjusted while the motor is running.
Set the main reactance of the motor using 1 of these methods:
Run an AMA on a cold motor. The frequency
Parameter Descriptions
VLT® Midi Drive FC 280
44
When parameter 1-10 Motor Construction is set to options that enable permanent motor mode, the only option available is [1] Enable Complete AMA.
Activate the AMA function by pressing [Hand On] after selecting [1] Enable Complete AMA or [2] Enable Reduced
AMA. After a normal sequence, the display reads: Press [OK] to nish AMA. After pressing [OK], the frequency converter
is ready for operation.
NOTICE
For the best adaptation of the frequency
converter, run AMA on a cold motor.
AMA cannot be performed while the motor is
running.
NOTICE
Avoid generating external torque during AMA.
If an LC lter is used, set the frequency converter to run in U/f control mode (recommended), or perform reduced AMA in VVC+ mode. If an LC complete AMA.
40 Danfoss A/S © 02/2019 All rights reserved. MG07C402
lter is not used, perform
1-35 Main Reactance (Xh)
Range: Function:
converter measures the value from the motor.
Enter the Xh value manually. Obtain the value from the motor supplier.
Use the Xh default setting. The frequency converter establishes the setting based on the motor nameplate data.
1-37 d-axis Inductance (Ld)
Range: Function:
Size related*
[ 0 - 65535
mH]
NOTICE
This parameter cannot be adjusted while the motor is running.
Enter the value of the d-axis inductance. Obtain the value from the permanent magnet motor datasheet or perform an AMA on a cold motor.
1-38 q-axis Inductance (Lq)
Range: Function:
Size related*
[ 0.000 -
65535 mH]
NOTICE
This parameter cannot be adjusted while the motor is running.
Set the value of the q-axis inductance. Find the value in the motor datasheet or perform an AMA on a cold motor.
1-39 Motor Poles
Range: Function:
Size related*
[2 - 100 ]
NOTICE
This parameter cannot be adjusted while the motor is running.
Enter the number of motor poles.
The motor pole value is always an even number, because it refers to the total pole numbers, not pairs of poles.
1-40 Back EMF at 1000 RPM
Range: Function:
Size related*
[ 1 - 9000 V] Set the nominal back EMF for the
motor when running at 1000 RPM. Back EMF is the voltage generated by a PM motor when no frequency converter is connected and the shaft is turned externally. Back EMF is normally specied for nominal motor speed or for 1000 RPM measured between 2 lines. If the value is not available for a motor speed of 1000 RPM, calculate the correct value as follows: If back EMF is, for example, 320 V at 1800 RPM, it can be calculated at 1000 RPM:
Example
Back EMF 320 V at 1800 RPM. Back EMF = (Voltage/RPM)*1000 = (320/1800)*1000 = 178.
This parameter is only active when parameter 1-10 Motor Construction is set to options that enable PM (permanent magnet) motors.
NOTICE
When using PM motors, it is recommended to use brake resistors.
1-42 Motor Cable Length
Range: Function:
50 m* [0 - 100 m] Set the motor cable length in
meters.
1-43 Motor Cable Length Feet
Range: Function:
164 ft* [0 - 328 ft] Set the motor cable length. The
length unit is foot.
1-44 d-axis Inductance Sat. (LdSat)
Range: Function:
Size related [ 0 - 65535
mH]
This parameter is active only when parameter 1-10 Motor Construction is set to [3] PM, salient IPM. This parameter corresponds to the saturation inductance of d-axis. The default value is the value set in
parameter 1-37 d-axis Inductance (Ld). In most cases, do not change
the default value. If the motor supplier provides the saturation curve, enter the d-axis inductance value, which is under 100% of the
Parameter Descriptions Programming Guide
4 4
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 41
1-44 d-axis Inductance Sat. (LdSat)
Range: Function:
nominal current or perform an AMA on a cold motor.
1-45 q-axis Inductance Sat. (LqSat)
Range: Function:
Size related*
[ 0 - 65535
mH]
This parameter is active only when parameter 1-10 Motor Construction is set to [3] PM, salient IPM. This parameter corresponds to the q-axis saturation inductance. The default value is the value set in
parameter 1-38 q-axis Inductance (Lq). In most cases, do not change
the default value. If the motor supplier provides the saturation curve, enter the q-axis inductance value, which is under 100% of the nominal current or perform an AMA on a cold motor.
1-46 Position Detection Gain
Range: Function:
100 %* [ 20 - 200 %] Adjust the amplitude of the test
pulse during position detection at start. Adjust this parameter to improve the position measurement.
1-48 Current at Min Inductance for d-axis
Range: Function:
100 % [ 20 - 200 %] Use this parameter to set the
inductance saturation point.
1-49 Current at Min Inductance for q-axis
Range: Function:
100 % [ 20 - 200 %] This parameter species the
saturation curve of the q­inductance values. From 20–100% of this parameter, the inductance is linearly approximated due to
parameter 1-38 q-axis Inductance (Lq) and parameter 1-45 q-axis Inductance Sat. (LqSat). These
parameters are related to the motor nameplate load compensations, the application load type, and the electronic brake function for quick stop/hold of the motor.
1-50 Motor Magnetisation at Zero Speed
Range: Function:
100 %* [0 - 300 %] Use this parameter along with
parameter 1-52 Min Speed Normal Magnetising [Hz] to obtain a
1-50 Motor Magnetisation at Zero Speed
Range: Function:
dierent thermal load on the motor when running at low speed. Enter a value that is a percentage of the rated magnetizing current. If the setting is too low, the torque on the motor shaft may be reduced.
Magn. current
130BB780.10
Hz
Par.1-50
90%
Par.1-52
Illustration 4.1 Motor Magneti-
zation
1-52 Min Speed Normal Magnetising [Hz]
Range: Function:
1 Hz* [ 0.1 - 10.0
Hz]
Set the required frequency for normal magnetizing current. Use this parameter along with
parameter 1-50 Motor Magnetisation at Zero Speed, also see Illustration 4.1.
1-55 U/f Characteristic - U
Range: Function:
Size related*
[0 - 1000 V] Enter voltage at each frequency
point to manually form a U/f characteristic matching motor. Frequency points are dened in parameter 1-56 U/f Characteristic - F.
1-56 U/f Characteristic - F
Range: Function:
Size related*
[ 0 - 500.0
Hz]
Enter frequency points to form a U/f characteristic matching motor. Voltage at each point is dened in parameter 1-55 U/f Characteristic - U.
Make a U/f characteristic based on 6 denable voltages and frequencies, see Illustration 4.2.
Parameter Descriptions
VLT® Midi Drive FC 280
44
42 Danfoss A/S © 02/2019 All rights reserved. MG07C402
1-56 U/f Characteristic - F
Range: Function:
Motor Voltage Par 1-55 [x]
Output Frequency Par 1-56 [x]
1-55[5]
1-55[4]
1-55[3]
1-55[2]
1-55[1] 1-55[0]
1-56 [0]
1-56 [1]
1-56 [2]
1-56 [3]
1-56 [4]
1-56 [5]
130BA166.10
Illustration 4.2 Example of U/f
Characteristic
1-60 Low Speed Load Compensation
Range: Function:
100 %* [0 - 300 %] Enter the low-speed voltage
compensation value in percent. This parameter is used for optimizing the low-speed load performance. This parameter is only active if
parameter 1-10 Motor Construction = [0] Asynchron.
1-61 High Speed Load Compensation
Range: Function:
100 %* [0 - 300 %] Enter the high-speed load voltage
compensation value in percent. This parameter is used for optimizing the high-speed load performance. This parameter is only active if
parameter 1-10 Motor Construction = [0] Asynchron.
1-62 Slip Compensation
Range: Function:
Size related*
[ -400 -
400.0 %]
Enter the % value for slip compen­sation to compensate for tolerance in the value of n
M,N
. Slip compen­sation is calculated automatically, that is, based on the nominal motor speed n
M,N
.
1-63 Slip Compensation Time Constant
Range: Function:
0.1 s* [0.05 - 5 s] Enter the slip compensation reaction speed. A high value results in slow reaction, and a low value results in quick reaction. If low­frequency resonance problems occur, use a longer time setting.
1-64 Resonance Dampening
Range: Function:
100 %* [0 - 500 %] Enter the resonance dampening
value. Set parameter 1-64 Resonance
Dampening and
parameter 1-65 Resonance Dampening Time Constant to help
eliminate high-frequency resonance problems. To reduce resonance oscillation, increase the value of
parameter 1-64 Resonance Dampening.
1-65 Resonance Dampening Time Constant
Range: Function:
0.005 s* [ 0.001 - 0.05s]Set parameter 1-64 Resonance Dampening and
parameter 1-65 Resonance Dampening Time Constant to help
eliminate high-frequency resonance problems. Enter the time constant that provides the best dampening.
1-66 Min. Current at Low Speed
Range: Function:
50 %* [ 0 - 120 %] Enter the minimum motor current
at low speed. Increasing this current improves motor torque at low speed.
Parameter 1-66 Min. Current at Low Speed is enabled only for PM motor.
1-70 Start Mode
Select the PM motor start-up mode. To initialize the VVC+ control core for previously free-running PM motor. Active for PM motors in VVC+ only if the motor is stopped (or running at low speed).
Option: Function:
[0] * Rotor
Detection
Estimates the electrical angle of the rotor and uses this angle as a starting point. This option is the standard selection for industrial applications. If ystart detects that the motor runs at low speed or has stopped, the frequency converter detects the rotor position (the angle) and starts the motor from that position.
[1] Parking The parking function applies DC
current across the stator winding and rotates the rotor to electrical 0 position. This option is typically for pump and fan applications. If ystart detects that the motor runs at low speed or has stopped, the frequency converter sends out a DC
Parameter Descriptions Programming Guide
4 4
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 43
1-70 Start Mode
Select the PM motor start-up mode. To initialize the VVC+ control core for previously free-running PM motor. Active for PM motors in VVC+ only if the motor is stopped (or running at low speed).
Option: Function:
current to make the motor park at an angle and then starts the motor from that position.
[3] Rotor Last
Position
This option takes the advantage of the last position of rotor at stop and gives a quick start. It is only used in the situation of controlled stop, the frequency converter records the last position of rotor at stop and starts the motor directly without rotor detection and angle calculation. When in the situation of non-controlled stop and power cycle, the frequency converter needs to detect the rotor position.
This option can be used for fast restart application. Start may fail if the rotor position has been changed.
1-72 Start Function
Option: Function:
Select the start function during start delay. This parameter is linked to parameter 1-71 Start Delay.
[0] DC Hold/delay
time
Energize motor with a DC hold current (parameter 2-00 DC Hold/ Motor Preheat Current) during the start delay time.
[1] DC-Brake/
delay time
Energize motor with a DC hold current (parameter 2-01 DC Brake Current) during the start delay time.
[2] * Coast/delay
time
Motor coasted during the start delay time (inverter o).
[3] Start speed
cw
Only possible with VVC+. Regardless of the value applied by the reference signal, the output speed applies the setting of the start speed in parameter 1-75 Star t Speed [Hz] and the output current corresponds to the setting of the
1-72 Start Function
Option: Function:
start current in parameter 1-76 Start Current. This function is typically
used in hoisting applications without counterweight and especially in applications with a cone-motor, where the start is clockwise, followed by rotation in the reference direction.
[4] Horizontal
operation
Only possible with VVC+. For obtaining the function described in parameter 1-75 Start
Speed [Hz] and parameter 1-76 Start Current during the start delay time.
The motor rotates in the reference direction. If the reference signal equals 0, parameter 1-75 Star t Speed [Hz] is ignored and the output speed equals 0. The output current corresponds to the setting of the start current in parameter 1-76 Start Current.
[5] VVC+
clockwise
The start current is calculated automatically. This function uses the start speed in the start delay time only.
1-73 Flying Start
Option: Function:
NOTICE
This parameter cannot be changed while the motor is running.
NOTICE
To obtain the best ying start performance, the advanced motor data,
parameter 1-30 Stator Resistance (Rs) to parameter 1-35 Main Reactance (Xh), must be correct.
Catch a motor which is spinning freely due to a mains dropout.
[0] * Disabled No function.
[1] Enabled Enable the frequency converter to
catch and control a spinning motor. When parameter 1-73 Flying Start is enabled, parameter 1-71 Start Delay, and parameter 1-72 Start Function have no function.
Parameter Descriptions
VLT® Midi Drive FC 280
44
1-71 Start Delay
Range: Function:
0 s* [0.0 -
10.0 s]
This parameter enables a delay of the starting time. The frequency converter begins with the start function selected in parameter 1-72 Start Function. Set the start delay time until acceleration is to begin.
44 Danfoss A/S © 02/2019 All rights reserved. MG07C402
1-73 Flying Start
Option: Function:
[2] Enabled
Always
Enable ying start at every start command.
[3] Enabled Ref.
Dir.
Enable the frequency converter to catch and control a spinning motor. The search is performed only in the reference direction.
[4] Enab. Always
Ref. Dir.
Enable ying start at every start command. The search is performed only in the reference direction.
1-75 Start Speed [Hz]
Range: Function:
Size related*
[ 0 - 500.0 Hz]
This parameter can be used for hoist applications (cone rotor). Set a motor start speed. After the start signal, the output speed leaps to the set value. Set the start function in parameter 1-72 Start Function to
[3] Start speed cw, [4] Horizontal operation, or [5] VVC+ clockwise, and
set a start delay time in parameter 1-71 Start Delay.
1-76 Start Current
Range: Function:
Size related*
[ 0 - 1000 A] Some motors, for example cone
rotor motors, need extra current/ starting speed to disengage the rotor. To obtain this boost, set the required current in this parameter. Set parameter 1-72 Start Function to
[3] Start speed cw or [4] Horizontal operation, and set a start delay time in parameter 1-71 Start Delay.
1-78 Compressor Start Max Speed [Hz]
Range: Function:
0 Hz* [ 0 - 500 Hz] This parameter enables high
starting torque. The time from the start signal is given until the speed exceeds the speed set in this parameter becomes a start zone. In the start zone, the current limit and motoric torque limit are set to the maximum possible value for the frequency converter/motor combination. The time without protection from the current limit and torque limit must not exceed the value set in
parameter 1-79 Compressor Start Max Time to Trip. Otherwise, the
1-78 Compressor Start Max Speed [Hz]
Range: Function:
frequency converter trips with alarm 18, Start Failed.
1-79 Compressor Start Max Time to Trip
Range: Function:
5 s* [0 - 10 s] The time from the start signal is
given until the speed exceeds the speed set in
parameter 1-78 Compressor Start Max Speed [Hz] must not exceed
the time set in this parameter. Otherwise, the frequency converter trips with alarm 18, Start Failed. Any time set in parameter 1-71 Start Delay for use of a start function must be executed within the time limit.
1-80 Function at Stop
Option: Function:
Select the frequency converter function after a stop command or after the speed is ramped down to the settings in parameter 1-82 Min Speed for Function at Stop [Hz].
Available selections depend on the setting in parameter 1-10 Motor Construction.
[0] Asynchron.
- [0] Coast.
- [1] DC hold /
Motor Preheat.
- [3] Pre-
magnetizing.
[1] PM, non salient SPM.
[3] PM, salient IPM.
- [0] Coast.
- [1] DC hold /
Motor Preheat.
[0] * Coast Leaves the motor in free mode.
[1] DC hold /
Motor Preheat
Energizes the motor with a DC hold current (see parameter 2-00 DC Hold/Motor Preheat Current.
[3] Pre-
magnetizing
Builds up a magnetic eld while the motor is stopped. This allows the motor to produce torque quickly at commands (asynchronous motors only). This premagnetizing function does not help the very rst start command. Two dierent solutions
Parameter Descriptions Programming Guide
4 4
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 45
1-80 Function at Stop
Option: Function:
are available to pre-magnetize the machine for the rst start command:
Solution 1:
1. Start the frequency converter with a 0 RPM reference.
2. Wait 2 to 4 rotor time constants (see the equation below) before increasing the speed reference.
Solution 2:
1. Set parameter 1-71 Start Delay to the premagnetize
time (2–4 rotor time constants).
2. Set parameter 1-72 Start Function to [0] DC hold.
3. Set the DC-hold current magnitude (parameter 2-00 DC Hold/ Motor Preheat Current to be equal to I
pre-mag
=
U
nom
/(1.73 x Xh).
Sample rotor time constants = (Xh+X2)/(6.3*Freq_nom*Rr) 1 kW = 0.2 s 10 kW = 0.5 s 100 kW = 1.7 s
1-82 Min Speed for Function at Stop [Hz]
Range: Function:
0 Hz* [0 - 20 Hz] Set the output frequency at which
to activate parameter 1-80 Function at Stop.
1-83 Precise Stop Function
Option: Function:
[0] * Precise ramp
stop
Only optimal when the operational speed (for example the operational speed of a conveyor belt) is constant. This is an open-loop control. Achieves high repetitive precision at the stopping point.
[1] Counter stop
with reset
Count the number of pulses, typically from an encoder, and generates a stop signal after a preprogrammed number of pulses
dened in parameter 1-84 Precise Stop Counter Value, which has been
received at terminal 29 or terminal
1-83 Precise Stop Function
Option: Function:
33. This is a direct feedback with one-way closed-loop control. The counter function is activated (starts timing) at the edge of the start signal (when it changes from stop to start). After each precise stop, the number of pulses counted during ramp down to 0 RPM is reset.
[2] Counter stop
without reset
Same as [1] Counter stop with reset, but the number of pulses counted during ramp down to 0 RPM is deducted from the counter value entered in parameter 1-84 Precise Stop Counter Value. This reset function can be used to compensate for the extra distance done during ramping down, and to reduce the impacts of gradual wear of mechanical parts.
[3] Speed
compensated stop
Stop at precisely the same point, regardless of the present speed. The stop signal is delayed internally when the present speed is lower than the maximum speed (set in
parameter 4-19 Max Output Frequency). The delay is calculated
on the basis of the reference speed of the frequency converter and not based on the actual speed. Make sure that the frequency converter has ramped up before activating the speed compensated stop.
[4] Speed
compensated counter stop with reset
Same as [3] Speed compensated stop, but after each precise stop, the number of pulses counted during ramp down to 0 RPM is reset.
[5] Speed
compensated counter stop without reset
Same as [3] Speed compensated stop, but the number of pulses counted during ramp down to 0 RPM is deducted from the counter value entered in
parameter 1-84 Precise Stop Counter Value. This reset function can be
used to compensate for the extra distance done during ramping down and to reduce the impacts of gradual wear of mechanical parts.
Parameter Descriptions
44
46 Danfoss A/S © 02/2019 All rights reserved. MG07C402
VLT® Midi Drive FC 280
1-84 Precise Stop Counter Value
Range: Function:
100000* [0 -
999999999 ]
Enter the counter value to be used in the integrated precise stop function in parameter 1-83 Precise Stop Function. The maximum permissible frequency at terminal 29 or 33 is 32 kHz.
1-85 Precise Stop Speed Compensation Delay
Range: Function:
10 ms* [0 - 100 ms] Enter the delay time for sensors,
PLCs, and so on for use in parameter 1-83 Precise Stop Function. In speed-compensated stop mode, the delay time at dierent frequencies has a major inuence on the stop function.
1-88 AC Brake Gain
Range: Function:
1.4* [1.0 - 2.0 ] This parameter is used to set AC brake power capability (set ramp­down time when inertia is constant). In cases where the DC­link voltage is not higher than DC­link voltage trip value, the generator torque can be adjusted with this parameter. The higher AC brake gain is, the stronger the brake capability is. Select 1.0 means that there is no AC brake capability.
NOTICE
If there is continuous generator torque, higher generator torque causes higher motor current, and the motor becomes hot. In this condition, parameter 2-16 AC Brake, Max current can be used to protect the motor from overheating.
1-90 Motor Thermal Protection
Option: Function:
[0] * No protection Continuously overloaded motor,
when no warning or trip of the frequency converter is required.
[1] Thermistor
warning
Activates a warning when the connected thermistor in the motor reacts to a motor overtemperature.
[2] Thermistor trip Stops (trips) the frequency
converter when the connected thermistor in the motor reacts to a motor overtemperature.
The thermistor cutout value must be >3 kΩ.
Integrate a thermistor (PTC sensor) in the motor for winding protection.
[3] ETR warning 1 Calculates the load and activates a
warning in the display when the motor is overloaded. Program a warning signal via 1 of the digital outputs.
[4] ETR trip 1 Calculates the load and stops (trips)
the frequency converter when the motor is overloaded. Program a warning signal via 1 of the digital outputs. The signal appears in the event of a warning and if the frequency converter trips (thermal warning).
[22] ETR Trip -
Extended Detection
Parameter Descriptions Programming Guide
4 4
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 47
1330
550
250
-20 °C
175HA183.11
4000
3000
R
(Ω)
nominal
nominal -5 °C nominal +5 °C
[°C]
PTC / Thermistor
R
OFF
ON
<800 Ω
+10 V
130BF693.10
>2.9 kΩ
12 13 1837 322719 29 3338
5550
42
53 54
PTC / Thermistor
R
OFF
ON
<800 Ω
+10 V
130BF694.10
>2.9 kΩ
5550
42
53 54
1-93 Thermistor Source
Option: Function:
NOTICE
This parameter cannot be changed while the motor is running.
NOTICE
Set the digital input to [0] PNP
- Active at 24 V in parameter 5-00 Digital Input Mode.
Select the input to which the thermistor (PTC sensor) should be connected. If an analog input in this parameter is set as a source, it cannot be used for other purpose, for example, reference, feedback.
[0] * None [1] Analog Input
53
[2] Analog Input
54
[3] Digital input
18
[4] Digital input
19
[5] Digital input
32
Parameter Descriptions
VLT® Midi Drive FC 280
44
Illustration 4.5 PTC Thermistor Connection - Analog Input
Illustration 4.3 PTC Prole
Using a digital input and 10 V as supply: Example: The frequency converter trips when the motor temperature is too high. Parameter set-up:
Set parameter 1-90 Motor Thermal Protection to [2]
Thermistor Trip.
Set parameter 1-93 Thermistor Source to [6] Digital
Input.
Input
digital/analog
Digital 10 V Analog 10 V
Table 4.1 Threshold Cutout Values
Supply voltage Threshold
cutout values
<800 Ω - 2.9 kΩ <800 Ω - 2.9 kΩ
NOTICE
Check that the selected supply voltage follows the specication of the used thermistor element.
Illustration 4.4 PTC Thermistor Connection - Digital Input
Using an analog input and 10 V as supply: Example: The frequency converter trips when the motor temperature is too high. Parameter set-up:
48 Danfoss A/S © 02/2019 All rights reserved. MG07C402
Set parameter 1-90 Motor Thermal Protection to [2] Thermistor Trip.
Set parameter 1-93 Thermistor Source to [2] Analog Input 54.
1-93 Thermistor Source
Option: Function:
[6] Digital input
33
2-00 DC Hold/Motor Preheat Current
Range: Function:
50 %* [0 - 160 %] Set the holding current as a
percentage of the rated motor current I
M,N
parameter 1-24 Motor Current. This parameter holds the motor function (holding torque) or pre-heats the motor. This parameter is active if [0] DC hold is selected in
parameter 1-72 Start Function, or if [1] DC hold/pre-heat is selected in parameter 1-80 Function at Stop.
NOTICE
The maximum value depends on the rated motor current. Avoid 100% current for too long. It may damage the motor.
2-01 DC Brake Current
Range: Function:
50 %* [0 - 150 %]
NOTICE
MOTOR OVERHEATING
The maximum value depends on the rated motor current. To avoid motor damage caused by overheating, do not run at 100% for too long.
Set current as % of rated motor current, parameter 1-24 Motor Current. When speed is below the limit set in parameter 2-04 DC Brake Cut In Speed, or when the DC-brake inverse function is active (in
parameter group 5-1* Digital Inputs
set to [5] DC-brake inverse; or via the serial port), a DC-brake current is applied on a stop command. See parameter 2-02 DC Braking Time for duration.
2-02 DC Braking Time
Range: Function:
10 s* [0 - 60 s] Set the duration of the DC brake
current set in parameter 2-01 DC Brake Current, once activated.
2-04 DC Brake Cut In Speed
Range: Function:
0 Hz* [ 0 - 500 Hz] This parameter is for setting the DC
brake cut-in speed at which the DC brake current parameter 2-01 DC Brake Current is to be active, with a stop command.
2-06 Parking Current
Range: Function:
100 %* [0 - 150 %] Set current as percentage of rated
motor current, parameter 1-24 Motor Current.
2-07 Parking Time
Range: Function:
3 s* [0.1 - 60 s] Set the duration of the parking
current set in parameter 2-06 Parking Current, once activated.
2-10 Brake Function
Option: Function:
[0] * O No brake resistor is installed.
[1] Resistor brake A brake resistor is incorporated in
the system for dissipating surplus brake energy as heat. Connecting a brake resistor allows a higher DC­link voltage during braking (generating operation). The brake resistor function is only active in frequency converters with an integral dynamic brake.
[2] AC brake Improve braking without using a
brake resistor. This parameter controls an overmagnetization of the motor when running with a generatoric load. This function can improve the OVC function. Increasing the electrical losses in the motor allows the OVC function to increase braking torque without exceeding the voltage limit.
NOTICE
The AC brake is not as ecient as dynamic braking with resistor. AC brake is for VVC+ mode in both open and closed loop.
Parameter Descriptions Programming Guide
4.3 Parameters: 2-** Brakes
4 4
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 49
2-11 Brake Resistor (ohm)
Range: Function:
Size related*
[ 0 - 6200 Ohm]
Set the brake resistor value in Ω. This value is used for monitoring the power to the brake resistor.
Parameter 2-11 Brake Resistor (ohm)
is only active in frequency converters with an integral dynamic brake. Use this parameter for values without decimals.
2-12 Brake Power Limit (kW)
Range: Function:
Size related*
[0.001 - 2000 kW]
Parameter 2-12 Brake Power Limit (kW) is the expected average power
dissipated in the brake resistor over a period of 120 s. It is used as the monitoring limit for
parameter 16-33 Brake Energy Average and species when a
warning/alarm is given. To calculate parameter 2-12 Brake Power Limit (kW), the following formula can be used.
P
br, avg
W =
U
br
2
V × tbrs
RbrΩ × Tbrs
P
br,avg
is the average power
dissipated in the brake resistor. R
br
is the resistance of the brake resistor. tbr is the active breaking time within the 120 s period Tbr. Ubr is the DC voltage where the brake resistor is active. For T4 units, the DC voltage is 770 V, which can be reduced by parameter 2-14 Brake voltage reduce.
NOTICE
If Rbr is not known or if Tbr is dierent from 120 s, the practical approach is to run the brake application, read out
parameter 16-33 Brake Energy Average, and then enter this
value + 20% in
parameter 2-12 Brake Power Limit (kW).
2-14 Brake voltage reduce
Range: Function:
0 V* [ 0 - 500 V] This parameter can reduce the DC
voltage where the brake resistor is active. It is only valid for T4 unit.
2-16 AC Brake, Max current
Range: Function:
100 %* [0 - 160 %] Enter the maximum allowed current
when using AC brake to avoid overheating of motor windings.
NOTICE
Parameter 2-16 AC Brake, Max current is only available for
asynchronous motors.
2-17 Over-voltage Control
Option: Function:
Overvoltage control (OVC) reduces the risk of the frequency converter tripping due to an overvoltage on the DC link caused by generative power from the load.
[0] * Disabled No OVC required.
[1] Enabled (not
at stop)
Activate OVC except when using a stop signal to stop the frequency converter.
[2] Enabled Activate OVC.
CAUTION
PERSONAL INJURY AND EQUIPMENT DAMAGE
Enabling OVC in hoisting applications may lead to personal injuries and equipment damage.
DO NOT enable OVC in hoisting applications.
2-19 Over-voltage Gain
Range: Function:
100 %* [0 - 200 %] Select overvoltage gain.
2-20 Release Brake Current
Range: Function:
0 A* [0 - 100 A] Set the motor current for release of
the mechanical brake when a start condition is present. The upper limit is specied in parameter 16-37 Inv. Max. Current.
Parameter Descriptions
VLT® Midi Drive FC 280
44
50 Danfoss A/S © 02/2019 All rights reserved. MG07C402
2-20 Release Brake Current
Range: Function:
NOTICE
When mechanical brake control output is selected, but no mechanical brake is connected, the function does not work by default setting due to too low motor current.
2-22 Activate Brake Speed [Hz]
Range: Function:
0 Hz* [0 - 400 Hz] Set the motor frequency for
activation of the mechanical brake when a stop condition is present.
2-23 Activate Brake Delay
Range: Function:
0 s* [0 - 5 s] Enter the brake delay time of the
coast after ramp-down time. The shaft is held at 0 speed with full holding torque. Ensure that the mechanical brake has locked the load before the motor enters coast mode.
3-00 Reference Range
Option: Function:
[0] * Min - Max Select the range of the reference
signal and the feedback signal. Signal values can be positive only, or positive and negative.
[1] -Max - +Max For both positive and negative
values (both directions), relative to
parameter 4-10 Motor Speed Direction.
3-01 Reference/Feedback Unit
Option: Function:
Select the unit for process PID control references and feedbacks.
[0] None [1] % [2] RPM [3] Hz [4] Nm [5] PPM [10] 1/min [12] Pulse/s [20] l/s [21] l/min
3-01 Reference/Feedback Unit
Option: Function:
[22] l/h [23] m³/s [24] m³/min [25] m³/h [30] kg/s [31] kg/min [32] kg/h [33] t/min [34] t/h [40] m/s [41] m/min [45] m [60] °C [70] mbar [71] bar [72] Pa [73] kPa [74] m WG [80] kW [120] GPM [121] gal/s [122] gal/min [123] gal/h [124] CFM [125] ft³/s [126] ft³/min [127] ft³/h [130] lb/s [131] lb/min [132] lb/h [140] ft/s [141] ft/min [145] ft [150] lb ft [160] °F [170] psi [171] lb/in2 [172] in WG [173] ft WG [180] HP
8-00 Option A warning control
This parameter is used to enable or disable installed options.
Option: Function:
[0] * None [1] Disable
Warning
Parameter Descriptions Programming Guide
4.4 Parameters: 3-** Reference/Ramps
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 51
4 4
3-03 Maximum Reference
Range: Function:
Size related*
[-4999.0 ­4999 Reference­FeedbackUnit]
Enter the maximum reference. The maximum reference is the highest value obtainable by summing all references.
The maximum reference unit matches:
The option selected in
parameter 1-00 Congu­ration Mode.
The unit selected in
parameter 3-00 Reference Range.
3-04 Reference Function
Option: Function:
[0] * Sum Sum both external and preset
reference sources.
[1] External/Preset Use either the preset or the
external reference source. Shift between external and preset via a command or a digital input.
3-10 Preset Reference
Range: Function:
0 %* [-100 -
100 %]
Enter up to 8 dierent preset references (0–7) in this parameter, using array programming. For selecting dedicated references, select preset reference bit 0/1/2 [16], [17], or [18] for the corresponding digital inputs in parameter group 5-1* Digital Inputs.
3-11 Jog Speed [Hz]
Range: Function:
5 Hz* [ 0 - 500.0
Hz]
The jog speed is a xed output speed at which the frequency converter runs when the jog function is activated. See also parameter 3-80 Jog Ramp Time.
The jog speed must not exceed the setting in parameter 4-14 Motor Speed High Limit [Hz].
3-12 Catch up/slow Down Value
Range: Function:
0 %* [0 - 100 %] Enter a percentage value to be
either added to or deducted from the actual reference for catching up or slowing down respectively. If [28] Catch up is selected via 1 of the digital inputs
3-12 Catch up/slow Down Value
Range: Function:
(parameter 5-10 Terminal 18 Digital Input to parameter 5-15 Terminal 33 Digital Input), the percentage value
is added to the total reference. If [29] Slow down is selected via 1 of the digital inputs (parameter 5-10 Terminal 18 Digital
Input to parameter 5-15 Terminal 33 Digital Input), the percentage value
is deducted from the total reference.
3-14 Preset Relative Reference
Range: Function:
0 %* [-100 -
100 %]
The actual reference, X, is increased or decreased with the percentage Y, set in parameter 3-14 Preset Relative Reference. This results in the actual reference Z. Actual reference (X) is the sum of the inputs selected in
parameter 3-15 Reference 1 Source, parameter 3-16 Reference 2 Source, parameter 3-17 Reference 3 Source, and parameter 8-02 Control Source.
Relative Z=X+X*Y/100
Resulting actual reference
Y
X
130BA059.12
Z
X
100
%
0-100
Z
Y
X+X*Y/100
P 3-14
130BA278.10
3-15 Reference 1 Source
Option: Function:
Select the reference input to be used for the rst reference signal.
Parameter 3-15 Reference 1 Source, parameter 3-16 Reference 2 Source, and parameter 3-17 Reference 3 Source dene up to 3 dierent
Parameter Descriptions
VLT® Midi Drive FC 280
44
52 Danfoss A/S © 02/2019 All rights reserved. MG07C402
Illustration 4.6 Preset Relative Reference
Illustration 4.7 Actual Reference
3-15 Reference 1 Source
Option: Function:
reference signals. The sum of these reference signals denes the actual reference.
[0] No function [1] * Analog Input
53
[2] Analog Input
54
[7] Frequency
input 29
[8] Frequency
input 33
[11] Local bus
reference
[20] Digital
pot.meter
[32] Bus PCD
3-16 Reference 2 Source
Option: Function:
Select the reference input to be used for the second reference signal. Parameter 3-15 Reference 1
Source, parameter 3-16 Reference 2 Source, and
parameter 3-17 Reference 3 Source
dene up to 3 dierent reference signals. The sum of these reference signals denes the actual reference.
[0] No function [1] Analog Input
53
[2] * Analog Input
54
[7] Frequency
input 29
[8] Frequency
input 33
[11] Local bus
reference
[20] Digital
pot.meter
[32] Bus PCD
3-17 Reference 3 Source
Option: Function:
Select the reference input to be used for the third reference signal.
Parameter 3-15 Reference 1 Source, parameter 3-16 Reference 2 Source, and parameter 3-17 Reference 3 Source dene up to 3 dierent
reference signals. The sum of these
3-17 Reference 3 Source
Option: Function:
reference signals denes the actual reference.
[0] No function [1] Analog Input
53
[2] Analog Input
54
[7] Frequency
input 29
[8] Frequency
input 33
[11] * Local bus
reference
[20] Digital
pot.meter
[32] Bus PCD
3-18 Relative Scaling Reference Resource
Option: Function:
NOTICE
This parameter cannot be adjusted while the motor is running.
Select a variable value to be added to the xed value (dened in
parameter 3-14 Preset Relative Reference). The sum of the xed
and variable values (labeled Y in Illustration 4.8) is multiplied by the actual reference (labeled X in Illustration 4.8). This product is then added to the actual reference (X +X*Y/100) to give the resulting actual reference.
Relative Z=X+X*Y/100
Resulting actual reference
Y
X
130BA059.12
Z
Illustration 4.8 Resulting Actual
Reference
[0] * No function [1] Analog Input
53
[2] Analog Input
54
[7] Frequency
input 29
[8] Frequency
input 33
Parameter Descriptions Programming Guide
4 4
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 53
3-18 Relative Scaling Reference Resource
Option: Function:
[11] Local bus
reference
3-31 Ramp Down w/ dir. Change
Select the deceleration ramp (both directions) when the shaft changes direction.
Option: Function:
[0] * O [1] Ramp 1 Ramp
Down Time
[2] Ramp 2 Ramp
Down Time
[3] Ramp 3 Ramp
Down Time
[4] Ramp 4 Ramp
Down Time
[9] Quick Stop
Ramp Time
3-40 Ramp 1 Type
Option: Function:
Select the ramp type, depending on requirements for acceleration/ deceleration. A linear ramp gives constant acceleration during ramping. A sine-2 ramp gives non­linear acceleration.
[0] * Linear [1] Sine Ramp [2] Sine 2 Ramp (Only be used with speed control
mode) S-ramp based on the values set in parameter 3-41 Ramp 1 Ramp
Up Time and parameter 3-42 Ramp 1 Ramp Down Time.
3-41 Ramp 1 Ramp Up Time
Range: Function:
Size related*
[0.01 - 3600s]Enter the ramp-up time, that is the
acceleration time from 0 Hz to the synchronous motor speed nS parameter 1-23 Motor Frequency or from 0 NM to the nominal torque if torque conguration modes are selected. It is applicable for Ramp 1 to Ramp 4. Select a ramp-up time such that the output current does not exceed the current limit in parameter 4-18 Current Limit during ramping. See ramp-down time in
parameter 3-42 Ramp 1 Ramp Down Time.
Par . 3 41 = 
t
acc
s xns Hzref Hz
3-42 Ramp 1 Ramp Down Time
Range: Function:
Size related*
[0.01 - 3600s]Enter the ramp-down time, that is
the deceleration time from the synchronous motor speed ns to 0 Hz or from the nominal torque to 0 NM if the torque conguration modes are selected. Select a ramp­down time such that no overvoltage occurs in the inverter due to regenerative operation of the motor, and such that the generated current does not exceed the current limit set in parameter 4-18 Current Limit. See ramp-up time in
parameter 3-41 Ramp 1 Ramp Up Time.
Par . 3 42 = 
t
dec
s xns Hzref Hz
3-50 Ramp 2 Type
Option: Function:
Select the ramp type, depending on requirements for acceleration/ deceleration. A linear ramp gives constant acceleration during ramping. A sine-2 ramp gives non­linear acceleration.
[0] * Linear [1] Sine Ramp [2] Sine 2 Ramp S-ramp based on the values set in
parameter 3-51 Ramp 2 Ramp Up Time and parameter 3-52 Ramp 2 Ramp Down Time.
3-51 Ramp 2 Ramp Up Time
Range: Function:
Size related*
[0.01 - 3600s]Enter the ramp-up time, which is
the acceleration time from 0 Hz to the rated motor speed ns. Select a ramp-up time such that the output current does not exceed the current limit in parameter 4-18 Current Limit during ramping. See ramp-down time in parameter 3-52 Ramp 2 Ramp Down Time.
Par . 3 51 = 
t
acc
s xns Hzref Hz
3-52 Ramp 2 Ramp Down Time
Range: Function:
Size related*
[0.01 - 3600s]Enter the ramp-down time, that is
the deceleration time from the rated motor speed ns to 0 Hz or
Parameter Descriptions
VLT® Midi Drive FC 280
44
54 Danfoss A/S © 02/2019 All rights reserved. MG07C402
3-52 Ramp 2 Ramp Down Time
Range: Function:
from the nominal torque to 0 NM if the torque conguration modes are selected. Select a ramp-down time such that no overvoltage arises in the frequency converter due to regenerative operation of the motor, and such that the generated current does not exceed the current limit set in parameter 4-18 Current
Limit. See ramp-up time in
parameter 3-51 Ramp 2 Ramp Up Time.
Par . 3 52 = 
t
dec
s xns Hzref Hz
3-60 Ramp 3 Type
Option: Function:
Select the ramp type, depending on requirements for acceleration/ deceleration. A linear ramp gives constant acceleration during ramping. An S-ramp gives non­linear acceleration.
[0] * Linear [1] Sine Ramp [2] Sine 2 Ramp S-ramp based on the values set in
parameter 3-61 Ramp 3 Ramp up Time and parameter 3-62 Ramp 3 Ramp down Time.
3-61 Ramp 3 Ramp up Time
Range: Function:
Size related*
[0.01 - 3600s]Enter the ramp-up time, which is
the acceleration time from 0 Hz to the rated motor speed ns. Select a ramp-up time such that the output current does not exceed the current limit in parameter 4-18 Current Limit during ramping. See ramp-down time in parameter 3-62 Ramp 3 Ramp down Time.
3-62 Ramp 3 Ramp down Time
Range: Function:
Size related*
[0.01 - 3600s]Enter the ramp-down time, which is
the deceleration time from the rated motor speed ns to 0 Hz. Select a ramp-down time such that no overvoltage arises in the inverter due to regenerative operation of the motor, and such that the generated current does not exceed the current limit set in parameter 4-18 Current Limit. See
3-62 Ramp 3 Ramp down Time
Range: Function:
ramp-up time in
parameter 3-61 Ramp 3 Ramp up Time.
Par . 3 62 = 
t
dec
s xns Hzref Hz
3-70 Ramp 4 Type
Option: Function:
Select the ramp type, depending on requirements for acceleration/ deceleration. A linear ramp gives constant acceleration during ramping. An S-ramp gives non­linear acceleration.
[0] * Linear [1] Sine Ramp [2] Sine 2 Ramp S-ramp based on the values set in
parameter 3-71 Ramp 4 Ramp up Time and parameter 3-72 Ramp 4 Ramp Down Time.
3-71 Ramp 4 Ramp up Time
Range: Function:
Size related*
[0.01 - 3600s]Enter the ramp-up time, which is
the acceleration time from 0 Hz to the rated motor speed ns. Select a ramp-up time such that the output current does not exceed the current limit in parameter 4-18 Current Limit during ramping. See ramp-down time in parameter 3-72 Ramp 4 Ramp Down Time.
Par . 3 71 = 
t
acc
s xns Hzref Hz
3-72 Ramp 4 Ramp Down Time
Range: Function:
Size related*
[0.01 - 3600s]Enter the ramp-down time, which is
the deceleration time from the rated motor speed ns to 0 Hz. Select a ramp-down time such that no overvoltage arises in the inverter due to regenerative operation of the motor, and such that the generated current does not exceed the current limit set in parameter 4-18 Current Limit. See ramp-up time in
parameter 3-71 Ramp 4 Ramp up Time.
Par . 3 72 = 
t
dec
s xns Hzref Hz
Parameter Descriptions Programming Guide
4 4
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 55
3-80 Jog Ramp Time
Range: Function:
Size related*
[0.01 - 3600s]Enter the jog ramp time, which is
the acceleration/deceleration time between 0 Hz and the rated motor frequency ns. Ensure that the resulting output current required for the given jog ramp time does not exceed the current limit in parameter 4-18 Current Limit. The jog ramp time starts when activating a jog signal via the LCP, a selected digital output, or the serial communication port. When jog state is disabled, the normal ramping times are valid.
130BD375.11
Time
P 3-80
Hz
P 4-14 Hz High limit
Jog speed
P 3-19
P 3-80
Ramp up (acc)
Ramp down (dec)
t jog t jog
P 4-12 Hz Low limit
P 1-23 Motor frequency
3-81 Quick Stop Ramp Time
Range: Function:
Size related*
[0.01 - 3600s]Enter the quick-stop ramp-down
time, which is the deceleration time from the synchronous motor speed to 0 Hz. Ensure that no resulting overvoltage occurs in the inverter due to regenerative operation of the motor required to achieve the given ramp-down time. Also, ensure that the generated current required to achieve the given ramp-down time does not exceed the current limit (set in parameter 4-18 Current Limit). Activate quick stop with a signal on a selected digital input, or via the serial communication port.
130BD376.11
Time
Hz
P 4-14 Hz high limit
Reference
P 1-23 Motor frequency
low limit
P 4-12 Hz
P 3-81
Qramp
Qstop
3-90 Step Size
Range: Function:
0.10 %* [0.01 ­200 %]
Enter the increment size required for increase/decrease as a percentage of the synchronous motor speed, ns. If increase/ decrease is activated, the resulting reference is increased/decreased by the amount set in this parameter.
3-92 Power Restore
Option: Function:
[0] * O Reset the digital potentiometer
reference to 0% after power-up.
[1] On Restore the most recent digital
potentiometer reference at power­up.
3-93 Maximum Limit
Range: Function:
100 %* [-200 -
200 %]
Set the maximum permissible value for the resulting reference. This is recommended if the digital potenti­ometer is used for ne-tuning of the resulting reference.
3-94 Minimum Limit
Range: Function:
-100 % [-200 ­200 %]
Set the minimum permissible value for the resulting reference. This is recommended if the digital potenti­ometer is used for ne-tuning of the resulting reference.
Parameter Descriptions
VLT® Midi Drive FC 280
44
Illustration 4.10 Quick Stop Ramp Time
Illustration 4.9 Jog Ramp Time
t
s xns Hz
Par . 3 80 = 
Δ jogspeedpar . 3 19  Hz
jog
56 Danfoss A/S © 02/2019 All rights reserved. MG07C402
3-95 Ramp Delay
Range: Function:
1000 ms* [0 - 3600000
ms]
Enter the delay required from activation of the digital potenti­ometer function until the frequency converter starts to ramp the reference. With a delay of 0 ms, the reference starts to ramp as soon as increase/decrease is activated.
3-96 Maximum Limit Switch Reference
Range: Function:
25 %* [0 - 200 %] Enter the maximum limit switch
reference. If the crane reaches a limit switch (OFF), and if the speed exceeds the value in this parameter, then the speed is reduced automat­ically to the value in this parameter. If the limit switch is o, the speed cannot exceed the value in this parameter.
4-10 Motor Speed Direction
Option: Function:
[0] * Clockwise
NOTICE
The setting in
parameter 4-10 Motor Speed Direction has impact on parameter 1-73 Flying Start.
Only operation in clockwise direction is allowed.
[2] Both
directions
Operation in both clockwise and counterclockwise directions are allowed.
4-14 Motor Speed High Limit [Hz]
Range: Function:
65 Hz* [ 0.1 - 500
Hz]
NOTICE
Maximum output frequency cannot exceed 10% of the inverter switching frequency (parameter 14-01 Switching Frequency).
Enter the maximum limit for motor speed. The motor speed high limit can be set to correspond to the manufacturer’s recommended maximum of the motor shaft.
The motor speed high limit must exceed the value in
parameter 4-12 Motor Speed Low Limit [Hz], and must not exceed the value in parameter 4-19 Max Output Frequency.
4-16 Torque Limit Motor Mode
Range: Function:
Size related*
[ 0 - 1000 %] This function limits the torque on
the shaft to protect the mechanical installation.
4-17 Torque Limit Generator Mode
Range: Function:
100 %* [ 0 - 1000 %] This function limits the torque on
the shaft to protect the mechanical installation.
4-18 Current Limit
Range: Function:
Size related*
[ 0 - 1000 %] This is a true current limit function
that continues in the oversyn­chronous range. However, due to eld weakening, the motor torque at current limit drops accordingly when the voltage increase stops above the synchronized motor speed.
Parameter Descriptions Programming Guide
4 4
4.5 Parameters: 4-** Limits/Warnings
4-12 Motor Speed Low Limit [Hz]
Range: Function:
0 Hz* [ 0 -
400.0 Hz]
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 57
Enter the minimum limit for motor speed. The motor speed low limit can be set to correspond to the minimum output frequency of the motor shaft. The motor speed low limit must not exceed the setting in parameter 4-14 Motor Speed High Limit [Hz].
4-19 Max Output Frequency
Range: Function:
Size related*
[ 0 - 500 Hz]
NOTICE
This parameter cannot be adjusted while the motor is running.
NOTICE
Maximum output frequency cannot exceed 10% of the inverter switching frequency (parameter 14-01 Switching Frequency).
Provide a nal limit on the output frequency for improved safety in applications at risk of overspeeding. This limit is nal in all congu- rations (independent of the setting in parameter 1-00 Conguration Mode).
4-20 Torque Limit Factor Source
Select an analog input for scaling the settings in
parameter 4-16 Torque Limit Motor Mode and parameter 4-17 Torque Limit Generator Mode 0–100% (or inverse).
The signal levels corresponding to 0% and 100% are dened in the analog input scaling, for example parameter group 6-1*
Analog Input 1. This parameter is only active when parameter 1-00 Conguration Mode is set to [0] Open Loop or [1] Speed Closed Loop.
Option: Function:
[0] * No function [2] Analog in 53 [4] Analog in 53
inv
[6] Analog in 54 [8] Analog in 54
inv
[18] Bus Control
4-21 Speed Limit Factor Source
Select an analog input for scaling the settings in parameter 4-19 Max Output Frequency 0–100% (or inverse). The signal levels corresponding to 0% and 100% are dened in the analog input scaling, for example parameter group 6-1* Analog
Input 1. This parameter is only active when parameter 1-00 Conguration Mode is in torque mode.
Option: Function:
[0] * No function [2] Analog in 53 [4] Analog in 53
inv
[6] Analog in 54
4-21 Speed Limit Factor Source
Select an analog input for scaling the settings in parameter 4-19 Max Output Frequency 0–100% (or inverse). The signal levels corresponding to 0% and 100% are dened in the analog input scaling, for example parameter group 6-1* Analog
Input 1. This parameter is only active when parameter 1-00 Conguration Mode is in torque mode.
Option: Function:
[8] Analog in 54
inv
[18] Bus Control
4-22 Break Away Boost
Option: Function:
[0] * O [1] On The frequency converter provides
higher current than normal current levels to enhance breakaway-torque capacity.
4-30 Motor Feedback Loss Function
Option: Function:
This function is used to monitor consistency in the feedback signal, that is if the feedback signal is available. Select the action of the frequency converter if a feedback fault is detected. The selected action takes place when the feedback signal diers from the output speed by the value set in
parameter 4-31 Motor Feedback Speed Error for longer than the value set in parameter 4-32 Motor Feedback Loss Timeout.
[0] Disabled [1] Warning [2] * Trip [3] Jog [4] Freeze Output [5] Max Speed [6] Switch to
Open Loop
4-31 Motor Feedback Speed Error
Range: Function:
20 Hz* [0 - 50 Hz] Select the maximum allowed error
in speed (output speed versus feedback).
Parameter Descriptions
VLT® Midi Drive FC 280
44
58 Danfoss A/S © 02/2019 All rights reserved. MG07C402
Time
[sec]
Speed [rpm]
n
calc
n
actual
P 4-32
130BA221.10
P 4-31
4-32 Motor Feedback Loss Timeout
Range: Function:
0.05 s* [0 - 60 s] Set the timeout value allowing the
speed error set in
parameter 4-31 Motor Feedback Speed Error to be exceeded before
enabling the function selected in
parameter 4-30 Motor Feedback Loss Function.
4-40 Warning Freq. Low
Range: Function:
Size related*
[ 0 - 500 Hz] Use this parameter for setting a
lower limit for the frequency range. When the motor speed drops below this limit, the display reads
Speed low. Warning bit 10 is set in parameter 16-94 Ext. Status Word.
Output relay can be congured to indicate this warning. LCP warning light is not lit when the limit set is reached.
The value must not exceed the setting in parameter 4-41 Warning Freq. High.
4-41 Warning Freq. High
Range: Function:
Size related*
[ 0 - 500 Hz] Use this parameter for setting a
higher limit for the frequency range. When the motor speed exceeds this limit, the display reads
Speed high. Warning bit 9 is set in parameter 16-94 Ext. Status Word.
Output relay can be congured to indicate this warning. LCP warning
4-41 Warning Freq. High
Range: Function:
light is not lit when the limit set is reached.
The value must exceed the value in parameter 4-40 Warning Freq. Low, and must not exceed the value in
parameter 4-14 Motor Speed High Limit [Hz].
4-42 Adjustable Temperature Warning
Range: Function:
0* [ 0 - 200 ] Use this parameter to set the motor
temperature limit.
4-50 Warning Current Low
Range: Function:
0 A* [ 0 - 500 A] Enter the I
LOW
value. When the motor current drops below this limit, a bit in the status word is set. This value can also be programmed to produce a signal on the digital output or the relay output.
4-51 Warning Current High
Range: Function:
Size related*
[ 0.0 - 500.00A]Enter the I
HIGH
value. When the motor current exceeds this limit, a bit in the status word is set. This value can also be programmed to produce a signal on the digital output or the relay output.
4-54 Warning Reference Low
Range: Function:
-4999* [-4999 ­4999 ]
Enter the low reference limit. When the actual reference drops below this limit, the display shows Ref
LOW
. Bit 20 is set in parameter 16-94 Ext. Status Word. The output relay or the digital output can be congured to indicate this warning. The LCP warning light is not turned on when this parameter set limit is reached.
4-55 Warning Reference High
Range: Function:
4999* [-4999 -
4999 ]
Use this parameter to set a high limit for the reference range. When the actual reference exceeds this limit, the display shows Ref
HIGH
. Bit 19 is set in parameter 16-94 Ext. Status Word. The output relay or the digital output can be congured to
Parameter Descriptions Programming Guide
Illustration 4.11 Motor Feedback Speed Error
4 4
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 59
4-55 Warning Reference High
Range: Function:
indicate this warning. The LCP warning light is not turned on when this parameter set limit is reached.
4-56 Warning Feedback Low
Range: Function:
-4999 ProcessCtrl Unit*
[-4999 - 4999 ProcessCtrlUnit ]
Use this parameter to set a low limit for the feedback range. When the feedback drops below this limit, the display shows Feedb Low. Bit 6 is set in parameter 16-94 Ext. Status Word. The output relay or the digital output can be congured to indicate this warning. The LCP warning light is not turned on when this parameter set limit is reached.
4-57 Warning Feedback High
Range: Function:
4999 ProcessCtrl Unit*
[-4999 - 4999 ProcessCtrlUnit ]
Use this parameter to set a high limit for the feedback range. When the feedback exceeds this limit, the display reads Feedb High. Bit 5 is set in parameter 16-94 Ext. Status Word. The output relay or the digital output can be congured to indicate this warning. The LCP warning light is not turned on when this parameter set limit is reached.
4-58 Missing Motor Phase Function
Option: Function:
[0] O No alarm is shown if a missing
motor phase occurs.
[1] * On An alarm is shown if a missing
motor phase occurs.
4-61 Bypass Speed From [Hz]
Range: Function:
0 Hz* [ 0 - 500 Hz] Some systems call for avoiding
certain output speeds due to resonance problems in the system. Enter the lower limits of the speeds to be avoided.
The bypass speed from must not exceed the setting in
parameter 4-14 Motor Speed High Limit [Hz].
4-63 Bypass Speed To [Hz]
Range: Function:
0 Hz* [ 0 - 500 Hz] Some systems call for avoiding
certain output speeds due to resonance problems in the system. Enter the upper limits of the speeds to be avoided.
The bypass speed to must not exceed the setting in
parameter 4-14 Motor Speed High Limit [Hz].
5-00 Digital Input Mode
Option: Function:
Set NPN or PNP mode for digital inputs.
NOTICE
This parameter cannot be adjusted while the motor is running.
[0] * PNP Action on positive directional pulses
(0). PNP systems are pulled down to ground (GND).
[1] NPN Action on negative directional
pulses (1). NPN systems are pulled up to +24 V, internally in the frequency converter.
5-01 Terminal 27 Mode
Option: Function:
[0] * Input Denes terminal 27 as a digital
input.
[1] Output Denes terminal 27 as a digital
output.
Parameter Descriptions
VLT® Midi Drive FC 280
44
4.6 Parameters: 5-** Digital In/Out
60 Danfoss A/S © 02/2019 All rights reserved. MG07C402
The digital inputs are used for selecting various functions in the frequency converter.
5-10 to 5-15 Digital Inputs
[0] No
operation
[1] Reset Resets frequency converter after a trip/alarm.
[2] Coast
inverse
[3] Coast and
reset inverse
No reaction to signals transmitted to the terminal.
Not all alarms can be reset. Coasting stop, inverted input (NC). The frequency converter leaves the motor in free mode. Logic 0coasting stop. Reset and coasting stop inverted input (NC). Leaves motor in free mode and resets frequency converter. Logic 0coasting stop.
Parameter Descriptions Programming Guide
Logic 1 to Logic 0reset.
[4] Quick stop
inverse
[5] DC-brake
inverse
[6] Stop
inverse
Inverted input (NC). Generates a stop in accordance with the quick stop ramp time set in parameter 3-81 Quick Stop Ramp Time. When the motor stops, the shaft is in free mode. Logic 0Quick-stop. Inverted input for DC braking (NC). Stops the motor by energizing it with a DC current for a certain time period. See parameter 2-01 DC
Brake Current to parameter 2-04 DC Brake Cut In Speed [Hz]. The function is only active when the value in parameter 2-02 DC Braking Time is
dierent from 0. Logic 0DC braking.
NOTICE
When the frequency converter is at the torque limit and has received a stop command, it may not stop by itself. To ensure that the frequency converter stops, congure a digital output to [27] Torque limit and stop and connect this digital output to a digital input that is congured as coast.
Stop inverted function. Generates a stop function when the selected terminal goes from logic 1 to logic 0. The stop is performed according to the selected ramp time (parameter 3-42 Ramp 1 Ramp Down Time,
parameter 3-52 Ramp 2 Ramp Down Time, parameter 3-62 Ramp 3 Ramp down Time, parameter 3-72 Ramp 4 Ramp Down Time).
[8] Start Select start for a start/stop command. Logic
1=start, logic 0=stop.
[9] Latched
start
[10] Reversing Change the direction of motor shaft rotation.
[11] Start
reversing
[12] Enable
start forward
[13] Enable
start reverse
[14] Jog Use to activate jog speed. See
[15] Preset
reference on
The motor starts when a pulse is applied for minimum 4 ms. The motor stops when stop commands are given.
Select logic 1 to reverse. The reversing signal only changes the direction of rotation. It does not activate the start function. Select both directions in parameter 4-10 Motor Speed Direction. The function is not active in process closed loop. Used for start/stop and for reversing on the same wire. Signals on start are not allowed at the same time. Disengage the counterclockwise movement and allows for the clockwise direction.
Disengage the clockwise movement and allows for the counterclockwise direction.
parameter 3-11 Jog Speed [Hz]. Shift between external reference and preset reference. It is assumed that [1] External/preset has been selected in parameter 3-04 Reference
Function. Logic 0 = external reference active; logic 1=1 of the 8 preset references is active.
[16] Preset ref
bit 0
[17] Preset ref
bit 1
[18] Preset ref
bit 2
Preset ref. bit 2 1 0
Preset ref. 0 0 0 0 Preset ref. 1 0 0 1 Preset ref. 2 0 1 0 Preset ref. 3 0 1 1 Preset ref. 4 1 0 0 Preset ref. 5 1 0 1 Preset ref. 6 1 1 0 Preset ref. 7 1 1 1
Table 4.2 Preset Ref. Bit
[19] Freeze
ref
[20] Freeze
output
Preset reference bits 0, 1, and 2 enable the selection of 1 of the 8 preset references according to Table 4.2. Same as [16] Preset ref bit 0.
Same as [16] Preset ref bit 0.
Freeze the actual reference, which is now the point of enable/condition for [21] Speed up and [22]
Speed down to be used. If [21] Speed up or [22] Speed down is used, the speed change always follows ramp 2 (parameter 3-51 Ramp 2 Ramp Up Time and parameter 3-52 Ramp 2 Ramp Down Time) in the range 0–parameter 3-03 Maximum Reference.
NOTICE
When [20] Freeze output is active, the frequency converter cannot be stopped by setting the signal on [8] Start to low. Stop the frequency converter via a terminal programmed for [2] Coasting inverse or [3] Coast and reset, inverse.
Freeze the actual motor frequency (Hz), which is now the point of enable/condition for [21] Speed
up and [22] Speed down to be used. If [21] Speed up or [22] Speed down is used, the speed change always follows ramp 2 (parameter 3-51 Ramp 2 Ramp Up Time and parameter 3-52 Ramp 2 Ramp Down Time) in the range 0–parameter 1-23 Motor Frequency.
[21] SpeedupSelect [21] Speed up and [22] Speed down if digital
control of the up/down speed is needed (motor potentiometer). Activate this function by selecting either [19] Freeze reference or [20] Freeze output. When speed up/down is activated for less than 400 ms, the resulting reference is increased/decreased by 0.1%. If speed up/down is activated for more than 400 ms, the resulting reference follows the setting in ramping up/down parameter 3-51/3-52.
4 4
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 61
Speed [rpm] Spee d [rpm]
Time[sec] Time[sec]a b
130BB462.10
Read Timer:
20 timer tides
Read Timer:
20 timer tides
Time Start
Time counter
Sample time
Timer
Pulse
130BB464.10
Parameter Descriptions
VLT® Midi Drive FC 280
Shut down Catch up
Unchanged speed 0 0 Reduced by %-value 1 0 Increased by %-value 0 1 Reduced by %-value 1 1
Table 4.3 Shut Down/Catch Up
[22] Speed
44
down
[23] Set-up
select bit 0
[24] Set-up
select bit
Same as [21] Speed up.
Select [23] Set-up select bit 0 or [1] Set-up select
bit 1 to select 1 of the 2 set-ups. Set parameter 0-10 Active Set-up to [9] Multi Set-up. Default digital input 32. Same as [23] Set-up select bit 0.
1
[26] Precise
stop inv.
Precise stop inverse function is available for terminals 18 or 19.
[27] Precise
start stop
[28] Catch up Increase reference value by percentage (relative)
set in parameter 3-12 Catch up/slow Down Value.
[29] Slow
down
[32] Pulse
input
Reduce reference value by percentage (relative) set in parameter 3-12 Catch up/slow Down Value. (Terminal 29 or 33 only) Measure the duration between pulse anks. This parameter has a higher resolution at lower frequencies, but is not as precise at higher frequencies. This principle has a cut o frequency, which makes it unsuited for encoders with low resolutions (for example 30 PPR) at low speeds.
Preset ramp bit 1 0
Ramp 1 0 0 Ramp 2 0 1 Ramp 3 1 0 Ramp 4 1 1
Table 4.4 Preset Ramp Bits
[40] Latched
precise start
A latched precise start only requires a pulse of 3 ms on terminals 18 or 19 when using
parameter 1-83 Precise Stop Function [1] Counter stop with reset or [2] Counter stop without reset. When the reference is reached,
the frequency converter internally enables the precise stop signal. This means that the frequency converter does the precise stop when the counter value of parameter 1-84 Precise Stop Counter Value is reached.
[41] Latch prec
stop inv
Send a latched stop signal when the precise stop function is activated in parameter 1-83 Precise Stop Function. The latched precise stop inverse function is available for terminals 18 or 19.
[45] Latched
start reverse
[51] External
interlock
The motor starts to run reverse when a pulse is applied for minimum 4 ms. The motor stops when stop commands are given. This function makes it possible to give an external fault to the frequency converter. This fault is treated as an internally generated alarm.
[55] DigiPot
increase
Increase signal to the digital potentiometer function described in parameter group 3-9* Digital Pot. Meter.
a: Low encoder resolution
b: Standard encoder resolution
[56] DigiPot
decrease
[57] DigiPot
clear
Decrease signal to the digital potentiometer function described in parameter group 3-9* Digital Pot. Meter. Clear the digital potentiometer reference described in parameter group 3-9* Digital Pot. Meter.
Illustration 4.12 Duration Between Pulse
Flanks
[34] Ramp bit0Enable a selection from the 4 ramps available,
according to Table 4.4.
[35] Ramp bit1Same as ramp bit 0.
[58] DigiPot
Hoist
[60] Counter A
(up)
[61] Counter A
(down)
[62] Reset
Counter A
[63] Counter B
(up)
[64] Counter B
(down)
[65] Reset
It’s used to increase the reference (on) or freeze the reference (o) in hoist mode. Input for increment counting in the SLC counter. Input for decrement counting in the SLC counter. Input for reset of counter A.
Input for increment counting in the SLC counter. Input for decrement counting in the SLC counter. Input for reset of counter B.
Counter B
[72] PID error
inverse
Invert the resulting error from the process PID controller. Available only if parameter 1-00 Conguration Mode is set to
62 Danfoss A/S © 02/2019 All rights reserved. MG07C402
5-19 Terminal 37/38 Safe Torque O
Use this parameter to set up the STO functionality. Warning makes the frequency converter coast and enables automatic restart. Alarm makes the frequency converter coast and requires a manual restart.
Option: Function:
[1] * Safe Torque
O Alarm
Coast the frequency converter when Safe Torque O is activated. Manual reset from LCP, digital input, or eldbus. This alarm can no longer be reset by automatic reset mode of parameter 14-20 Reset Mode in software 1.2 and further versions.
[3] Safe Torque
O Warning
Coast the frequency converter when Safe Torque O is activated (terminal 37 and terminal 38 o). When Safe Torque O circuit is reestablished, the frequency converter continues without manual reset.
Parameter Descriptions Programming Guide
[6] Surface Winder or [7] Extended PID Speed OL.
[73] PID reset I-
part
[74] PID enable This option enables the extended process PID
[150] Go To
Home
[151] Home Ref.
Switch
[155] HW Limit
Positive Inv
[156] HW Limit
Negative Inv
[157] Pos. Quick
Stop Inv
[160] Go To
Target Pos.
[162] Pos. Idx
Bit0
[163] Pos. Idx
Bit1
[164] Pos. Idx
Bit2
[171] Limit
switch cw inverse
[172] Limit
switch ccw inverse
5-10 Terminal 18 Digital Input
Option: Function:
[8] * Start Functions are described in parameter group 5-1*
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 63
Reset the I-part of the process PID controller. Equivalent to parameter 7-40 Process PID I-part
Reset. Available only when parameter 1-00 Conguration Mode is set to [6] Surface Winder or [7] Extended PID Speed OL.
controller. Equivalent to parameter 7-50 Process PID Extended PID. Available only if parameter 1-00 Conguration Mode is set to [7] Extended PID Speed OL. The frequency converter moves to the home position. Indicate the status of the home referenced switch. On means that the home position is reached, o means that the home position is not reached. The positive hardware position limit is exceeded. This option is active on the falling edge. The negative hardware position limit is exceeded. This option is active on the falling edge. Stop the frequency converter during positioning with the ramp time that is set in parameter 32-81 Motion Ctrl Quick Stop Ramp. This option is only eective when
parameter 37-00 Application Mode is set to [2] Position Control.
The frequency converter moves to the target position. This option is only eective when
parameter 37-00 Application Mode is set to [2] Position Control.
Position index bit 0. This option is only
eective when parameter 37-00 Application Mode is set to [2] Position Control.
Position index bit 1. This option is only
eective when parameter 37-00 Application Mode is set to [2] Position Control.
Position index bit 2. This option is only
eective when parameter 37-00 Application Mode is set to [2] Position Control.
Digital Inputs.
5-11 Terminal 19 Digital Input
Option: Function:
[10] * Reversing Functions are described in parameter group
5-1* Digital Inputs.
5-12 Terminal 27 Digital Input
Option: Function:
[2] * Coast inverse Functions are described in parameter group
5-1* Digital Inputs.
5-13 Terminal 29 Digital Input
Option: Function:
[14] * Jog Functions are described in parameter group
5-1* Digital Inputs.
[32] Pulse input
5-14 Terminal 32 Digital Input
Option: Function:
[0] * No operation Functions are described in parameter
group 5-1* Digital Inputs.
[82] Encoder input B
5-15 Terminal 33 Digital Input
Option: Function:
[0] * No operation Functions are described in parameter
group 5-1* Digital Inputs.
[32] Pulse input [81] Enocder input A
4 4
Parameter Descriptions
VLT® Midi Drive FC 280
4.6.1 5-3* Digital Outputs
[17] Above
frequency, high
The 2 solid-state digital outputs are common for terminal
27. Set the I/O function for terminal 27 in parameter 5-01 Terminal 27 Mode.
Terminal 42 can also be congured as digital outputs.
44
NOTICE
These parameters cannot be adjusted while the motor is running.
[18] Out of
feedback range
[19] Below feedback
low
[20] Above
feedback high
[21] Thermal
warning
5-30 Digital Outputs
[0] * No operation Default for all digital outputs. [1] Control ready The control card is ready. [2] Drive ready The frequency converter is ready for
operation and applies a supply signal on the control board.
[3] Drive ready /
remote control
[4] Stand-by / no
warning
[5] Running The motor is running and shaft torque is
[6] Running / no
warning
[7] Run in range /
no warning
[8] Run on
reference / no
warning [9] Alarm An alarm activates the output. [10] Alarm or
warning [11] At torque limit The torque limit set in
[12] Out of current
range [13] Below current,
low [14] Above current,
high [15] Out of
frequency
range [16] Below
frequency, low
The frequency converter is ready for operation and is in auto-on mode. Ready for operation. No start or stop command is given (start/disable). No warnings are active.
present. The motor is running and there are no warnings. The motor is running within the programmed current and speed ranges set in parameter 4-50 Warning Current Low to parameter 4-51 Warning Current High. There are no warnings. The motor runs at reference speed. No warnings.
An alarm or a warning activates the output.
parameter 4-16 Torque Limit Motor Mode or parameter 4-17 Torque Limit Generator Mode has been exceeded.
The motor current is outside the range set in parameter 4-18 Current Limit. The motor current is lower than set in parameter 4-50 Warning Current Low. The motor current is higher than set in parameter 4-51 Warning Current High. Output frequency is outside the frequency range.
The output speed is lower than the setting in parameter 4-40 Warning Freq. Low.
[22] Ready, no
thermal warning
[23] Remote, ready,
no thermal warning
[24] Ready, no
overvoltage/ undervoltage
[25] Reverse The motor runs (or is ready to run)
[26] Bus OK Active communication (no timeout) via
[27] Torque limit
and stop
[28] Brake, no brake
warning
[29] Brake ready, no
fault
[30] Brake fault
(IGBT)
[31] Relay 123 The relay is activated when [0] Control
[32] Mechanical
brake control
[36] Control word
bit 11
[37] Control word
bit 12
The output speed is higher than the setting in parameter 4-41 Warning Freq. High. The feedback is outside the range set in
parameter 4-56 Warning Feedback Low and parameter 4-57 Warning Feedback High.
The feedback is below the limit set in parameter 4-56 Warning Feedback Low. The feedback is above the limit set in parameter 4-57 Warning Feedback High. The thermal warning turns on when the temperature exceeds the limit in the motor, the frequency converter, the brake resistor, or the thermistor. The frequency converter is ready for operation, and there is no overtem­perature warning. The frequency converter is ready for operation and is in auto-on mode. There is no overtemperature warning. The frequency converter is ready for operation and the mains voltage is within the specied voltage range (see chapter General Specications in the design guide).
clockwise when logic=0 and counter­clockwise when logic=1. The output changes when the reversing signal is applied.
the serial communication port. Use in performing a coast stop and in torque limit condition. If the frequency converter has received a stop signal and is at the torque limit, the signal is logic 0. The brake is active and there are no warnings. The brake is ready for operation and there are no faults. The output is logic 1 when the brake IGBT is short-circuited. Use this function to protect the frequency converter if there is a fault on the brake modules. Use the output/relay to cut out the mains voltage from the frequency converter.
Word is selected in parameter group 8-** Communications and Options.
Enable control of an external mechanical brake. See parameter group 2-2* Mechanical Brake for more details.
64 Danfoss A/S © 02/2019 All rights reserved. MG07C402
Parameter Descriptions Programming Guide
[40] Out of ref
range
[41] Below
reference low
[42] Above
reference high
[43] Extended PID
Limit [45] Bus Ctrl Control output via eldbus. The state of
[46] Bus control,
timeout: On
[47] Bus Ctrl O at
timeout [55] Pulse output [56] Heat sink
cleaning
warning, high [60] Comparator 0 See parameter group 13-1* Comparators. If
[61] Comparator 1 See parameter group 13-1* Comparators. If
[62] Comparator 2 See parameter group 13-1* Comparators. If
[63] Comparator 3 See parameter group 13-1* Comparators. If
[64] Comparator 4 See parameter group 13-1* Comparators. If
[65] Comparator 5 See parameter group 13-1* Comparators. If
[70] Logic Rule 0 See parameter group 13-4* Logic Rules. If
[71] Logic Rule 1 See parameter group 13-4* Logic Rules. If
[72] Logic Rule 2 See parameter group 13-4* Logic Rules. If
[73] Logic Rule 3 See parameter group 13-4* Logic Rules. If
This option is active when the actual speed is outside the settings in
parameter 4-54 Warning Reference Low to parameter 4-55 Warning Reference High.
This option is active when the actual speed is below the speed reference setting. This option is active when the actual speed is above the speed reference setting.
the output is set in parameter 5-90 Digital & Relay Bus Control. The output state is retained in the event of eldbus timeout. Control output via eldbus. The state of the output is set in parameter 5-90 Digital & Relay Bus Control. When bus timeout occurs, the output state is set high (On).
comparator 0 is evaluated as true, the output goes high. Otherwise, it is low.
comparator 1 is evaluated as true, the output goes high. Otherwise, it is low.
comparator 2 is evaluated as true, the output goes high. Otherwise, it is low.
comparator 3 is evaluated as true, the output goes high. Otherwise, it is low.
comparator 4 is evaluated as true, the output goes high. Otherwise, it is low.
comparator 5 is evaluated as true, the output goes high. Otherwise, it is low.
logic rule 0 is evaluated as true, the output goes high. Otherwise, it is low.
logic rule 1 is evaluated as true, the output goes high. Otherwise, it is low.
logic rule 2 is evaluated as true, the output goes high. Otherwise, it is low.
logic rule 3 is evaluated as true, the output goes high. Otherwise, it is low.
[74] Logic Rule 4 See parameter group 13-4* Logic Rules. If
logic rule 4 is evaluated as true, the output goes high. Otherwise, it is low.
[75] Logic Rule 5 See parameter group 13-4* Logic Rules. If
logic rule 5 is evaluated as true, the output goes high. Otherwise, it is low.
[80] SL Digital
Output A
[81] SL Digital
Output B
[82] SL Digital
Output C
[83] SL Digital
Output D
[91] Encoder
emulate output A
[160] No alarm The output is high when no alarm is
[161] Running
reverse
[165] Local ref active [166] Remote ref
active
[167] Start command
active
[168] Drive in hand
mode
[169] Drive in auto
mode
[170] Homing
Completed
[171] Target Position
Reached
See parameter 13-52 SL Controller Action. The output goes high whenever the smart logic action [38] Set dig. out. A high is executed. The output goes low whenever the smart logic action [32] Set dig. out. A low is executed. See parameter 13-52 SL Controller Action. The input goes high whenever the smart logic action [39] Set dig. out. B high is executed. The input goes low whenever the smart logic action [33] Set dig. out. B low is executed. See parameter 13-52 SL Controller Action. The input goes high whenever the smart logic action [40] Set dig. out. C high is executed. The input goes low whenever the smart logic action [34] Set dig. out. C low is executed. See parameter 13-52 SL Controller Action. The input goes high whenever the smart logic action [41] Set dig. out. D high is executed. The input goes low whenever the smart logic action [35] Set dig. out. D low is executed.
present. The output is high when the frequency converter is running counterclockwise (the logical product of the status bits Running AND Reverse).
The output is high when there is an active start command, and no stop command is active. The output is high when the frequency converter is in hand-on mode. The output is high when the frequency converter is in auto-on mode. The homing operation is completed. This option is only eective when
parameter 37-00 Application Mode is set to [2] Position Control.
The target position is reached. This option is only eective when
parameter 37-00 Application Mode is set to [2] Position Control.
4 4
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 65
5-34 On Delay, Digital Output
Range: Function:
0.01 s* [0 - 600 s]
5-35 O Delay, Digital Output
Range: Function:
0.01 s* [0 - 600 s]
Parameter Descriptions
VLT® Midi Drive FC 280
[172] Position
Control Fault
[173] Position Mech
Brake
44
[190] STO function
active [193] Sleep mode The frequency converter/system has
[194] Broken Belt
Function
[239] STO function
fault
4.6.2 5-4* Relay
Parameters for conguring the timing and the output functions for the relay.
The parameter shows 1 relay.
5-40 Function Relay
Option: Function:
[0] No operation Default setting for all digital outputs. [1] * Control Ready The control card is ready. [2] Drive ready The frequency converter is ready to
[3] Drive rdy/rem
ctrl [4] Stand-by / no
warning
[5] Running The motor runs, and a shaft torque is
[6] Running / no
warning [7] Run in
range/no
warn
A fault occurred in the positioning process. Refer to parameter 37-18 Pos. Ctrl Fault Reason for details about the fault. This option is only eective when
parameter 37-00 Application Mode is set to [2] Position Control.
Select mechanical control for positioning. This option is only eective when
parameter 37-00 Application Mode is set to [2] Position Control.
entered sleep mode. See parameter group 22-4* Sleep Mode.
A broken-belt condition has been detected. See parameter group 22-4* Sleep Mode.
operate. Mains and control supplies are OK. The frequency converter is ready for operation and is in auto-on mode. Ready for operation. No start or stop commands have been applied. No warnings are active.
present. The motor is running and no warnings are present. The motor runs within the programmed current ranges set in parameter 4-50 Warning Current Low.
5-40 Function Relay
Option: Function:
[8] Run on ref/no
warn [9] Alarm An alarm activates the output. [10] Alarm or
warning [11] At torque
limit
[12] Out of
current range [13] Below
current, low [14] Above
current, high [15] Out of
frequency
range
[16] Below
frequency,
low [17] Above
frequency,
high [18] Out of feedb.
range
[19] Below
feedback, low [20] Above
feedback,
high [21] Thermal
warning
[22] Ready, no
thermal
warning [23] Remote,
ready, no TW
[24] Ready, no
over-/ under
voltage [25] Reverse The motor runs (or is ready to run)
[26] Bus OK Active communication (no timeout) via the
The motor runs at reference speed. No warnings.
An alarm or warning activates the output.
The torque limit set in
parameter 4-16 Torque Limit Motor Mode or
parameter 4-17 Torque Limit Generator Mode
has been exceeded. The motor current is outside the range set in parameter 4-18 Current Limit. The motor current is lower than set in parameter 4-50 Warning Current Low. The motor current is higher than set in parameter 4-51 Warning Current High. The output speed/frequency exceeds the limit that is set in parameter 4-40 Warning
Freq. Low and parameter 4-41 Warning Freq. High.
The output frequency is lower than the setting in parameter 4-40 Warning Freq. Low. The frequency is higher than the setting in parameter 4-41 Warning Freq. High.
The feedback is outside the range set in
parameter 4-56 Warning Feedback Low and parameter 4-57 Warning Feedback High.
The feedback is below the limit set in parameter 4-56 Warning Feedback Low. The feedback is above the limit set in parameter 4-57 Warning Feedback High.
Thermal warning turns on when the temperature exceeds the limit within the motor, frequency converter, brake resistor, or connected resistor. The frequency converter is ready for operation, and there is no overtemperature warning. The frequency converter is ready for operation and is in auto-on mode. There is no overtemperature warning. The frequency converter is ready for operation, and the mains voltage is within the specied voltage range.
clockwise when logic=0 and counter­clockwise when logic=1. The output changes when the reversing signal is applied.
serial communication port.
66 Danfoss A/S © 02/2019 All rights reserved. MG07C402
Parameter Descriptions Programming Guide
5-40 Function Relay
Option: Function:
[27] Torque limit &
stop
[28] Brake, no
brake warning
[29] Brake ready,
no fault
[30] Brake fault
(IGBT)
[31] Relay 123 Digital output/relay is activated when [0]
[32] Mech brake
ctrl
[36] Control word
bit 11
[37] Control word
bit 12
[40] Out of ref
range
[41] Below
reference, low
[42] Above ref,
high
[45] Bus ctrl. Control the digital output/relay via bus.
Use for performing a coasted stop for frequency converter in torque limit condition. If the frequency converter has received a stop signal and is in torque limit, the signal is logic=0. The brake is active, and there are no warnings.
The brake is ready for operation, and there are no faults. The output is logic=1 when the brake IGBT is short-circuited. Use this function to protect the frequency converter if there is a fault on the brake module. Use the digital output/relay to cut out the mains voltage from the frequency converter.
Control word is selected in parameter group 8-** Comm. and Options.
Selection of mechanical brake control. When the parameters selected in parameter group 2-2* Mechanical Brake are active, reinforce the output to carry the current for the coil in the brake. This issue is solved by connecting an external relay to the selected digital output. Activate relay 1 by a control word from the eldbus. No other functional impact on the frequency converter. Typical application: Controlling an auxiliary device from a eldbus. The function is valid when [0] FC
Prole is selected in parameter 8-10 Control Word Prole.
Activate relay 2 by a control word from the eldbus. No other functional impact on the frequency converter. Typical application: Controlling an auxiliary device from a eldbus. The function is valid when [0] FC
Prole is selected in parameter 8-10 Control Word Prole.
Active when the actual speed is outside the settings in parameter 4-54 Warning
Reference Low and parameter 4-55 Warning Reference High.
Active when the actual speed is below the speed reference setting. Active when the actual speed is above the speed reference setting.
The state of the output is set in parameter 5-90 Digital & Relay Bus Control. The output state is retained in the event of a bus timeout.
5-40 Function Relay
Option: Function:
[46] Bus control,
timeout: On
[47] Bus control,
timeout: O
[56] Heat sink
cleaning
warning, high [60] Comparator 0 See parameter group 13-1* Smart Logic
[61] Comparator 1 See parameter group 13-1* Smart Logic
[62] Comparator 2 See parameter group 13-1* Smart Logic
[63] Comparator 3 See parameter group 13-1* Smart Logic
[64] Comparator 4 See parameter group 13-1* Smart Logic
[65] Comparator 5 See parameter group 13-1* Smart Logic
[70] Logic rule 0 See parameter group 13-4* Logic Rules. If
[71] Logic rule 1 See parameter group 13-4* Logic Rules. If
[72] Logic rule 2 See parameter group 13-4* Logic Rules. If
[73] Logic rule 3 See parameter group 13-4* Logic Rules. If
[74] Logic rule 4 See parameter group 13-4* Logic Rules. If
[75] Logic rule 5 See parameter group 13-4* Logic Rules. If
[80] SL digital
output A
[81] SL digital
output B
Control output via bus. The state of the output is set in parameter 5-90 Digital & Relay Bus Control. When a bus timeout occurs, the output state is set high (on). Control output via bus. The state of the output is set in parameter 5-90 Digital & Relay Bus Control. When a bus timeout occurs, the output state is set low (o).
Control. If comparator 0 in SLC is true, the output goes high. Otherwise, it goes low.
Control. If comparator 1 in SLC is true, the output goes high. Otherwise, it goes low.
Control. If comparator 2 in SLC is true, the output goes high. Otherwise, it goes low.
Control. If comparator 3 in SLC is true, the output goes high. Otherwise, it goes low.
Control. If comparator 4 in SLC is true, the output goes high. Otherwise, it goes low.
Control. If comparator 5 in SLC is true, the output goes high. Otherwise, it goes low.
logic rule 0 in SLC is true, the output goes high. Otherwise, it goes low.
logic rule 1 in SLC is true, the output goes high. Otherwise, it goes low.
logic rule 2 in SLC is true, the output goes high. Otherwise, it goes low.
logic rule 3 in SLC is true, the output goes high. Otherwise, it goes low.
logic rule 4 in SLC is true, the output goes high. Otherwise, it goes low.
logic rule 5 in SLC is true, the output goes high. Otherwise, it goes low. See parameter 13-52 SL Controller Action. Output A is low on [32] Smart Logic Action. Output A is high on [38] Smart Logic Action. See parameter 13-52 SL Controller Action. Output B is low on [32] Smart Logic Action.
4 4
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 67
5-41 On Delay, Relay
Range: Function:
0.01 s* [0 - 600 s] Enter the delay of the relay cut-in time. The relay only cuts in if the condition in parameter 5-40 Function Relay is uninterrupted during the specied time.
Selected Event
Relay output
Selected Event
Relay output
On Delay
P 5-41
On Delay
P 5-41
O Delay
P 5-42
130BA171.10
5-42 O Delay, Relay
Range: Function:
0.01 s* [0 - 600 s] Enter the delay of the relay cutout time.
Selected Event
Relay output
On Delay P 5-41
O Delay P 5-42
130BA172.10
Parameter Descriptions
VLT® Midi Drive FC 280
5-40 Function Relay
Option: Function:
Output B is high on [38] Smart Logic Action.
[82] SL digital
output C
44
[83] SL digital
output D
[160] No alarm The output is high when no alarm is
[161] Running
reverse
[165] Local ref
active
[166] Remote ref
active
[167] Start
command activ
[168] Drive in hand
mode
[169] Drive in auto
mode
[170] Homing
Completed
[171] Target
Position Reached
[172] Position
Control Fault
[173] Position Mech
Brake
[190] STO function
active
[193] Sleep Mode The frequency converter/system has
[194] Broken Belt
Function
68 Danfoss A/S © 02/2019 All rights reserved. MG07C402
See parameter 13-52 SL Controller Action. Output C is low on [32] Smart Logic Action. Output C is high on [38] Smart Logic Action. See parameter 13-52 SL Controller Action. Output D is low on [32] Smart Logic Action. Output D is high on [38] Smart Logic Action.
present. The output is high when the frequency converter is running counterclockwise (the logical product of the status bits Running AND Reverse).
The output is high when there is an active start command, and no stop command is active. The output is high when the frequency converter is in hand-on mode. The output is high when the frequency converter is in auto-on mode. The homing operation is completed. This option is only eective when
parameter 37-00 Application Mode is set to [2] Position Control.
The target position is reached. This option is only eective when
parameter 37-00 Application Mode is set to [2] Position Control.
A fault occurred in the positioning process. Refer to parameter 37-18 Pos. Ctrl Fault Reason for details about the fault. This option is only eective when
parameter 37-00 Application Mode is set to [2] Position Control.
Select mechanical control for positioning. This option is only eective when
parameter 37-00 Application Mode is set to [2] Position Control.
entered sleep mode. See parameter group 22-4* Sleep Mode.
A broken-belt condition has been detected. See parameter group 22-4* Sleep Mode.
5-40 Function Relay
Option: Function:
[239] STO Function
Fault
Illustration 4.13 On Delay, Relay
Illustration 4.14 O Delay, Relay
If the selected event condition changes before the on- or o delay timer expires, the relay output is unaected.
130BD377.10
Ref.
Low freq. P 5-50/ P 5-55
Input (Hz)
High ref.
value P 5-53/ p 5-58
High freq. P 5-51/ P 5-56
Low ref.
value P 5-52/ p 5-57
5-50 Term. 29 Low Frequency
Range: Function:
4 Hz* [0 - 31999
Hz]
Enter the low frequency limit corresponding to the low motor shaft speed (that is low reference value) in parameter 5-52 Term. 29
Low Ref./Feedb. Value. Refer to Illustration 4.15.
5-51 Term. 29 High Frequency
Range: Function:
32000 Hz* [1 - 32000
Hz]
Enter the high frequency limit corresponding to the high motor shaft speed (which is high reference value) in parameter 5-53 Term. 29 High Ref./Feedb. Value.
5-52 Term. 29 Low Ref./Feedb. Value
Range: Function:
0* [-4999 -
4999 ]
Enter the low reference value limit for the motor shaft speed [Hz]. This value is also the lowest feedback value. See also parameter 5-57 Term. 33 Low Ref./Feedb. Value. Set terminal 29 to digital input (parameter 5-02 Terminal 29 Mode =
[0] Input and
parameter 5-13 Terminal 29 Digital Input = applicable value).
5-53 Term. 29 High Ref./Feedb. Value
Range: Function:
Size related*
[-4999 ­4999 ]
Enter the high reference value [Hz] for the motor shaft speed, and the high feedback value. See also
parameter 5-58 Term. 33 High Ref./ Feedb. Value. Select terminal 29 as a
digital input (parameter 5-02 Terminal 29 Mode =
[0] Input (default) and
parameter 5-13 Terminal 29 Digital Input = applicable value).
5-55 Term. 33 Low Frequency
Range: Function:
4 Hz* [0 - 31999
Hz]
Enter the low frequency corresponding to the low motor shaft speed (which is low reference value) in parameter 5-57 Term. 33 Low Ref./Feedb. Value.
5-56 Term. 33 High Frequency
Range: Function:
32000 Hz* [1 - 32000
Hz]
Enter the high frequency corresponding to the high motor shaft speed (that is high reference value) in parameter 5-58 Term. 33 High Ref./Feedb. Value.
5-57 Term. 33 Low Ref./Feedb. Value
Range: Function:
0* [-4999 -
4999 ]
Enter the low reference value [Hz] for the motor shaft speed. This value is also the low feedback value. See also parameter 5-52 Term. 29 Low Ref./Feedb. Value.
5-58 Term. 33 High Ref./Feedb. Value
Range: Function:
Size related*
[-4999 ­4999 ]
Enter the high reference value [Hz] for the motor shaft speed. See also
parameter 5-53 Term. 29 High Ref./ Feedb. Value.
5-60 Terminal 27 Pulse Output Variable
Select the desired output on terminal 27.
Option: Function:
[0] * No operation [45] Bus ctrl. [48] Bus ctrl.,
timeout
[100] Output
frequency
[101] Reference
Parameter Descriptions Programming Guide
4.6.3 5-5* Pulse Input
The pulse input parameters are used to dene an appropriate window for the impulse reference area by conguring the scaling and lter settings for the pulse inputs. Input terminals 29 or 33 act as frequency reference inputs. Set terminal 29 (parameter 5-13 Terminal 29 Digital
Input) or terminal 33 (parameter 5-15 Terminal 33 Digital Input) to [32] Pulse input. If terminal 29 is used as an input, then set parameter 5-02 Terminal 29 Mode to [0] Input.
4 4
Illustration 4.15 Pulse Input
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 69
5-60 Terminal 27 Pulse Output Variable
Select the desired output on terminal 27.
Option: Function:
[102] Process
Feedback [103] Motor Current [104] Torque rel to
limit [105] Torq relate to
rated [106] Power [107] Speed [109] Max Out Freq [113] PID Clamped
Output
5-62 Pulse Output Max Freq 27
Range: Function:
5000 Hz* [4 - 32000
Hz]
Set the maximum frequency for terminal 27, corresponding to the output variable selected in
parameter 5-60 Terminal 27 Pulse Output Variable.
5-70 Term 32/33 Pulses Per Revolution
Range: Function:
1024* [1 - 4096 ] Set the encoder pulses per
revolution on the motor shaft. Read the correct value from the encoder.
5-71 Term 32/33 Encoder Direction
Option: Function:
NOTICE
This parameter cannot be adjusted while the motor is running.
Change the detected encoder rotation direction without changing the wiring to the encoder.
[0] * Clockwise
Set channel A 90° (electrical degrees) behind channel B after clockwise rotation of the encoder shaft.
[1] Counter
clockwise
Set channel A 90° (electrical degrees) ahead of channel B after clockwise rotation of the encoder shaft.
5-90 Digital & Relay Bus Control
Range: Function:
0* [0 -
0xFFFFFFFF ]
This parameter holds the state of the bus-controlled digital outputs and relays.
5-90 Digital & Relay Bus Control
Range: Function:
A logical 1 indicates that the output is high or active. A logical 0 indicates that the output is low or inactive.
5-93 Pulse Out 27 Bus Control
Range: Function:
0 %* [0 - 100 %] Set the output frequency
transferred to the output terminal 27 when the terminal is congured as [45] Bus Controlled in
parameter 5-60 Terminal 27 Pulse Output Variable.
5-94 Pulse Out 27 Timeout Preset
Range: Function:
0 %* [0 - 100 %] Set the output frequency
transferred to the output terminal 27 when the terminal is congured as [48] Bus Ctrl Timeout in
parameter 5-60 Terminal 27 Pulse Output Variable and a timeout is
detected.
6-00 Live Zero Timeout Time
Range: Function:
10 s* [1 - 99 s] Enter the timeout time.
6-01 Live Zero Timeout Function
Option: Function:
Select the timeout function. The function set in parameter 6-01 Live Zero Timeout Function is activated if the input signal on terminal 53 or 54 is below 50% of the value in
parameter 6-10 Terminal 53 Low Voltage, parameter 6-20 Terminal 54 Low Voltage, or
parameter 6-22 Terminal 54 Low Current for a time period dened in
parameter 6-00 Live Zero Timeout Time.
Parameter Descriptions
44
VLT® Midi Drive FC 280
Bit 0 Digital Output Terminal 27 Bit 1–3 Reserved Bit 4 Relay 1 output terminal Bit 6–23 Reserved Bit 24 Terminal 42 digital output Bit 26–31 Reserved
Table 4.5 Bit Functions
70 Danfoss A/S © 02/2019 All rights reserved. MG07C402
4.7 Parameters: 6-** Analog In/Out
6-01 Live Zero Timeout Function
Option: Function:
[0] * O [1] Freeze output [2] Stop [3] Jogging [4] Max. speed [5] Stop and trip
Ref./Feedback
Analog input
High Ref./
Feedb. Value'
Low Ref./
Feedb. Value'
'Low Voltage'or
'Low Current'
'High Voltage'or
'High Current'
1 V 5 V 10 V
10
20
30
40
50
[V]
5
Par 6-xx
Par 6-xx
Par 6-xx
Par 6-xx
130BD378.11
6-10 Terminal 53 Low Voltage
Range: Function:
0.07 V* [0 - 10 V] Enter the voltage (V) that
corresponds to
parameter 6-14 Terminal 53 Low Ref./ Feedb. Value. To activate
parameter 6-01 Live Zero Timeout Function, set the value to >1 V.
6-11 Terminal 53 High Voltage
Range: Function:
10 V* [0 - 10 V] Enter the voltage (V) that
corresponds to the high reference value (set in
parameter 6-15 Terminal 53 High Ref./Feedb. Value).
6-14 Terminal 53 Low Ref./Feedb. Value
Range: Function:
0* [-4999 -
4999 ]
Enter the reference or feedback value that corresponds to the voltage or current set in
parameter 6-10 Terminal 53 Low Voltage.
6-15 Terminal 53 High Ref./Feedb. Value
Range: Function:
Size related*
[-4999 -
4999 ]
Enter the reference or feedback value that corresponds to the voltage or current set in
parameter 6-11 Terminal 53 High Voltage.
6-16 Terminal 53 Filter Time Constant
Range: Function:
0.01 s* [0.01 - 10 s] Enter the time constant. This
constant is a rst-order digital low­pass lter time constant for suppressing electrical noise in terminal 53. A high time constant value improves dampening, but also increases the time delay through the lter.
6-18 Terminal 53 Digital Input
Option: Function:
[0] * No operation [1] Reset [2] Coast inverse [3] Coast and
reset inverse [4] Quick stop
inverse [5] DC-brake
inverse [6] Stop inverse [8] Start [10] Reversing [11] Start reversing [12] Enable start
forward [13] Enable start
reverse [14] Jog [15] Preset
reference on [16] Preset ref bit 0 [17] Preset ref bit 1 [18] Preset ref bit 2 [19] Freeze
reference [20] Freeze output [21] Speed up [22] Speed down [23] Set-up select
bit 0 [24] Set-up select
bit 1 [28] Catch up [29] Slow down
Parameter Descriptions Programming Guide
4 4
Illustration 4.16 Timeout Function
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 71
6-18 Terminal 53 Digital Input
Option: Function:
[34] Ramp bit 0 [35] Ramp bit 1 [51] External
Interlock [55] DigiPot
increase [56] DigiPot
decrease [57] DigiPot clear [58] DigiPot Hoist [72] PID error
inverse [73] PID reset I
part [74] PID enable [150] Go To Home [151] Home Ref.
Switch [155] HW Limit
Positive Inv [156] HW Limit
Negative Inv [157] Pos. Quick
Stop Inv [160] Go To Target
Pos. [162] Pos. Idx Bit0 [163] Pos. Idx Bit1 [164] Pos. Idx Bit2 [171] Limit switch
cw inverse [172] Limit switch
ccw inverse
6-20 Terminal 54 Low Voltage
Range: Function:
0.07 V* [0 - 10 V] Enter the voltage (V) that
corresponds to the low reference value (set in
parameter 6-24 Terminal 54 Low Ref./ Feedb. Value). To activate
parameter 6-01 Live Zero Timeout Function, set the value to >1 V.
6-21 Terminal 54 High Voltage
Range: Function:
10 V* [0 - 10 V] Enter the voltage (V) that
corresponds to the high reference value (set in
parameter 6-25 Terminal 54 High Ref./Feedb. Value).
6-22 Terminal 54 Low Current
Range: Function:
4 mA* [0 - 20 mA] Enter the low current value. This
reference signal corresponds to the low reference/feedback value set in
parameter 6-24 Terminal 54 Low Ref./ Feedb. Value. To activate the live
zero timeout function in
parameter 6-01 Live Zero Timeout Function, set the value to >2 mA.
6-23 Terminal 54 High Current
Range: Function:
20 mA* [0 - 20 mA] Enter the high current value
corresponding to the high reference/feedback value set in
parameter 6-25 Terminal 54 High Ref./Feedb. Value.
6-24 Terminal 54 Low Ref./Feedb. Value
Range: Function:
0* [-4999 -
4999 ]
Enter the reference or feedback value that corresponds to the voltage or current set in
parameter 6-21 Terminal 54 High Voltage/parameter 6-22 Terminal 54 Low Current.
6-25 Terminal 54 High Ref./Feedb. Value
Range: Function:
Size related*
[-4999 -
4999 ]
Enter the reference or feedback value that corresponds to the voltage or current set in
parameter 6-21 Terminal 54 High Voltage/parameter 6-23 Terminal 54 High Current.
6-26 Terminal 54 Filter Time Constant
Range: Function:
0.01 s* [0.01 - 10 s] Enter the time constant, which is a
rst-order digital low-pass lter time constant for suppressing electrical noise in terminal 54. A high time constant value improves dampening, but also increases the time delay through the lter.
Parameter Descriptions
VLT® Midi Drive FC 280
44
6-19 Terminal 53 mode
Select the terminal 53 input mode.
Option: Function:
[1] * Voltage mode [6] Digital input
72 Danfoss A/S © 02/2019 All rights reserved. MG07C402
6-29 Terminal 54 mode
Option: Function:
Select if terminal 54 is used for current input or voltage input.
[0] Current mode [1] * Voltage mode
6-90 Terminal 42 Mode
Option: Function:
Set terminal 42 to act as analog output or as digital output. When digital output is set, terminal 42 outputs 0 mA as OFF or 20 mA as ON. External resistor (1 kΩ) should be connected between terminals 42 and 55.
[0] * 0-20 mA [1] 4-20 mA [2] Digital Output
6-91 Terminal 42 Analog Output
Option: Function:
[0] * No operation [100] Output
frequency [101] Reference [102] Process
Feedback [103] Motor Current [104] Torque rel to
limit [105] Torq relate to
rated [106] Power [107] Speed [111] Speed
Feedback [113] PID Clamped
Output [139] Bus Control [143] Ext. CL 1 [254] DC Link
Voltage
6-93 Terminal 42 Output Min Scale
Range: Function:
0 %* [0 - 200 %] Scale for the minimum output (0
mA or 4 mA) of the analog signal
6-93 Terminal 42 Output Min Scale
Range: Function:
at terminal 42. Set the value to be the percentage of the full range of the variable selected in
parameter 6-91 Terminal 42 Analog Output.
6-94 Terminal 42 Output Max Scale
Range: Function:
100 %* [0 - 200 %] Scale for maximum output (20 mA)
of the scaling at terminal 42. Set the value to be the percentage of the full range of the variable selected in parameter 6-91 Terminal 42 Analog Output.
(mA)
0%
20
0/4
100%
Current
Analog output Min Scale par. 6-93
Variable for output example: Power
Analog
Output
Max Scale
par. 6-94
130BB772.10
Illustration 4.17 Output Scale
versus Current
6-96 Terminal 42 Output Bus Control
Range: Function:
0* [0 - 16384 ] Hold the analog output at terminal
42 if controlled by bus. This parameter is N2 format.
7-00 Speed PID Feedback Source
Option: Function:
NOTICE
This parameter cannot be changed while the motor is running.
Select feedback source for speed CL control.
[1] 24V encoder [6] Analog Input
53 [7] Analog Input
54
Parameter Descriptions Programming Guide
4 4
6-92 Terminal 42 Digital Output
Option: Function:
[0] * No operation [198] Drive Bypass
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 73
See chapter 4.6.1 5-3* Digital Outputs for each option and description.
4.8 Parameters: 7-** Controllers
7-00 Speed PID Feedback Source
Option: Function:
[8] Frequency
input 29 [9] Frequency
input 33 [20] * None
7-02 Speed PID Proportional Gain
Range: Function:
0.015* [0 - 1 ] Enter the speed controller propor-
tional gain. The proportional gain amplies the error (that is the deviation between the feedback signal and the setpoint). This parameter is used with
parameter 1-00 Conguration Mode [1] Speed closed loop control. Quick
control is obtained at high ampli­cation. However, if the amplication
is too high, the process may become unstable.
7-03 Speed PID Integral Time
Range: Function:
8 ms* [2 - 20000
ms]
Enter the speed controller integral time, which determines the time the internal PID control takes to correct errors. The greater the error, the more quickly the gain increases. The integral time causes a delay of the signal, and therefore a dampening eect, and can be used to eliminate steady-state speed error. Obtain quick control through a short integral time, though if the integral time is too short, the process becomes unstable. An excessively long integral time disables the integral action, leading to major deviations from the required reference, since the process regulator takes too long to regulate errors. This parameter is used with [1] Speed closed loop control set in parameter 1-00 Cong- uration Mode.
7-04 Speed PID Dierentiation Time
Range: Function:
30 ms* [0 - 200 ms] Enter the speed controller dieren-
tiation time. The dierentiator does
not react to constant error. It provides gain proportional to the rate of change of the speed feedback. The quicker the error
7-04 Speed PID Dierentiation Time
Range: Function:
changes, the stronger the gain from the dierentiator. The gain is proportional with the speed at which errors change. Setting this parameter to 0 disables the dier- entiator. This parameter is used with parameter 1-00 Conguration Mode [1] Speed closed loop control.
7-05 Speed PID Di. Gain Limit
Range: Function:
5* [1 - 20 ] Set a limit for the gain provided by
the dierentiator. Since the dier- ential gain increases at higher frequencies, limiting the gain may be useful. For example, set up a pure D-link at low frequencies and a constant D-link at higher frequencies. This parameter is used with parameter 1-00 Conguration Mode [1] Speed closed loop control.
7-06 Speed PID Lowpass Filter Time
Range: Function:
10 ms* [1 - 6000 ms]
NOTICE
Severe ltering can be detrimental to dynamic performance.
Set a time constant for the speed control low-pass lter. The low-pass lter improves steady-state performance and dampens oscillations on the feedback signal. This parameter is used with
parameter 1-00 Conguration Mode [1] Speed closed loop. This
parameter is useful if there is a great amount of noise in the system, see Illustration 4.18. For example, if a time constant (τ) of 100 ms is programmed, the cuto frequency for the low-pass lter is 1/0.1=10 RAD/s, corresponding to (10/2 x π)=1.6 Hz. The PID regulator only regulates a feedback signal that varies by a frequency of less than 1.6 Hz. If the feedback signal varies by a higher frequency than
1.6 Hz, the PID regulator does not react. Practical settings of
parameter 7-06 Speed PID Lowpass Filter Time taken from the number
Parameter Descriptions
VLT® Midi Drive FC 280
44
74 Danfoss A/S © 02/2019 All rights reserved. MG07C402
7-06 Speed PID Lowpass Filter Time
Range: Function:
of pulses per revolutions from encoder:
Encoder PPR Parameter 7-06
Speed PID
Lowpass Filter
Time
512 10 ms 1024 5 ms 2048 2 ms 4096 1 ms
0.6
0.6
f
g
= 10 Hz
175ZA293.11
Feedback
Disturbed feedback signal
t (Sec.)
t (Sec.)
Filtered feedback signal
Lowpass lter
Feedback
Illustration 4.18 Feedback Signal
7-07 Speed PID Feedback Gear Ratio
Range: Function:
1* [0.0001 - 32 ]
Par 7-07=1.00 Par 7-07=n1/n2
130BA871.10
Motor
n1 n2
Illustration 4.19 Speed PID
Feedback Gear Ratio
The frequency converter multiplies the speed feedback by this ratio.
7-08 Speed PID Feed Forward Factor
Range: Function:
0 %* [0 - 500 %] The reference signal bypasses the
speed controller by the amount specied. This feature increases the dynamic performance of the speed control loop.
7-12 Torque PID Proportional Gain
Range: Function:
100 %* [0 - 500 %] Enter the proportional gain value
for the torque controller. Selection of a high value makes the controller react faster. Too high a setting leads to controller instability.
7-13 Torque PID Integration Time
Range: Function:
0.020 s* [0.002 - 2 s] Enter the integration time for the
torque controller. The lower the integration time, the faster the controller reacts. However, too low a setting leads to controller instability.
7-20 Process CL Feedback 1 Resource
Option: Function:
The eective feedback signal is made up of the sum of up to 2 dierent input signals. Select which input is treated as the source of the 1st of these signals. The 2nd input signal is dened in
parameter 7-22 Process CL Feedback 2 Resource.
[0] * No function [1] Analog Input
53 [2] Analog Input
54 [3] Frequency
input 29 [4] Frequency
input 33
7-22 Process CL Feedback 2 Resource
Option: Function:
The eective feedback signal is made up of the sum of up to 2 dierent input signals. Select which input is treated as the source of the 2nd of these signals. The 1st input signal is dened in
Parameter Descriptions Programming Guide
4 4
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 75
7-22 Process CL Feedback 2 Resource
Option: Function:
parameter 7-20 Process CL Feedback 1 Resource.
[0] * No function [1] Analog Input
53 [2] Analog Input
54 [3] Frequency
input 29 [4] Frequency
input 33
7-30 Process PID Normal/ Inverse Control
Option: Function:
Normal and inverse controls are implemented by introducing a dierence between the reference signal and the feedback signal.
[0] * Normal Set process control to increase the
output frequency.
[1] Inverse Set process control to decrease the
output frequency.
7-31 Process PID Anti Windup
Option: Function:
[0] O Continue regulation of an error
even when the output frequency cannot be increased or decreased.
[1] * On Cease regulation of an error when
the output frequency can no longer be adjusted.
7-32 Process PID Start Speed
Range: Function:
0 RPM* [0 - 6000
RPM]
Enter the motor speed to be attained as a start signal for commencement of PID control. When the power is switched on, the frequency converter starts to ramp and then operates under speed open-loop control. When the process PID start speed is reached, the frequency converter changes to process PID control.
7-33 Process PID Proportional Gain
Range: Function:
0.01* [0 - 10 ] Enter the PID proportional gain. The
proportional gain multiplies the error between the setpoint and the feedback signal.
7-34 Process PID Integral Time
Range: Function:
9999 s* [0.10 - 9999s]Enter the PID integral time. The
integrator provides an increasing gain at a constant error between the setpoint and the feedback signal. The integral time is the time needed by the integrator to reach the same gain as the proportional gain.
7-35 Process PID Dierentiation Time
Range: Function:
0 s* [0 - 20 s] Enter the PID dierentiation time.
The dierentiator does not react to a constant error, but provides a gain only when the error changes. The shorter the PID dierentiation time, the stronger the gain from the dierentiator.
7-36 Process PID Di. Gain Limit
Range: Function:
5* [1 - 50 ] Enter a limit for the dierentiator
gain. If there is no limit, the dier- entiator gain increases when there are fast changes. To obtain a pure dierentiator gain at slow changes and a constant dierentiator gain where fast changes occur, limit the dierentiator gain.
7-38 Process PID Feed Forward Factor
Range: Function:
0 %* [0 - 200 %] Enter the PID feed forward (FF)
factor. The FF factor sends a constant fraction of the reference signal to bypass the PID control, so the PID control only aects the remaining fraction of the control signal. Any change to this parameter aects the motor speed. When the FF factor is activated, it provides less overshoot, and high dynamics when changing the setpoint. Parameter 7-38 Process PID
Feed Forward Factor is active when
parameter 1-00 Conguration Mode is set to [3] Process.
7-39 On Reference Bandwidth
Range: Function:
5 %* [0 - 200 %] Enter the on-reference bandwidth.
When the PID control error (the dierence between the reference
Parameter Descriptions
VLT® Midi Drive FC 280
44
76 Danfoss A/S © 02/2019 All rights reserved. MG07C402
7-39 On Reference Bandwidth
Range: Function:
and the feedback) is less than the value of this parameter, the on­reference status bit is 1.
7-40 Process PID I-part Reset
Option: Function:
[0] * No [1] Yes Select [1] Yes to reset the I-part of
the process PID controller. The selection automatically returns to [0] No. Resetting the I-part makes it possible to start from a well- dened point after changing something in the process, for example changing a textile roll.
7-41 Process PID Output Neg. Clamp
Range: Function:
-100 %* [ -100 -
100 %]
Enter a negative limit for the process PID controller output.
7-42 Process PID Output Pos. Clamp
Range: Function:
100 %* [ -100 -
100 %]
Enter a positive limit for the process PID controller output.
7-43 Process PID Gain Scale at Min. Ref.
Range: Function:
100 %* [0 - 100 %] Enter a scaling percentage to apply
to the process PID output when operating at the minimum reference. The scaling percentage is adjusted linearly between the scale at minimum reference (parameter 7-43 Process PID Gain Scale at Min. Ref.) and the scale at maximum reference (parameter 7-44 Process PID Gain Scale at Max. Ref.).
7-44 Process PID Gain Scale at Max. Ref.
Range: Function:
100 %* [0 - 100 %] Enter a scaling percentage to apply
to the process PID output when operating at the maximum reference. The scaling percentage is adjusted linearly between the scale at minimum reference (parameter 7-43 Process PID Gain Scale at Min. Ref.) and the scale at maximum reference (parameter 7-44 Process PID Gain Scale at Max. Ref.).
7-45 Process PID Feed Fwd Resource
Option: Function:
Select which frequency converter input is used as the feed-forward factor. The FF factor is added directly to the output of the PID controller. This parameter can increase dynamic performance. The feed-forward set from bus should be in N2 format.
[0] * No function [1] Analog Input
53 [2] Analog Input
54 [7] Frequency
input 29 [8] Frequency
input 33 [11] Local bus
reference [32] Bus PCD
7-46 Process PID Feed Fwd Normal/ Inv. Ctrl.
Option: Function:
[0] * Normal Select [0] Normal to set the feed-
forward factor to treat the FF resource as a positive value.
[1] Inverse Select [1] Inverse to treat the feed-
forward resource as a negative value.
7-48 PCD Feed Forward
Range: Function:
0* [0 - 65535 ] Readout parameter where the bus
parameter 7-45 Process PID Feed Fwd Resource [32] can be read.
The feed forward set from bus should be in N2 format.
7-49 Process PID Output Normal/ Inv. Ctrl.
Option: Function:
[0] * Normal Select [0] Normal to use the
resulting output from the process PID controller as is.
[1] Inverse Select [1] Inverse to invert the
resulting output from the process PID controller. This operation is performed after the feed-forward factor is applied.
Parameter Descriptions Programming Guide
4 4
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 77
7-50 Process PID Extended PID
Option: Function:
[0] Disabled Disable the extended parts of the
process PID controller.
[1] * Enabled Enable the extended parts of the
PID controller.
7-51 Process PID Feed Fwd Gain
Range: Function:
1* [0 - 100 ] The feed forward is used to obtain
the gain, based on a well-known signal available. The PID controller then only takes care of the smaller part of the control, necessary because of unknown characters. The standard feed-forward factor in
parameter 7-38 Process PID Feed Forward Factor is always related to
the reference whereas
parameter 7-51 Process PID Feed Fwd Gain has more options. In winder
applications, the feed-forward factor is typically the line speed of the system.
7-52 Process PID Feed Fwd Ramp up
Range: Function:
0.01 s* [0.01 - 100 s] Control dynamics of the feed-
forward signal when ramping up.
7-53 Process PID Feed Fwd Ramp down
Range: Function:
0.01 s* [0.01 - 100 s] Control the dynamics of the feed-
forward signal when ramping down.
7-56 Process PID Ref. Filter Time
Range: Function:
0.001 s* [0.001 - 1 s] Set a time constant for the
reference rst-order low-pass lter. The low-pass lter improves steady­state performance and dampens oscillations on the reference/ feedback signals. However, severe ltering can be detrimental to dynamic performance.
7-57 Process PID Fb. Filter Time
Range: Function:
0.001 s* [0.001 - 1 s] Set a time constant for the
feedback rst-order low-pass lter. The low-pass lter improves steady­state performance and dampens oscillations on the reference/ feedback signals. However, severe
7-57 Process PID Fb. Filter Time
Range: Function:
ltering can be detrimental to dynamic performance.
7-60 Feedback 1 Conversion
Select a conversion for the feedback 1 signal. Select [0] Linear to leave the feedback signal unchanged.
Option: Function:
[0] * Linear [1] Square root
7-62 Feedback 2 Conversion
Select a conversion for the feedback 2 signal. Select [0] Linear to leave the feedback signal unchanged.
Option: Function:
[0] * Linear [1] Square root
8-00 Option A warning control
This parameter is used to enable or disable installed options.
Option: Function:
[0] * None [1] Disable
Warning
8-01 Control Site
Option: Function:
The setting in this parameter overrides the settings in
parameter 8-50 Coasting Select to
parameter 8-58 Prodrive OFF3 Select.
[0] * Digital and
ctrl.word
Control by using both digital input and control word.
[1] Digital only Control by using digital inputs only.
[2] Controlword
only
Control by using control word only.
8-02 Control Source
Option: Function:
Select the source of the control word.
[0] None [1] FC Port [2] FC USB [3] Option A
Parameter Descriptions
VLT® Midi Drive FC 280
44
4.9 Parameters: 8-** Communications and Options
78 Danfoss A/S © 02/2019 All rights reserved. MG07C402
8-03 Control Timeout Time
Range: Function:
1 s* [0.5 - 6000 s] Enter the maximum time expected
to pass between the reception of 2 consecutive telegrams. If this time is exceeded, it indicates that the serial communication has stopped. The function that is selected in
parameter 8-04 Control Timeout Function is then carried out.
8-04 Control Timeout Function
Option: Function:
[0] * O Select the timeout function. The
timeout function is activated when the control word fails to be updated within the time period
specied in parameter 8-03 Control Timeout Time.
[1] Freeze output [2] Stop [3] Jogging [4] Max. speed [5] Stop and trip
8-07 Diagnosis Trigger
Option: Function:
[0] * Disable Send no extended diagnosis data
(EDD).
[1] Trigger on
alarms
Send EDD upon alarms.
[2] Trigger alarm/
warn.
Send EDD upon alarms or warnings in parameter 16-90 Alarm Word,
parameter 9-53 Probus Warning Word, or parameter 16-92 Warning Word.
8-10 Control Word Prole
Select the interpretation of the control and status words corresponding to the installed eldbus.
Option: Function:
[0] * FC prole [1] PROFIdrive
prole
[5] ODVA [7] CANopen DSP
402
8-13 Congurable Status Word STW
Option: Function:
[0] No function [1] * Prole Default [2] Alarm 68 Only [3] Trip excl
Alarm 68
8-13 Congurable Status Word STW
Option: Function:
[10] T18 DI status [11] T19 DI status [12] T27 DI status [13] T29 DI status [14] T32 DI status [15] T33 DI status [21] Thermal
warning
[30] Brake fault
(IGBT)
[40] Out of ref
range [60] Comparator 0 [61] Comparator 1 [62] Comparator 2 [63] Comparator 3 [64] Comparator 4 [65] Comparator 5 [70] Logic Rule 0 [71] Logic Rule 1 [72] Logic Rule 2 [73] Logic Rule 3 [74] Logic Rule 4 [75] Logic Rule 5 [80] SL digital out
A [81] SL digital out
B [82] SL digital out
C [83] SL digital out
D [93] Alarm68 or
Alarm188
8-14 Congurable Control Word CTW
The control word has 16 bits (0–15). Bits 10 and 12–15 are
congurable.
Option: Function:
[0] None [1] * Prole default [2] CTW Valid,
active low [4] PID error
inverse [5] PID reset I
part [6] PID enable
Parameter Descriptions Programming Guide
4 4
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 79
8-19 Product Code
Range: Function:
Size related*
[0 -
2147483647 ]
Select 0 to read out the actual eldbus product code according to the mounted eldbus option. Select 1 to read out the actual vendor ID.
8-30 Protocol
Option: Function:
Select the protocol for the integrated RS485 port.
[0] * FC Communication according to the FC
protocol.
[2] Modbus RTU Communication according to the
Modbus RTU protocol.
8-33 Parity / Stop Bits
Parity and stop bits for the protocol using the FC port. For some of the protocols, not all options are available.
Option: Function:
[0] Even Parity, 1
Stop Bit [1] Odd Parity, 1
Stop Bit [2] No Parity, 1
Stop Bit [3] No Parity, 2
Stop Bits
8-35 Minimum Response Delay
Range: Function:
0.01 s* [ 0.0010 - 0.5s]Specify the minimum delay time
between receiving a request and transmitting a response. This is used for overcoming modem turn­around delays.
8-36 Maximum Response Delay
Range: Function:
Size related*
[ 0.1 - 10.0 s] Specify the maximum allowed delay
time between receiving a request and transmitting the response. If this time is exceeded, no response is returned.
8-42 PCD Write Conguration
Select the parameters to be assigned to the PCD's telegrams. The number of available PCDs depends on the telegram type. The values in the PCDs are then written to the selected parameters as data values.
Option: Function:
[0] None [1] [302]
Minimum
Reference [2] [303]
Maximum
Reference [3] [341] Ramp 1
Ramp up time [4] [342] Ramp 1
Ramp down
time [5] [351] Ramp 2
Ramp up time [6] [352] Ramp 2
Ramp down
time [7] [380] Jog
Ramp Time [8] [381] Quick
Stop Time [9] [412] Motor
Speed Low
Limit [Hz] [10] [414] Motor
Speed High
Limit [Hz] [11] [590] Digital &
Relay Bus
Control [12] [676] Terminal
45 Output Bus
Control [13] [696] Terminal
42 Output Bus
Control [15] FC Port CTW [16] FC Port REF [18] [311] Jog
Speed [Hz]
Parameter Descriptions
44
8-31 Address
Range: Function:
1* [ 0 - 247 ] Enter the address for the RS485 port. Valid
range: 1–126 for FC-bus, or 1–247 for Modbus.
8-32 Baud Rate
Option: Function:
[0] 2400 Baud [1] 4800 Baud [2] * 9600 Baud [3] 19200 Baud [4] 38400 Baud [5] 57600 Baud [6] 76800 Baud [7] 115200 Baud
80 Danfoss A/S © 02/2019 All rights reserved. MG07C402
Select the baud rate for the RS485 port.
VLT® Midi Drive FC 280
8-42 PCD Write Conguration
Select the parameters to be assigned to the PCD's telegrams. The number of available PCDs depends on the telegram type. The values in the PCDs are then written to the selected parameters as data values.
Option: Function:
[19] [427] Torque
limit bus
control [20] [428] Speed
limit bus
control
8-50 Coasting Select
Option: Function:
Select control of the coasting function via the terminals (digital input) and/or via the bus.
[0] Digital input Activate coasting command via a
digital input.
[1] Bus Activate coasting command via the
serial communication port or eldbus option.
[2] Logic AND Activate coasting command via the
eldbus/serial communication port and 1 extra digital input.
[3] * Logic OR Activate coasting command via the
eldbus/serial communication port or via 1 of the digital inputs.
8-51 Quick Stop Select
Option: Function:
[0] Digital input Activate quick stop command via a
digital input.
[1] Bus Activate quick stop command via
the serial communication port or eldbus option.
[2] Logic AND Activate quick stop command via
the eldbus/serial communication port and additionally via 1 of the digital inputs.
[3] * Logic OR Activate quick stop command via
the eldbus/serial communication port or via 1 of the digital inputs.
8-52 DC Brake Select
Option: Function:
Select control of the DC brake via the terminals (digital input) and/or via the eldbus.
NOTICE
When parameter 1-10 Motor Construction is set to [1] PM non-salient SPM, only selection [0] Digital input is available.
Parameter Descriptions Programming Guide
8-43 PCD Read Conguration
Select the parameters to be assigned to the PCDs of the telegrams. The number of available PCDs depends on the telegram type. PCDs contain the actual data values of the selected parameters.
Option: Function:
[0] * None [1] [1500] Operation Hours [2] [1501] Running Hours [3] [1502] kWh Counter [4] [1600] Control Word [5] [1601] Reference [Unit] [6] [1602] Reference % [7] [1603] Status Word [8] [1605] Main Actual Value [%] [9] [1609] Custom Readout [10] [1610] Power [kW] [11] [1611] Power [hp] [12] [1612] Motor Voltage [13] [1613] Frequency [14] [1614] Motor Current [15] [1615] Frequency [%] [16] [1616] Torque [Nm] [17] [1618] Motor Thermal [18] [1630] DC Link Voltage [19] [1634] Heatsink Temp. [20] [1635] Inverter Thermal [21] [1638] SL Controller State [22] [1650] External Reference [23] [1652] Feedback [Unit] [24] [1660] Digital Input 18, 19, 27,
29, 32, 33 [25] [1661] Terminal 53 Switch Setting [26] [1662] Analog Input 53(V) [27] [1663] Terminal 54 Switch Setting [28] [1664] Analog Input 54 [29] [1665] Analog Output 42 [mA] [30] [1671] Relay Output [bin] [31] [1672] Counter A [32] [1673] Counter B [33] [1690] Alarm Word
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 81
8-43 PCD Read Conguration
Select the parameters to be assigned to the PCDs of the telegrams. The number of available PCDs depends on the telegram type. PCDs contain the actual data values of the selected parameters.
Option: Function:
[34] [1692] Warning Word [35] [1694] Ext. Status Word
4 4
8-52 DC Brake Select
Option: Function:
[0] Digital input Activate DC brake command via a
digital input.
[1] Bus Activate DC brake command via the
serial communication port or eldbus option.
[2] Logic AND Activate DC brake command via the
eldbus/serial communication port and additionally via 1 of the digital inputs.
[3] * Logic OR Activate DC brake command via the
eldbus/serial communication port or via 1 of the digital inputs.
8-53 Start Select
Select the trigger for the start function.
Option: Function:
[0] Digital input A digital input triggers the start
function.
[1] Bus A serial communication port or the
eldbus triggers the start function.
[2] Logic AND The eldbus/serial communication
port and a digital input trigger the start function.
[3] * Logic OR The eldbus/serial communication
port or a digital input triggers the start function.
8-54 Reversing Select
Option: Function:
Select the trigger for the reversing function.
[0] Digital input A digital input triggers the
reversing function.
[1] Bus A serial communication port or the
eldbus triggers the reversing function.
[2] Logic AND The eldbus/serial communication
port and a digital input trigger the reversing function.
[3] * Logic OR The eldbus/serial communication
port or a digital input triggers the reversing function.
8-55 Set-up Select
Select the trigger for the set-up selection.
Option: Function:
[0] Digital input A digital input triggers the set-up
selection.
8-55 Set-up Select
Select the trigger for the set-up selection.
Option: Function:
[1] Bus A serial communication port or the
eldbus triggers the set-up selection.
[2] Logic AND The eldbus/serial communication
port and a digital input trigger the set-up selection.
[3] * Logic OR The eldbus/serial communication
port or a digital input triggers the set-up selection.
8-56 Preset Reference Select
Option: Function:
Select the trigger for the preset reference selection.
[0] Digital input A digital input triggers the preset
reference selection.
[1] Bus A serial communication port or the
eldbus triggers the preset reference selection.
[2] Logic AND The eldbus/serial communication
port and a digital input trigger the preset reference selection.
[3] * Logic OR The eldbus/serial communication
port or a digital input triggers the preset reference selection.
8-57 Prodrive OFF2 Select
Select control of the frequency converter OFF2 selection via the terminals (digital input) and/or via the eldbus. This parameter is active only when parameter 8-01 Control Site is set to [0] Digital
and ctrl. word and parameter 8-10 Control Word Prole is set to [1] PROFIdrive prole.
Option: Function:
[0] Digital input [1] Bus [2] Logic AND [3] * Logic OR
8-58 Prodrive OFF3 Select
Select control of the frequency converter OFF3 selection via the terminals (digital input) and/or via the eldbus. This parameter is active only when parameter 8-01 Control Site is set to [0] Digital
and ctrl. word, and parameter 8-10 Control Word Prole is set to [1] PROFIdrive prole.
Option: Function:
[0] Digital input [1] Bus [2] Logic AND [3] * Logic OR
Parameter Descriptions
VLT® Midi Drive FC 280
44
82 Danfoss A/S © 02/2019 All rights reserved. MG07C402
8-79 Protocol Firmware version
Range: Function:
Size related*
[0 - 655 ] Firmware revision: FC is in index 0;
Modbus is in index 1; indexes 2–4 are reserved.
8-80 Bus Message Count
Range: Function:
0* [0 -
4294967295 ]
This parameter shows the number of valid telegrams detected on the bus.
8-81 Bus Error Count
Range: Function:
0* [0 -
4294967295 ]
This parameter shows the number of telegrams with faults (for example CRC faults) detected on the bus.
8-82 Slave Messages Rcvd
Range: Function:
0* [0 -
4294967295 ]
This parameter shows the number of valid telegrams sent by the frequency converter to the slave.
8-83 Slave Error Count
Range: Function:
0* [0 -
4294967295 ]
This parameter shows the number of error telegrams, which could not be executed by the frequency converter.
8-84 Slave Messages Sent
Range: Function:
0* [0 -
4294967295 ]
This parameter shows the number of messages sent from the slave.
8-85 Slave Timeout Errors
Range: Function:
0* [0 -
4294967295 ]
This parameter shows the number of slave timeout errors.
8-88 Reset FC port Diagnostics
Reset all FC port diagnostic counters.
Option: Function:
[0] * Do not reset [1] Reset counter
8-90 Bus Jog 1 Speed
Range: Function:
100 RPM* [ 0 - 1500
RPM]
Enter the jog speed. This is a xed jog speed activated via the serial port or eldbus option.
8-91 Bus Jog 2 Speed
Range: Function:
200 RPM* [ 0 - 1500
RPM]
Enter the jog speed. This value is a xed jog speed activated via the serial port or eldbus option.
13-00 SL Controller Mode
Option: Function:
[0] * O Disable the smart logic controller.
[1] On Enable the smart logic controller.
13-01 Start Event
Select the condition (true or false) which activates the smart logic controller.
Option: Function:
[0] False [1] True [2] Running [3] In range [4] On reference [7] Out of current
range [8] Below I low [9] Above I high [16] Thermal
warning [17] Mains out of
range [18] Reversing [19] Warning [20] Alarm (trip) [21] Alarm (trip
lock) [22] Comparator 0
Parameter Descriptions Programming Guide
4.10 Parameters: 9-** PROFIdrive
For PROFIBUS parameter descriptions, see the VLT® Midi Drive FC 280 PROFIBUS DP Programming Guide.
For PROFINET parameter descriptions, see the VLT® Midi Drive FC 280 PROFINET Programming Guide.
4.11 Parameters: 10-** CAN Fieldbus
For CAN Fieldbus parameter descriptions, see the VLT® Midi Drive FC 280 CANopen Programming Guide.
4.12 Parameters: 12-** Ethernet
For Ethernet parameter descriptions, see the VLT® Midi
Drive FC 280 EtherNet/IP Programming Guide, VLT® Midi Drive FC 280 PROFINET Programming Guide, and VLT® Midi Drive
FC 280 POWERLINK Programming Guide.
Parameters: 13-** Smart Logic Control
4.13
4 4
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 83
13-01 Start Event
Select the condition (true or false) which activates the smart logic controller.
Option: Function:
[23] Comparator 1 [24] Comparator 2 [25] Comparator 3 [26] Logic rule 0 [27] Logic rule 1 [28] Logic rule 2 [29] Logic rule 3 [33] Digital input
DI18 [34] Digital input
DI19 [35] Digital input
DI27 [36] Digital input
DI29 [39] * Start
command [40] Drive stopped [42] Auto Reset
Trip [50] Comparator 4 [51] Comparator 5 [60] Logic rule 4 [61] Logic rule 5 [83] Broken Belt
13-02 Stop Event
Select the condition (true or false) which deactivates the smart logic controller.
Option: Function:
[0] False [1] True [2] Running [3] In range [4] On reference [7] Out of current
range [8] Below I low [9] Above I high [16] Thermal
warning [17] Mains out of
range [18] Reversing [19] Warning [20] Alarm (trip) [21] Alarm (trip
lock) [22] Comparator 0 [23] Comparator 1 [24] Comparator 2
13-02 Stop Event
Select the condition (true or false) which deactivates the smart logic controller.
Option: Function:
[25] Comparator 3 [26] Logic rule 0 [27] Logic rule 1 [28] Logic rule 2 [29] Logic rule 3 [30] SL Time-out 0 [31] SL Time-out 1 [32] SL Time-out 2 [33] Digital input
DI18 [34] Digital input
DI19 [35] Digital input
DI27 [36] Digital input
DI29 [39] Start
command [40] * Drive stopped [42] Auto Reset
Trip [50] Comparator 4 [51] Comparator 5 [60] Logic rule 4 [61] Logic rule 5 [70] SL Time-out 3 [71] SL Time-out 4 [72] SL Time-out 5 [73] SL Time-out 6 [74] SL Time-out 7 [83] Broken Belt
13-03 Reset SLC
Option: Function:
[0] * Do not reset
SLC
Retain programmed settings in parameter group 13-** Smart Logic.
[1] Reset SLC Reset all parameters in parameter
group 13-** Smart Logic to default settings.
13-10 Comparator Operand
Select the variable to be monitored by the comparator. This is an array parameter containing comparators 0 to 5.
Option: Function:
[0] * Disabled [1] Reference % [2] Feedback % [3] Motor speed [4] Motor Current [6] Motor power
Parameter Descriptions
VLT® Midi Drive FC 280
44
84 Danfoss A/S © 02/2019 All rights reserved. MG07C402
13-10 Comparator Operand
Select the variable to be monitored by the comparator. This is an array parameter containing comparators 0 to 5.
Option: Function:
[7] Motor voltage [12] Analog input
AI53 [13] Analog input
AI54 [18] Pulse input
FI29 [19] Pulse input
FI33 [20] Alarm number [30] Counter A [31] Counter B
13-11 Comparator Operator
Option: Function:
Select the operator to be used in the comparison. This is an array parameter containing comparator operators 0–5.
[0] Less Than (<) The result of the evaluation is true
when the variable selected in
parameter 13-10 Comparator Operand is smaller than the xed
value in parameter 13-12 Comparator Value. The result is false if the variable selected in
parameter 13-10 Comparator Operand is greater than the xed
value in parameter 13-12 Comparator Value.
[1] * Approx.Equal
(~)
The result of the evaluation is true when the variable speed selected in
parameter 13-10 Comparator Operand is approximately equal to
the xed value in parameter 13-12 Comparator Value.
[2] Greater Than
(>)
Inverse logic of [0] Less Than (<).
13-12 Comparator Value
Range: Function:
0* [-9999 -
9999 ]
Enter the trigger level for the variable that is monitored by this comparator. This is an array parameter containing comparator values 0–5.
13-20 SL Controller Timer
Range: Function:
0 s* [0 - 3600 s] Enter the value to dene the
duration of the false output from the programmed timer. A timer is only false if it is started by an action (for example [29] Start timer
1) and until the given timer value has elapsed.
13-40 Logic Rule Boolean 1
Option: Function:
Select the 1st boolean (true or false) input for the selected logic rule. See parameter 13-01 Start Event ([0]–[61]) and parameter 13-02 Stop Event ([70]–[74]) for further description.
[0] * False [1] True [2] Running [3] In range [4] On reference [7] Out of current
range [8] Below I low [9] Above I high [16] Thermal
warning [17] Mains out of
range [18] Reversing [19] Warning [20] Alarm (trip) [21] Alarm (trip
lock) [22] Comparator 0 [23] Comparator 1 [24] Comparator 2 [25] Comparator 3 [26] Logic rule 0 [27] Logic rule 1 [28] Logic rule 2 [29] Logic rule 3 [30] SL Time-out 0 [31] SL Time-out 1 [32] SL Time-out 2 [33] Digital input
DI18 [34] Digital input
DI19 [35] Digital input
DI27 [36] Digital input
DI29
Parameter Descriptions Programming Guide
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 85
4 4
13-40 Logic Rule Boolean 1
Option: Function:
[39] Start
command [40] Drive stopped [42] Auto Reset
Trip [50] Comparator 4 [51] Comparator 5 [60] Logic rule 4 [61] Logic rule 5 [70] SL Time-out 3 [71] SL Time-out 4 [72] SL Time-out 5 [73] SL Time-out 6 [74] SL Time-out 7 [83] Broken Belt
13-41 Logic Rule Operator 1
Option: Function:
Select the 1st logical operator to use on the boolean inputs from
parameter 13-40 Logic Rule Boolean 1 and parameter 13-42 Logic Rule Boolean 2.
[0] * Disabled Ignore parameter 13-42 Logic Rule
Boolean 2, parameter 13-43 Logic Rule Operator 2, and
parameter 13-44 Logic Rule Boolean
3.
[1] AND Evaluate the expression [13-40]
AND [13-42].
[2] OR Evaluate the expression [13-40] OR
[13-42].
[3] AND NOT Evaluate the expression [13-40]
AND NOT [13-42].
[4] OR NOT Evaluate the expression [13-40] OR
NOT [13-42].
[5] NOT AND Evaluate the expression NOT [13-40]
AND [13-42].
[6] NOT OR Evaluate the expression NOT [13-40]
OR [13-42].
[7] NOT AND NOT Evaluate the expression NOT [13-40]
AND NOT [13-42].
[8] NOT OR NOT Evaluate the expression NOT [13-40]
OR NOT [13-42].
13-42 Logic Rule Boolean 2
Option: Function:
Select the 2nd boolean (true or false) input for the selected logic rule. See parameter 13-01 Start Event
13-42 Logic Rule Boolean 2
Option: Function:
([0]–[61]), and parameter 13-02 Stop Event ([70]–[74]) for further
description.
[0] * False [1] True [2] Running [3] In range [4] On reference [7] Out of current
range [8] Below I low [9] Above I high [16] Thermal
warning [17] Mains out of
range [18] Reversing [19] Warning [20] Alarm (trip) [21] Alarm (trip
lock) [22] Comparator 0 [23] Comparator 1 [24] Comparator 2 [25] Comparator 3 [26] Logic rule 0 [27] Logic rule 1 [28] Logic rule 2 [29] Logic rule 3 [30] SL Time-out 0 [31] SL Time-out 1 [32] SL Time-out 2 [33] Digital input
DI18 [34] Digital input
DI19 [35] Digital input
DI27 [36] Digital input
DI29 [39] Start
command [40] Drive stopped [42] Auto Reset
Trip [50] Comparator 4 [51] Comparator 5 [60] Logic rule 4 [61] Logic rule 5 [70] SL Time-out 3 [71] SL Time-out 4 [72] SL Time-out 5
Parameter Descriptions
44
86 Danfoss A/S © 02/2019 All rights reserved. MG07C402
VLT® Midi Drive FC 280
13-42 Logic Rule Boolean 2
Option: Function:
[73] SL Time-out 6 [74] SL Time-out 7 [83] Broken Belt
13-43 Logic Rule Operator 2
Option: Function:
Select the 2nd logical operator to be used on the boolean input calculated in parameter 13-40 Logic
Rule Boolean 1,
parameter 13-41 Logic Rule Operator 1, and parameter 13-42 Logic Rule Boolean 2, and the boolean input coming from parameter 13-42 Logic Rule Boolean 2.
Parameter 13-42 Logic Rule Boolean 2 signies the boolean input of
parameter 13-44 Logic Rule Boolean
3. Parameter 13-40 Logic Rule Boolean 1, and
parameter 13-42 Logic Rule Boolean 2 signify the boolean input calculated in parameter 13-40 Logic Rule Boolean 1,
parameter 13-41 Logic Rule Operator 1, and parameter 13-42 Logic Rule Boolean 2.
[0] * Disabled Ignore parameter 13-44 Logic Rule
Boolean 3.
[1] AND [2] OR [3] AND NOT [4] OR NOT [5] NOT AND [6] NOT OR [7] NOT AND NOT [8] NOT OR NOT
13-44 Logic Rule Boolean 3
Option: Function:
Select the 3rd boolean (true or false) input for the selected logic rule. See parameter 13-40 Logic Rule
Boolean 1, parameter 13-41 Logic Rule Operator 1, and
parameter 13-42 Logic Rule Boolean 2, and the boolean input. See parameter 13-01 Start Event ([0]– [61]), and parameter 13-02 Stop Event ([70]–[74]) for further
description.
[0] * False [1] True
13-44 Logic Rule Boolean 3
Option: Function:
[2] Running [3] In range [4] On reference [7] Out of current
range [8] Below I low [9] Above I high [16] Thermal
warning [17] Mains out of
range [18] Reversing [19] Warning [20] Alarm (trip) [21] Alarm (trip
lock) [22] Comparator 0 [23] Comparator 1 [24] Comparator 2 [25] Comparator 3 [26] Logic rule 0 [27] Logic rule 1 [28] Logic rule 2 [29] Logic rule 3 [30] SL Time-out 0 [31] SL Time-out 1 [32] SL Time-out 2 [33] Digital input
DI18 [34] Digital input
DI19 [35] Digital input
DI27 [36] Digital input
DI29 [39] Start
command [40] Drive stopped [42] Auto Reset
Trip [50] Comparator 4 [51] Comparator 5 [60] Logic rule 4 [61] Logic rule 5 [70] SL Time-out 3 [71] SL Time-out 4 [72] SL Time-out 5 [73] SL Time-out 6 [74] SL Time-out 7 [83] Broken Belt
Parameter Descriptions Programming Guide
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 87
4 4
13-51 SL Controller Event
Option: Function:
Select the 3rd boolean (true or false) input for the selected logic rule. See parameter 13-40 Logic Rule
Boolean 1, parameter 13-41 Logic Rule Operator 1,
parameter 13-42 Logic Rule Boolean 2, and the boolean input. See parameter 13-01 Start Event ([0]– [61]) and parameter 13-02 Stop Event
([70]–[74]) for further description.
[0] * False [1] True [2] Running [3] In range [4] On reference [7] Out of current
range [8] Below I low [9] Above I high [16] Thermal
warning [17] Mains out of
range [18] Reversing [19] Warning [20] Alarm (trip) [21] Alarm (trip
lock) [22] Comparator 0 [23] Comparator 1 [24] Comparator 2 [25] Comparator 3 [26] Logic rule 0 [27] Logic rule 1 [28] Logic rule 2 [29] Logic rule 3 [30] SL Time-out 0 [31] SL Time-out 1 [32] SL Time-out 2 [33] Digital input
DI18 [34] Digital input
DI19 [35] Digital input
DI27 [36] Digital input
DI29 [39] Start
command [40] Drive stopped [42] Auto Reset
Trip [50] Comparator 4
13-51 SL Controller Event
Option: Function:
[51] Comparator 5 [60] Logic rule 4 [61] Logic rule 5 [70] SL Time-out 3 [71] SL Time-out 4 [72] SL Time-out 5 [73] SL Time-out 6 [74] SL Time-out 7 [83] Broken Belt
13-52 SL Controller Action
Option: Function:
[0] * Disabled Select the action corresponding to
the SLC event. Actions are executed when the corresponding event
(dened in parameter 13-51 SL Controller Event) is evaluated as
true.
[1] No action [2] Select set-up 1 Change the active set-up
(parameter 0-10 Active Set-up) to 1. If the set-up is changed, it merges with other set-up commands coming from either the digital inputs, or via a eldbus.
[3] Select set-up 2 Change the active set-up
(parameter 0-10 Active Set-up) to 2. If the set-up is changed, it merges with other set-up commands coming from either the digital inputs, or via a eldbus.
[4] Select set-up 3 Change the active set-up
(parameter 0-10 Active Set-up) to 3. If the set-up is changed, it merges with other set-up commands coming from either the digital inputs, or via a eldbus.
[5] Select set-up 4 Change the active set-up
(parameter 0-10 Active Set-up) to 4. If the set-up is changed, it merges with other set-up commands coming from either the digital inputs, or via a eldbus.
[10] Select preset
ref 0
Select preset reference 0. If the active preset reference is changed, it merges with other preset reference commands coming from either the digital inputs or via a
eldbus.
[11] Select preset
ref 1
Select preset reference 1. If the active preset reference is changed, it merges with other preset
Parameter Descriptions
44
88 Danfoss A/S © 02/2019 All rights reserved. MG07C402
VLT® Midi Drive FC 280
13-52 SL Controller Action
Option: Function:
reference commands coming from either the digital inputs, or via a
eldbus.
[12] Select preset
ref 2
Select preset reference 2. If the active preset reference is changed, it merges with other preset reference commands coming from either the digital inputs, or via a
eldbus.
[13] Select preset
ref 3
Select preset reference 3. If the active preset reference is changed, it merges with other preset reference commands coming from either the digital inputs, or via a
eldbus.
[14] Select preset
ref 4
Select preset reference 4. If the active preset reference is changed, it merges with other preset reference commands coming from either the digital inputs, or via a
eldbus.
[15] Select preset
ref 5
Select preset reference 5. If the active preset reference is changed, it merges with other preset reference commands coming from either the digital inputs, or via a
eldbus.
[16] Select preset
ref 6
Select preset reference 6. If the active preset reference is changed, it merges with other preset reference commands coming from either the digital inputs, or via a
eldbus.
[17] Select preset
ref 7
Select preset reference 7. If the active preset reference is changed, it merges with other preset reference commands coming from either the digital inputs, or via a
eldbus.
[18] Select ramp 1 Select ramp 1.
[19] Select ramp 2 Select ramp 2.
[22] Run Issue a start command to the
frequency converter.
[23] Run reverse Issue a start reverse command to
the frequency converter.
[24] Stop Issue a stop command to the
frequency converter.
[25] Qstop Issue a quick stop command to the
frequency converter.
13-52 SL Controller Action
Option: Function:
[26] DC Brake Issue a DC-brake command to the
frequency converter.
[27] Coast The frequency converter coasts
immediately. All stop commands including the coast command stop the SLC.
[28] Freeze output Freeze the output of the frequency
converter.
[29] Start timer 0 See parameter 13-20 SL Controller
Timer for further description.
[30] Start timer 1 See parameter 13-20 SL Controller
Timer for further description.
[31] Start timer 2 See parameter 13-20 SL Controller
Timer for further description.
[32] Set digital out
A low
Any output with SL output A is low.
[33] Set digital out
B low
Any output with SL output B is low.
[34] Set digital out
C low
Any output with SL output C is low.
[35] Set digital out
D low
Any output with SL output D is low.
[38] Set digital out
A high
Any output with SL output A is high.
[39] Set digital out
B high
Any output with SL output B is high.
[40] Set digital out
C high
Any output with SL output C is high.
[41] Set digital out
D high
Any output with SL output D is high.
[60] Reset CounterAReset counter A to 0.
[61] Reset CounterBReset counter B to 0.
[70] Start Timer 3 See parameter 13-20 SL Controller
Timer for further description.
[71] Start Timer 4 See parameter 13-20 SL Controller
Timer for further description.
[72] Start Timer 5 See parameter 13-20 SL Controller
Timer for further description.
[73] Start Timer 6 See parameter 13-20 SL Controller
Timer for further description.
[74] Start Timer 7 See parameter 13-20 SL Controller
Timer for further description.
Parameter Descriptions Programming Guide
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 89
4 4
14-01 Switching Frequency
Adjust the switching frequency to nd a suitable balance between the acoustic noise from the motor and thermal losses in the frequency converter. Increasing the switching frequency reduces the noise, but increases thermal losses.
Option: Function:
[0] Ran3 [1] Ran5 [2] 2.0 kHz [3] 3.0 kHz [4] 4.0 kHz [5] 5.0 kHz [6] 6.0 kHz [7] 8.0 kHz [8] 10.0 kHz [9] 12.0 kHz [10] 16.0 kHz
14-03 Overmodulation
Option: Function:
[0] O To avoid torque ripple on the
motor shaft, select [0] O for no overmodulation of the output voltage. This feature may be useful for applications such as grinding machines.
[1] * On Select [1] On to enable the overmo-
dulation function for the output voltage. Select this setting when it is required that the output voltage is >95% of the input voltage (typical when running oversynchro­nously). The output voltage is increased according to the degree of overmodulation.
NOTICE
Overmodulation leads to increased torque ripple as harmonics are increased.
14-07 Dead Time Compensation Level
Range: Function:
Size related*
[0 - 100 ] Level of applied deadtime compen-
sation in percentage. A high level (>90%) optimizes the dynamic motor response; a level 50–90% is good for both motor-torque-ripple minimization and the motor dynamics. A 0-level turns the deadtime compensation o.
14-08 Damping Gain Factor
Range: Function:
Size related*
[0 - 100 %] Damping factor for DC-link voltage
compensation.
14-09 Dead Time Bias Current Level
Range: Function:
Size related*
[0 - 100 %] Set a bias signal (in [%]) to add to
the current-sense signal for deadtime compensation for some motors.
14-10 Mains Failure
Option: Function:
NOTICE
Parameter 14-10 Mains Failure
cannot be changed while the motor is running.
Parameter 14-10 Mains Failure is typically used where short mains interruptions (voltage dips) are present. At 100% load and a short voltage interruption, the DC voltage on the main capacitors drops quickly. For larger frequency converters, it only takes a few milliseconds before the DC level is down to about 373 V DC and the IGBTs cut o and lose control of the motor. When mains is restored, and the IGBTs start again, the output frequency and voltage vector do not correspond to the speed/ frequency of the motor, and the result is normally an overvoltage or overcurrent, mostly resulting in a trip lock. Parameter 14-10 Mains Failure can be programmed to avoid this situation.
Select the function to which the frequency converter must act when the threshold in
parameter 14-11 Mains Voltage at Mains Fault has been reached.
[0] * No function The frequency converter does not
compensate for a mains interruption. The voltage on the DC-link drops quickly, and the motor is lost within milliseconds to seconds. Trip lock is the result.
[1] Ctrl. ramp-
down
The frequency converter retains control of the motor and does a controlled ramp down from
Parameter Descriptions
4.14 Parameters: 14-** Special Functions
44
VLT® Midi Drive FC 280
90 Danfoss A/S © 02/2019 All rights reserved. MG07C402
14-10 Mains Failure
Option: Function:
parameter 14-11 Mains Fault Voltage Level level. If parameter 2-10 Brake Function is [0] O or [2] AC brake,
the ramp follows the overvoltage ramping. If parameter 2-10 Brake Function is [1] Resistor Brake, the ramp follows the setting in
parameter 3-81 Quick Stop Ramp Time. This selection is useful in
pump applications, where the inertia is low and the friction is high. When mains is restored, the output frequency ramps the motor up to the reference speed (if the mains interruption is prolonged, the controlled ramp down might take down the output frequency to 0 RPM, and when the mains is restored, the application is ramped up from 0 RPM to the previous reference speed via the normal ramp up). If the energy in the DC­link disappears before the motor is ramped to 0, the motor is coasted.
[2] Ctrl. ramp-
down, trip
This selection is similar to selection
[1] Ctrl. ramp-down, except that in [2] Ctrl. ramp-down, trip a reset is
necessary for starting up after power-up.
[3] Coasting Centrifuges can run for an hour
without power supply. In those situations, it is possible to select a coast function at mains interruption, together with a ying start, which occurs when the mains is restored.
[4] Kinetic back-upKinetic back-up ensures that the
frequency converter keeps running as long as there is energy in the system due to the inertia from motor and load. This is done by converting the mechanical energy to the DC-link and thereby maintaining control of the frequency converter and motor. This can extend the controlled operation, depending on the inertia in the system. For fans, it is typically several seconds, for pumps up to 2 s and for compressors only for a fraction of a second. Many industry applications can extend controlled operation for many
14-10 Mains Failure
Option: Function:
seconds, which is often enough time for the mains to return.
130BC918.10
U
14-11*1.35
Ref
n [RPM]
t [S]
A B CDE A
DC
U
DC
[V]
t [S]
A Normal operation B Mains failure C Kinetic back-up D Mains return E Normal operation: Ramping
Illustration 4.20 Kinetic Back-up
The DC-level during [4] Kinetic back­up is parameter 14-11 Mains Fault Voltage Level x 1.35.
If the mains does not return, UDC is maintained as long as possible by ramping the speed down towards 0 RPM. Finally, the frequency converter coasts.
If mains returns while in kinetic back-up, UDC increases above
parameter 14-11 Mains Fault Voltage Level x 1.35. This is detected in 1 of
the following ways:
If U
DC
>parameter 14-11 Mains Fault Voltage Level x 1.35 x
1.05
If the speed is above the reference. This is relevant if mains comes back at a lower level than before, for example,
parameter 14-11 Mains Fault Voltage Level x 1.35 x
1.02. This does not fulll the criterion above, and the frequency converter tries to reduce UDC to
parameter 14-11 Mains Fault Voltage Level x 1.35
by increasing the speed. This does not succeed as mains cannot be lowered.
If running motoric. The same mechanism as in the
Parameter Descriptions Programming Guide
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 91
4 4
14-10 Mains Failure
Option: Function:
previous point, but where the inertia prevents the speed from going above the reference speed. This leads to the motor running motoric until the speed is above the reference speed, and the above situation occurs. Instead of waiting for that, the present criterion is introduced.
[5] Kinetic back-
up, trip
The dierence between kinetic back-up with and without trip is that the latter always ramps down to 0 RPM and trips, regardless of whether mains return or not. The function is made so that it does not even detect if mains return. This is the reason for the relatively high level on the DC-link during ramp down.
14-11*1.35
Ref
790 V
0
A B C D
130BC920.10
U
n [RPM]
t [S]
DC
U
DC
[V]
t [S]
A Normal operation B Mains failure C Kinetic back-up D Trip
Illustration 4.21 Kinetic Back-up
Trip
[6] Alarm [7] Kin. back-up,
trip w
recovery
Kinetic back-up with recovery combines the features of kinetic back-up and kinetic back-up with trip. This feature makes it possible to select between kinetic back-up and kinetic back-up with trip based on a recovery speed, which is
congurable in parameter 14-15 Kin. Back-up Trip Recovery Level to
enable detection of mains returning. If the mains do not return, the frequency converter ramps down to 0 RPM and trips. If
14-10 Mains Failure
Option: Function:
mains return while kinetic back-up is at a speed above the value set in
parameter 14-15 Kin. Back-up Trip Recovery Level, normal operation is resumed. This is equal to [4] Kinetic Back-up. The DC level during [7] Kinetic back-up is
parameter 14-11 Mains Fault Voltage Level x 1.35. If mains return while
kinetic back-up is at a speed below
parameter 14-15 Kin. Back-up Trip Recovery Level, the frequency
converter ramps down to 0 RPM using the ramp and then trips.
14-11 Mains Fault Voltage Level
Range: Function:
342 V* [100 - 800 V] This parameter denes the
threshold voltage at which the selected function in parameter 14-10 Mains Failure is activated. Based on the supply quality, consider to select 90% of the nominal mains as the detection level. For a supply of 380 V,
parameter 14-11 Mains Fault Voltage Level should be set to 342 V. This
results in a DC detection level of 462 V (parameter 14-11 Mains Fault Voltage Level x 1.35).
14-15 Kin. Back-up Trip Recovery Level
Range: Function:
Size related*
[ 0 -
60000.000
Reference-
FeedbackUnit]
This parameter species the kinetic back-up trip recovery level.
14-17 Fast Mains Phase Loss Level
Range: Function:
300 %* [0 - 500 %] Tuning it smaller makes the
detection more sensitive, tuning bigger is opposite.
Parameter Descriptions
44
VLT® Midi Drive FC 280
92 Danfoss A/S © 02/2019 All rights reserved. MG07C402
14-12 Function at Mains Imbalance
Option: Function:
Operation under severe mains imbalance conditions reduces the lifetime of the motor. Conditions are considered severe if the motor is operated continuously near nominal load (for
example, a pump or fan running near full speed). [0] * Trip Trip the frequency converter. [1] Warning Issue a warning. [2] Disabled No action is taken.
14-18 Fast Mains Phase Loss Min Power
Range: Function:
10 %* [0 - 100 %] The fast detection does not activate
if actual power is lower than it.
14-19 Counter Clear Time
Range: Function:
10 min* [0 - 65535
min]
When the time dened runs out, the auto reset counter is reset to 0 and one auto reset is executed.
14-20 Reset Mode
Option: Function:
WARNING
UNINTENDED START
When the frequency converter is connected to AC mains, DC supply, or load sharing, the motor may start at any time. Unintended start during programming, service, or repair work can result in death, serious injury, or property damage. The motor can start via an external switch, a eldbus command, an input reference signal from the LCP, or after a cleared fault condition. To prevent unintended motor start:
Disconnect the frequency converter from the mains.
Press [O/Reset] on the LCP before programming parameters.
Fully wire and assemble the frequency converter, motor, and any driven equipment before connecting the frequency converter to AC mains, DC supply, or load sharing.
14-20 Reset Mode
Option: Function:
NOTICE
If the specied number of automatic resets is reached within 10 minutes, the frequency converter enters [0] Manual reset mode. After the manual reset is performed, the setting of
parameter 14-20 Reset Mode
reverts to the original selection. If the number of automatic resets is not reached within 10 minutes, or when a manual reset is performed, the internal automatic reset counter returns to 0.
Select the reset function after tripping. Once reset, the frequency converter can be restarted. Automatic reset mode does not
aect alarm 68, Safe Torque O and alarm 188, STO internal fault in
software v1.2 and later versions.
[0] * Manual reset Select [0] Manual reset to perform a
reset via [Reset] or via the digital inputs.
[1] Automatic
reset x 1
Select [1]-[12] Automatic reset x 1…x 20 to perform between 1 and 20 automatic resets after tripping.
[2] Automatic
reset x 2
[3] Automatic
reset x 3
[4] Automatic
reset x 4
[5] Automatic
reset x 5
[6] Automatic
reset x 6
[7] Automatic
reset x 7
[8] Automatic
reset x 8
[9] Automatic
reset x 9
[10] Automatic
reset x 10
[11] Automatic
reset x 15
[12] Automatic
reset x 20
Parameter Descriptions Programming Guide
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 93
4 4
14-20 Reset Mode
Option: Function:
[13] Innite auto
reset
Select [13] Innite Automatic Reset for continuous resetting after tripping.
[14] Reset at
power-up
14-21 Automatic Restart Time
Range: Function:
10 s* [0 - 600 s] Enter the time interval from trip to
start of the automatic reset function. This parameter is active when parameter 14-20 Reset Mode is set to [1]–[13] Automatic reset.
14-22 Operation Mode
Option: Function:
[0] * Normal
operation
Normal operation with motor selected.
[2] Initialisation Reset parameter values to default
settings. The frequency converter resets during the next power-up.
14-24 Trip Delay at Current Limit
Range: Function:
60 s* [0 - 60 s] Enter the current limit trip delay in
seconds. When the output current reaches the current limit (parameter 4-18 Current Limit), a warning is triggered. When the current limit warning has been continuously present for the period specied in this parameter, the frequency converter trips. To run continuously in current limit without tripping, set the parameter to 60 s = O. Thermal monitoring of the frequency converter remains active.
14-25 Trip Delay at Torque Limit
Range: Function:
60 s* [0 - 60 s] Enter the torque limit trip delay in
seconds. When the output torque reaches the torque limits (parameter 4-16 Torque Limit Motor
Mode and parameter 4-17 Torque Limit Generator Mode), a warning is
triggered. When the torque limit warning has been continuously present for the period specied in this parameter, the frequency converter trips. Disable the trip delay by setting the parameter to
14-25 Trip Delay at Torque Limit
Range: Function:
60 s = O. Thermal monitoring of the frequency converter remains active.
14-27 Action At Inverter Fault
Option: Function:
Select how the frequency converter reacts when an overvoltage or grounding fault occurs.
[0] Trip Disable the protection lters and
trips at the rst fault.
[1] * Warning Run the protection lters normally.
14-28 Production Settings
Option: Function:
[0] * No action [1] Service reset [3] Software Reset
14-29 Service Code
Range: Function:
0* [0 -
0x7FFFFFFF ]
Only for service technicians’ use.
14-30 Current Lim Ctrl, Proportional Gain
Range: Function:
100 %* [0 - 500 %] Enter the proportional gain value
for the current limit controller. Selection of a high value makes the controller react faster. Too high a setting leads to controller instability.
14-31 Current Lim Ctrl, Integration Time
Range: Function:
0.020 s* [0.002 - 2 s] Control the current limit control integration time. Setting it to a lower value makes it react faster. A setting too low leads to control instability.
14-32 Current Lim Ctrl, Filter Time
Range: Function:
5 ms* [1 - 100 ms] Set a time constant for the current
limit controller low-pass lter.
Parameter Descriptions
VLT® Midi Drive FC 280
44
94 Danfoss A/S © 02/2019 All rights reserved. MG07C402
14-40 VT Level
Range: Function:
66 %* [40 - 90 %]
NOTICE
This parameter cannot be adjusted while the motor is running.
NOTICE
This parameter is not active when parameter 1-10 Motor Construction is set to options that enable PM motor mode.
Enter the level of motor magneti­zation at low speed. Selection of a low value reduces energy loss in the motor, but also reduces load capability.
14-41 AEO Minimum Magnetisation
Range: Function:
66 %* [40 - 75 %] Enter the minimum allowable
magnetization for AEO. Selection of a low value reduces energy loss in the motor, but can also reduce resistance to sudden load changes.
14-44 d-axis current optimization for IPM
Range: Function:
100 %* [0 - 200 %] This parameter is available only
when parameter 1-10 Motor
Construction is set to [3] PM, salient IPM.
Normally, VVC+ PM control automatically optimizes d-axis demagnetizing current based on d­axis and q-axis settings. When parameter 1-10 Motor Construction is set to [3] PM, salient IPM, use this parameter to compensate the saturation eect at high load. Usually, decreasing this value improves the eciency. However, 0% means no optimization and the d-axis current is 0 (not recommended).
14-51 DC-Link Voltage Compensation
Option: Function:
[0] O Disable DC-link compensation.
[1] * On Enable DC-link compensation.
14-55 Output Filter
Option: Function:
NOTICE
This parameter cannot be changed while the motor is running.
Select the type of output lter connected.
[0] * No Filter [1] Sine-Wave
Filter
14-61 Function at Inverter Overload
When the frequency converter issues a frequency converter overload warning, select whether to continue and trip the frequency converter, or derate the output current.
Option: Function:
[0] * Trip [1] Derate
14-63 Min Switch Frequency
Option: Function:
Set the minimum switch frequency allowed by the output lter.
[2] * 2.0 kHz [3] 3.0 kHz [4] 4.0 kHz [5] 5.0 kHz [6] 6.0 kHz [7] 8.0 kHz [8] 10.0 kHz [9] 12.0 kHz [10] 16.0 kHz
14-64 Dead Time Compensation Zero Current Level
Option: Function:
[0] * Disabled [1] Enabled If using a long motor cable, select
this option to minimize the motor torque ripple.
14-65 Speed Derate Dead Time Compensation
Range: Function:
Size related*
[ 20 - 1000 Hz]
Deadtime compensation level is reduced linearly versus output frequency from the maximum level
Parameter Descriptions Programming Guide
14-52 Fan Control
Option: Function:
[5] Constant-on mode [6] Constant-o mode [7] On-when-Inverter-is-on-else-o Mode [8] * Variable-speed mode
4 4
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 95
14-65 Speed Derate Dead Time Compensation
Range: Function:
set in parameter 14-07 Dead Time Compensation Level to a minimum
level set in this parameter.
14-70 Compatibility Selections
Select the compatibility mode for the frequency converter.
Option: Function:
[0] * No Function [12] VLT2800 3M [13] VLT2800 3M
incl. MAV [14] VLT2800 12M [15] VLT2800 12M
incl. MAV
14-88 Option Data Storage
Range: Function:
0* [0 - 65535 ] This parameter stores data related
to options over a power cycle.
14-89 Option Detection
Select the behavior when an option change is detected. This parameter returns to [0] Protect Option Cong. after an option change.
Option: Function:
[0] * Protect Option
Cong.
Freeze the current settings and prevents unwanted changes when missing or defective options are detected.
[1] Enable Option
Change
Settings can be changed when the system conguration is being
modied.
14-90 Fault Level
Use this parameter to customize fault levels.
Option: Function:
[0] O
This option uses the 5th element to control the fault level of alarm 14, Earth Fault.
[3] * Trip Lock Alarm is set to trip lock.
[4] Trip w.
delayed reset
Alarm is congured into trip alarm, which can be reset after a delay time. For example, if alarm 13, Overcurrent is congured to this option, it can be reset 3 minutes after the alarm. This option uses the 8th element to control the fault level of alarm 13, Overcurrent.
[5] Flystart At start-up, the frequency converter
tries to catch a spinning motor. If this option is selected,
14-90 Fault Level
Use this parameter to customize fault levels.
Option: Function:
parameter 1-73 Flying Start is forced to [1] Enabled. This option uses the 8th element to control the fault level of alarm 13, Overcurrent.
15-00 Operating hours
Range: Function:
0 h* [0 - 0x7f.h]View how many hours the
frequency converter has run. The value is saved, when the frequency converter is turned o.
15-01 Running Hours
Range: Function:
0 h* [0 - 0x7f.h]View how many hours the motor
has run. Reset the counter in
parameter 15-07 Reset Running Hours Counter. The value is saved,
when the frequency converter is turned o.
15-02 kWh Counter
Range: Function:
0 kWh* [0 -
2147483647
kWh]
Register the power consumption of the motor as an average value over 1 hour. Reset the counter in parameter 15-06 Reset kWh Counter.
15-03 Power Up's
Range: Function:
0* [0 -
2147483647 ]
View the number of times the frequency converter has been powered up.
Parameter Descriptions
VLT® Midi Drive FC 280
44
Index Alarm Trip lock Trip w.
delayed
0 Reserved – 1 Reserved – 2 Reserved – 3 Reserved – 4 Reserved – 5 Reserved – 6 Reserved – 7 Overcurrent D x x
Table 4.6 Table for Selection of Action when
Selected Alarm Appears (Parameter 14-90 Fault Level)
D = Default setting
x = Possible selection
Parameters: 15-** Drive Information
4.15
Flystart
96 Danfoss A/S © 02/2019 All rights reserved. MG07C402
15-04 Over Temp's
Range: Function:
0* [0 - 65535 ] View the number of frequency
converter temperature faults.
15-05 Over Volt's
Range: Function:
0* [0 - 65535 ] View the number of frequency
converter overvoltages.
15-06 Reset kWh Counter
Option: Function:
[0] * Do not reset No reset of the kWh counter is
required.
[1] Reset counter Press [OK] to reset the kWh counter
to 0 (see parameter 15-02 kWh Counter).
15-07 Reset Running Hours Counter
Option: Function:
[0] * Do not reset [1] Reset counter Press [OK] to reset the running
hours counter to 0 (see parameter 15-01 Running Hours).
15-30 Alarm Log: Error Code
Range: Function:
0* [0 - 255 ] View the error code and look up its
meaning in chapter 6 Trouble- shooting.
15-31 InternalFaultReason
Range: Function:
0* [-32767 -
32767 ]
View an extra description of the error. This parameter is mostly used in combination with alarm 38, Internal Fault.
15-40 FC Type
Range: Function:
0* [0 - 0 ] View the frequency converter type.
The readout is identical to the power eld of the type code denition, characters 1–6.
15-41 Power Section
Range: Function:
0* [0 - 20 ] View the FC type. The readout is
identical to the power eld of the type code denition, characters 7–
10.
15-42 Voltage
Range: Function:
0* [0 - 20 ] View the FC type. The readout is
identical to the power eld type of the type code denition, characters 11–12.
15-43 Software Version
Range: Function:
0* [0 - 5 ] View the combined SW version (or
package version) consisting of power SW and control SW.
15-44 Ordered Typecode String
Range: Function:
0* [0 - 40 ] View the type code string used for
reordering the frequency converter in its original conguration.
15-45 Actual Typecode String
Range: Function:
0* [0 - 40 ] View the actual type code.
15-46 Drive Ordering No
Range: Function:
0* [0 - 0 ] View the 8-digit ordering number
used for reordering the frequency converter in its original congu-
ration.
15-48 LCP Id No
Range: Function:
0* [0 - 20 ] View the LCP ID number.
15-49 SW ID Control Card
Range: Function:
0* [0 - 20 ] View the control card software
version number.
15-50 SW ID Power Card
Range: Function:
0* [0 - 20 ] View the power card software
version number.
15-51 Frequency Converter Serial Number
Range: Function:
0* [0 - 10 ] View the frequency converter serial
number.
15-52 OEM Information
Range: Function:
0* [0 - 0 ] View OEM information.
Parameter Descriptions Programming Guide
4 4
MG07C402 Danfoss A/S © 02/2019 All rights reserved. 97
15-53 Power Card Serial Number
Range: Function:
0* [0 - 19 ] View the power card serial number.
15-57 File Version
Range: Function:
0* [0 - 65535 ] View the le version.
15-59 Filename
Range: Function:
0* [0 - 16 ] View the actual le name of OEM
les.
15-60 Option Mounted
Range: Function:
Size related*
[0 - 30 ] View the installed option type.
15-61 Option SW Version
Range: Function:
Size related*
[0 - 20 ] View the installed option software
version.
15-70 Option in Slot A
Range: Function:
0* [0 - 30 ] View the type code string for the
option A, and a translation of the type code string.
15-71 Slot A Option SW Version
Range: Function:
0* [0 - 20 ] View the software version for the
option A.
15-92 Dened Parameters
Range: Function:
0* [0 - 2000 ] View a list of all dened parameters
in the frequency converter. The list ends with 0.
15-97 Application Type
Range: Function:
0* [0 -
0xFFFFFFFF ]
This parameter contains data used by MCT 10 Set-up Software.
15-98 Drive Identication
Range: Function:
0* [0 - 56 ] This parameter contains data used
by MCT 10 Set-up Software.
15-99 Parameter Metadata
Range: Function:
0* [0 - 9999 ] This parameter contains data used
by MCT 10 Set-up Software.
16-00 Control Word
Range: Function:
0* [0 - 65535 ] View the control word sent from
the frequency converter via the serial communication port in hex code.
16-01 Reference [Unit]
Range: Function:
0 Referen­ceFeedback Unit*
[-4999 - 4999
Reference-
FeedbackUnit]
View the present reference value applied on impulse or analog basis in the unit resulting from the conguration selected in parameter 1-00 Conguration Mode.
16-02 Reference [%]
Range: Function:
0 %* [-200 -
200 %]
View the total reference. The total reference is the sum of digital, analog, preset, bus, and freeze references, plus catch up and slow down.
16-03 Status Word
Range: Function:
0* [0 - 65535 ] View the status word sent from the
frequency converter via the serial communication port in hex code.
16-05 Main Actual Value [%]
Range: Function:
0 %* [-200 -
200 %]
View the 2-byte word sent with the status word to the bus master reporting the main actual value.
16-09 Custom Readout
Range: Function:
0 Custom­ReadoutUni t*
[0 - 9999
CustomRea-
doutUnit]
View the custom readout from
parameter 0-30 Custom Readout Unit to parameter 0-32 Custom Readout Max Value.
16-10 Power [kW]
Range: Function:
0 kW* [0 - 1000
kW]
Show motor power in kW. The calculated value shown is based on the actual DC-link voltage and DC-
Parameter Descriptions
VLT® Midi Drive FC 280
4.16 Parameters: 16-** Data Readouts
44
98 Danfoss A/S © 02/2019 All rights reserved. MG07C402
Loading...